Input-Output Modules BMS INPUT/OUTPUT MODULES 2 STAGE RELAY, RAISE-LOWER, HIGH-LOW 0-10VDC E2RMD Liquid crystal display for set up and relay status Digital set up of relay energisation voltages Volt free relay contacts Ambient -10 to +50 deg C Din rail mounting. This product accepts a 0-10VDC input and produces a 2 stage relay output which can be used for external plant switching. The default voltage values for relay energisation are fixed but if required these values can be modified. Type E2RMD 24VAC/DC 0-10VDC DIMENSIONS/TERMINATIONS: 54mm Input Resolution Power Consumption Switch Rating 230VAC SPDT Enclosure 0.1VDC 1.0W max 2 x 10(3)A IP00 67mm 126mm Supply Input Range +-15% TIMING DIAGRAM: INPUT BINARY RELAY1 RELAY2 0V 0 OFF OFF 4V 1 ON OFF 7V 2 OFF ON 10V 3 ON ON INPUT RAISE/LOWER LOWER RAISE 0V 0 OFF OFF 4V 1 ON OFF 7V 2 OFF OFF 10V 3 OFF ON INPUT HIGH HIGH/LOW LOW 0V 0 OFF OFF 5V 1 ON OFF 10V 2 ON ON BINARY MODE: OFF RELAY2 ON OFF RELAY1 ON OFF OFF RELAY2RAISE OFF RELAY1LOWER OFF ON OFF ON ON OFF ON ON OFF RELAY1LOW OFF OFF OFF RELAY2HIGH ON This diagram shows how the states of the relays change with input 0-10VDC voltage for the default voltage settings case. This diagram also identifies the step numbers for each mode for use if the default energisation voltages are to be changed. OFF ON OFF INPUT(VDC) 0 1 2 3 4 5 6 7 8 9 10 9 8 7 6 5 4 3 2 1 0 SET UP: Wire the E2RMD to the wiring diagram noting that the correct polarity of the 0-10VDC is important. Set both the AUTO-OFF-HAND links to AUTO. Setting the control mode pushbuttons step through Whilst holding down the pushbutton turn on the power. The display will show MODE and SET. Using the the modes of BINARY, HIGH/LOW and RAISE/ LOWER. Confirm the required mode using the SET button. Setting the required relay energisation voltages The Timing diagram shows the default relay state at various DC input voltages. If these values are satisfactory there is no need to make any changes. If changes are required to the energisation voltages proceed as follows: Press the SET pushbutton. The display will show MODE and the selected control mode eg BINARY or RAISE/LOWER or HIGH/LOW, the step number 0 and a flashing SET indication and voltage value. Use the pushbuttons to set the required voltage value. Press the SET button to confirm. The display will now show the step number 1 and a flashing SET indication and voltage value. Use the pushbuttons to set the required value. Press the SET button to confirm. Continue this process for the step number 3 (if appropriate for the selected mode) until the display shows TIME DELAY with SET flashing. Use the pushbuttons to set the required time delay and press SET button again to confirm. The display will now show MODE and selected control mode and the input DC voltage being received. In use, when either relay is energised the adjacent red led will be lit. INSTALLATION: Observe the local regulations regarding electrical installations. Size the power cables according to the load. Telephone: +44 (0)1480 407074 Fax: +44 (0)1480 407076 Email: sales@electrocontrols.co.uk H1 H5 44