SUM 1001

advertisement
SUM 1001
SUM 1001
Voltage measuring relay
•
•
•
•
•
•
For failing to meet and for exceeding the threshold value of single-phased voltages
3 operating ranges AC/DC: 0.5 to 500 V
Curve shape: sine, square, triangle
10 time domains: non-delayed, 0.1 s to 3 h for the operate time delay
Frequency range of the measured variable from 45 to 400 Hz
Multifunction: Operating or rest current principle, hysteresis 3 % or 10 % of the target
value
Wiring diagram
Applications
•
•
•
•
•
Monitoring of voltage levels
Monitoring of external voltage in mains with external supply
Monitoring of field excitation in motors
Monitoring of frequency actuators
Monitoring of analog actuating variables
Function
The voltage measuring relay SUM 1001 is a monitoring relay for singlephase voltages. The measurand is supplied via various terminals, based
on the desired operating range (see Table I). With the potentiometer
target value, the response value can be set analogously within the preselected operating range. The operate time delay can be set with the time
domain switch and the potentiometer time target value (see Table II).
Notes:
• The supply voltage is galvanically separated from the measurement
circuit and is displayed via the LED "SUPPLY".
• The measurand is recorded with an integrating full-wave rectification.
With that, in certain limits, the monitoring of voltages, which are not sineshaped (e.g. voltages with a harmonic wave concentration, square or
triangular voltages in the range of 45 - 400 Hz) is possible.
• The devices assess (for AC) the rectification value calibrated to the
effective value of a sine voltage.
• For DC measurands, a rectification occurs and the mean value is monitored.
• In the delay domain NO DELAY and with the simultaneously poweredon function measurand exceedance (> V) the monitoring relays respond as of a certain threshold to the present value of the measured
variable, and the output relay toggles instantaneously (see technical
data).
• Prior to the insulation or voltage test in the switching installation, the
connector lines are to be disconnected from the voltage measuring
relay.
Page 92
SUM 1001
Function operating current principle
After application of the supply voltage and the falling below or exceeding of the preselected response value (based on the function selection see Table III), the output relay toggles to the operating position. This
takes place either after the preselected response delay or immediately. If
the response value - based on the setting - falls below or exceeds by at
least 3 or 10 % (hysteresis), then the output relay returns to the Standby
position.
Function standby current principle
After application of the supply voltage, the relay toggles to tB, to the
operating position. If the preselected limit value falls below or exceeds
(based on the function selection), then the output relay re-toggles to the
Standby position, depending on the preselected delay time. According
to the preselected hysteresis (3 or 10 %), the output relay re-toggles to
the operating position after falling below or exceeding the response
value.
Subject to change without further notice
SUM 1001
Application example
Application example
Example setting:
Target value (response value) AC/DC 25 V
Time delay
210 s
Function
Exceeding, operating current principle, 3 %
hysteresis
Example setting:
Target value (response value) AC/DC 4 V
Time delay
without
Function
Falling below, standby current principle, 10 %
hysteresis
Table I
• operating range 2 (terminals B1 and B3)
• potentiometer target value to 0.5 (0.5 x operating range end value 50
V) = 25 V (target value)
Table I
• operating range 1 (terminals B1 and B2)
• potentiometer target value to 0.8 (0.8 x operating range end value 5
V) = 4 V (target value)
Table II
• Time domain-end value 300 s
• potentiometer time target value to 0.7 (0.7 x Time domain-end value
300 s) = 210 s (response time delay)
Table II
• Time domain-end value NO DELAY
• potentiometer time target value random = without response time
delay
Table III
• Function > V 3 %
• Function selector switch, Position 4
Table III
• Function < V 10 %
• Function selector switch, Position 8
If the measurand exceeds the target value of 25 V, then the LED TRIPPED
starts flashing. After the elapse of the preselected operate time delay of
210 s, the output relay toggles to the operating position, and die LED
TRIPPED stays on. If the actual value of the measured variable falls below
the target value minus the 3% hysteresis, then the output relay retoggles to its Standby position. If the measurand falls below before
reaching the preselected time, then the LED "TRIPPED" goes out (see
function diagram 1).
If the measurand falls below the target value of 4 V, then the output relay
without time delay toggles to the Standby position, and the LED
"TRIPPED" lights up. If the actual value of the measured variable exceeds
the target value plus the 10% hysteresis, then the output relay toggles to
the operating position. The LED "TRIPPED" goes out (see function diagram 4).
Page 93
SUM 1001
Subject to change without further notice
SUM 1001
Function diagrams
Settings
Table I
operating range
Nr • AC/DC
Connector interior
resistance
Frequency
1 • 0.5 to 5 V
B1 - B2
11.3 kΩ
45 - 400 Hz
2 • 5 to 50 V
B1 - B3
102.2 kΩ
45 - 400 Hz
3 • 50 to 500 V
B1 - B4
1,022 MΩ
45 - 400 Hz
* Observe the rated voltage and excess voltage category
permissible
excess voltage
(constant)
25 V
250 V
625 V *
Table II
Time domain
1s
3s
10 s
30 s
100 s
300 s
1000 s
1h
3h
NO DELAY
Value
0.1 s to
1s
0.3 s to
3s
1 s to
10 s
3 s to
30 s
10 s to 100 s
30 s to 300 s
100 s to 1000 s
0.1 h to
1h
0.3 h to
3h
without delay
A toggle of the time domain switch or the function
switch during the countdown ends the countdown
immediately.
