Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Scope of functions Scope of functions (see also page 9, applications) 87 87 50 87H 87H 50N 51 87N 50 51 * * 49 49 7UT512 * Note: With 60 Hz only for two–winding differential function 7UT513 Fig. 1 7UT51 differential protection relays Application The 7UT512/7UT513 differential protection relays are used for fast and selective isolation of short-circuits in transformers of all voltage levels and also in rotating electric machines and short lines. The particular application can be chosen by setting. In this way an optimal adaptation of the relay to the protected object can be achieved. The protection relay can be parameterized for use with three–phase and single–phase transformers. In addition to this, a thermal replica is integrated for the supervision of the ohmic losses in the plant. Two variants of the differential relay can be supplied: The device 7UT512 with a compact design is suited for two–winding transformers as well as for motors or generators and short lines. A standby overcurrent– time protection and two thermal monitoring functions are also integrated. The larger 7UT513 unit is used for two– winding and three–winding transformers, generators/motors and short two–end and three–end lines. Two thermal monitoring functions are integrated as additional functions. Moreover, as an alternative a standby definite–time/inverse–time overcurrent or a restricted earth fault (REF) or a tank protection function is available for one winding. The 7UT513 can also be used where the neutral point current of the transformer must be acquired or more inputs and outputs are required than are provided by the 7UT512. The device can interface with conventional control systems or alternatively be integrated in the modern SINAUT LSA substation control system. Siemens LSA 2.2.4 . May 1996 Construction Within its compact construction, the device contains all the components required for capture and evaluation of measurands, operator panel and display field, alarm and command outputs, binary inputs, serial interfaces and power supply converter. The device can be supplied in three case variations. The model for panel surface mounting is supplied with two–tier terminals accessible from the front. The variants for panel flush mounting or cubicle mounting have rear connection terminals and are available with or without glass cover. Mode of operation The 7UT51 differential protection units have a complete, digital analog value processing function ranging from sampling and digitizing the analog values to operating decisions for the circuit–breaker. Digital techniques in the measurement process extensively suppress the influence of switching currents (inrushs), high–frequency transients, transient DC current components and varying degrees of CT saturation. Features Short–circuit protection for two and three–winding transformers with integrated vector group and ratio adaptation. Restraint during inrush, overexcitation and CT–saturation. Short–circuit protection for generators and motors with high setting sensitivity Overload protection with a thermal characteristic for 2 windings/2 terminations Two–stage definite–time/inverse–time overcurrent standby protection for one winding. On the basis of the 7UT513 hardware, a restricted earth fault protection or a sensitive, definite time overcurrent for one starpoint (tank protection) is available as an alternative. Direct injection of two external open commands. Marshallable binary inputs, LEDs, alarm and tripping relays. Operational current measurement. Realtime clock and permanently stored operational and fault indications in the event of auxiliary voltage failure. Previous substation control interface (Siemens–specific) or IEC 870–5–103 VDEW interface (standard of the Association of German Power Utilities) up to 8 faults to the substation control and protection. Fault recording Commissioning aid. Serial interfaces The device has two serial interfaces. The operator interface for the connection of an AT–compatible PC is arranged at the front. An operator program DIGSI is available for comfortable and easy setting, fault recording, evaluation and commissioning. On software version V3 and higher of the 7UT51, the unit can be operated via the substation control interface using the DIGSI V3 