SUM 1001 SUM 1001 Voltage measuring relay • • • • • • For failing to meet and for exceeding the threshold value of single-phased voltages 3 operating ranges AC/DC: 0.5 to 500 V Curve shape: sine, square, triangle 10 time domains: non-delayed, 0.1 s to 3 h for the operate time delay Frequency range of the measured variable from 45 to 400 Hz Multifunction: Operating or rest current principle, hysteresis 3 % or 10 % of the target value Wiring diagram Applications • • • • • Monitoring of voltage levels Monitoring of external voltage in mains with external supply Monitoring of field excitation in motors Monitoring of frequency actuators Monitoring of analog actuating variables Function The voltage measuring relay SUM 1001 is a monitoring relay for singlephase voltages. The measurand is supplied via various terminals, based on the desired operating range (see Table I). With the potentiometer target value, the response value can be set analogously within the preselected operating range. The operate time delay can be set with the time domain switch and the potentiometer time target value (see Table II). Notes: • The supply voltage is galvanically separated from the measurement circuit and is displayed via the LED "SUPPLY". • The measurand is recorded with an integrating full-wave rectification. With that, in certain limits, the monitoring of voltages, which are not sineshaped (e.g. voltages with a harmonic wave concentration, square or triangular voltages in the range of 45 - 400 Hz) is possible. • The devices assess (for AC) the rectification value calibrated to the effective value of a sine voltage. • For DC measurands, a rectification occurs and the mean value is monitored. • In the delay domain NO DELAY and with the simultaneously poweredon function measurand exceedance (> V) the monitoring relays respond as of a certain threshold to the present value of the measured variable, and the output relay toggles instantaneously (see technical data). • Prior to the insulation or voltage test in the switching installation, the connector lines are to be disconnected from the voltage measuring relay. Page 92 SUM 1001 Function operating current principle After application of the supply voltage and the falling below or exceeding of the preselected response value (based on the function selection see Table III), the output relay toggles to the operating position. This takes place either after the preselected response delay or immediately. If the response value - based on the setting - falls below or exceeds by at least 3 or 10 % (hysteresis), then the output relay returns to the Standby position. Function standby current principle After application of the supply voltage, the relay toggles to tB, to the operating position. If the preselected limit value falls below or exceeds (based on the function selection), then the output relay re-toggles to the Standby position, depending on the preselected delay time. According to the preselected hysteresis (3 or 10 %), the output relay re-toggles to the operating position after falling below or exceeding the response value. Subject to change without further notice SUM 1001 Application example Application example Example setting: Target value (response value) AC/DC 25 V Time delay 210 s Function Exceeding, operating current principle, 3 % hysteresis Example setting: Target value (response value) AC/DC 4 V Time delay without Function Falling below, standby current principle, 10 % hysteresis Table I • operating range 2 (terminals B1 and B3) • potentiometer target value to 0.5 (0.5 x operating range end value 50 V) = 25 V (target value) Table I • operating range 1 (terminals B1 and B2) • potentiometer target value to 0.8 (0.8 x operating range end value 5 V) = 4 V (target value) Table II • Time domain-end value 300 s • potentiometer time target value to 0.7 (0.7 x Time domain-end value 300 s) = 210 s (response time delay) Table II • Time domain-end value NO DELAY • potentiometer time target value random = without response time delay Table III • Function > V 3 % • Function selector switch, Position 4 Table III • Function < V 10 % • Function selector switch, Position 8 If the measurand exceeds the target value of 25 V, then the LED TRIPPED starts flashing. After the elapse of the preselected operate time delay of 210 s, the output relay toggles to the operating position, and die LED TRIPPED stays on. If the actual value of the measured variable falls below the target value minus the 3% hysteresis, then the output relay retoggles to its Standby position. If the measurand falls below before reaching the preselected time, then the LED "TRIPPED" goes out (see function diagram 1). If the measurand falls below the target value of 4 V, then the output relay without time delay toggles to the Standby position, and the LED "TRIPPED" lights up. If the actual value of the measured variable exceeds the target value plus the 10% hysteresis, then the output relay toggles to the operating position. The LED "TRIPPED" goes