Comfort Functions

advertisement
39231
GE Consumer & Industrial
Power Protection
GE Consumer & Industrial
Power Protection (former GE Power Controls),
a division of GE Consumer & Industrial,
is a first class European supplier of
low-voltage products including wiring
devices, residential and industrial electrical
distribution components, automation
products, enclosures and switchboards.
Demand for the company’s products
comes from wholesalers, installers,
panel-board builders, contractors, OEMs
and utilities worldwide
GE Consumer & Industrial
Power Protection
Redline
ED.04
Comfort Functions
Just feel protected
www.gepowercontrols.com
www.ge.com/eu/powerprotection
Redline - Modulair DIN-rail devices
ED.04
GE imagination at work
GE imagination at work
GE POWER CONTROLS
International Sales
Nieuwevaart 51
B-9000 Gent - Belgium
Tel.
+32/9 265 21 11
Fax
+32/9 265 28 90
E-mail: gepcbel@gepc.ge.com
GE imagination at work
GE imagination at work
GE imagination at work
GE imagination at work
680803
Ref. R/2260/E/X 15.0 Ed. 11/06
© Copyright GE Power Controls 2006
Redline
Modular DIN-rail devices and residential enclosures
Circuit Protection
A
People Protection
B
Add-on Devices
C
Comfort Functions D
Busbars
E
Enclosures
F
Record Plus
G
Numerical Index
X
Redline
D.2
Switches & Push-buttons - Aster
D.4
Indication Lamp - Aster
D.6
Contactors - Contax
D.8
Relays - Contax R
D.10
Impulse Switches - Pulsar S
D.14
Staircase Switches - Pulsar TS
D.16
Time Relays - Pulsar T
D.18
Analogue Time Switches - Classic
D.20
Digital Time Switches - Galax
D.22
Time Switches - 72x72 Classic and Galax
D.24
Light Sensitive Switches - Galax LSS
D.26
Transformers - Series T
D.28
Measurement Instruments - Series MT
D.32
Priority relays - PR
D.34
Surge Arresters - SurgeGuard
D.36
Dimensional drawings
Circuit Protection
A
People Protection
B
Add-on Devices
C
Comfort Functions
D
Busbars
E
Enclosures
F
Record Plus
G
Numerical Index
X
protected
D.1
Redline
Switches & Push-buttons
Comfort functions
Aster
Applications
Switching of lighting and heating in homes, shops, offices, warehouses,
factories, hospitals, etc.
Features
Function
Manual control of all kinds of
electrical devices.
A
Approvals (1)
B
C
Wide range with respect to available contact combinations and switching
capacity. Mains disconnect switches and switches with change-over
contact and off position available.
Compact (4-pole in 1 module) with high switching capacity due to double
interruption per path.
All switches are sealable through padlock or by means of a lock.
The terminals are equipped with captive Pozidriv screws and have
IP20 protection degree.
Mains disconnect switches accepts auxiliary contacts CA.
Standards
D
E
BS EN
VDE
BS EN
VDE
BS EN
Switches
16/32A
Mains disconnect
switches 40-100
Rotary switches
(1) Depending on type.
60669-1
0632 Part 1
60947-3
0632 Part 101
60947-3
F
Performance
G
Nominal rated current
Usable as mains disconnect switch
Nominal breaking capacity at 415V, cos ϕ =0.95
Nominal breaking capacity at 415V, cos ϕ =0.65
Nominal voltage single pole devices
Nominal voltage multipole devices
Maximum allowed current during less than 1 s.
Mechanical service life (complete on-off-cycle)
Electrical service life, cos ϕ = 0.95, Un and In
Short-circuit resistance with upfront fuses Gg/gL 100A (nominal)
(peak)
Protection degree
Screws
Terminal capacity: min
max
X
Auxiliary contacts
More technical data
Dimensions
D.2
pg. C.4 to C.5
website
pg D.36
Push-buttons
Switches
16A | 32A
Rotary
switches
32-40-63A
Mains disconnect
switches
40-63-80-100A
16A
no
240V
>20000
>20000
4.5kA (nominal)
3kA (peak)
IP20
Pozidriv 1
1x1.5mm2
1x10mm2
no
1.25xIn
240V
415V
>20000
>20000 | >5000
4.5kA (nominal)
3kA (peak)
IP20
Pozidriv 1
1x1.5mm2
1x10mm2
yes
8xIn
8xIn
240/415V
>10000
>1500
15kA (nominal)
10kA (peak)
IP20
Pozidriv 2
1x2.5mm2
1x25mm2
yes
3xIn
3xIn
240/415V
240/415V
2kA
>20000
>1500
16kA (nominal)
7kA (peak)
IP20
Pozidriv 2
1x6mm2
1x50mm2
Redline
Aster - Switches & push-buttons
Contact
combination
Number of
modules
Cat. No.
Ref. No.
Pack.
40A/240V
40A/415V
40A/415V
40A/415V
63A/240V
63A/415V
63A/415V
63A/415V
1NO
2NO
3NO
4NO
1NO
2NO
3NO
4NO
1
2
3
4
1
2
3
4
AST M 40 10
AST M 40 20
AST M 40 30
AST M 40 40
AST M 63 10
AST M 63 20
AST M 63 30
AST M 63 40
666614
666615
666616
666617
666562
666563
666564
666565
12
6
4
3
12
6
4
3
80A/240V
80A/415V
80A/415V
80A/415V
100A/240V
100A/415V
100A/415V
100A/415V
1NO
2NO
3NO
4NO
1NO
2NO
3NO
4NO
1
2
3
4
1
2
3
4
AST M 80 10
AST M 80 20
AST M 80 30
AST M 80 40
AST M 100 10
AST M 100 20
AST M 100 30
AST M 100 40
666566
666567
666568
666569
666558
666559
666560
666561
12
6
4
3
12
6
4
3
32A/415V
32A/415V
32A/415V
32A/415V
40A/415V
40A/415V
40A/415V
40A/415V
63A/415V
63A/415V
63A/415V
63A/415V
2NO
3NO
3NO+NC
4NO
2NO
3NO
3NO+NC
4NO
2NO
3NO
3NO+NC
4NO
4
4
4
4
4
4
4
4
4
4
4
4
AST R 32 20
AST R 32 30
AST R 32 3N
AST R 32 40
AST R 40 20
AST R 40 30
AST R 40 3N
AST R 40 40
AST R 63 20
AST R 63 30
AST R 63 3N
AST R 63 40
666574
666575
666576
666577
666578
666579
666580
666581
666582
666583
666584
666585
1
1
1
1
1
1
1
1
1
1
1
1
16A/240V
16A/240V
16A/415V
16A/415V
16A/415V
16A/415V
16A/240V
16A/240V
1NO
2NO
3NO
4NO
3NO
4NO
1CO
2CO
1
1
1
1
2
2
1
1
AST S 16 10
AST S 16 20
AST S 16 30
AST S 16 40
AST S 16 30 2
AST S 16 40 2
AST S 16 1
AST S 16 2
666587
666589
666590
666593
666591
666592
666586
666588
12
12
12
12
6
6
12
12
32A/240V
32A/240V
32A/415V
32A/415V
32A/415V
32A/415V
32A/240V
32A/240V
1NO
2NO
3NO
4NO
3NO
4NO
1CO
2CO
1
1
1
1
2
2
1
1
AST S 32 10
AST S 32 20
AST S 32 30
AST S 32 40
AST S 32 30 2
AST S 32 40 2
AST S 32 1
AST S 32 2
666595
666597
666599
666600
666598
666601
666594
666596
12
12
12
12
6
6
12
12
Switch with
signal lamp
16A/240V
16A/240V
32A/240V
32A/240V
1NO
2NO
1NO
2NO
1
1
1
1
AST SL 16 10
AST SL 16 20
AST SL 32 10
AST SL 32 20
666602
666603
666604
666605
12
12
12
12
Changeover
switches with
zero position
16A/240V
16A/240V
32A/240V
32A/240V
1CO
2CO
1CO
2CO
1
1
1
1
AST SZ 16 1
AST SZ 16 2
AST SZ 32 1
AST SZ 32 2
666606
666607
666608
666609
12
12
12
12
Push-button
16A/240V
16A/240V
16A/240V
1NC
1NO
1NO 1NC
1
1
1
AST P 16 01
AST P 16 10
AST P 16 11
666570
666571
666572
12
12
12
16A/240V
1NO
1
AST PL 16 10
666573
12
AST R ES E
AST R ES S
666555
666556
1
1
AST R TS
666557
1
Mains disconnect switch
Rotary switch
Changeover switches
Push-button
with signal lamp
Aster
Nominal
current
A
B
C
D
E
F
G
X
Accessories for rotary switches
Extension
shaft
Sealing piece
238 mm with emergency handle
238 mm with standard handle
4
D.3
Redline
Indication Lamp
Aster
Function
Comfort functions
Status visualisation.
Applications
Mainly used to visualise the status of a (sub)part of the installation,
heater, motor, fan, pump etc.
Features
Available in different voltages and with different coloured lenses.
A
Performance
B
C
Nominal voltage
12V
24V
230V
Own consumption
Lamp
Lens colours
120mA
Incandescent lamp
Red, green, orange
and transparent
IP20
Pozidriv 1
1x1.5mm2
1x10mm2 / 2x4mm2
85mA
Incandescent lamp
Red, green, orange
and transparent
IP20
Pozidriv 1
1x1.5mm2
1x10mm2 / 2x4mm2
2.2mA
Neon lamp
Red, green, orange
and transparent
IP20
Pozidriv 1
1x1.5mm2
1x10mm2 / 2x4mm2
Protection degree
Screws
Terminal capacity: min
max
D
E
Socket-outlets
F
MSC
G
Standards
BS EN C61112-1, NF C61-303 (86), IEC 60884-1
X
Approvals (1)
(1) Depending on type.
Performance
Nominal current
More technical data
Dimensions
D.4
website
pg D.36, D.37
Nominal voltage
Operating temperature
Protection degree
Screws
Terminal capacity: min
max
16A
250V
-20 ... +55°C
IP20
Pozidriv 2
1x1 mm2
1x6 mm2 or 2x2.5 mm2
Redline
Aster - Indication lamp
Colour
Number of
modules
-
-
1
Nominal
operating voltage
Colour
12V
24V
230V
Lampholder
Cat. No.
Ref. No.
Pack.
AST B
666347
12
Number of
modules
Cat. No.
Ref. No.
Pack.