operating program. Siemens AG 19961 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines The substation control interface is a 820 nm fibre–optic interface for connecting to the SINAUT LSA substation protection system or other substation control system with IEC 870–5–103 standard interface. Alternatively this can be an isolated V.24/V.28 interface (RS 232C) (protocol either Siemens–specific or according to IEC–870–5–103 recommendation. KnlW1 Differential protection for transformers When the 7UT51 is employed as fast and selective short–circuit protection for two respectively three–winding transformers the following properties apply: Tripping characteristic according to Fig. 3 Vector group and ratio adaptation Depending on the treatment of the transformer neutral point, neutral current elimination can be with or without consideration of the neutral current. With the 7UT513, the neutral current at the neutral CT can be measured and considered in the treatment of this current, which increases sensitivity by one third for single–pole faults. Fast clearance of heavy internal transformer faults. Restrain of inrush current with 2nd harmonic. Cross–block function that can be limited in time. Restrain against over fluxing with a choice of 3rd or 5th harmonic stabilization is only active up to a settable value for the 50 Hz component of the differential current. Additional restrain for an external fault with current transformer saturation (CT–saturation detector). Insensitivity to DC current elements and current transformer faults due to the freely programmable response characteristic. The differential protection function can be externally blocked by means of a binary input. 2 yn0 KnlW2 d5 KnlW3 L2 L3 Settings All setting parameters can be input by means of the integrated operator panel and display field or a PC under user control. The parameters are stored in a non– volatile memory, so that they cannot get lost even during interruption of the supply voltage. Self monitoring Hardware and software are monitored continuously and any irregularities are immediately detected and alarmed. As a result, the security, reliability and availability are significantly improved. YN L1 Overload protection 1 Overcurrent– time protection, definite/ inverse Overload protection 2 Restricted earth–fault protection REF Tank protection Transformer differential protection Commissioning test 7UT513 Fig. 2 Functions of the differential protection (DMT or REF) Differential quantity IDIFF Fundamental component of the differential current IRest Restrain current (bias current) Rated current of the transformer, generator or line IN DIFF N 5 Fault characteristic with single–end infeed 4 Trip 3 m2 2 DIFF Setting value 1 1 N m1 Restrain 0,5 0,15 Rest FP 1 2 3 4 5 6 7 8 9 10 N Restrain quantity Fig. 3 Response characteristic with preset transformer parameters for two–phase faults Differential protection for generators/ motors When the 7UT51 is employed as fast and selective short–circuit protection for generators or motors the following properties apply: Tripping characteristic according to Fig. 3 Short response times within one system cycle. Monitoring of the incoming lines for wire break (for short lines). Additional restrain for external faults with current transformer saturation. Commissioning aids The resolution of the display of the operational, restrain and differential currents is selected such that commissioning is possible using the low–voltage method without additional measuring instruments. In addition to the absolute value of the operational currents, the phase angle of the currents between the windings is also displayed. Moreover, the protection function calculates the values of the differential and restrain current. Siemens LSA 2.2.4 . May 1996 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Thermal overload protection The thermal replica evaluates the largest phase current of a selectable set of CT secondary currents. The tripping characteristics (Fig. 4) are exponential functions according to IEC 255–8 standards and take into account the 2R losses due to the particular operational current and the simultaneous cooling due to the coolant. In this way the tripping time during an overload condition takes the pre–load into consideration. An alarm stage can be set to operate before