Features • Digital programmability permits precise customization. • Sixteen setpoints can be programmed for maximum protection. 777-KW/HP 777-LR-KW/HP 777-575-KW/HP 777-HVR-KW/HP 777-HVR-LR-KW/HP • Last fault memory provides instant troubleshooting diagnostics. • Voltage, current, last 4 faults, kW, hp and power factor are recordable when using communications package. Power Monitor Motor Protection Relay • Engineered Protection • An RS485 communication port comes standard for use with computerized systems using Modbus protocol. • UL and CSA listed as an overload relay. Applications The Model 777-KW/HP can be used on ANY 3-phase motor. It has advantages over current monitors in low speed motor applications (less than 1800 rpm), lower power applications and in lightly loaded applications. Some examples include LOW SPEED MIXERS, CAN PUMPS, MAG DRIVE PUMPS, FRACTIONAL HORSEPOWER PUMPS and MOTORS, SUBMERSIBLE PUMPS AND COAL BED METHANE WELLS. Description The Model 777-KW/HP is a fully-programmable motor and pump protection relay with power-monitoring capability. Voltage, current and power measurements are displayed on the threedigit display, as well as fault information and setpoints. The display simplifies troubleshooting and allows the user to easily and precisely configure setpoints. The Model 777-KW/HP has the following adjustable protection features: 1) Low voltage 2) High voltage 3) Voltage unbalance 4) UL listed/CSA approved overload 5) Trip class (5, 10, 15, 20, 30) 6) Current unbalance 7) Ground fault 8) Low power 9) High power (via network only) 10) Rapid-cycle timer 11) Fault/overload restart delay 12) Underload restart delay 13) Underpower/overpower trip delay Other user adjustable features include: 1) CT/loop multiplier so overcurrent and power setpoints can be made in actual amps, kW or hp 2) Number of restarts after faults - manual, automatic and semiautomatic options 3) Number of restarts after underload - manual, automatic and semiautomatic options 4) Network address Adding the optional RS485MS-2W communications module activates the built-in Modbus RTU bus capabilities. The 777-KW/HP can communicate with the SymCom RM-1000 and RM-2000 remote display modules, PLCs, RTUs, SCADA systems, PCs and other similar control devices. Real-time operating parameters can be gathered and setpoints can be viewed or modified via the RS-485 bus using Modbus RTU protocol. Protects 3-Phase Motors and Pumps from: • Underload (Low KW or HP) • High power • Overload (UL listed) • Jams • Undervoltage • Overvoltage • Single-phasing • Unbalance (voltage & current) • Ground fault (Class II) • Rapid cycling • Phase reversal Additional Features • Fully programmable • UL and CSA listed • CE marked • Automatic or manual reset • Tamper guard • RS-485 communications port • Surface or DIN rail mountable • Alphanumeric LED diagnostic display • Last fault memory • Up to 99 individually programmable addresses • 5-year warranty • Made in USA New Features • Network programmable • Ability to clear last fault • Remote setup, Diagnostics and control • Remote data logging 2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email: sales@symcominc.com 11/05 Specifications • Operating Points • Special Options 777-KW/HP 777-LR-KW/HP 777-575-KW/HP 777-HVR-KW/HP 777-HVR-LR-KW/HP Power Monitor/Motor Protection Relay CURRENT TRANSFORMER WIRING DIAGRAM FOR MODEL 777-KW/HP (80-800 AMPS) TYPICAL WIRING DIAGRAM FOR MODEL 777-KW/HP (20-90 AMPS) & 777-LR-KW/HP (2-9 AMPS) SYMCOM RECOMMENDS USING CTs WITH TERMINALS TO SIMPLIFY INSTALLATION. L2 C NC DISPLAY / PROGRAM A G C U E A B R C L2-L3 LV HV VUB AVG KW -L2 L1 E N T L3 -L1 R + IND. CONT. EQ. ® 784X L1 L2 L3 NO C NC LISTED SUITABLE 10 KA RMS, 600 VAC MAX SYMCOM INC. 800-243-8848 RAPID CITY, SD MODE SELECT G C U E A B R C L2-L3 AVG KW -L2 L1 E N T L3 -L1 G MULT DISPLAY / PROGRAM R OC MODEL 777-KW/HP OVERLOAD RELAY 20-90A AV #RU/ADDR #RF RD3 RD2 KWS RD1 GF TC RUN CUB LV LKW HV A RESET/ PROGRAM LR46510 V O LT MULT NO G AV CUB LKW OC L3 MODEL 777-KW/HP OVERLOAD RELAY 20-90A V O LT L1 MODE SELECT #RU/ADDR #RF RD3 RD2 KWS RD1 GF TC RUN + VUB IND. CONT. EQ. ® 784X