-
-
AST B 12
AST B 24
AST B 230
666340
666342
666341
12
12
12
Green
Amber
Red
Blue
White
-
AST LG 230V
AST LA 230V
AST LR 230V
AST LB 230V
AST LW 230V
666876
666874
666877
666875
666878
10
10
10
10
10
Transparent
Green
Orange
Red
-
AST L CL
AST L GN
AST L OR
AST L RD
666343
666344
666345
666346
12
12
12
12
Accessories
Lamp
Lamp LED E10
Lens
235V
235V
235V
235V
235V
/
/
/
/
/
-
Aster and MSC
Nominal
operating voltage
A
B
C
D
E
MSC - Socket-outlets
Nominal
current
Nominal
voltage
Number of
modules
Cat. No.
Ref. No.
Pack.
Edged with
child protection
16A
250V
2.5
MSC SEP
666501
4
Edged without
child protection
16A
250V
2.5
MSC SE
666499
4
F
G
X
Pin with
child protection
16A
250V
2.5
MSC SPP
666502
4
D.5
Redline
Contactors
Contax
Comfort functions
Applications
Switching of lighting, heating-equipment, motors for pumps and fans, ...
Day and night contactors are used mainly in combination with dual-tariff
applications to allow high-energy-loads (i.e. electrical water heaters,
accumulation heaters) only to consume energy during the low-tariff period.
A forced-on, forced-off, auto-switch allows to overrule the normal operation of
the DN-contactor at all times.
Features
Function
Contactors are electromechanically
controlled switches used to control
single or multi-phase (high) power
loads while the control itself can
be (very) low power.
A
B
Except for the 20A version, all contactors have DC coils, resulting in an
absolutely noise-free, real silent operation: 50 or 60Hz noise generation by the
contactor is impossible. As all DC coil contactors have an internal diode
rectifier bridge, they all can be operated by both DC and AC power supplies.
The built-in varistor protects the coil against an overvoltage of up to 5kV.
The switch position of the contactor is visualised through an indicator flag.
The loss-proof safety terminals are equipped with Pozidriv screws and have
IP20 protection degree. Add-on auxiliary contacts as well as spacers and
sealing pieces are available.
Standards
C
IEC 60947-4-1, BS EN 60947-4-1, IEC 61095, BS EN 61095. Approval VDE.
Performance
D
Rated switching capacity
Contacts
E
Switching capacity for different loads
Rated insulation voltage
Rated operational voltage
Switching-on capacity
cos ϕ = 0.65 at 380-400V 3phase
cos ϕ = 0.95 at 220-230V 1phase
Switching-off capacity
cos ϕ = 0.65 at 380-400V 3phase
cos ϕ = 0.95 at 220-230V 1phase
Fuse type GL for short-circuit protection
Ohmic loss per contact at In
Maximum switching frequency AC1 / AC7a
Maximum switching frequency AC3 / AC7b
Mechanical service life
Electrical service life AC1 / AC7a
Electrical service life AC3 / AC7b
Screws
Terminal capacity: min
max
F
G
X
20A
24A
40A
63A
More technical information see T4
400V
250V
500V
440V
500V
440V
500V
440V
100A
90A
-
220A
-
300A
-
80A
20A
1.0W
300/h
600/h
106
150000
150000
Pozidriv 1
1x1 mm2
1x10mm2 or 2x4 mm2
72A
35A
1.5W
300/h
600/h
106
150000
500000
Pozidriv 1
1x1 mm2
1x10mm2 or 2x4 mm2
176A
240A
63A
80A
3.0W
6.0W
300/h
300/h
600/h
600/h
106
106
150000
150000
170000
240000
Pozidriv 2
Pozidriv 2
1x1.5 mm2
1x1.5 mm2
1x25mm2 or 2x10 mm2 1x25mm2 or 2x10 mm2
85 ... 110%xUn
50 or 60Hz
-25 ... +55°C(1)
8.0VA / 5.0W
3.2VA / 1.2W
9 ... 12 ms
10 ... 12 ms
Pozidriv 1
1x1 mm2
1x4mm2 or 2x2.5 mm2
85 ... 110%xUn
DC, 40 ... 450Hz
-25 ... +55°C(1)
4VA / 4W
4VA / 4W
< 40 ms
< 40 ms
Pozidriv 1
1x1 mm2
1x4mm2 or 2x2.5 mm2
85 ... 110%xUn
DC, 40 ... 450Hz
-25 ... +55°C(1)
5VA / 5W
5VA / 5W
< 40 ms
< 40 ms
Pozidriv 1
1x1 mm2
1x4mm2 or 2x2.5 mm2
Magnetic control system
Control voltage range
Rated operating frequency
Operating temperature range
Maximum pull-in coil power loss
Maximum holding coil power loss
Switching-on delay
Switching-off delay
Screws
Terminal capacity: min
max
85 ... 110%xUn
DC, 40 ... 450Hz
-25 ... +55°C(1)
65VA / 65W
4.2VA / 4.2W
< 40 ms
< 40 ms
Pozidriv 1
1x1 mm2
1x4mm2 or 2x2.5 mm2
(1) Remark: If several contactors are mounted next to each-other and the time of operation exceeds 1 hour and the ambient
temperature rises above 40°C, a 1/2-module spacer must be added every second contactor (I.e. contactor contactor spacer contactor contactor spacer contactor contactor etc.)
D.6
Redline
Contax - Contactors
Contact
combination
Coil
voltage
AC/DC
Number of
modules
20A
20A
20A
20A
20A
20A
20A
20A
20A
1NO 1NC
1NO 1NC
2NC
2NC
2NO
2NO
2NO
2NO
2NO
24V
230V
24V
230V
12V
24V
48V
230V
240V
AC
AC
AC
AC
AC
AC
AC
AC
AC
1
1
1
1
1
1
1
1
1
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
24A
2NO 2NC
2NO 2NC
3NO
3NO
4NC
4NC
4NO
4NO
4NO
4NO
4NO
24V
230V
24V
230V
24V
230V
12V
24V
48V
230V
240V
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
40A
40A
40A
40A
40A
40A
40A
40A
40A
40A
2NC
2NO
3NO
3NO
4NO
4NO
4NO
4NO
2NO
4NO
230V
230V
24V
230V
12V
24V
48V
230V
24V
240V
4 NO
63A
63A
63A
63A
63A
2NC
4NO
4NO
2NO
4NO
Contactor Day and Night
20A
Contactor
1 NO 1 NC
2 NC
2 NO
2 NO 2 NC
3 NO
4 NC
Cat. No.
Ref. No.
Pack.
CTX 20 11 024 A
CTX 20 11 230 A
CTX 20 02 024 A
CTX 20 02 230 A
CTX 20 20 012 A
CTX 20 20 024 A
CTX 20 20 048 A
CTX 20 20 230 A
CTX 20 20 240 A
666127
666126
666129
666128
666130
666133
666134
666131
666132
12
12
12
12
12
12
12
12
12
2
2
2
2
2
2
2
2
2
2
2
CTX 24 22 024 U
CTX 24 22 230 U
CTX 24 30 024 U
CTX 24 30 230 U
CTX 24 04 024 U
CTX 24 04 230 U
CTX 24 40 012 U
CTX 24 40 024 U
CTX 24 40 048 U
CTX 24 40 230 U
CTX 24 40 240 U
666136
666135
666138
666137
666140
666139
666141
666144
666145
666142
666143
5
5
5
5
5
5
5
5
5
5
5
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
3
3
3
3
3
3
3
3
3
3
CTX 40 02 230 U
CTX 40 20 230 U
CTX 40 30 024 U
CTX 40 30 230 U
CTX 40 40 012 U
CTX 40 40 024 U
CTX 40 40 048 U
CTX 40 40 230 U
CTX 40 20 024 U
CTX 40 40 240 U
666170
666146
666149
666148
666150
666153
666154
666151
666147
666152
3
3
3
3
3
3
3
3
3
3
230V
24V
230V
230V
240V
AC/DC
AC/DC
AC/DC
AC/DC
AC/DC
3
3
3
3
3
CTX 63 02 230 U
CTX 63 40 024 U
CTX 63 40 230 U
CTX 63 20 230 U
CTX 63 40 240 U
666171
666158
666156
666155
666157
3
3
3
3
3
2NO
230V
AC
1
CTX DN 20 20 230 A
666164
12
24A
24A
3NO
4NO
230V
230V
AC/DC
AC/DC
2
2
CTX DN 24 30 230 U
CTX DN 24 40 230 U
666165
666166
5
5
40A
40A
40A
2NO
3NO
4NO
230V
230V
230V
AC/DC
AC/DC
AC/DC
3
3
3
CTX DN 40 20 230 U
CTX DN 40 30 230 U
CTX DN 40 40 230 U
666167
666168
666169
3
3
3
Contax
Nominal
current
A
B
C
D
2 NO
3 NO
E
4NO
F
Add-on auxiliary contact for 24-40-63A contactors
Left mounting
1 NO 1 NC
Nominal
current
Contact
combination
6A
6A
1NO 1NC
2NO
-
-
Number of
modules
Cat. No.
Ref. No.
Pack.
0.5
0.5
CTX 06 11
CTX 06 20
666162
666163
5
5
G
X
2 NO
Accessories
Sealing piece
Spacer
Number of
modules
Cat. No.
Ref. No.
Pack.
2
3
CTX TS 2
CTX TS 3
666160
666159
3
3
0.5
CTX SP
666161
12
D.7
Redline
Relays
Contax R
Comfort functions
Applications
Switching of lighting, heating, etc. Galvanic insulation of i.e. status
signalisation lamps from a (high) power (high voltage) circuit . Galvanic
insulation of PLC-inputs or outputs to avoid destruction through excessive
voltage.
Features
Besides the normal operation through electrically energising the coil,
manual operation is possible at all times. The switch position of the relay
is visualised through an indicator flag. The safety terminals are equipped with
captive Pozidriv screws and have IP20 protection degree.
An add-on auxiliary contact as well as spacer are available.
Function
Relays are electromechanically
controlled switches used to
control low power loads.