reaching the tripping condition. Backup overcurrent–time protection for one winding or one end As backup protection, overcurrent–time protection with a choice of definite–time or inverse–time characteristic is available. The definite–time and inverse–time protection has two stages, i.e. there is not only an overcurrent stage (I>) but also a high current stage (Iơ). Both stages can be blocked via the binary input. The response value of the standby protection is derived from the measured phase currents for one winding or one end. Restricted earth fault protection (REF) Restricted earth fault protection (REF) is used with earth transformer windings or coil arrangements with a common neutral point. The winding can be more sensitively protected by the measuring principle than by differential protection because the sum of the phase currents is compared with the measured zero current. For example, the interturn fault against earth, which is hardly noticeable in the differential current, can frequently be detected by the REF. With this method, the absolute value and phase angle of the fundamental of the zero current is compared with the absolute value and phase angle of the sum of the line currents. This results in a high degree of stability during equalization processes. Tank protection monitors the current between earth and transformer tank mounted in an isolated fashion with a sensitive input winding. The response value can be set in a milliampere range. One of these functions can be set in the 7UT513 as an alternative to the standby protection. The sensitive measuring input of the tank protection is an ordering option (2 in the 13th position of the order number). Note: For 60 Hz and three winding differential protection the REF and tank protection cannot be used parallel to the differential protection. t (min) t (min) Parameters setting value time constant (min) 100 100 50 50 20 20 10 10 5 5 3 3 2 100 2 1 50 1 0.5 0.5 0.3 0.3 0.2 100 0.2 10 0.1 Parameters setting value time constant (min) 50 0.1 5 0.05 0.05 0,5 0,5 1 1 5 10 0.03 0.03 1 I k @ IN 2 3 4 5 8 10 Without previous load 1 2 3 4 5 8 10 With 90 % previous load I k @ IN Fig. 4 Thermal overload trip–time characteristic I 0Ȁ I EDS I1 I2 4 limit = 130 120 110 100 I3 90 I0 ’ 3 I0” = I1 + I2 + I3 2 Block Trip 1 130 120 110 100 90 80 70 60 IREF Response value ( I0”; I0’ ) Fig. 5 Tripping characteristic as a function of the phase angle between I0” and I0 ’ at I0 ” = I0 ’ (180 = external fault) Siemens LSA 2.2.4 . May 1996 3 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Marshallable event/alarm relays, LEDs, binary inputs To enable user specific indication and/or output of alarms these are supplied fully marshallable. Individual events can be grouped together to form a group alarm. Indications The 7UT51 provides detailed data for the analysis of faults and to check states during operations. All indications subsequently listed are backed up in the event of a supply voltage failure. Clock time The standard version contains a battery–backed clock that can be synchronized via the binary input or the substation control interface. A date and time are assigned to all indications with millisecond resolution. Fault indications The last three fault indications are available for the faults stored in the unit. Operational indications All indications that are not directly associated with the fault are stored in the operational indication buffer. Fault recording The sampling values of the currents measured at the transformer are stored if a fault occurs. It is also possible to initiate fault recording on energization so that, for example, an inrush current can be recorded during commissioning. The current can be transferred to a PC or read out via the SINAUT LSA substation control and protection. If the IEC 870–5–103 standard interface is used, up to eight fault recordings can be stored. The fault recording buffer is a ring buffer with a maximum length. The oldest fault being overwritten by each new fault. Coupling of external binary signals For the processing of external signals or commands such as reverse interlocking, Buchholz alarm, temperature limit monitoring, tank pressure switch etc. The associated events/alarms can be transmitted via the serial system interface to a central device such as for example a SINAUT