RESET/ PROGRAM Wiring configuration based on motor amps. LR46510 LISTED SUITABLE 10 KA RMS, 600 VAC MAX SYMCOM INC. 800-243-8848 RAPID CITY, SD Overload Trip Classes 777-LR-KW/HP 777-KW/HP External CTs required. See wiring diagram for external CTs Full Load Amps 1-2 2-9 8 - 12 12 - 25 25 - 90 80 - 110 110 - 160 160 - 220 220 - 320 320 - 420 400 - 520 480 - 600 560 - 800 # of # of Conductors MULT to Program Loops through A, B and C (CT Ratio) 2 1 2 1 0 1 2 3 3 1 2 2 0 1 1 4 5 100 (100:5) 4 5 150 (150:5) 4 5 200 (200:5) 4 5 300 (300:5) 4 5 400 (400:5) 4 5 500 (500:5) 4 5 600 (600:5) 4 5 800 (800:5) Trip Time (Seconds) 10000 Model 1000 100 Class 30 10 Class 20 Class 15 Class 10 Class 5 1 0 100 200 300 400 500 600 700 800 900 1000 % of OC Setting 2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email: sales@symcominc.com 11/05 Advantages: Specifications • Operating Points • Special Options • Integrated UL Listed/CSA approved electronic overload relay • Greater underload sensitivity than power factor or current monitors • Built-in undervoltage, overvoltage and unbalance protection • Digitally programmable • Remote programmability • Digital display • Optional remote display • Data logging capabilities 777-KW/HP 777-LR-KW/HP 777-575-KW/HP 777-HVR-KW/HP 777-HVR-LR-KW/HP Power Monitor/Motor Protection Relay 0.002" (5.08) MODE SELECT L3 NO MODEL 777-KW/HP C NC DISPLAY / PROGRAM OVERLOAD RELAY 20-90A G C U E A B R C AVG KW E N T L3 -L1 L2-L3 -L2 L1 2.280" (57.91) 3.050" (77.47) + IND. CONT. EQ. ® 784X RESET/ PROGRAM 2.650" (67.31) R #RU/ADDR #RF RD3 RD2 KWS RD1 GF TC RUN CUB LV LKW HV OC VUB MULT L2 A L1 G AV Small motors, those under 3 hp and especially fractional horsepower, exhibit small changes in current vs. load but the change in power is large. When larger motors are derated, run below their rated horsepower, the change in current is small vs. load, but again, the change in power is large and linear. Other typical applications include slower speed mixer or agitator motors up to 50 hp and beyond. These motors and others that run slower than around 3400 rpm usually have small current changes vs. load. Dimensions for All 777-KW/HP Units V O LT The Model 777-KW/HP has important advantages over current monitors in many protection applications. Any motor load that has a small or very non-linear change in current vs. load requires the use of a power monitor for underload, dry-run and dead-head protection. The change in power vs. load is more linear for most motor loads and is greater in magnitude than the change in current in all motor loads. This is because power measurements take into account both power factor (pf) and current. LR46510 LISTED SUITABLE 10 KA RMS, 600 VAC MAX SYMCOM INC. 800-243-8848 RAPID CITY, SD 3.100" (78.74) Magdrive and can pumps tend to be small horsepower, positive displacementtype pumps. These pumps need the high sensitivity of a power monitor to protect them from dry-run using the underpower feature and dead-head conditions using the underpower feature if the motor decouples from the pump and the overpower feature if the motor does not decouple. 3.600" (91.44) 3.850" (97.79) The built-in UL Listed/CSA approved overload, current unbalance, reversephase, single-phase and other protection features are significant benefits over similar products. The Modbus communications capability allows this device to be directly integrated with the SymCom RM-1000 and RM-2000 remote displays or other remote monitoring and control equipment. 1.200" (30.48) 777-KW/HP uses power measurements for sensitive underload protection, while using current measurements for UL listed overload protection. 