A
B
BSEN 60669-1, BSEN 60669-1, VDE 0632, VDE 0660-107, NBN C61-111,
NF C61-810, VDE 0637, IEC 60669-1, IEC 60669-2-2, IEC 61095, BSEN 61095
Performance
Rated switching capacity
Contacts
C
16A
Contact spacing / material
Spacing between control and load circuit
Isolation voltage contact/contact
Isolation voltage contact/magnetic system
Switching capacity
Incandescent lamp load
Fluorescent lamp load, lead-lag circuit
Fluorescent lamp load, inductive or capacitive
Fluorescent lamp load, parallel compensated
Electronic ballast load
D
E
Inductive load, cos ϕ = 0.6 at 230V
DC switching capacity
Minimum contact load
Maximum switching frequency
Mechanical service life
Electrical service life, cos ϕ = 1 (1)
Electrical service life, cos ϕ = 0.6 (1)
Electrical service life, 1000W incandescent lamp (1)
Contact closing time
Contact opening time
Screws
Terminal capacity: min
max
F
G
X
Standards
3 mm/AgSnO2
> 6 mm
400V
400V
16A/250V; 10A/400V
10A (2300W)
16A (3500W)
10A (1300W)
4A (500W)
10A (2300W)
ION ≤ 140A/10ms
10A (1300W)
100W
6V/50mA
1000/h
>106
>105
> 2x104
>105
10 ... 20 ms
5 ... 15 ms
Pozidriv 1
1x0.5mm2
1x6 mm2 or 2x2.5 mm2
Magnetic control system
Control voltage range
Relative duty/switching reliability
Operating temperature range
Maximum coil power loss at Un and In
Maximum control line capacitance
Screws
Terminal control capacity: min
max
0.9 ... 1.1xUn
100%
-5 ... +50°C
6W/module
0.06µF (= ±200 m.)
Pozidriv 1
1x0.5 mm2
1x4 mm2 or 2x2.5 mm2
(1) Guaranteed at maximum switching frequency.
More technical data
Dimensions
D.8
website
pg D.38
Redline
Contax R - Relays
Contact
combination
Coil
voltage
AC/DC
Number of
modules
Cat. No.
Ref. No.
Pack.
16A
16A
16A
16A
16A
16A
16A
1NO
1NO
1NO
1NO
1NO
1NO
1NO
8V
12V
24V
48V
230V
12V
24V
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
CTX R 16 10 008 A
CTX R 16 10 012 A
CTX R 16 10 024 A
CTX R 16 10 048 A
CTX R 16 10 230 A
CTX R 16 10 012 D
CTX R 16 10 024 D
666489
666454
666458
666460
666456
666455
666459
12
12
12
12
12
12
12
16A
16A
16A
16A
16A
16A
16A
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
8V
12V
24V
48V
230V
12V
24V
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
CTX R 16 11 008 A
CTX R 16 11 012 A
CTX R 16 11 024 A
CTX R 16 11 048 A
CTX R 16 11 230 A
CTX R 16 11 012 D
CTX R 16 11 024 D
666491
666461
666465
666467
666463
666462
666466
12
12
12
12
12
12
12
16A
16A
16A
16A
16A
16A
16A
2NO
2NO
2NO
2NO
2NO
2NO
2NO
8V
12V
24V
48V
230V
12V
24V
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
CTX R 16 20 008 A
CTX R 16 20 012 A
CTX R 16 20 024 A
CTX R 16 20 048 A
CTX R 16 20 230 A
CTX R 16 20 012 D
CTX R 16 20 024 D
666490
666468
666472
666474
666470
666469
666473
12
12
12
12
12
1
12
16A
16A
16A
16A
16A
16A
16A
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
8V
12V
24V
48V
230V
12V
24V
AC
AC
AC
AC
AC
DC
DC
2
2
2
2
2
2
2
CTX R 16 22 008 A
CTX R 16 22 012 A
CTX R 16 22 024 A
CTX R 16 22 048 A
CTX R 16 22 230 A
CTX R 16 22 012 D
CTX R 16 22 024 D
666492
666475
666479
666481
666477
666476
666480
1
6
6
6
6
1
6
16A
16A
16A
16A
16A
16A
16A
4NO
4NO
4NO
4NO
4NO
4NO
4NO
8V
12V
24V
48V
230V
12V
24V
AC
AC
AC
AC
AC
DC
DC
2
2
2
2
2
2
2
CTX R 16 40 008 A
CTX R 16 40 012 A
CTX R 16 40 024 A
CTX R 16 40 048 A
CTX R 16 40 230 A
CTX R 16 40 012 D
CTX R 16 40 024 D
666493
666482
666486
666488
666484
666483
666487
5
6
6
6
6
6
6
Nominal
current
Number of
modules
Cat. No.
Ref. No.
Pack.
4A
0.5
PLS 04 11
666207
12
Contax R
Nominal
current
A
B
C
Auxiliary contact
Auxiliary contact (left mounting)
D
E
F
G
X
Accessories
Spacer
Number of
modules
Cat. No.
Ref. No.
Pack.
0.5
PLS SP
666206
12
D.9
Redline
Impulse Switches
Comfort functions
Pulsar S
A
B
Function
Performance
Impulse switches are electromechanically or electronically controlled
switches used to control single- or multi-phase medium-power loads
while the control itself can be (very) low power. The device switches
between 2 stable positions, each time a (brief) impulse energises its
control circuit.
Applications
C
D
E
F
G
X
Mainly used for the switching of lighting and heating equipment
and/or to obtain a simplified wiring in case the load needs to be
controlled at reduced voltage and/or from more than 4 different
places.
Features
Besides the normal operation through electrically energising the coil,
manual operation is possible at all times. The switch position of
the impulse switch is visualised through an indicator flag for the
EM-version, or through an LED for the electronic version. The central
command version was developed to force several devices at the same
time to the on or off position, independently of the current status of each
individual device. Also in this case, the possibility of operating the device
locally remains. The safety terminals are equipped with captive Pozidriv
screws and have IP20 protection degree. An add-on auxiliary contact,
add-on central-command module and a spacer are available.
Standards
IEC 60669-1, IEC 60669-2-2, BS EN 60669-1, BS EN 60669-2-2
Rated switching capacity
Contacts
Contact spacing / material
Spacing between control and load circuit
Isolation voltage contact/contact
Isolation voltage contact/magnetic system
Switching capacity
Incandescent lamp load
Fluorescent lamp load, lead-lag circuit
Fluorescent lamp load, inductive or capacitive
Fluorescent lamp load, parallel compensated
Electronic ballast load
Inductive load, cos ϕ = 0.6 at 230V
DC switching capacity
Minimum contact load
Maximum switching frequency
Mechanical service life
Electrical service life, cos ϕ = 1 (1)
Electrical service life, cos ϕ = 0.6 (1)
Electrical service life, 1000W incandescent lamp (1)
Screws
Terminal capacity: min
max
Magnetic control system
Control voltage range
Relative duty at rated voltage 1&2-pole/3&4-pole
Maximum continuous time of coil excitation
Minimum duration of command impulse / pause
Operating temperature range
Maximum load of illuminated push-buttons
- Without parallel compensating capacitor
- With 1µF/250V capacitor parallel to coil
- With 2.2µF/250V capacitor parallel to coil
Maximum coil power loss at Un and In
Maximum control line capacitance
Screws
Terminal capacity: min
max
(1) Guaranteed at maximum switching frequency.
More technical data
Dimensions
D.10
website
pg D.38
Redline
Pulsar S
10A
16A
25A
0.5 mm/AgCdO 10
3 mm
250V
400V
10A/250V
1000W
1000W
1000W
Not allowed
700W; ION ≤ 70A/10 ms
650W
100W
4V/10mA
1000/h
>107
>105
>104
>105
Pozidriv 1
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
3 mm/AgSnO2
> 6 mm
400V
400V
16A/250V; 10A/400V
10A (2300W)
16A (3500W)
10A (1300W)
4A (500W)
10A (2300W); ION ≤ 140A/10 ms
10A (1300W)
100W
6V/50mA
1000/h
>106
>105
> 2x104
>105
Pozidriv 1
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
2x2 mm/AgSnO2
> 6 mm
400V
400V
25A/250V; 16A/400V
16A (3600W)
25A (5500W)
16A (2000W)
8A (1000W)
10A (2300W); ION ≤ 140A/10 ms
16A (2000W)
150W
12V/150mA
1000/h
>106
>105
> 2x104
>105
Pozidriv 1
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
0.9 ... 1.1xUn
100%
50 ms / 800 ms
-20 ... +50°C
0.9 ... 1.1xUn
100% / 60%
100% for 1&2 poles, 1h for 4 poles
50 ms / -5 ... +50°C
0.9 ... 1.1xUn
100% / 60%
100% for 1&2 poles, 1h for 4 poles
50 ms / -5 ... +50°C
30mA
3.5W
Pozidriv 1
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
5mA
10mA
15mA
7W for 1 pole, 10 for 2 poles, 20 for 4 poles
0.06µF (= ±200 m.)
Pozidriv 1
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
5mA
10mA
15mA
7W for 1 pole, 10 for 2 poles, 20 for 4 poles
0.06µF (= ±200 m.)
Pozidriv 1
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
A
B
C
D
E
F
G
X
1. Special care must be taken when connecting electromechanical impulse switches with central command. Terminals A1, B1 and C1 must be connected to the same voltage (I.e.
live), whereas A2 must be connected to the opposite voltage (I.e. neutral). Incorrect connection I.e. different voltages on A1, B1 and C1 will destroy the central command circuit
immediately after energising.
2. If several impulse switches are going to be permanently energised, please ensure that there is adequate ventilation in accordance with the power loss calculation.
As a rule of thumb, use a 1/2 mod spacer every 2nd impulse switch when continuously energised.
D.11
Redline
Pulsar S - Impulse switches
Comfort functions
Electromechanical
A
B
C
D
E
F
G
X
Electromechanical
Step-by-step / Multi-circuit
D.12
Nominal
current
Contact
combination
Coil
voltage
AC/DC
Number of
modules
Ref. No.
Pack.