LSA or a central data protection device via alarm or tripping relays and LED’s for local indication. Technical data Input circuits Rated current N 1 or 5 A (commutable, for mixed 1 A/5 A primary CTs order a 5 A relay) Rated frequency fN, can be parameterized Overload capability current inputs, thermal 50, 60 or 16 23 Hz dynamic Burden current inputs DC voltage supply continuous 10 s 1s half cycle at N = 1 A at N = 5 A Rated auxiliary voltage Vaux Permissible rated auxiliary voltage ranges Permissible max. ripple Power consumption of 7UT512 of 7UT513 at rated auxiliary voltage quiescent energized quiescent energized Stored energy time at Vaux w110 V 24, 48 V or 60, 110, 125 V or 220, 250 V 19 to 56 V 48 to 144 V 176 to 288 V v12 % approx. 9 W approx. 11 W approx. 10 W approx. 15 W v50 ms Binary inputs 7UT512 7UT513 DC operating voltage Current input Alarm contacts Number of malfunction alarm relays not marshallable Number of alarm relays 7UT512 marshallable 7UT513 marshallable Contacts per relay Switching capacity make/break Switching voltage Permissible current 1 Ready for operation Internal fault Marshallable LEDs 7UT512 7UT513 green red 1 1 red red 6 14 LED displays 4 marshallable marshallable 4 x N 30 x N 100 x N 250 x N <0.1 VA <0.5 VA 2 5 24 to 250 V approx. 2.5 mA 4 10 see connection diagrams 20 W/VA 250 V AC/DC 1A Siemens LSA 2.2.4 . May 1996 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Technical data (continued) Trip contacts Number of trip relays 7UT512 7UT513 Contacts per relay Switching capacity Switching voltage Permissible current Serial interfaces marshallable marshallable make break continuous 0.5 s Operator interface Substation control interface Protocol Safety Transfer speed Type of transfer Connection electric or connection distance fibre optic optical wave length permissible fibre damping distance Construction Housing, dimensions Weight, terminals 7UT512 panel flush mounting/ cubicle mounting 7UT512 panel surface mounting 7UT513 panel surface mounting cubicle mounting 7UT513 panel surface mounting Degree of protection according to EN 60 529 2 5 see connection diagrams 1 000 W/VA 30 W/VA 250 V AC/DC 5A 30 A on the front, not isolated, for connection to an AT compatible PC isolated, for connection to a central unit Siemens–specific or according to IEC 870–5–103 (standard) Hamming distance d = 4 4 800, 9 600 or 19 200 bauds asynchronous similar to V.24/V.28 to CCITT or RS232C to EIA, 2 kV isolated max. 1 000 m two integrated FSMA plug connectors for fibre optic connection 820 nm max. 8 dB for glass fibre 62.5/125 mm max. 2 km 7XP20, see dimension drawings approx. 6.5 kg, see connection diagrams approx. 8 kg, 60 terminals approx. 10 kg, see connection diagrams approx. 11.5 kg, 100 terminals IP 51 CE–conformity, standards This product is in conformity with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to the electromagnetic compatibility (EMC Council Directive 89/336/EEC). The product conforms with the international standard IEC 255 and the national standard DIN VDE 57 435 /part 303. The relay is designed for use in an industrial environment, for installation in standard relay rooms and compartments such that with proper installation electro–magnetic compatibility (EMC) is ensured. Conformity is proved by tests performed by Siemens AG in line with article 10 of the Council Directive in accordance with the generic standards EN 50081–2 and EN 50082–2. Insulation tests IEC 255–5, DIN VDE 0435 part 303 High voltage test (routine test), all circuits except d.c. voltage supply input High voltage test (routine test), only d.c. voltage supply input Impulse voltage test (type test), all circuits, class III 2 kV (rms), 50 Hz High frequency IEC 255–22–1, class III Electrostatic discharge IEC 255–22–2, class III and EN 61000–4–2, class III Radio–frequency electromagnetic field, non–modulated IEC 255–22–3 (report), class III Radio–frequency electromagnetic field, amplitude modulated ENV 50140, class III Radio–frequency electromagnetic field, puls modulated ENV 5014 / ENV 50204, class III Fast transients IEC 255–22–4 and EN 61000–4–4, class III 2,5 kV (peak), 1 MHz, = 15 ms, 400 shots/s, duration 2 s 4 / 6 kV contact discharge, 8 kV air discharge, both polarities, 150 pF, Rl = 330 W 10 V/m, 27 to 500 MHz EMC–tests; immunity (type test) Standards: