DIA TECH RTMP - Rotor Winding Temperature Monitoring

advertisement
DIA TECH RTMP
Rotor Winding Temperature Monitoring
RTMP Measurement Scheme
Required Parameters
Rotor current & voltage
SCADA
(Supervisory
Control and
Data
Acquisition)
DIA TECH RTMP supplies continuously
the rotor winding temperature by calculation using rotor current, rotor voltage and
cold-resistance (as constant). Conventional limit values can be specified on customer’s request, in order to announce critical
thermal conditions in time.
LAN
Monitoring
Computer
Graļ¬cal User
Interface
Acquisition of measured values
The required rotor values – current and
voltage – are generally available in power
plants. The DIA TECH System usually obtains these measured values from the existing automation, instrumentation or control
system. The data transfer happens on a
standardised interface based on Ethernet
under TCP/IP as well as on serial connection.
Processing of measured values
After using the standard calculation method the DIA TECH RTMP module sends
the results to the data management – DIA
TECH CORE system – which distributes
them to database for long-term storage
and graphical user interface (GUI) for smart
trend visualisation. In case of limit violation
the DIA TECH RTMP module generates a
message, which will be displayed on the
DIA TECH visualisation screen.
www.andritz.com/diatech
DIA TECH RTMP
Rotor Winding Temperature Monitoring
Acquisition requirements:
Required hardware:
Data acquisition components – SCADA,
control system or any PLC
Auxiliary parameters for diagnosis
Rotor current
Rotor voltage
Main specification:
Number of monitored generators:
One (1) software package is able to cover
all generators of a large power plant with
up to 10 units.
Limit monitoring
(pre-warning, warning) upon
Rotor winding temperature
System requirements:
DIA TECH RTMP requires the data
management software package DIA
TECH CORE. All DIA TECH Modules are
running on standard personal computers and a Windows®-based platform.
Available DIA TECH Knowledge Modules:
DIA TECH CAA-HS (Cooling air analysis – hotspot detection)
DIA TECH CAA-O3(Cooling air analysis – ozone diagnosis for surface partial discharge)
DIA TECH CAV (Cavitation monitoring)
DIA TECH IRD (Rotor pole temperature module based on infrared measurement)
DIA TECH MFX (Magnetic flux monitoring)
DIA TECH MGM (Machine gap monitoring module for air gap and turbine clearance)
DIA TECH RTMP (Rotor winding temperature module based on calculation)
DIA TECH SBS (Structure borne sound diagnosis for stator core vibration
DIA TECH ThM (Thermal diagnosis for stator core & winding and cooling circuit)
HP.DIATECH_RTMP 01.e.04.12
DIA TECH CORE
DIA TECH TPOT
(Data management package with graphical user interface)
(Turbine / pump operation time counter)
ANDRITZ HYDRO GmbH
Eibesbrunnergasse 20
1120 Vienna, Austria
Phone: +43 50805 5
Fax: +43 50805 5 1015
E-Mail: contact-hydro@andritz.com
ANDRITZ HYDRO GmbH
Monitoring & Diagnosis
Dr.-Karl-Widdmannstraße 5, 8160 Weiz, Austria
Phone: +43 (3172) 606-2296
Fax: +43 (3172) 606-496
E-Mail: diatech@andritz.com
DIA TECH is part of NEPTUN, the integrated
common solution for secondary technology.
www.andritz.com/diatech