16A
16A
16A
16A
16A
16A
16A
16A
1NO
1NO
1NO
1NO
1NO
1NO
1NO
1NO
8V
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
1
PLS 16 10 008 A
PLS 16 10 012 A
PLS 16 10 024 A
PLS 16 10 048 A
PLS 16 10 230 A
PLS 16 10 240 A
PLS 16 10 012 D
PLS 16 10 024 D
666330
666210
666214
666216
666212
666213
666211
666215
12
12
12
12
12
12
12
12
16A
16A
16A
16A
16A
16A
16A
16A
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
1NO 1NC
8V
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
1
PLS 16 11 008 A
PLS 16 11 012 A
PLS 16 11 024 A
PLS 16 11 048 A
PLS 16 11 230 A
PLS 16 11 240 A
PLS 16 11 012 D
PLS 16 11 024 D
666332
666217
666221
666223
666219
666220
666218
666222
12
12
12
12
12
12
12
12
16A
16A
16A
16A
16A
16A
16A
16A
2NO
2NO
2NO
2NO
2NO
2NO
2NO
2NO
8V
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
1
PLS 16 20 008 A
PLS 16 20 012 A
PLS 16 20 024 A
PLS 16 20 048 A
PLS 16 20 230 A
PLS 16 20 240 A
PLS 16 20 012 D
PLS 16 20 024 D
666331
666224
666228
666230
666226
666227
666225
666229
12
12
12
12
12
12
12
12
16A
16A
16A
16A
16A
16A
16A
16A
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
2NO 2NC
8V
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
AC
DC
DC
2
2
2
2
2
2
2
2
PLS 16 22 008 A
PLS 16 22 012 A
PLS 16 22 024 A
PLS 16 22 048 A
PLS 16 22 230 A
PLS 16 22 240 A
PLS 16 22 012 D
PLS 16 22 024 D
666333
666231
666235
666237
666233
666234
666232
666236
6
6
6
6
6
6
6
6
16A
16A
16A
16A
16A
16A
16A
16A
4NO
4NO
4NO
4NO
4NO
4NO
4NO
4NO
8V
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
AC
DC
DC
2
2
2
2
2
2
2
2
PLS 16 40 008 A
PLS 16 40 012 A
PLS 16 40 024 A
PLS 16 40 048 A
PLS 16 40 230 A
PLS 16 40 240 A
PLS 16 40 012 D
PLS 16 40 024 D
666334
666238
666242
666244
666240
666241
666239
666243
6
6
6
6
6
6
6
6
25A
25A
25A
25A
25A
25A
25A
1NO
1NO
1NO
1NO
1NO
1NO
1NO
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
PLS 25 10 012 A
PLS 25 10 024 A
PLS 25 10 048 A
PLS 25 10 230 A
PLS 25 10 240 A
PLS 25 10 012 D
PLS 25 10 024 D
666245
666249
666251
666247
666248
666246
666250
12
12
12
12
12
12
12
25A
25A
25A
25A
25A
25A
25A
2NO
2NO
2NO
2NO
2NO
2NO
2NO
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
DC
DC
1
1
1
1
1
1
1
PLS 25 20 012 A
PLS 25 20 024 A
PLS 25 20 048 A
PLS 25 20 230 A
PLS 25 20 240 A
PLS 25 20 012 D
PLS 25 20 024 D
666252
666256
666258
666254
666255
666253
666257
12
12
12
12
12
12
12
25A
25A
25A
25A
25A
25A
25A
4NO
4NO
4NO
4NO
4NO
4NO
4NO
12V
24V
48V
230V
240V
12V
24V
AC
AC
AC
AC
AC
DC
DC
2
2
2
2
2
2
2
PLS 25 40 012 A
PLS 25 40 024 A
PLS 25 40 048 A
PLS 25 40 230 A
PLS 25 40 240 A
PLS 25 40 012 D
PLS 25 40 024 D
666259
666263
666265
666261
666262
666260
666264
6
6
6
6
6
6
6
16A
16A
16A
16A
1NO 1NO
1NO 1NO
1NO 1NO
1NO 1NO
12V
24V
48V
230V
AC
AC
AC
AC
1
1
1
1
PLS S 16 20 012 A
PLS S 16 20 024 A
PLS S 16 20 048 A
PLS S 16 20 230 A
666316
666319
666320
666317
12
12
12
12
Cat. No.
Redline
Pulsar S - Impulse switches
Electronic
Central command
Nominal
current
Contact
combination
Coil
voltage
AC/DC
Number of
modules
Cat. No.
Ref. No.
Pack.
16A
1NO
12V-230V
AC/DC
1
PLS C 10 10 230 U
666322
12
16A
1NO 1NC
12V-230V
AC/DC
1
PLS C 10 11 230 U
666325
12
16A
2NO
12V-230V
AC/DC
1
PLS C 10 20 230 U
666328
12
Add-on modules for electromechanical impulse switches
Contact
combination
Coil
voltage
AC/DC
Number of
modules
Cat. No.
Ref. No.
Pack.
4A
1NO 1NC
-
-
0.5
PLS 04 11
666207
12
Pulsar S
Add-on auxiliary contact
(left mounting)
Nominal
current
A
Accessories
Spacer
Number of
modules
Cat. No.
Ref. No.
Pack.
0.5
PLS SP
666206
12
B
C
D
E
F
G
X
D.13
Redline
Staircase Switches
Pulsar TS
Comfort functions
Function
A
Push-button operated single-shot timer, switching the power to the load
after the push-button has been pushed briefly, and switching off again
after the presetted time has elapsed.
Applications
Lighting or ventilation of staircases, basements, halls, etc.
Standards
User adjustable time. Electromechanical or digital clockwork. Manual
override off or on possible at all times. 3 or 4 wire wiring possible. Device
with pre-extinction warning available. The safety terminals are equipped
with captive Pozidriv screws and have IP20 protection degree.
B
C
Features
VDE 0632, BS EN 60669-1
More technical data
Dimensions
website
pg D.39
Performance
D
PLT S EM
PLT S EF
3mm/AgSnO2
400V
16A/250V
2300W
3500W
1300W
1000W
2300W; ION ≤ 140A/10ms
1300W
6V/50mA
0.5 … 5min.
>5x104
>5x104
>2x104
>5x104
Pozidriv 1
1x0.5mm2
1x6mm2 or 2x2.5mm2
0.5mm/AgSnO2
400V
16A/250V
2000W
1000W
1000W
500W
700W; ION ≤ 70A/10ms
650W
4V/10mA
0.5 … 12min.
>107
>105
>104
>105
Pozidriv 1
1x0.5mm2
1x6mm2 or 2x2.5mm2
0.9…1.1xUn
100%
50ms / 50ms
-5...+60°C
50mA
1A
Pozidriv 1
1x0.5mm2
1x6mm2 or 2x2.5mm2
0.9…1.1xUn
100%
50ms / 50ms
-20...+50°C
150mA
330mA
20mA
Pozidriv 1
1x0.5mm2
1x6mm2 or 2x2.5mm2
Contacts
E
F
G
X
Contact spacing / material
Isolation voltage contact/contact
Switching capacity
Incandescent lamp load
Fluorescent lamp load, lead-lag circuit
Fluorescent lamp load, inductive or capacitive
Fluorescent lamp load, parallel compensated
Electronic ballast load
Inductive load, cos ϕ = 0.6 at 230V
DC switching capacity
Minimum contact load
Time range
Mechanical service life(1)
Electrical service life, cos = 1(1)
Electrical service life, cos ϕ = 0.6(1)
Electrical service life, 1000W incandescent lamp(1)
Screws
Terminal capacity: min
max
Control system
Control voltage range
Relative duty at rated voltage
Minimum duration of command impulse
Operating temperature range
Power consumption
Maximum load of illuminated push-buttons
Inrush current at 230V (first µs)
Continuous excitation current
Screws
Terminal capacity: min
max
(1) Guaranteed at a switching frequency of 1000/h
D.14
Redline
Pulsar TS - Staircase switches
Delay
Nominal
current
Contact
combination
Operating
voltage
Number of
modules
Cat. No.
Ref. No.
Pack.
Electromechanical
0.5...12 min.
16A/250V
1NO
230V
1
PLT S EM
666510
12
Electronic Flasher
0.5...12 min.
16A/250V
1NO
230V
1
PLT S EF
666518
1
Pulsar TS
A
B
C
Selection knob of type PLT S EM
D
E
F
G
Staircase function
X
Staircase function plus switch off warning
Staircase function plus push-button continuous light
Staircase function plus switch off warning and push-button continuous light
Sign for continuous light
Sign for push-button 230V
Sign for glow lamp max. load 150mA
Lamp connection
D.15
Redline
Time Relays
Pulsar T
Comfort functions
Applications
From the delayed lighting of driveways (to avoid unnecesary on/off
switching), to after-circulation of a pump (to build in some hysteresis,
again to avoid continuous on/off switching) to the post-present
ventilation of a meeting-room.
Features
Function
A
Conditioning of incoming
impulses to exact predictable
output impulses.
B
Standard
Devices with delay on (ON), delay off (OFF), combined on-off-delay (OO),
astable (AS), positive edge single shot (PS) negative edge single shot (NS)
and even with all the above combined in one multi-function (MF) device
are available. User presettable prescaler and time. In the case of the
multi-function relay, the function itself is also user selectable. All devices
have an internal step-down voltage converter. Therefore an AC as well as
a DC supply and a very wide range of supply-voltages can be used to
operate those devices. The loss-proof safety terminals are equipped with
Pozidriv screws and have IP20 protection degree.
IEC 60669-2-3
C
D
E
F
G
X
Performance
Electronic time relays with simple or multifunction
Contacts
Contact spacing / material
Spacing between control and load circuit
Isolation voltage contact/contact
Isolation voltage contact/magnetic system
Switching capacity
Incandescent lamp load
Fluorescent lamp load, lead-lag circuit
Fluorescent lamp load, inductive or capacitive
Fluorescent lamp load, parallel compensated
Electronic ballast load
Inductive load, cos ϕ = 0.6 at 230V
DC switching capacity
Minimum contact load
Time range
Mechanical service life (1)
Electrical service life, cos ϕ = 1 (1)
Electrical service life, cos ϕ = 0.6 (1)
Electrical service life, 1000W incandescent lamp (1)
Screws
Terminal capacity: min
max
0.5mm/AgSnO2
3mm
250V
250V
10A/250V
1000W
1000W
1000W
500W
700W; ION ≤ 70A/10 ms
650W
100W
4V/10mA
0.1s. ... 40h
>107
>105
>104
>105
Pozidriv 1
1x0.5 mm2
1x12 mm2 or 2x6 mm2
Control system
Control voltage range
Relative duty at rated voltage
Minimum duration of command impulse
Operating temperature range
Power consumption
Maximum load of illuminated push-buttons
Inrush current at 230V (first µs)
Screws
Terminal capacity: min
max
(1) Guaranteed at a switching frequency of 1000/h.
D.16
12 ... 230VUC (=DC or AC 50/60Hz)
100%
50ms
-20 ... +50°C
0.2 ... 2.5W
NOT ALLOWED
6 ... 25mA for all voltage-range
Pozidriv 1
1x0.5 mm2
1x12 mm2 or 2x6 mm2
Redline
Pulsar T - Time relays
Contact
combination
Operating
voltage
AC/DC
Number of
modules
Cat. No.