IEC 255–22 (product norm) EN 50082–2 (generic standard) DIN VDE 0435 part 303 Conducted disturbances induced by radio–frequency fields, amplitude modulated ENV 50141, class III Power frequency magnetic field EN 61000–4–8, class IV Siemens LSA 2.2.4 . May 1996 2,8 kV DC 5 kV (peak), 1,2/50 ms, 0,5 J, 3 positive and 3 negative shots at intervals of 5 s 10 V/m, 80 to 1 000 MHz, AM 80 %, 1 kHz 10 V/m, 900 MHz, repetition frequency 200 Hz, duty cycle 50 % 2 kV, 5/50 ns, 5 kHz, burst length = 15 ms, repetition rate 300 ms, both polarities, Rl = 50 W, duration 1 min 10 V, 150 kHz to 80 MHz, AM 80 %, 1 kHz 30 A /m, continuous, 300 A /m for 3 s, 50 Hz 5 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Technical data (continued) EMC–tests; emission (typ tests) Standard: EN 50081–2 (generic standard) Climatic stress tests Conducted interference voltage, auxiliary voltage CISPR 11, EN 55011, class A and DIN VDE 0875 part 11, class A Interference field strength CISPR 11, EN 55011, class A and DIN VDE 0875 part 11, class A 150 kHz to 30 MHz permissible ambient temperature during service during storage during transport –5 to +55 °C –25 to +55 °C –25 to +70 °C mean value per year v75 % relative humidity, on 30 days per year up to 95 % relative humidity, condensation not permissible during service 10 to 60 Hz, 0,035 mm amplitude 60 to 500 Hz, 0,5 g acceleration 5 to 8 Hz, 7,5 mm amplitude 8 to 500 Hz, 2 g acceleration 30 to 1 000 MHz permissible humidity Mechanical stress tests IEC 255–21–1, IEC 68–2 permissible mechanical stress during transport Differential protection for transformers Setting ranges Differential current IDIFF>/IN High current DIFFơ/N Inrush stabilization 2fN/fN Overexcitation stabilization 5fN/fN Response times (single–sided infeed) at DIFF w1.5 x set value DIFF> at DIFF = 1.5 x set value DIFFơ at DIFF = 5 x set value DIFFơ Additional time delay for tripping Reset time Drop–out to pick–up ratio Tolerances Tripping characteristic Inrush stabilization Additional time delay Frequency range Accuracy Differential protection for transformers generators, motors and short lines Overload protection Setting range Differential current DIFF>/N Response times (single–sided infeed) at DIFF w1.5 x set value DIFF> at DIFF = 5 x set value DIFF> Reset time Drop–out to pick–up ratio Tolerances tripping characteristic Frequency range Accuracy at 0.8 to 1.2 fN Accuracy at 0.5 to 0.8 or 1.2 to 1.4 fN Setting ranges Factor k acc. to IEC 255.8 Time constant t Temperature alarm stage QAlarm/QOff Current dependent alarm stage Alarm Thermal image Drop–out to pick–up ratio Tolerances Frequency range Accuracy Overcurrent–time protection, setting ranges Overcurrent–time protection, definite time 6 High set current phase ơ Overcurrent phase > Delay times t>, t ơ Tolerances Current pick–up value Time Release value times Steps 0.01 Steps 0.1 Steps 1 % Steps 1 % 0.15 to 2 0.8 to 20 10 to 80 % 10 to 80 % (alternatively with 3rd or 4th harmonic) at 16 2/3; 50; 60 Hz at 16 2/3; 50; 60 Hz at 16 2/3; 50; 60 Hz Steps 0.01 approx. 85; 35; 35 ms approx. 55; 25; 25 ms approx. 25; 17; 16 ms 0 to 60 ms approx. 100 ms approx. 0.7 "3 % of specified value for <5 N "3 % of set value "1 % or 10 ms 0.95 vf/fN v1.05 v1 % of tripping characteristic Steps 0.01 at 16 at 16 2/ ; 3 2/ ; 3 50; 60 Hz 50; 60 Hz 0.05 to 1 approx. 70; 25; 25 approx. 25; 17; 15 to 17 ms approx. 100 ms approx. 0.7 "3 % of specified value for <5 N 0.5 vf/fN v1.4 v3 % of tripping characteristic v30 % of tripping characteristic Steps 0.01 Steps 0.1 min Trip temperature 0.1 to 4 0.5 to 999.9 min 70 to 100 % Alarm wmax = k N t + tIn 2 – 2pre 2 –(k @ N) 2 Q/QAlarm approx. 0.99 Q/QOff approx. 0.99 /Alarm approx. 0.99 Class 5 % acc. to IEC 0.95 vf/fN v1.05 v1 % of tripping characteristic /N = 0.1 to 30 /N = 0.1 to 30 0 to 32 s or inactive " 3% of the setting value " 1% or " 10 ms approx. 35 ms Siemens LSA 2.2.4 . May 1996 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Technical data (continued) Overcurrent–time protection, setting ranges (continued) Overcurrent–time protection, inverse time Setting ranges Restricted earth–fault protection Tank protection (normal) sensitive one stage definite time overcurrent for on star–point CT) p/N = 0.1 to 20 0.5 to 32 s 1.1 x p Overcurrent phase Time multiplier tp Energization threshold Characteristics according to IEC 255–4, Section 3.5.2 or BS142 Linear measuring range Tolerances Energization threshold Timing 40 x N " 5% " 5% for 2 (/p) <20 and tp = 1 30 ms Response value REF/N Phase angle Response time for 5 x REF REF = 0.05 to 2 90 to 135 in steps of 10 approx. 