Fan Flued Non-Condensing Water Heaters

advertisement
Fan Flued Non-Condensing Water Heater | PRODUCT SPECIFICATION
PRODUCT SPECIFICATION
Fan Flued Non-Condensing Water Heaters
With all the advantages of the Standard and HIflo
ranges, the Fan flued range has the addition of
a fan assisted flue, making it the perfect choice for
installations where longer flue runs are required.
B
Technical Specification
All the technical information you need is easy to find
on our website, using your smart phone, tablet or PC:
-BIM files
-CAD files
-Brochures
-Technical specification sheets
-Case studies
-Installation manuals
-User guides
-Size-It Tool
Sales
0345 070 1055
Technical
0345 070 1057
Website
andrewswaterheaters.co.uk
Twitter
@AndrewsWH
ICOM
15kW and
17.5kW
76.9%
OUTPUT
GROSS EFFICIENCY
300 l\hr
50°C rise
Up to
at
RECOVERY RATE
Andrews. Built to perform.
Registered office address: Baxi Heating UK, Coventry Road, Warwick CV34 4LL
500403
NOx EMISSIONS [0%O2]
Features
Benefits
Two models, 190 and 280 litres storage capacity
Provides instant hot water for peak demands
Recovery rate up to 300 litres per hour
Excellent hot water recovery rate
Vitraglas® lined storage tank
Thermally efficient water storage. Protects glass lining and reduces service
and maintenance time and costs
Factory installed Hydrojet® sediment reduction system
Longer and more efficient working life
Supplied with draught diverter, gas cock and water drain valve
Easy, cost effective installation
80mm diameter horizontal or vertical flue kits available
Flexible siting and longer flue runs
WRAS approved
Complies with the Water Supply (Water Fittings) Regulations and
Scottish Byelaws
Energy Association
RS 33961
As low as
111mg/kWh
Tel 0345 070 1055
Web andrewswaterheaters.co.uk
Andrews. Built to perform.
Model
Specifications
Energy
23
Heat output
kW
15
17.5
ALL
Gross thermal efficiency
%
76.9
76.1
Part No
Mj/month
327
712
Horizontal flue kit
B176
mg/kWh
115
111
Vertical flue kit
B227
ppm
56
54
1m flue
C793
B
B
0.5m flue
E361
1.82
2.15
90° bend
C792
C794
ErP
ErP efficiency rating
Gas data
Gas flow rate (natural gas)
m3/h
Litre
190
280
45° bend
Recovery rate through 50°CΔt
Litre/hr
257
300
Flue condensate trap
E548
Recovery rate through 56°CΔt
Litre/hr
230
268
Wall terminal guard
E105
Operating pressure (unvented)
bar
3.5
3.5
Water Controls
200
Storage capacity
Minimum working pressure
bar
0.2
0.2
Maximum pressure
bar
10
10
Fuse rating
amp
5
5
W
236
236
ALL
Noise level
dBA
34
38
Part No
Weight full
kg
273
418
Unvented systems kit
B171
Weight empty
kg
85
132
Correx powered anode kit
B196
Max. flue run (vertical)
m
8
5
Max. flue run (horizontal)
m
7
4
Electrical power consumption
Dimensions
Andrews. Built to perform.
Flueing and Ancillary
19.5
NOx emissions (0% O2) natural/propane
Misc
RFF280
kW
NOx emissions (0% O2) natural
Electrical
RFF190
Heat input (gross)
Standby heat loss
Water
Accessories
unit
RFF190
RFF280
A. Height of heater
mm
1451
1527
B. Height of flue spigot
mm
267
267
C. Diameter
mm
559
660
D. Water connection centers
mm
279
279
E. Flue diameter
mm
80
80
F. Top service clearance
mm
1400
1400
G. Gas connection height
mm
378
438
H. Min/max wall thickness
mm
I. Min/max flue horizontal
mm
483 / 7000
533 / 4000
J. Max flue vertical
mm
8000
5000
K. Height to flue centre from floor
mm
1867
1943
L. Side & rear service clearance
mm
305
305
M. Front service clearance
mm
610
610
N. Flue connection centre
mm
171
222
O. Flue connection centre
mm
394
444
Inlet and flow connections
BSP
¾"
¾"
Return connection
BSP
¾"
¾"
Drain port size
BSP
¾"
¾"
150 - 300
View from top
Flue Options
Front View
Download