Ref. No.
Pack.
Delay On
10A/250V
1CO
12 ... 230V
AC/DC
1
PLT ON
666622
12
Delay Off
10A/250V
1CO
12 ... 230V
AC/DC
1
PLT OF
666621
12
Delay On/Off
10A/250V
1CO
12 ... 230V
AC/DC
1
PLT OO
666627
12
Pulsar T
Switching
capacity
A
B
Positive edge single shot
10A/250V
1CO
12 ... 230V
AC/DC
1
PLT PS
666625
12
C
D
Negative edge single shot
10A/250V
1CO
12 ... 230V
AC/DC
1
PLT NS
666624
12
E
F
Symmetrical flasher
10A/250V
1CO
12 ... 230V
AC/DC
1
PLT AS
666620
12
G
X
Multifunction
10A/250V
1CO
12 ... 230V
AC/DC
1
PLT MF
666623
12
D.17
Redline
Analogue Time Switches
Classic
Comfort functions
Features
A
Very easy programming by means of mechanical switches on a dial,
but with restricted possibilities compared to the digital time switches.
Both devices with 1 dial for programming of daily or weekly events, as
well as devices with 2 dials for 2 channel daily events and combined daily
and weekly events are available in 2 versions: quartz and net
synchronised, with and without running reserve respectively.
Manual override Off or On is possible at all times. All devices are sealable.
Applications
Function
Pre-programmed switching of all
kinds of electrical devices.
Going from the pre-programmed switching of lighting (car park,
advertising signs, public roads, etc.) over pre-programmed switching of
heating equipment (home and work-environment , waterheating, etc.), to
the pre-programmed switching of motors for pumps and fans and even to
presence simulation.
B
Standards
C
VDE 0633, BS EN 60730-1, BS EN 60730-2-7
D
Performance
Plastic switches
Metallic switches
Net
synchronised
1 module
Net
synchronised
3&6 modules
Quartz
synchronised
1 module
Quartz
synchronised
3&6 modules
Net
synchronised
3 modules
Quartz
synchronised
Voltage free NO
Not fix off
Voltage free CO
yes
Voltage free NO
Not fix off
Voltage free CO
yes
Voltage free CO
yes
Voltage free CO
yes
16A/250V
4A/250V
1000W
30min.
Pozidriv 1
1x0.5mm2
1x6 or 2x2.5mm2
16A/250V
4A/250V
1350W
30min.
3h
Pozidriv 1
1x0.5mm2
1x6 or 2x2.5mm2
16A/250V
4A/250V
1000W
30min.
Pozidriv 1
1x0.5mm2
1x6 or 2x2.5mm2
16A/250V
4A/250V
1350W
30min.
3h
Pozidriv 1
1x0.5mm2
1x6 or 2x2.5mm2
16A/250V
4A/250V
1350W
15min.
2h
Pozidriv 1
1x0.5mm2
1x6 or 2x2.5mm2
16A/250V
2A/250V
1350W
15min.
2h
Pozidriv 1
1x0.5mm2
1x6 or 2x2.5mm2
220 - 240V 50Hz
1VA
-20...+55°C
net synchronised
yes
Pozidriv 1
1x0.5mm2
1x6 or 2x2.5mm2
230V - 130VDC
230V 50/60Hz
220 - 240V 50Hz
230V - 130VDC
230V 50Hz
1VA
1VA
1VA
1VA
1VA
150h
300h
150h
70h
72h
70h
-20...+55°C
-20...+55°C
-20...+55°C
-20...+55°C
-20...+55°C
net synchronised ±2.5s./day at 20°C ±2.5s./day at 20°C ±2.5s./day at 20°C ±2.5s./day at 20°C
yes
yes
yes
yes
yes
Pozidriv 1
Pozidriv 1
Pozidriv 1
Pozidriv 1
Pozidriv 1
1x0.5mm2
1x0.5mm2
1x0.5mm2
1x0.5mm2
1x0.5mm2
1x6 or 2x2.5mm2 1x6 or 2x2.5mm2 1x6 or 2x2.5mm2 1x6 or 2x2.5mm2 1x6 or 2x2.5mm2
E
Contacts
F
G
X
Contact
Fix on, Fix off, Auto switch
Rated switching capacity
- Resistive load
- Inductive load (cos ϕ = 0.6)
- Incandescent lamps
Shortest switching time day-program
Shortest switching time week-program
Screws
Terminal capacity: min
max
Clockwork
Operating voltage
Own consumption at 230V
Running reserve
Battery charging time
Operating temperature range
Accuracy
Sealable
Screws
Terminal capacity: min
max
More technical data
Dimensions
D.18
website
pg D.39
Redline
Classic - Analogue time switches
NET SYNCHRONISED
Week programmable
Ref. No. Pack.
No. of
channels
Nominal
current
Operating
voltage
1x24x2
1x24x2
1x24x4
1NO
1CO
1CO
16A/250V
16A/250V
16A/250V
220 ... 240V 50Hz
220 ... 240V 50Hz
230V 50Hz
-
30min.
30min.
15min.
Not "OFF"
yes
yes
1
3
3
CLS S 11 D
CLS S 31 D
CLS S 31 D M
666111
666112
666113
1
1
1
1CO
1CO
16A/250V
16A/250V
220 ... 240V 50Hz
230V 50Hz
-
3h
2h
yes
yes
3
3
CLS S 31 W
666114
CLS S 31 W M 666115
1
1
1NO
1CO
1CO
16A/250V
16A/250V
16A/250V
130VDC/ 230V
130VDC/ 230V
230V
50h
150h
300h
30min.
30min.
15min.
Not "OFF"
yes
yes
1
3
3
CLS Q 11 D
666105
CLS Q 31 D
666104
CLS Q 31 D M 666106
1
1
1
1NO
7x24/3
7x24/2
Running Shortest Fix on/off No. of
reserve switch time auto
mod.
Cat. No.
Program
Day programmable
1CO
QUARTZ SYNCHRONISED
Day programmable
1x24x2
1x24x2
1x24x4
Classic
1CO
A
1NO
Week programmable
7x24/3
7x24/3
1CO
1CO
1CO
16A/250V
16A/250V
130VDC/ 230V
230V
150h
300h
3h
2h
yes
yes
3
3
CLS Q 31 W
666109
CLS Q 31 W M 666110
1
1
B
C
D
1CO
Day-Day
programmable
1x24x2 + 1x24x2
2CO
16A/250V
130VDC/ 230V
150h
30/30min.
yes
6
CLS Q 62 DD
666103
1
E
F
1CO
Day-Week
programmable
1x24x2 + 7x24/3
2CO
16A/250V
130VDC/ 230V
150h
30min./3h
yes
6
CLS Q 62 DW
666108
1
G
X
1CO
Accessories
Surface mounting set
No. of
mod.
Cat. No.
1
3
6
SMS 1
SMS 3
SMS 6
Ref. No. Pack.
666100
666101
666102
1
1
1
D.19
Redline
Digital Time Switches
Comfort functions
Galax
A
Applications
Going from the pre-programmed switching of lighting (car park,
advertising signs, public roads, etc.) over pre-programmed switching of
heating equipment (home and work environment , water heating, etc.), to
the pre-programmed switching of motors for pumps and fans
and even to random presence simulation.
Function
Pre-programmed switching of all
kinds of electrical devices.
B
C
D
Features
Very easy programming, with quasi unlimited possibilities compared to
the analogue time switches. Devices with daily, weekly and yearly event
programming possibilities are available in 1, 2 and 4 channel execution.
All devices have a shortest switching time of one minute, some of them
even one second, and are all internally quartz-synchronized, some of
them with the possibility of being DCF77-synchronized. On some devices,
the summer/winter time change is fully automatic. Devices with blockprogramming, holiday, random and impulse-function are available.
Manual On or Off override is possible at all times and all devices are
sealable.
Standards
E
BS EN-60730-1, BS EN-60730-2-7, VDE 0633
Performance
F
G
X
Contacts
Contact
Rated switching capacity
- Resistive load
- Inductive load (cos ϕ = 0.6)
- Incandescent lamps
DC switching capacity
Shortest switching time
Screws
Terminal capacity: min
max
Voltage-free changeover
16A/250V
2.5A/250V
1000W
On request
depending on type: 1min. or 1s.
Pozidriv 1
1x0.5mm2
1x6mm2 or 2x2.5mm2
Clockwork
Operating voltage
Own consumption at 230V
Running reserve (at 20º C)
Battery
Operating temperature range
Accuracy
Sealable and unloosable cover
Screws
Terminal capacity: min
max
More technical data
Dimensions
D.20
220 - 240V 50-60Hz
5VA
1 module device: 150h / 2&3 modules: 3 years / 6 modules:6 years
Lithium ( except 1 module device )
-25...+55°C
±2.5s./day at 20°C / 6 modules device: ±1s./day at 20ºC
yes
Pozidriv 1
1x0.5mm2
1x6mm2 or 2x2.5mm2
website
pg D.39
Redline
Galax - Digital time switches
QUARTZ SYNCHRONISED
Day programmable
Program
1x24x60
No. of Switching
channels capacity
Operating
voltage
Running Shortest No. of proreserve switch time gram steps
No. of
mod.
Cat. No.
Ref. No. Pack.
1CO
16A/250V
220 ... 240V
3yr
1min.
12
2
GLX Q 21 D 12
666186
1
7x24x60
1CO
16A/250V
220 ... 240V
150h
1min.
42
1
GLX Q 11 W 42
666187
1
7x24x60
7x24x60
7x24x60
7x24x60
1CO
2CO
1CO
2CO
16A/250V
16A/250V
16A/250V
16A/250V
220 ... 240V
220 ... 240V
220 ... 240V
220 ... 240V
3yr
3yr
3yr
3yr
1min.
1min.
1s.
1s.
20
30
30
40
2
2
2
2
GLX Q 21 W 20
GLX Q 22 W 30
GLX Q 21 W 30
GLX Q 22 W 40
666188
666190
666189
666191
1
1
1
1
16A/250V
16A/250V
220 ... 240V
220 ... 240V
6yr
6yr
1s.
1s.
400
400
6
6
GLX Q 62 W 400 666192
GLX Q 64 W 400 666193
1
1
1CO
Day/Week
programmable
7x24x3600
7x24x3600
2CO
2CO
4CO
Galax
1CO
A
2CO
Day/Week/Year
programmable
365x24x3600
365x24x3600
4CO
2CO
4CO
16A/250V
16A/250V
220 ... 240V
220 ... 240V
6yr
6yr
1s.
