Wiring Guide - Peerless Lighting

advertisement
Wiring
Guide
Switching Options
SCT Key
Power Feed and Support Location
Support Location
Emergency Power Feed and Support Location
Power Feed, Emergency Power Feed and Support Location
Single Circuit. All lamps are wired to a single circuit.
DCT Dual Circuit. Two light levels are achieved by switching separate rows of lamps in
the same fixture on two independently switched circuits. Dual circuit fixtures share a
common neutral.
For fixtures or runs with 2 lamps in the cross section the standard circuiting is one
side is wired to circuit “A” and the other side is wired to a circuit “B”.
A
B
A
4'-0"
B
A
B
8'-0"
A
B
A
B
12'-0"
The default for a fixture with 3 lamps (or more) in the cross section is the row of
lamps on the outside are wired to a switched circuit “A” and the lamps located in the
middle are wired to a switched circuit “B”.
AB
A
AB
AB
A
4'-0"
ALC A
B
A
AB
8'-0"
A
AB
A
AB
A
12'-0"
Alternating Lamp Circuits. Lamps in the same cross section are wired to one circuit
and the next cross section is wired to the second circuit. These two circuits alternate
across the fixture row. Alternating lamp circuits share a common neutral.
ALC
Single Lamp in Cross Section
A
4'-0"
A
B
8'-0"
A
B
A
12'-0"
PEERLESS LIGHTING • 2246 5th Street, Berkeley, CA 94710 • Tel: 510.845.2760 • Fax: 510.845.2776 • PeerlessLighting.com
© 2012 Acuity Brands Lighting, Inc. All Rights Reserved. “Peerless” is a registered trademark. Products in this brochure may be covered by one or more U.S. Patents and Patents Pending.
Peerless Lighting reserves the right to change materials or modify the design of its product without notification as part of the company’s continuing product improvement program.
WG-1
FO-1
Wiring
Guide
Switching Options
Key
Power Feed and Support Location
Support Location
Emergency Power Feed and Support Location
Power Feed, Emergency Power Feed and Support Location
Number of Emergency Modules
1SE
1 Section. One 4FT module per run will have an Emergency Lighting option.
2SE
2 Sections. Two 4FT modules per run.
The standard maximum number of 4FT modules is one per 4 / 8 /12 foot fixture section.
Emergency Type
EL
Emergency battery pack. In the event of a power failure the battery pack will
supply emergency power. Each battery pack will be connected to one lamp unless
otherwise specified.
Single Lamp in Cross Section
EL
4'-0"
EL
8'-0"
EL
12'-0"
Two Lamps in Cross Section
EL
4'-0"
EL
8'-0"
EL
12'-0"
Three Lamps in Cross Section
EL
EL
4'-0"
8'-0"
EL
12'-0"
PEERLESS LIGHTING • 2246 5th Street, Berkeley, CA 94710 • Tel: 510.845.2760 • Fax: 510.845.2776 • PeerlessLighting.com
© 2012 Acuity Brands Lighting, Inc. All Rights Reserved. “Peerless” is a registered trademark. Products in this brochure may be covered by one or more U.S. Patents and Patents Pending.
Peerless Lighting reserves the right to change materials or modify the design of its product without notification as part of the company’s continuing product improvement program.
WG-2
FO-2
Wiring
Guide
Switching Options
EC Key
Power Feed and Support Location
Support Location
Emergency Power Feed and Support Location
Power Feed, Emergency Power Feed and Support Location
Emergency Circuit or Night Light circuit. When used as an emergency circuit, separate circuit
wiring is provided for an alternate building power source (generator, uninterruptable power supply,
etc.) When used as a nightlight circuit, separate circuit wiring is provided for an un-switched
circuit so that designated lamps will always remain on. Each emergency or nightlight circuit will be
connected to a single lamp when only one lamp is in the cross section. When two or more lamps
are in the cross section the two outer most lamps will be connected to the circuit.
EC
Single Lamp in Cross Section
EC
4'-0"
EC
8'-0"
EC
12'-0"
Two Lamps in Cross Section
EC
EC
EC
4'-0"
EC
EC
8'-0"
EC
12'-0"
Three Lamps in Cross Section
EC
4'-0"
EN EC
EC
EC
EC
8'-0"
EC
12'-0"
Emergency Battery Pack with Night Light circuit. This option combines EL and EC options into one
emergency section. Like EC, this option provides a separate circuit for connection to an alternate
building power source (generator, uninterruptable power supply, etc.) or to an un-switched circuit
for the specific use as a nightlight. When lamps are powered by an alternate building power source
or un-switched circuit the two most outer lamps will be lit or a single lamp in the case of a one
lamp cross section. Additionally, like EL, in the event of a power failure a battery pack will supply
emergency power to one lamp unless otherwise specified.