Table III
Switch,
Function
monitoring
>V
>V
<V
<V
>V
>V
<V
<V
Exceeding
Exceeding
Falling below
Falling below
Exceeding
Exceeding
Falling below
Falling below
3%
3%
3%
3%
10 %
10 %
10 %
10 %
Functional principle
Output relay
Operating current
Rest current
Operating current
Rest current
Operating current
Rest current
Operating current
Rest current
Hysteresis
3%
3%
3%
3%
10 %
10 %
10 %
10 %
Dimensional drawing
Device overview / Order numbers
Type
SUM 1001
Page 94
Operating range
AC/DC 0.5-500 V
SUM 1001
Rated voltage
AC 115 V 50-60 Hz
AC 230 V 50-60 Hz
Order number
R3.185.0299.0
R3.185.0229.0
Subject to change without further notice
SUM 1001
Technical Data
SUM 1001
Function type according to DIN EN 60255-6:11.94
Function check
Function diagram
Supply circuit
Nominal voltage UN
Rated output at 50 Hz and UN (AC)
Rated output at 50 Hz and UN (AC)
Maximum power-on current pulse at UN (< 1 ms)
Nominal frequency
Operating voltage range
Parallel consumer loads permissible
Voltage measuring relay with operating and standby current principle
1 LED green, 1 LED red
FD 0242-5-1 W1 to +FD 0242-5-4 W1
AC
115 V
2.5 VA
2.3 W
0.25 A
50 to 60 Hz
0.8 to 1.1 x UN
yes
230 V
2.5 VA
2.3 W
0.13 A
Measurement circuit (DC and/or sine-shaped measured voltage)
Galvanic separation from the supply circuit
Setting / Quantity of operating ranges
Setting ranges for measurement circuit-response values
Setting ranges for measurement circuit-Hysteresis values
Response delay
Scatter
Influence of the supply voltage
Influence of the ambient temperature
Nominal frequency range of the measured variable
Minimum impulse length of the measured variable
Minimum impulse length of the measured variable at NO DELAY
yes
analog / 3
see Table I
approx. 3 % and approx. 10 % of the response value, rigidly adjustable
see Table II
≤ ± 0.5 %
≤ ± 0.05 % / % ∆UN
≤ ± 0.05 % / K∆T
45 to 400 Hz AC, DC
25 ms with exceeding/falling below the DC-response value
1 ms with 1.5-fold exceedance of the DC-response value
Timing circuit
Median value of the fault
Scatter
Influence of the supply voltage
Influence of the ambient temperature
< 5 % of the end value
≤ ± 0.2 % + ≤ 50 ms
≤ ± 0.02 % / % ∆UN
≤ ± 0.005 % / K∆T
Output circuit
Contact assembly
Contact material
Switching nominal voltage Un
Max. steady current In per current path
Usage category according to EN 60947-5-1:1991
Short circuit safeguard, max. fuse insert Class gG
Permissible frequency of operation
Mechanical service life
Response time at NO DELAY and > V (AC 50 Hz)
Response time at NO DELAY and > V (DC)
Fallback interval at NO DELAY and > V
Fallback interval at 0.1 s to 3 h
Minimum impulse time output relay
Metering readiness time after powering on the supply voltage
Metering bypass time after powering on the supply voltage
General Data
Air and creep sections between the electric circuits
Rated voltage impulse
Excess voltage category
Degree of contamination
Rated voltage
Testing voltage Ueff 50 Hz according to DIN VDE 0110-1, Table
A.1
Safety class for casing / terminals according to DIN VDE 0470 Section
1:11.92
Interference resistance according to IEC 61000-4
Ambient temperature, work area
Dimensional drawing
Wiring diagram
Connector sections, fine wire / single core
or fine wire with wire end ferrules
Permissible tightening torque
Weight
Accessories
Page 95
SUM 1001
1 NC, 1 NO contacts
Ag alloy, gold-plated
AC/DC 230/230 V
5A
AC-15: Ue 230 V AC, Ie 3 A / DC-13: Ue 24 V DC, Ie 2 A
6A
≤ 6000 switching cycles/h
6
30 x 10 switching cycles
≤ 80 ms at 1.05-fold Response value of the measured variable
≈ 25 ms at 1.3-fold Response value of the measured variable (instantaneous)
≤ 50 ms at 1.1-fold Response value of the measured variable
≈ 15 ms at 1.6-fold Response value of the measured variable (instantaneous)
≈ 30 ms after 1.1-fold Response value of the measured variable
≤ 150 ms after 1.6-fold Response value of the measured variable
≈ 30 ms after 1.1-fold Response value of the measured variable
≈ 35 ms after 1.6-fold Response value of the measured variable
> 100 ms, during the elapse of the minimum impulse time, this is reset upon the
next response from the relay
≤ 100 ms
≤ 60 ms
according to DIN VDE 0110-1:04.97
5 kV
III
3 exterior, 2 interior
500 V AC
2.7 kV
IP 40 / IP 20
Test acuity 3
–20 to +60 °C
S 7-1
KS 0338/1
2 x 0.75 to 1.5 mm² / 2 x 0.75 to 2.5 mm²
1 or 2 x 0.5 to 1.5 mm²
0.8 to 1 Nm
0.3 kg
–
Subject to change without further notice