1s.
400
400
6
6
GLX Q 62 Y 400
GLX Q 64 Y 400
666194
666195
1
1
B
C
2CO
4CO
D
Accessories
Battery
for 2 and 6 module devices
No. of
mod.
Cat. No.
Ref. No. Pack.
-
GLX BAT
666180
E
1
F
DCF-77 antenna
for year programmable time switches
-
GLX DCF
666181
1
G
X
Programming
tools
Surface mounting set
for 6 module devices
-
GLX PRG
666182
1
1
3
6
SMS 1
SMS 3
SMS 6
666100
666101
666102
1
1
1
D.21
Redline
Time Switches
Comfort functions
72 X 72 Classic and Galax
Applications
Going from the pre-programmed switching of lighting (car park,
advertising signs, public roads, etc.) over pre-programmed switching of
heating equipment (home and work environment , water heating, etc.), to
the pre-programmed switching of motors for pumps and fans
and even to random presence simulation.
A
Features
B
Very easy programing by means of mechanical switches or digital
buttons. Devices with daily and weekly event programing possibilities.
Analogue devices have a shortest switching time of 15 minutes and
digital device has 1 minute.
C
Function
D
Pre-programmed switching of all kind of electrical devices.
E
Performance
F
G
X
D.22
Weekly timers
Code
Type
Running reserve
Shortest switch time
Modules
Nominal current
Accuracy
Number of channels
Operating voltage
Fix on/off auto
Flush mounting
Surface mounting
DIN-rail mounting
Number of memory position
666176
CLS 72Q41W
150 h
2h
4
16A/250V
<2.5 s/day
1CO
220-240VAC/50-60Hz
yes
yes
yes
yes
-
666175
CLS72S41W
2h
4
16A/250V
<2.5 s/day
1CO
220-240VAC/50-60Hz
yes
yes
yes
yes
-
Daily timers
666178
CLS72Q41D
150 h
15 min
4
16A/250V
<2.5 s/day
1CO
220-240VAC/50-60Hz
yes
yes
yes
yes
-
666177
CLS72S41D
15 min
4
16A/250V
<2.5 s/day
1CO
220-240VAC/50-60Hz
yes
yes
yes
yes
-
Daily/weekly timer
666179
GLX72Q41DW
150 h
15 min
4
16A/250V
<2.5 s/day
1CO
220-240VAC/50-60Hz
yes
yes
yes
yes
20
Redline
72 X 72 Classic - Analogue time switches
Program
No. of
channels
Nominal
current
Operating
voltage
Running Shortest Fix on/off No. of
mod.
reserve switch time auto
Day program
1x24
1x24
1CO
1CO
16A/250V
16A/250V
220...240 VAC
220...240 VAC
150 h
15 min
15 min
yes
yes
4
4
CLS72S41D
CLS72Q41D
666177
666178
1
1
Week program
7x24
7x24
1CO
1CO
16A/250V
16A/250V
220...240 VAC
220...240 VAC
150 h
2h
2h
yes
yes
4
4
CLS72S41W
CLS72Q41W
666175
666176
1
1
Cat. No.
Ref. No. Pack.
Day-Week program
Program
No. of
channels
Nominal
current
Operating
voltage
1x24/7x24
1CO
16A/250 V
220 240VAC
Running Shortest Fix on/off No. of
reserve switch time auto
mod.
150 h
72 x 72 Classic & Galax
A
72 X 72 Galax - Digital time switches
1 min
yes
4
Cat. No.
Ref. No. Pack.
GLX72Q41DW 666179
1
B
C
D
E
F
G
X
D.23
Redline
Light Sensitive Switches
Galax LSS
Comfort functions
Applications
A
Control of lighting in shop windows, offices, car parking areas, controlling
street lights, advertising signs, sun blinds, shutters, or even lighting in a
home to simulate the presence of people.
Features
User presettable switch light intensity, intensity range and hysteresis
(to avoid on/off a stable behavior). Reaction time is also user presettable.
1 channel, 2 channel and 1 channel with incorporated digital time switch
with week-cycle, all with separate photocell are available besides a 1
channel all-in-one device.
Standards
VDE 0632, VDE 0633,
BS EN 60669-1
Function
B
Electronic switch controlled by the intensity of the ambient light , detected
by a separate or integrated photocell (depending on the model). When the
light intensity drops below the threshold setting, the switch changes its
state to the on position. An increasing ambient light intensity eventually
will switch off the device again.
C
Performance
D
1 channel
2 channel
1 channel + digital time
switch
1 channel
wall mounting
1 Voltage-free contact NO
Voltage-free change over
Voltage-free change over
1 Voltage-free contact NO
Contacts
E
F
G
Contact
Switching capacity
- Resistive load
- Inductive load (cos ϕ = 0.6)
- Incandescent lamps
Switching capacity
Shortest switching time
Screws
Terminal capacity: min
max
16A/250V
8A/250V
2000W
10A/250V
16A/250V
8A/250V
8A/250V
2000W
2000W
800mA at 24V, 300mA at 60V; 150mA at 220V
1 min.
Pozidriv 1
Pozidriv 1
Pozidriv 1
1x0.5 mm2
1x0.5 mm2
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
1x6 mm2 or 2x2.5 mm2
1x6 mm2 or 2x2.5 mm2
10A/250V
2A/250V
1200W
Not allowed
Slot head
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
Light sensitive operating part
X
2 ... 500 lux
Light intensity switching range
Switching hysteresis
On/Off switching delay
Light sensitive sensor wire-length
Light sensitive sensor protection degree
Operating voltage
Own consumption at 230V
Running reserve
Battery
Operating temperature range
Accuracy
Sealable
Screws
Terminal capacity: min
max
More technical data
Dimensions
D.24
website
pg D.39
100 s. On
100 s. Off
max 100m
IP65
220/240V 50/60Hz
5VA
-20 ... +55°C
yes
Pozidriv 1
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
2 ... 500 lux
2 ... 500 lux
30% above On-switching point
Use presettable from
Use presettable from
0 to 100 s.
0 to 100 s.
max 100 m
max 100 m.
IP65
IP65
230V 50/60Hz
230V 50/60Hz
2.5VA
2.5VA
3 years at 20°C
Lithium
-20 ... +55°C
-10 ... +55°C
±2.5 s./day at 20°C
yes
yes
Pozidriv 1
Pozidriv 1
1x0.5 mm2
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
1x6 mm2 or 2x2.5 mm2
2 ... 2000 lux
50 s. On
50 s. Off
IP54 (complete device)
220/240V 50/60Hz
6VA
-35 ... +60°C
Slot head
1x0.5 mm2
1x6 mm2 or 2x2.5 mm2
Redline
Galax LSS - Light sensitive switches
DIN rail mounting,
separate photocell
included
No. of
channels
Nominal
current
Operating
voltage
No. of
modules
Cat. No.
Ref. No.
Pack.
2 ... 500 lux
1NO
16A/250V
230V
1
LSS 11
666361
1
2 ... 500 lux
2CO
16A/250V
230V
3
LSS 32
666362
1
2 ... 2000 lux
1NO
16A/250V
230V
-
LSS W
666364
1
Galax LSS
Wall mounting,
photocell
incorporated
Program
A
GALAX – Light sensitive switches with digital clock
Program Number of Nominal OperatingRunning Shortest
No. of
channels current voltage reserve switch time program steps
DIN rail mounting, separate photocell
included with digital clock
2 ... 500 lux
& 7x24x60
1CO
16A/250V
230V
3yr
1 min.
No. of Cat. No. Ref. No. Pack.
mod.
30
3
LSS 31 666363
1
B
C
D
E
F
Accessories
No. of
modules
Cat. No.
Ref. No.
Pack.
Photocell
(spare part)
-
LSS LDR
666358
1
Tinted cover
-
-
601795
1
Surface mounting set
1
3
SMS 1
SMS 3
666100
666101
1
1
G
X
D.25
Redline
Transformers
Comfort functions
Series T
A
B
C
Function
Applications
Reducing the voltage to a very low
(safety) voltage used mainly as
control-voltage in order to reduce
the risk of electrocution due to
environmental circumstances
(I.e. high degree of humidity like outdoors, in a swimming pool complex,
etc.).
Features
Approvals (1)
Safety transformers have short-circuit protection and continuous nominal
power. Bell transformers are recommended for intermittent use at the
nominal power declared (50% for continuous use). Devices with integrated
on/off switch or with integrated buzzer are available. Complete noiseless
operation. Full power available at all secondary voltages. The safety
terminals are equipped with captive Pozidriv screws and have IP20
protection degree.
D
E
F
G
X
Standards
(1) Depending on the type
IEC 61558-1-2-6: Safety transformer
IEC 61558-1-2-8: Bell transformer
Performance
Nominal primary voltage and frequency
Secondary voltage at nominal primary voltage
Maximum secondary voltage at zero load
Minimum secondary voltage at nominal load
Maximum load
Short-circuit protection
Operating temperature
Isolation voltage
Protection degree
Screw
Terminal capacity: min
max
More technical data
Dimensions
D.26
Going from supplying power to a bell circuit , to supplying power to the
control circuit of impulse switches, relays or contactors for the control of
lighting, heating, etc.
website
pg D.41
Bell transformer
Safety transformer
230V 50Hz / 240V 60Hz
8 or 12V
1.5xUn sec.
0.85xUn sec.
Nominal power
PTC
-20…+40°C
4kV
IP 20
Pozidriv 1
1x1mm2
1x16mm2 or 2x6mm2
230V 50Hz / 240V 60Hz
12 or 24V
1.05xUn sec.
1xUn sec.
Nominal power
PTC
-20…+40°C
4kV
IP 20
Pozidriv 1
1x1mm2
1x16mm2 or 2x6mm2
Redline
Series T - Transformers
Output
power
Secondary
voltages
Primary
voltage
Number of
modules
5VA
10VA
15VA
8/12V
8/12V
8/12V
220..240V
220..240V
220..240V
8VA
16VA
30VA
12/24V
12/24V
12/24V
Bell transformer
Integrated on-off switch
8VA
Safety transformer
15VA
Bell transformer
Cat. No.
Ref. No.
Pack.