25; 17 ms Response value Sensitive, normal input transformer > Response time for 5 x response value Delay time tI > at 50; 60 Hz at 16 2/3; 50, 60 Hz 10 to 1000 mA; 0.1 to 10 x N approx. 25; 20; 20 ms 0 to 60 s Note: For three winding differential protection the REF and tank protection do not work parallel to differential protection Measuring transducer/operational measurement Load currents primary secondary tertiary with 7UT513 Measuring range Tolerance Overload protection values Winding temperature Measuring range Tolerance Fault logging Storage Fault recording on the high–voltage side on the low–voltage side tertiary (for 7UT513) Max. storage time at 16 2/3; 50; 60 Hz Time resolution of the Instantaneous values at 16 2/3; 50; 60 Hz Siemens LSA 2.2.4 . May 1996 L1; L2; L3 L1; L2; L3 L1; L2; L3, E1, E2 0 to 240 % N v2 % of rated value /Off calculated 0 to 240 % v3 % referred to Off Up to last 8 faults L1; L2; L3 L1; L2; L3 L1; L2; L3 E1. E2 15; 5; 4.1 s 5; 1.66; 1.39 ms 7 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Selection and ordering data Order No. 7UT51 – B 1 – A 0 7UT512/513 differential protection relay Application for Two–winding transformer or machine or short two–end line Two–winding/three–winding transformer or machine or short two–/three–line 2 3 Rated current at 50/60 Hz AC, 16 2/3 1A 5A 1 5 Rated auxiliary voltage 24, 48 V DC 60, 110, 125 V DC 220, 250 V DC 2 4 5 Construction For panel flush mounting or cubicle mounting For panel surface mounting For panel flush mounting or cubicle mounting, without glass cover C D E Country–specific presetting German/English, 50 Hz (switchable for each parameter to 16 2/3 and 60 Hz) 0 Additional functions Overcurrent–time protection, two overload functions (standard on 7UT512) Overcurrent–time protection or restricted earth–fault protection, two overload functions (standard on 7UT513) Overcurrent–time protection (phase) or normal/sensitive overcurrent (earth), two times overload protection (one sensitive measuring input for 7UT513) 0 1 2 Serial system interface Without Electric according RS 232 Fibre optic interface (820 nm) A B C Operating program DIGSI 1) DIGSI Version V3 for Windows, full version for 10 PC’s and update for 3 years, German English 7XS5020–0AA00 7XS5020–1AA00 DIGSI Version V3 for Windows, demo–/testversion, German English 7XS5021–0AA00 7XS5021–1AA00 Documentation English: Catalog LSA 2.2.4: 7UT512/513 (V3) Differential protection relay for transformers, generators, motors and short lines Manual: 7UT512/513 (V3) Numerical differential protection for transformers, generators, motors and short lines E50001–K5722–A141–A2–7600 C53000–G1176–C99–2 German: Katalogblatt LSA 2.2.4: Differentialschutz 7UT512/513 (Version V3) für Transformatoren, Generatoren, Motoren und kurze Leitungen Handbuch: Digitaler Differentialschutz 7UT512/513 (Version V3) für Transformatoren, Generatoren, Motoren und kurze Leitungen E50001–K5722–A141–A2 Spanish E50001–K5722–A141–A2–7800 Catálogo LSA 2.2.4: Protección diferencial 7UT512/513 (version V3) para transformadores, generadores, motores y líneas cortas C53000–G1100–C99–2 1) German and English available, other languages on request. 8 Siemens LSA 2.2.4 . May 1996 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines 7UT512xx–xxBx–0xA0 Transformer CT1 Short line Generator/motor CT2 G/M 87T 87 G/M 50/51 49 87L 50/51 49 49 50/51 49 49 49 Note: (50/51) and (49) can freely be assigned to CT1 or CT2 of protected device. The 7UT512 selects the appropriate set of measured currents for each protection function depending on the above assignment. 7UT513xx–xxBx–1xA0 Transformer CT1 Transformer CT2 CT2 87N CT3 87T 50/51 Short line CT1 CT1 CT3 CT3 87T 49 49 CT2 87L 49 50/51 49 49 49 (50/51) and (49) can freely be assigned to CT1, CT2 or CT3. (87N) and (49) can freely be assigned to CT1, CT2 or CT3. (50/51) and (49) can freely be assigned to CT1, CT2 or CT3. 7UT513xx–xxBx–2xA0 Transformer CT1 CT2 50N CT3 49 49 Thermal relay 50/51 Two step time overcurrent relay 87T 49 (50N) is available as normal/sensitive function. 