Safety CountS What is GFCI Protection? By Tom Ruffner GFCI stands for “ground fault circuit interrupter.” This is an elec- was grounded, a GFCI would not help. The person’s hand or finger would tronic device that measures the ac current flowing through the “hot” essentially act as a bridge between the two conductors and current would wire and “neutral” wire of the tool or appliance being powered. GFCI’s flow from the “hot” wire or wires through the body. Since the currents are usually built directly into receptacles and circuit breakers. They are in both wires are equal, the GFCI would not disconnect the power and most commonly used on 120V ac and 240V AC single-phase circuits. They the person could receive a potentially fatal shock. are also offered by some manufactures as “in-line” devices that can be GFCI’s are sophisticated devices that must be wired properly in order used with just about any power tool or appliance. They are designed to function as intended. Like any mechanical or electrical device, GFCI’s with very fast response times that help protect people from fatal electric can also go bad. Always consult a qualified electrician if there is any shocks in the event of a ground fault. doubt about the correct way to install these devices. GFCI devices typi- What is the difference between GFCI’s, circuit breakers, and fuses? GFCI’s are safety devices that protect people from potentially fatal electric shocks. Circuit breakers and fuses are designed to protect the wiring to the equipment being powered and to protect the equipment from being damaged in case of a malfunction. They are designed to trip or open when excessive currents are detected. Conventional circuit breakers and fuses do not prevent people from being electrocuted. How does a GFCI work? As long as the currents in the power and return conductors are equal, the GFCI takes no action. If the current differs by more than a few milliamperes (typically less than 6 milliamperes), the GFCI recognizes that current is escaping to some alternate path and it quickly disconnects the incoming power to prevent electrocution. The leakage could be from a short circuit to the chassis of the equipment, to the ground lead or through a person. Any of these situations are hazardous and could be fatal if a GFCI in not being used. Are there any situations when a GFCI would not protect the user? It is important to understand that a GFCI does not protect against every type of electric shock. For example, if a person simultaneously touched the “hot” and the “neutral” wires of a 120V AC circuit, or touched two “hot” wires of a 240V AC circuit, and no part of that person cally contain a “test” and a “reset” button to make sure that the device is functioning properly. It is recommended that all GFCI’s be tested a least once a month to ensure they are operating correctly and providing the required protection. Can GFCI protection be installed on a three-phase generator? The answer to this question is, “not exactly.” A device called an “equipment leakage current interrupter” (ELCI) can be used on three phase equipment with line voltages of 230V AC or 460V AC. In order for a device to be classified as a GFCI by Underwriters Laboratories (UL), it has to have a trip level setting less than 6 milliamperes of leakage current. For this reason, GFCI’s are considered personal protection devices while ELCI’s are considered to be equipment protection devices. ELCI’s have user-adjustable trip level settings, up to 30 milliamps. The reason for the adjustable trip level is to avoid nuisance tripping. When the line voltage or line current increases, so does the likelihood of nuisance tripping. GFCI devices are limited to 30 amps while ELCI devices go as high as 100 amps. ELCI’s are “inline” devices that operate on three-phase 230V AC or 460V ac power sources. How does an ELCI work? An ELCI operates in the same manner as the single phase GFCI devices mentioned earlier. Even though an ELCI allows more leakage current through in the event of a ground fault, an ELCI still provides an additional level of user safety because it disconnects the incoming power much REPRINTED FROM CONCRETE OPENINGS | VOL.16 | NUM.4 | DECEMBER 2007 quicker than a conventional three-pole circuit motor, but this is what is required to handle breaker. The disconnecting time of the line the high surge currents during initial start-up voltage is 25 milliseconds or less which means to ensure trouble-free equipment operation. The most commonly used plugs and recep- that the person operating the equipment may If a single-phase motor is to be powered, fol- tacles on portable equipment are “twistlock” only receive a mild shock instead of a fatal one. low the same procedure but only multiply the devices. These devices plug together and have Because ELCI’s are “in- line” devices, they can horsepower by 2½ times for selecting the gen- a locking feature to keep them from pulling be added to practically any type of three-phase erator size. Single-phase motors are even more apart. They are available in current ratings equipment. difficult to start than three-phase motors and, from 20 amps to 50 amps and cover voltages therefore, require a larger generator. up to 600V AC three-phase depending on the An ELCI should be considered as an additional safety device and in no way should be a substitute for the equipment grounding conductor. A secure ground should be attached to the metal frame or housing of the equipment at all times. Always select an ELCI with the proper line voltage and load current What will happen if a generator is too small? Some of the most common components that fail from selecting a generator that is too small are circuit breakers, fuses, motor rating for the application. starters, motor windings, motor start wind- What size generator is right to power various pieces of equipment? generator windings, and generator voltage This is probably one of the most asked and the current demanded, the magnetic field in least understood questions for anyone using the generator winding starts to collapse and power equipment. In order to avoid costly this causes a rapid drop in line voltage and downtime and damage to the generator and line frequency. When this happens, generator the equipment being powered, it is import to and motor winding temperatures increase and properly size the generator for the job. On damage to the winding insulation can occur. In the nameplate of the generator there will be this type of situation, the supporting electrical two ratings kVA (Kilovolt Amperes) and kW components are also being overworked which (Kilowatts). The kVA number will always be leads to premature failure. higher than the kW number due to a variable called “power factor”. The ideal power factor number is 1. This means that all of the power drawn is used to perform work and kVA equals kW. In real world conditions, the power factor number is more often about .80 due to the energy losses within the equipment being powered. Manufacturers of generators will usually designate a continuous output rating for a generator at a given temperature rise of the winding, usually 125 degrees centigrade. Use the kW output rating at this temperature when choosing the generator size. When operating three-phase induction motors, a good rule of thumb is to select the size of the generator by doubling the horsepower of the motor to find ings and capacitors (single phase motors only), regulators. When the generator can’t supply What type of plugs & receptacles should be used? model chosen. Each device is numbered with a National Electrical Manufacturers Association (NEMA) code for standardization purposes. The NEMA number on the plug and receptacle have to be identical, otherwise, they will not connect together. As long as the number matches, different brands with the same ratings are interchangeable. Devices called “pin and sleeve” are available for currents above 50 amps three-phase. These devices are physically bigger in size and usually carry a much higher price tag than “twistlock” type devices. They are also available up to 600V AC and currents up to 100 amps. When choosing any plug and receptacle configuration, always choose devices that are rated for the maximum current and supply voltage at which the equipment will be operated. It is important that the devices be installed properly to avoid loose connections or “hot spots. ” Always perform a visual inspection of plugs and receptacles before each use and repair or replace any device that shows signs of damage or excessive wear. To prolong lifetime and reduce the likelihood of failures, always keep plugs and receptacles away from excessive moisture or water. Tom Ruffner is the Electrical Engineer at Diamond Products, Inc. in Elyria, Ohio. He can be reached at 800-321-5335. how many kW is needed. For example, if the equipment has a 20 horesepower three-phase motor, you will need a total of 40 kilowatts of useable power from the generator to insure enough surge capacity just for starting the motor. At 40kW, this same generator would have a total of 50kVA assuming a .80 power factor. This may sound like a large safety cushion for a 20 horesepower REPRINTED FROM CONCRETE OPENINGS | VOL.16 | NUM.4 | DECEMBER 2007