5.050" (128.27) Current Power Full Load 4.700" (119.38) Current is not linear, low sensitivity for low loads and high sensitivity for high loads. Power is Linear, equal sensitivity at both low and high loads. No Load 0.650" (16.51) 200-480 VAC 3Ø 50/60 HZ No Load Full Load 3.600" (91.44) 3.850" (97.79) 2880 North Plaza Drive • Rapid City, SD 57702 (800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685 www.symcominc.com • email: sales@symcominc.com 11/05 Specifications Electrical Input Voltage Ranges and Low and High Voltage Setpoints 777-KW/HP Low Setpoint (LV) 170-HV Setting Nominal Voltage Range 200-480 VAC High Setpoint (HV) LV Setting - 528 340-HV Setting 380-480 VAC LV Setting - 528 450-HV Setting 480-600 VAC LV Setting - 660 Nom. Current Range 2-25A Looped Overcurrent Setpoint (OC) (20 to 100A)/MULT Ground Fault Setpoint (GF) OFF, (3 to 20A)/MULT 777-LR-KW/HP 777-HVR 777-HVR-LR 777-575 777-575-LR Nominal Motor Full Load Current and Overcurrent Setpoint 777, 777-HVR, 777-575 777-LR, 777-HVR-LR, 777-575-LR 25-90A Direct 20 to 100A OFF, 3-20A 80-800A Ext CTs 80-120% of CT Prim OFF, 10-30% of CT Prim 1-2.5A Looped 1-5A 0.15-1A 2-9A Direct 2-10A 0.3-2A Frequency 50/60 Hz Short Circuit 100 kA Power Consumption 10 Watts (max.) Output Contact Rating SPDT (Form C) All 777-XXX-XX KW/HP types except -HVR Pilot duty rating: 480VA @ 240VAC General purpose: 10A @ 240VAC Max Voltage: 277VAC 777-HVR-KW/HP Pilot duty rating: 480VA @ 600VAC 777-HVR-LR-KW/HP Expected Life Mechanical 1 x 106 operations Electrical 1 x 105 operations at rated load Accuracy at 25° C (77° F) Voltage ±1% Current ±3%(<100 Amps Direct) GF Current ±15% Timing 5% ± 1 second Repeatability Voltage ± 0.5% of nominal voltage Current ± 1% (<100 amps direct) Safety Marks UL UL508, UL1053 CSA LR46510 CE IEC 60947-1, IEC 60947-5-1 Standards Passed Electrostatic Discharge (ESD) IEC 1000-4-2, Level 3, 6kV contact, 8kV air Radio Frequency Immunity (RFI), Conducted IEC 1000-4-6, Level 3 10V/m Radio Frequency Immunity (RFI), Radiated IEC 1000-4-3, Level 3 10V/m Fast Transient Burst IEC 1000-4-4, Level 3, 3.5 kV input power Surge IEC 1000-4-5, Level 3, 2kV line-to-line; Level 4, 4kV line-to-ground ANSI/IEEE C62.41 Surge and Ring Wave Compliance to 6kV line-line Hi-potential Test Meets UL508 (2 x rated V +1000V for 1 minute) Vibration IEC 68-2-6, 10-55Hz, 1mm peak-to-peak, 2 hours, 3 axis Shock IEC 68-2-27, 30g, 3 axis, 11ms duration, half-sine pulse Mechanical Dimensions 3.0"H x 5.1 " D x 3.6"W Terminal Torque 7 in.-lb. Enclosure Material Polycarbonate Weight 1.2 lbs. Maximum Conductor Size Through 777-KW/HP 0.65" with insulation Environmental Temperature Range Ambient Operating: -20° to 70° C (-4° to 158°F) Ambient Storage: -40° to 80° C (-40° to 176°F) Pollution Degree 3 Class of Protection IP20, NEMA 1 Relative Humidity Programmable Operating 10-95%, non-condensing per IEC 68-2-3 Points Range LV, HV, OC, GF See electrical specifications above UB- Voltage Unbalance Threshold 2 - 15% or 999% MULT- # of Loops or CT Ratio (XXX:5) 1-10 Loops or 100-800 Ratio LP- Low Power Setting See Power Ranges Below or 0=off CUB- Current Unbalance Threshold 2 - 25% or 999% TC- Overcurrent Trip Class ** 5, J5, 10, J10, 15, J15, 20, J20, 30, J30 RD1- Rapid Cycle Timer RD2- Restart Delay After All Faults Except Underload (motor cool down timer) 0, 2 - 500 Seconds 2 - 500 Minutes RD3- Restart Delay After Underload (dry-well recovery timer) 2 - 500 Minutes #RU- Number of Restarts After Underload 0, 1, 2, 3, 4, A(Automatic) ADDR- RS485 Address A01- A99 #RF-Number of Restarts After All Faults Except Underload*** Low Power (LP) / Power Range Setting (PWS) 0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, ocA (PWS = LP Range) NOTES: SymCom's 777-KW/HP & 777-LRKW/HP can be preprogrammed prior to installation by applying 120 VAC between the L1 and L2 terminals. 1 = 0.01 - 0.99 KW 5 = 0.01 - 0.99 HP 2 = 1.00 - 9.95 KW 6 = 1.00 - 9.95 HP 3 = 10.0 - 99.5 KW 8 = 10.0 - 99.5 HP 4 = 100 - 650 KW 9 = 100 SymCom warrants its microcontroller based products against defects in material or workmanship for a period of five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms returns, and cancellations, please refer to the SymCom Terms and Conditions of Sale document. - 650 HP * 575 volt Model (MS 777-575-KW/HP) ** If J prefix is displayed in trip class setting, jam protection is enabled. *** If "oc" is disabled in the #RF setting, the overcurrent will be included as a normal fault and the relay will automatically restart after RD2 expires, otherwise, manual reset is required after an overcurrent fault. 11/05