49 can freely be assigned to CT1, CT2 or CT3. 50N Tank protection as single step definite time overcurrent relay (optional sensitive) 87N Restricted earth fault protection 87T Transformer differential relay Fig. 6 Applications Siemens LSA 2.2.4 . May 1996 9 10 L2 L1 L3 L3 N L1 L2 L3 L1 L2 L3 Side 2 N G N Side 1 N L3 L1 L2 L3 L2 L1 L2 L3 L1 Binary input, alarm relays, command relays and LEDs are marshallable L2 L1 N L3 Power supply MR RxD I >> blocking (definite/inverse time) LED Reset Exciter L2 L1 N L3 L2 L1 3B2 2B1 2B2 1B1 1B2 20 18 21 19 22 16 32 31 4B1 10 L+ L–11 4A2 4A 4A1 4B2 8A4 8A3 36 35 8A2 33 8A1 3B1 17 34 1A2 2A2 1A1 5 3 6 3A2 2A1 3A1 4 2 1 Command relay 2 Link with the central equipment either fibre–optic or V.24 interface (RS 232C) 2–kV–isolated Binary input 2 Binary input 1 7UT512 Command relay 1 Malfunction alarm relay Alarm relay 4 Alarm relay 3 Alarm relay 2 Alarm relay 1 Version for panel flush mounting/cubicle mounting Version for panel surface mounting 4A4 4A 4A3 5B1 5B3 5B4 5B2 5A1 5A3 5A4 5A2 7B1 8B1 6B1 7B2 8B2 6B2 7B3 8B3 6B3 7B4 8B4 6B4 6A3 6A1 6A2 47 46 MT TxD 12 27 28 General trip 13 14 29 30 General trip 15 44 Backup general trip 43 57 56 Fault indications of the device 55 60 59 Device operative 58 45 39 38 37 Device general trip 42 41 Trip command 40 DIFF > and DIFF >> Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Fig. 7 Connection diagram for 7UT512 differential protection relay, with overcurrent standby and two overload functions Siemens LSA 2.2.4 . May 1996 Siemens LSA 2.2.4 . May 1996 Side 2 L1 L2 L3 L1 L2 L3 N L1 L2 L3 N Side 3 N L1 L2 L3 N i E2 i E1 L3 L2 L1 N L3 L2 L1 N L3 L2 L1 MR RxD Buchholz indication Buchholz warning 3A2 2A1 2A2 1A1 1A2 3B1 4 2 5 3 6 7 2C2 1C1 30 28 31 29 26 52 51 4A1 4A 4A2 4B2 4B1 15 L+ L– 16 7D1 62 7D2 8D4 8D3 59 60 58 8D2 8A4 8D1 55 57 8A3 8A2 8A1 2D2 1D2 2D1 56 53 54 34 14 33 1C2 1D1 3D2 2C1 27 32 13 1B2 3D1 12 11 2B2 9 1B1 10 3B2 8 2B1 3A1 1 Command relay 1 Alarm relay 5 Alarm relay 10 Alarm relay 9 Alarm relay 8 Command relay 5 Command relay 4 Command relay 3 Link with the central equipment either fibre–optic or V.24 interface (RS 232C) 2–kV–isolated Binary input 5 Binary input 4 Command Binary input 3 relay 2 Binary input 2 Binary input 1 7UT513 Alarm relay 7 Alarm relay 6 Malfunction alarm relay Alarm relay 4 Alarm relay 3 Alarm relay 2 Alarm relay 1 Version for panel flush mounting/cubicle mounting Version for panel surface mounting 61 User defined indication I >> blocking (definite/inverse time) LED Reset Power supply Binary inputs, alarm relays, command relays LEDs can be marshalled L1 L2 L3 Side 1 L1 L2 L3 65 64 63 68 67 66 71 70 69 86 85 84 88 Device operative Fault indications of the device Backup general trip Trip command I DIFF> andI DIFF >> Device general trip 43 19 18 17 74 99 100 75 72 97 98 73 20 22 23 21 24 44 General trip General trip General trip Buchholz indication Buchholz warning 96 95 Tank protection trip command 91 Thermal warning stage overload 1, 2 94 93 Restricted earth fault trip command 4A3 76 4A 4A4 77 MT TxD 5D2 25 General trip 5D3 49 General trip 5D4 50 7D3 6A3 6A1 6A2 5B1 5B3 5B4 5B2 5A1 5A3 5A4 5A2 6D1 6D3 6D4 6D2 5D1 4C1 4C4 4C2 4C3 3C4 3C2 3C3 7D4 4D3 89 Overload trip 1, 2 3C1 92 4D1 87 4D4 90 7B1 8B1 6B1 7B2 8B2 6B2 7B3 8B3 6B3 7B4 8B4 6B4 4D2 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Fig. 8 Connection diagram for 7UT513 differential protection relay with overcurrent standby and two overload functions 11 Differential Relays 7UT512/513 differential protection relay (Version V3) for transformers, generators, motors and short lines Version for panel surface mounting Version for panel flush mounting/cubicle mounting L1 L2 L3 L1 L1 L2 L3 L2 L3 N N Restricted earth–fault protection E2 Tank protection 1 4 7 6 3 4 7 10 3 11 12 27 30 28 31 20 32 13 14 33 34 3A1 3A2 2A1 2A2 1A1 1A2 3B1 3B2 2B1 2B2 1B1 1B2 3D1 3D2 2C1 2C2 1C1 1C2 1D1 1D2 2D1 2D2 IL1 Winding1 7B1 8B1 6B1 7B2 8B2 6B2 7B3 8B3 6B3 7B4 8B4 6B4 4D2 Alarm relay 1 IL2 Winding 1 Alarm relay 2 IL3 Winding 1 IL1 Winding 2 IL2 Winding 2 IL3 Winding 2 IL1 Winding 3 Alarm relay 3 Alarm relay 4 Malfunction alarm relay IE2 Alarm relay 8 IE1 Alarm relay 10 Alarm relay 11 Binary input 1 Command relay 1 55 3A4 Connection of the restricted earth fault protection is freely allocable