BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL or IEC approved wire for input/output connections.
Minimum size 18 AWG (0.75mm2).
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des fils approuvés par UL ou IEC pour les entrées/sorties de connexion. Taille minimum 18 AWG (0.75mm2).
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Prepare Electrical Wiring
Electrical Requirements
• The LED luminaire must be connected to the mains supply according to its ratings on the product label.
Grounding Instructions
• The grounding and bonding of the overall system shall be done in accordance to local electric code of the country
where the luminaire is installed.
imagination at work
Unit Installation
Note: Steps 1 through 4 should be completed before the dry-wall has been installed.
Option A
Option B
T-grid
1
Slide hanger bars through
adjustable mounting brackets.
2
Option A: Mount fixture by attaching hanger bars to T-grid ceiling
(BH3 SKU 94890).
Option B: Mount fixture with 1/2” EMT conduit and clips (not supplied).
NOTE: Per local building codes, attach safety cables to seismic tabs located
on each corner on top of the fixture.
3
6
If necessary, adjust the height
of the mounting brackets by
loosening the nut so that the
bottom of the fixture is flush with
the bottom of the ceiling tile. It is
recommended that the operator
use a wrench to tighten nut.
Finish the ceiling, taping and
mudding around the fixture to the
lip for a clean, finished edge.
4
See the Wiring Instructions on
the next page and complete the
necessary wiring connections.
5
Install dry-wall ceiling tile with the
appropriately sized hole cut out
for the fixture (see table below).
Fixture
Hole Size
TSMTL-2
14.17 in. x 9.34 in. (359.86 mm x 237.28 mm)
TSMTL-3
19.17 in. x 9.34 in. (486.86 mm x 237.28 mm)
Wiring Instructions
1
Remove the cover plate with
knockouts from the top of the
fixture by removing its screws.
2
Remove one or both knockouts
from the plate as desired, and
secure the conduit or cable
supplying the power to the plate.
3
Connect the supply line to the black
(hot), white (neutral/common), and
green (ground) leads.
Optional: If using a dimming controller, connect matching-colored
wires together (violet and gray leads).
Risk of damage: Make sure that supply connection, light fixture wiring,
and dimming cables are connected to proper driver inputs. Wrong
connection may cause damage to the product.
Must use UL approved conduit fittings for all enclosure box connections
to prevent wire cuts by sharp edges and excessive strain on wiring.
4
Carefully fold the wires into the
fixture while replacing the cover
plate and screwing it back down.
Optional Installation: 0-10 Volt Dimming Lighting Controller
1-10V wiring diagram
Line (black)
Neutral (white)
Ground (green)
(1-10) + (violet)
(1-10) - (gray)
5
Line
Neutral
Ground
DRIVER
(0-10V) (0-10V) +
At output side of LED driver, make appropriate
connections using twist-on wire connectors.
Follow lighting controller installation instructions.
Troubleshooting
Note: For a replacement driver, please contact GE Lighting and request the following driver: 50W Class 1 CC Lightech
Driver (GELD50MV700PVNA).
Through Wiring
Catalogue No.
Maximum number of fixtures
TSM-S/R-3-L1 & TSMTL-S/R-3-L1
40
TSM-S/R-3-L2 & TSMTL-S/R-3-L2
30
TSM-S/R-2-L1 & TSMTL-S/R-2-L1
60
TSM-S/R-2-L2 & TSMTL-S/R-2-L2
40
Calculations assume use with a 15A circuit (80% loading)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This Class
[A] RFLD complies with the Canadian standard ICES-003. Ce DEFR de la classe [A] est conforme á la NMB-003 du Canada.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the interference at his own expense.
Fixture intended for commercial use only. Use only in non-insulated applications.
GE Lighting • 1-888-MY-GE-LED
(1-888-69-43-533)
• www.gelighting.com