2
2
2
TR B 5
TR B 10
TR B 15
666638
666636
666637
1
1
1
220..240V
220..240V
220..240V
2
2
2
TR B 8
TR B 16
TR B 30
666650
666651
666652
1
1
1
8/12V
220..240V
2
TR B 8S
666640
1
12/24V
220..240V
3
TR S 15
666641
1
5VA, 10VA, 15VA
8VA, 16VA, 30VA
Series T
A
B
25VA
40VA
12/24V
12/24V
220..240V
220..240V
4
4
TR S 25
TR S 40
666642
666643
1
1
C
D
63VA
12/24V
220..240V
6
TR S 63
666644
20
E
F
Buzzers
Buzzer
Buzzer
220..240V
12V
1
1
BU 230
BU 12
666629
666630
12
12
G
X
Bells
Bell
Bell
220..240V
12V
1
1
BE 230
BE 12
666632
666633
12
12
D.27
Redline
Measurement Instruments
Series MT
Comfort functions
Applications
A
B
C
Measurement of all possible electrical values from simple measurement as
voltage, current, frequency over more complex such as power and energy,
to all-in-one measurement with the netanalysing devices. To avoid downtime due to abnormal situations, i.e. power-supply voltage too high,
absorbed power too high, etc., leading to malfunctionning and even breakdown of the machinery, the measurement and monitoring of the electrical
values like voltage, current, power, energy etc. is an absolute must and even
an indespensable asset when it comes to preventive maintenance.
Function
Features
Measurement , visualisation and
logging of voltage, current ,
frequency, hours of operation,
power, energy, cos ϕ , etc.
Standards
EN 61010-1, BS EN 60051-1-2
D
E
Performance
F
Readout
G
X
Scale selection
Own consumption current meters
Own consumption other meters
Operating temperature range
Test voltage
Class of precision (accuracy)
Overload current coils
- 1 second
- Continuous
Overload voltage coils
- 0.5 second
- Continuous
Vibration resistance
D.28
Analogue instruments
Polycarbonate+carbon needle
Digital instruments
3digit 7segment LED
Net analyser
LCD display
Interchangeable
scaleplate
0.3VA
1.5VA
-10 ... +55ºC
2000V at 50Hz during 1 minute
1.5
(0.5 for frequency meter)
Dip-switches
Dip-switches
0.5VA
1.5VA
-10 ... +55ºC
2000V at 50Hz during 1 minute
0.5%
±1 digit referred to full scale
-10 ... +55ºC
2000V at 50Hz during 1 minute
0.5%
±1 digit referred to full scale
10xIn
2xIn
10xIn
2xIn
10xIn
2xIn
2xUn
2xUn
2xUn
1.2xUn
1.2xUn
1.2xUn
0.35 mm at 10/55Hz on 3 axes, 0.35 mm at 10/55Hz on 3 axes, 0.35 mm at 10/55Hz on 3 axes,
duration of 6 hours
duration of 6 hours
duration of 6 hours
50g
50g
50g
IP40
IP40
IP40
Pozidriv 1
Pozidriv 1
Pozidriv 1
1x1 mm2
1x1 mm2
1x1 mm2
1x16 mm2 or 2x6 mm2
1x16 mm2 or 2x6 mm2
1x16 mm2 or 2x6 mm2
Shock resistance
Protection degree
Screws
Terminal capacity: min
max
More technical data
Dimensions
AC measurement devices with analogue as well as with digital technology and
readout are available. The simple devices (one measurement only i.e. voltage,
current, frequency) are only available in single phase, while the complex
devices (more than one measurement i.e. power, energy, netanalyser) are also
available in 3-phase execution. High currents can be measured through the
intermediate use of a current transformer (for the analogue amp-meter
combined with an interchangeable scale-plate). All devices have very good
precision and have also a very low self-consumption to limit as much as
possible the measurement error. Using one monophase-volt or amp-meter in a
3-phase system is possible by using the appropriate selector switch.
The energy meters as well as the netanalysers are true RMS measuring
devices. Monitoring and logging all electrical values on to a PC is possible by
using the MT PRG software.
website
pg D.41
Redline
Series MT - Analogue measurement instruments
Accuracy
Number of
phases
Number of
modules
Cat. No.
Ref. No.
Pack.
Volt meter
300V
500V
1.5
1.5
1
1
3
3
MT AV 300
MT AV 500
666417
666418
1
1
Ammeter
5A
10A
15A
20A
25A
30A
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1
1
1
1
1
1
1
3
3
3
3
3
3
3
MT AA
MT AA 5
MT AA 10
MT AA 15
MT AA 20
MT AA 25
MT AA 30
666414
666413
666408
666409
666410
666411
666412
1
1
1
1
1
1
1
Series MT
Scale
A
B
C
Frequency meter
45 ... 65Hz
0.5
1
3
MT AF
666415
1
D
E
F
G
Hour counter
230V/50Hz
110V/50Hz
24V/50Hz
-
1
1
1
2
2
2
MT AH
MT AH 110
MT AH 24
666416
666431
666432
1
1
1
X
D.29
Redline
Series MT - Digital measurement instruments
Volt meter
Scale
Accuracy
Number of
phases
Number of
modules
Cat. No.
Ref. No.
Pack.
600V
500V
0.5 ± 1 dig
0.5 ± 1 dig
1
1
3
2
MT DV 600
MT DV 600 2M
666427
666670
1
1
5A
25A
0.5 ± 1 dig
0.5 ± 1 dig
1
1
3
3
MT DA 5
MT DA 25
666420
666419
1
1
5A
25A
0.5 ± 1 dig
0.5 ± 1 dig
1
1
2
2
MT DA 5 2M
MT DA 25 2M
666671
666672
1
1
5A
0.5 ± 1 dig
1
2
MT DA DV 52M
666674
1
40 ... 80Hz
0.5 ± 1 dig
1
3
MT DF
666424
1
40 ... 80Hz
0.5 ± 1 dig
1
2
MT DF 2M
666673
1
9.999kW
999.9kW
1.5
1.5
1
1
3
3
MT DW 110
MT DW 11000
666428
666429
1
1
999.9kW
1.5
3
6
MT DW 31000
666430
1
30A
30A
1.5
1.5
1
1
3
3
MT DE 1
MT DE 1I
666421
666422
1
1
30A
32A
1.5
1.5
1
1
1
2
MT DE 1 1M
MT DE 1I 32A
666675
666434
1
1
5A
1.5
3+N
6
MT DE 3I(1)
666423
1
5A
1.5
3
6
MT DE 3I O
666676
1
5A
5A
5A
1
1
1
1
3(+N)
3(+N)
8
8
6
MT DN 1
MT DN 3
MT DN 3L
666425
666426
666451
1
1
1(2)
666436
1
Comfort functions
Ammeter
Ammeter
and Voltmeter
Frequency meter
A
Watt meter
B
C
D
Energy meter
E
F
G
Net analyser
X
V
Digital multimeter
A
5A (x/5A)
V
A
Var
W
1.5
W
(1) Only for net 3P+N
(2) Oscilloscope function
D.30
Hz
VA
VA
3
Var
Hz
cosϕ
h1...h15%
6
kWh cosϕ
kwh
4 tarifs
kwhr
4 tarifs
MODBUS
MT DN 3R
Redline
Series MT - Current transformer
Accuracy
Cat. No.
Ref. No.
Pack.
40/5A
50/5A
60/5A
80/5A
3
3
3
3
MT CT 40
MT CT 50
MT CT 60
MT CT 80
666381
666383
666385
666387
1
1
1
1
100/5A
150/5A
200/5A
250/5A
300/5A
400/5A
1
1
1
0.5
0.5
0.5
MT CT 100
MT CT 150
MT CT 200
MT CT 250
MT CT 300
MT CT 400
666375
666377
666378
666379
666380
666382
1
1
1
1
1
1
500/5A
600/5A
0.5
0.5
MT CT 500
MT CT 600
666384
666386
1
1
800/5A
1000/5A
0.5
0.5
MT CT 800
MT CT 1000
666388
666376
1
1
1200/5A
1500/5A
2000/5A
0.5
0.5
0.5
MT CT 1200
MT CT 1500
MT CT 2000
666677
666678
666679
1
1
1
40/5A
50/5A
60/5A
80/5A
100/5A
150/5A
200/5A
250/5A
300/5A
400/5A
500/5A
600/5A
800/5A
1000/5A
-
MT SP 40
MT SP 50
MT SP 60
MT SP 80
MT SP 100
MT SP 150
MT SP 200
MT SP 250
MT SP 300
MT SP 400
MT SP 500
MT SP 600
MT SP 800
MT SP 1000
666395
666397
666399
666401
666389
666391
666392
666393
666394
666396
666398
666400
666402
666390
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Accessories
RS485 to RS232
signal converter
Series MT
Interchangeable Ammeter
scaleplates
Scale
A
B
C
D
Number of
phases
Number of
modules
Cat. No.
Ref. No.
Pack.
-
2
MT RSC
666404
1
E
F
G
Selector switch
Amperage
Voltage
3
3
3
3
MT S 4
MT S 7
666405
666406
1
1
X
D.31
Redline
Priority Relays
Control and sequence phase relays
Series PR
Comfort functions
Applications
A
B
C
Function
Priority relays offer the possibility to
limit the energy consumption
in installations with a defined
maximum power. This limitation is
getting measuring the installation
total current continuously and in the
case consumption would be higher
then fixed value, priority relay would
disconnect the non-priority load.
D
In some installations the maximum power is limited by the contracted power
with the electricity company. If this contracted power is surpassed, the main
MCB of the installation opens. Priority relays are used in order to avoid the
opening of the main MCB.
A similar case, for exemple, would be an installation where new loads would
be added without changing the installation (cable sizes, MCB’s...). In this
case a priority relay will be installed before the non priority load that would
be disconnected when the contracted or limited power is surpassed.
Priority... disconnected. The priority relay will realise that the installation
total load will come back to be lower than its..., the non priority load will
come back to be connected.
Characteristics
Priority relay can work in nets with nominal power of 6 kW if we make a
direct connection or higher if we use a current transformer to connect the
priority relay to the net . In each case priority relay could be able to
disconnect loads with a nominal power from 0 to 6kW or from 0% to
100% when current transformer is used.
Standard/Marking
IEC 61095
E
Performance
F
Priority Relay Series PR
230V
Nominal Voltage Un
G
X
Maximum nominal current
Nominal current
Compact capacity
Contact type
Work temperature
Work area
Fixed delay time
Isolation tension (contact-coil)
Isolation class
IP
Electrical endurance
Mechanical endurance
Maximum changeover frequency
Dimensions
D.32
32A direct, 5A with current transformer
2...32A
Pozidriv 1/2x2.5mm2 or 1x6mm2
NC or NO
-20...+55°C
0 to 7 kW
0.5sc
2.5 kV
II
IP20
100,000 ops.