to side 1, side 2 or side 3. For ordering with normal/sensitive overcurrent earth (Pos. 13 = 2) E2 is the sensitive input (also as tank protection). For ordering with REF or overcurrent (Pos. 13 = 1) both inputs E1, E2 are normal inputs. Power supply Fibre optic Binary input 2 57 8D2 58 8D1 Command relay 2 Binary input 3 59 8D4 60 8D3 Binary input 4 Command relay 3 61 7D2 62 7D1 Binary input 5 15 4B1 L+ +12 V 4B5 16 4B2 L– –12 V 4B4 81 4A1 4A 82 4A2 Fault indications of the device 5D3 49 5D4 50 General trip Alarm relay 7 53 3A2 56 3A3 Standby general trip Command relay 5 IL3 Winding 3 Alarm relay 9 54 3A1 Trip command I DIFF> andI DIFF>> Command relay 4 Alarm relay 6 E1 Device general trip Device operative 4D1 87 (not marshallable) 4D4 90 4D3 89 Overload trip 1, 2 3C1 92 Thermal warning stage 4C1 91 overload 1, 2 4C4 94 4C2 93 Restricted earth fault 4C3 trip command 3C4 96 3C2 95 Tank protection trip 3C3 command 7D4 44 7D3 43 Buchholz warning 6A3 19 6A1 18 Buchholz indication 6A2 17 5B1 74 5B3 99 5B4 100 General trip 5B2 75 5A1 72 5A3 97 5A4 98 General trip 5A2 73 6D1 20 6D3 22 6D4 23 General trip 6D2 21 5D1 24 5D2 25 General trip IL2 Winding 3 7UT513 65 64 63 68 67 66 71 70 69 86 85 84 88 76 4A 77 V.24 interface (RS 232 C) Fibre–optic interface Connection for the LSA 4A3 4A4 TxD–K Fibre optic MT 26 SV Connection of the restricted earth–fault protection can be parameterized for different winding. Fig. 9 Connection diagram for 7UT513 differential protection relay with restricted earth fault protection (low impedance) or sensitive/normal overcurrent (earth) 12 Siemens LSA 2.2.4 . May 1996 Differential Relays Dimension drawings in mm 145 172 29.5 131.5 105 7.3 13.2 5.4 30 Diam. 5 or M4 255.8 Fibre optic connection 245 266 244 10 1.5 Diam. 6 150 146 231,5 Front view Side view Panel cutout Fig. 10 7UT512 with housing 7XP2030–2 (for panel flush mounting or cubicle mounting) 30 172 29.5 206.5 180 7.3 13.2 5.4 220 255.8 245 244 266 Diam. 5 or M4 Fibre optic connection 1.5 10 Diam. 6 225 231.5 221 Front view Side view Panel cutout Fig. 11 7UT513 with housing 7XP2040–2 (for panel flush mounting or cubicle mounting) 234 31 46 159 ..... ..... 27 7.5 45 60 51 76 ..... ..... 29.5 75 100 266 40 344 280 344 280 Cutout 20 x 60 (without paint) 1.5 39 Detail Z: 1 16 ..... ..... 144 15 30 1 26 ..... ..... 219 7UT512 (7XP2030–1) 7UT513 (7XP2040–1) Front view Side view 25 50 Z 71 260 Side view Fibre optic interface Fig. 12 7UT512/513 for panel surface mounting Siemens LSA 2.2.4 . May 1996 13 Differential Relays Conditions of Sale and Delivery S Export Regulations S Trademarks S Dimensions Conditions of Sale and Delivery Subject to the General Conditions of Supply and Delivery for Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon with the recipients of catalogs. J The technical data, dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. We reserve the right to adjust the prices and shall charge the price applying on the date of delivery. The illustrations are for reference only. A 9.91 a Export Regulations In accordance with present German and US export regulations export licences (dated 05.96) are not required for the products listed in this catalog. Export and re–export are therefore Trademarks All product designations used are trademarks or product names of Siemens AG or of other suppliers. permissible without the approval of the relevant authorities except where current German export regulations contain country–specific restrictions. Subject to change. Relevant are the criteria stated in the delivery note and in the invoice. An export licence may be required due to country–specific application of the product. Dimensions All dimensions in this catalog are given in mm. Siemens online! You will find Siemens Power Transmission and Distribution in the Internet: http://www.ev.siemens.de Responsible for Technical contents: Norbert Schuster, Siemens AG, EV S V13, Nürnberg General editing: Roland Reichel/Claudia Kühn–Sutiono, Siemens AG, EV S SUP22, Nürnberg/EV BK2, Erlangen Bereich Energieübertragung und -verteilung Geschäftsgebiet Sekundärtechnik P. O. Box 48 06 D-90026 Nürnberg 14 Siemens Aktiengesellschaft Power Transmission and Distribution Order No.: E50001-K5722–A141-A2–7600 Siemens LSA 2.2.4 . May 1996 Printed in the Federal Republic of Germany KG K 0696 3.0 SC 14 En