Single Lamp in Cross Section
EN (EL)
4'-0"
EN (EL)
8'-0"
EN (EL)
12'-0"
Two Lamps in Cross Section
EN
EN
EN (EL)
4'-0"
EN
EN (EL)
8'-0"
EN (EL)
12'-0"
Three Lamps in Cross Section
EN
EN
EN (EL)
4'-0"
8'-0"
EN
EN (EL)
EN (EL)
12'-0"
PEERLESS LIGHTING • 2246 5th Street, Berkeley, CA 94710 • Tel: 510.845.2760 • Fax: 510.845.2776 • PeerlessLighting.com
© 2012 Acuity Brands Lighting, Inc. All Rights Reserved. “Peerless” is a registered trademark. Products in this brochure may be covered by one or more U.S. Patents and Patents Pending.
Peerless Lighting reserves the right to change materials or modify the design of its product without notification as part of the company’s continuing product improvement program.
WG-3
FO-3
Wiring
Guide
Switching Options
Key
Power Feed and Support Location
Support Location
Emergency Power Feed and Support Location
Power Feed, Emergency Power Feed and Support Location
(No option) Each emergency lighting section is powered at the support point that follows it.
With Emergency Battery Pack
EL
EL
8'-0"
8'-0"
16'-0"
ELH Current load permitting, all emergency lighting modules are powered by through
wires to one emergency power feed location. The emergency lighting power feed
is located at the last support in the fixture run. ELH provides separate neutrals
for emergency and normal power throughout the fixture. Check local code for
compliance.
With Emergency Battery Pack
EL
EL
8'-0"
8'-0"
16'-0"
ELS Current load permitting, all emergency lighting modules are powered by a
continuous through wire to one emergency power feed location. The emergency
lighting power feed is located at the first support point in the fixture run and
combined within the normal power feed cord, sharing a common neutral. Check
local electrical code for compliance.
ELS2 Current load permitting, all emergency lighting modules are powered by continuous
through wires to one emergency power feed location. Normal and emergency power
are fed via adjoining but separate feed cords located at the first support in the
fixture run. ELS2 provides separate neutrals for emergency and normal throughout
the fixture. Check local code for compliance.
ELS/ELS2 With Emergency Battery Pack
EL
EL
8'-0"
8'-0"
16'-0"
PEERLESS LIGHTING • 2246 5th Street, Berkeley, CA 94710 • Tel: 510.845.2760 • Fax: 510.845.2776 • PeerlessLighting.com
© 2012 Acuity Brands Lighting, Inc. All Rights Reserved. “Peerless” is a registered trademark. Products in this brochure may be covered by one or more U.S. Patents and Patents Pending.
Peerless Lighting reserves the right to change materials or modify the design of its product without notification as part of the company’s continuing product improvement program.
WG-4
FO-4
Wiring
Guide
Switching Options
Key
Power Feed and Support Location
Support Location
Emergency Power Feed and Support Location
Power Feed, Emergency Power Feed and Support Location
EXAMPLE RUNS
With Emergency Battery Pack
A
A
A
8'-0"
A
A
8'-0"
A EL
8'-0"
24'-0"
2 Lamp Cross Section, Single Circuit with Two Emergency Battery Packs
A
A
A
A
A
A
A
8'-0"
A EL
A
A
A
8'-0"
A EL
8'-0"
24'-0"
3 Lamp Cross Section, Dual Circuit with Two Emergency Battery Packs
A
A
BA
BA
A
A
BA
8'-0"
BA EL
A
A
BA
8'-0"
BA EL
8'-0"
24'-0"
3 Lamp Cross Section, Dual Circuit with Two Emergency Battery Packs and ELH Option
A
A
BA
BA
A
A
BA
8'-0"
BA EL
A
A
BA
8'-0"
BA EL
8'-0"
24'-0"
3 Lamp Cross Section, Dual Circuit with Two Emergency Battery Packs and ELS Option
3 Lamp Cross Section, Dual Circuit with Two Emergency Battery Packs and ELS Option
A
A
BA
8'-0"
BA
A
A
BA
8'-0"
BA EL
A
A
BA
BA EL
8'-0"
24'-0"
Assumptions: 277V.
PEERLESS LIGHTING • 2246 5th Street, Berkeley, CA 94710 • Tel: 510.845.2760 • Fax: 510.845.2776 • PeerlessLighting.com
© 2012 Acuity Brands Lighting, Inc. All Rights Reserved. “Peerless” is a registered trademark. Products in this brochure may be covered by one or more U.S. Patents and Patents Pending.
Peerless Lighting reserves the right to change materials or modify the design of its product without notification as part of the company’s continuing product improvement program.
WG-5
FO-5
Download