1,000,000 ops.
750 ops./h
pg D.44
Redline
Series PR - Priority relay
Output
number
Module
number
Contact
Cat. No.
Ref. No.
Pack.
1
1
2
2
1NO
1NC
PRI 10
PRI 01
666445
666446
1
1
1 NO
1 NC
Direct insertion
C-T / 5A insertion
Series PR
A
B
C
D
Controls and sequence phase relays
Functions
number
Module
number
Contact
Cat. No.
Ref. No.
Pack.
4
2
3
3
1CO
1CO
MTAP 3N
MTAP 3N2F
666433
666690
1
1
E
F
G
Functions
Phases sequence
Phases presence
Neutral presence
Min. voltage control
Phases sequence
Phases presence
Min. voltage value range
Ref. No.
70-100%
666433
-
666690
X
D.33
Redline
Surge Arresters
Comfort functions
SurgeGuard
A
B
C
Applications
SurgeGuard surge arresters cover the protection of home appliances (TV,
HiFi, VCR, laundry-machine, dishwasher, ...), commercial building
equipment (computer and data communication network, intrusion and fire
alarm system, access-control and building automation system), industrial
equipment (PLC, instrumentation, medical apparatus, monitoring devices)
and even the protection of entire off-shore drilling platforms.
Function
Protection of an electrical
installation and all electrical and
electronic devices connected to this
installation against destructive
overvoltage surges. Such voltage
surges can be generated by
lightning induced currents, by
network-polluting devices such as
motors, frequency-converters,
dimmers etc. and by power supplier
network switching operations.
D
Features
Single and multi-pole devices (for TNC and IT respectively TNS and TT
energy supplier networks); class 1 high energy deviation (10/350) and
class 2 medium energy deviation (3/20) devices available; high current
combined with low protection voltage; plug-in and monoblock devices
both with and without voltage free signalling contact.
In addition, all MOV-based devices have a built-in thermal fuse, to isolate
the device from the rest of the installation in case of short-circuit or thermal
runaway.
A special low energy surge-suppression device (Sine Wave Tracking) is
also part of this range of devices.
Standards
E
NF C61-740, IEC 61643-1
F
Performance
G
X
Class 1
Single pole monoblock
Class 2
Single pole plug-in
Class 2
Multi pole monoblock
Energy impulse wave
Technology
Response time
Thermal fuse
Thermal fuse healty indication
Nominal voltage
Frequency
Protection mode
10/350 µs
Closed spark-gap
<100ns
no
230V
50/60Hz
L-PE and/or N-PE
Useable in network
Operating temperature
Screws
Terminal capacity: min
max
IT, TN-C, TN-S, TT
-30…+75°C
Pozidriv 3
1x2.5mm2
1x50mm2
8x20
MOV
<5ns
yes
Mechanical flag
230V or 400V
50/60Hz
Single mode:
L-to-PE, N-to-PE
IT, TN-C, TN-S, TT
-30…+75°C
Pozidriv 3
1x2.5mm2
1x50mm2
8x20
MOV
<5ns
yes
LED
230V or 400V
50/60Hz
3- or 7-mode:
L-to-PE, L-to-N and N-to-PE
TN-S, TT
-30…+75°C
Pozidriv 3
1x2.5mm2
1x50mm2
More technical data
Dimensions
D.34
website
pg D.46
Redline
Surgeguard - Surge arresters
CLASS 1
Single-Multi pole
monoblock
IIMP
IN
Up
Up
(L-N)
Un
50kA
100kA
100kA
-
4kV
4kV
4kV
-
-
No. of Auxiliary Number of
phases contact modules
1
3
1
-
2
4
2
Cat. No.
Ref. No.
Pack.
VBAB1
VBAB3
VBANPE
560174
560186
544331*
Cat. No.
Ref. No.
Pack.
1
1
1
* N-PE lighting current arresters
CLASS 2
Replacement module
(plug only)
IN
Up
(L-PE)
Up
(L-N)
Un
No. of Auxiliary Number of
phases contact modules
20kA
20kA
5kA
5kA
960V
1580V
-
230V
400V
1
1
-
1
1
SG SP 2 20 2
SG SP 2 20 4
666545
666546
1
1
45kA
45kA
45kA
45kA
10kA
10kA
10kA
10kA
1000V
1000V
1490V
1450V
-
230V
230V
400V
400V
1
1
1
1
1CO
1CO
1
1
1
1
SG SP 2 45 2
SG SP 2 45 2 C
SG SP 2 45 4
SG SP 2 45 4 C
666547
666537
666548
666539
1
1
1
1
65kA
65kA
65kA
65kA
20kA
20kA
20kA
20kA
1200V
1200V
1950V
1950V
-
230V
230V
400V
400V
1
1
1
1
1CO
1CO
1
1
1
1
SG SP 2 65 2
SG SP 2 65 2 C
SG SP 2 65 4
SG SP 2 65 4 C
666549
666542
666551
666544
1
1
1
1
40kA
20kA
1500V
-
230V
1
1CO
1
SG SP NGND PI
666552*
1
20kA
20kA
5kA
5kA
960kA
1580kA
-
230V
400V
1
1
-
1
1
SG SP 2 20 2 P
SG SP 2 20 4 P
666534
666535
1
1
45kA
45kA
10kA
10kA
1000kA
2100kA
-
230V
400V
1
1
-
1
1
SG SP 2 45 2 P
SG SP 2 45 4 P
666536
666538
1
1
65kA
65kA
20kA
20kA
1200kA
1950kA
-
230V
400V
1
1
-
1
1
SG SP 2 65 2 P
SG SP 2 65 4 P
666541
666543
1
1
40kA
20kA
1500kA
-
230V
1
-
1
SG SP 2 40 2 NPE P
666553*
1
990V
990V
230V
230V
1+N
1+N
-
2
2
SG MM 2 20 2
SG MM 2 45 2
666525
666527
1
1
Surgeguard
Single pole plug-in
Plug and Base
IMAX
A
B
C
* N-PE lighting current arresters
Multi pole
monoblock
20kA
45kA
5kA
10kA
960V
1000V
D
E
20kA
45kA
45kA
80kA
5kA
10kA
10kA
20kA
960V
1000V
1000V
1200V
990V
990V
990V
990V
400V
400V
400V
400V
3+N
3+N
3+N
3+N
1CO
1CO
5
5
5
5
SG MM 2 20 4
SG MM 2 45 4 C
SG MM 2 45 4
SG MM 2 80 4 C
666526
666530
666529
666533
1
1
1
1
F
G
X
Accessories
Decoupling
coil
Sine wave tracker
In
Number of
phases
Number of
modules
Cat. No.
Ref. No.
Pack.
35A
40A
63A
1
1
1
2
2
4
VED35
SG C 40
VED63
545879
666532
545857
1
1
1
-
1
1
SG SWT
666524
1
D.35
Redline
Comfort functions
Mains disconnect switches - Aster
Switches - Aster
A
B
C
D
Rotary switches - Aster
Switches with signal lamp - Aster
Push-buttons - Aster
Indication lamp - Aster
E
F
G
X
D.36
Redline
Socket-outlet - Series MSC
Dimensional drawings
Contactors - Contax
A
B
C
Contactors Day and Night - Contax
D
E
F
G
Contactors - Auxiliary contact
Contactors - Spacer
X
D.37
Redline
Comfort functions
Relays - Contax R
Relays - Auxiliary contact
Impulse switches 1P - Pulsar S
Impulse switches 2P - Pulsar S
Electromechanical step-by-step - Pulsar S
A
B
C
D
E
F
G
X
Impulse switches - Add-on module for electromechanical switches
left mounting
D.38
right mounting
Redline
Impulse switches - Spacer
Staircase switches/Time relays - Pulsar T/TS
Dimensional drawings
Analogue time switches 1 module - Classic
A
B
C
Analogue time switches 3 & 6 modules - Classic
D
E
F
G
Digital time switches 1 module - Galax
X
D.39
Redline
Comfort functions
Digital time switches 2 & 6 modules - Galax
Light sensitive switch 1 module - Galax LSS Light sensitive switches 3 mod. - Galax LSS
A
B
C
D
Light sensitive switch with digital clock - Galax LSS
E
F
G
X
D.40
Light sensitive switch photocell incorporated Light sensitive switches - Photocell
Redline
Bell transformers - Series T
Dimensional drawings
Safety transformers - Series T
A
B
C
Buzzers and bells - 1 module
Buzzers and bells - 2 modules
D
E
F
G
Analogue measurement instruments - Series MT
X
D.41
Redline
Comfort functions
Digital measurement instruments - Series MT
Energy meter - Series MT
A
B
C
D
Network analyser - Series MT
E
F
G
X
D.42
Signal converter - Series MT
Selector switch - Series MT
Redline
Current transformer - Series MT
100 up to 400A
500 and 600A
800 and 1000A
Dimensional drawings
40 up to 80A
A
B
C
D
E
F
G
X
D.43
Redline
Surge arresters - SurgeGuard
Comfort functions
Class 1
Surge arresters - SurgeGuard
Class 2 - Single pole plug-in
Surge arresters - SurgeGuard
Class 2 - Multipole monobloc
A
B
C
D
Decoupling coil - SurgeGuard
E
F
G
X
D.44
Priority relay - Series PR
Sine wave tracker - SurgeGuard
39231
GE Consumer & Industrial
Power Protection
GE Consumer & Industrial
Power Protection (former GE Power Controls),
a division of GE Consumer & Industrial,
is a first class European supplier of
low-voltage products including wiring
devices, residential and industrial electrical
distribution components, automation
products, enclosures and switchboards.
Demand for the company’s products
comes from wholesalers, installers,
panel-board builders, contractors, OEMs
and utilities worldwide
GE Consumer & Industrial
Power Protection
Redline
ED.04
Modular DIN-rail devices
and residential enclosures
Just feel protected
www.gepowercontrols.com
www.ge.com/eu/powerprotection
Redline - Modulair DIN-rail devices
ED.04
GE imagination at work
GE imagination at work
GE POWER CONTROLS
International Sales
Nieuwevaart 51
B-9000 Gent - Belgium
Tel.
+32/9 265 21 11
Fax
+32/9 265 28 90
E-mail: gepcbel@gepc.ge.com
GE imagination at work
GE imagination at work
GE imagination at work
GE imagination at work
680803
Ref. R/2260/E/X 15.0 Ed. 11/06
© Copyright GE Power Controls 2006