out (see function diagram 4). Page 93 SUM 1001 Subject to change without further notice SUM 1001 Function diagrams Settings Table I operating range Nr • AC/DC Connector interior resistance Frequency 1 • 0.5 to 5 V B1 - B2 11.3 kΩ 45 - 400 Hz 2 • 5 to 50 V B1 - B3 102.2 kΩ 45 - 400 Hz 3 • 50 to 500 V B1 - B4 1,022 MΩ 45 - 400 Hz * Observe the rated voltage and excess voltage category permissible excess voltage (constant) 25 V 250 V 625 V * Table II Time domain 1s 3s 10 s 30 s 100 s 300 s 1000 s 1h 3h NO DELAY Value 0.1 s to 1s 0.3 s to 3s 1 s to 10 s 3 s to 30 s 10 s to 100 s 30 s to 300 s 100 s to 1000 s 0.1 h to 1h 0.3 h to 3h without delay A toggle of the time domain switch or the function switch during the countdown ends the countdown immediately. Table III Switch, Function monitoring >V >V <V <V >V >V <V <V Exceeding Exceeding Falling below Falling below Exceeding Exceeding Falling below Falling below 3% 3% 3% 3% 10 % 10 % 10 % 10 % Functional principle Output relay Operating current Rest current Operating current Rest current Operating current Rest current Operating current Rest current Hysteresis 3% 3% 3% 3% 10 % 10 % 10 % 10 % Dimensional drawing Device overview / Order numbers Type SUM 1001 Page 94 Operating range AC/DC 0.5-500 V SUM 1001 Rated voltage AC 115 V 50-60 Hz AC 230 V 50-60 Hz Order number R3.185.0299.0 R3.185.0229.0 Subject to change without further notice SUM 1001 Technical Data SUM 1001 Function type according to DIN EN 60255-6:11.94 Function check Function diagram Supply circuit Nominal voltage UN Rated output at 50 Hz and UN (AC) Rated output at 50 Hz and UN (AC) Maximum power-on current pulse at UN (< 1 ms) Nominal frequency Operating voltage range Parallel consumer loads permissible Voltage measuring relay with operating and standby current principle 1 LED green, 1 LED red FD 0242-5-1 W1 to +FD 0242-5-4 W1 AC 115 V 2.5 VA 2.3 W 0.25 A 50 to 60 Hz 0.8 to 1.1 x UN yes 230 V 2.5 VA 2.3 W 0.13 A Measurement circuit (DC and/or sine-shaped measured voltage) Galvanic separation from the supply circuit Setting / Quantity of operating ranges Setting ranges for measurement circuit-response values Setting ranges for measurement circuit-Hysteresis values Response delay Scatter Influence of the supply voltage Influence of the ambient temperature Nominal frequency range of the measured variable Minimum impulse length of the measured variable Minimum impulse length of the measured variable at NO DELAY yes analog / 3 see Table I approx. 3 % and approx. 10 % of the response value, rigidly adjustable see Table II ≤ ± 0.5 % ≤ ± 0.05 % / % ∆UN ≤ ± 0.05 % / K∆T 45 to 400 Hz AC, DC 25 ms with exceeding/falling below the DC-response value 1 ms with 1.5-fold exceedance of the DC-response value Timing circuit Median value of the fault Scatter Influence of the supply voltage Influence of the ambient temperature < 5 % of the end value ≤ ± 0.2 % + ≤ 50 ms ≤ ± 0.02 % / % ∆UN ≤ ± 0.005 % / K∆T Output circuit Contact assembly Contact material Switching nominal voltage Un Max. steady current In per current path Usage category according to EN 60947-5-1:1991 Short circuit safeguard, max. fuse insert Class gG Permissible frequency of operation Mechanical service life Response time at NO DELAY and > V (AC 50 Hz) Response time at NO DELAY and > V (DC) Fallback interval at NO DELAY and > V Fallback interval at 0.1 s to 3 h Minimum impulse time output relay Metering readiness time after powering on the supply voltage Metering bypass time after powering on the supply voltage General Data Air and creep sections between the electric circuits Rated voltage impulse Excess voltage category Degree of contamination Rated voltage Testing voltage Ueff 50 Hz according to DIN VDE 0110-1, Table A.1 Safety class for casing / terminals according to DIN VDE 0470 Section 1:11.92 Interference resistance according to IEC 61000-4 Ambient temperature, work area Dimensional drawing Wiring diagram Connector sections, fine wire / single core or fine wire with wire end ferrules Permissible tightening torque Weight Accessories Page 95 SUM 1001 1 NC, 1 NO contacts Ag alloy, gold-plated AC/DC 230/230 V 5A AC-15: Ue 230 V AC, Ie 3 A / DC-13: Ue 24 V DC, Ie 2 A 6A ≤ 6000 switching cycles/h 6 30 x 10 switching cycles ≤ 80 ms at 1.05-fold Response value of the measured variable ≈ 25 ms at 1.3-fold Response value of the measured variable (instantaneous) ≤ 50 ms at 1.1-fold Response value of the measured variable ≈ 15 ms at 1.6-fold Response value of the measured variable (instantaneous) ≈ 30 ms after 1.1-fold Response value of the measured variable ≤ 150 ms after 1.6-fold Response value of the measured variable ≈ 30 ms after 1.1-fold Response value of the measured variable ≈ 35 ms after 1.6-fold Response value of the measured variable > 100 ms, during the elapse of the minimum impulse time, this is reset upon the next response from the relay ≤ 100 ms ≤ 60 ms according to DIN VDE 0110-1:04.97 5 kV III 3 exterior, 2 interior 500 V AC 2.7 kV IP 40 / IP 20 Test acuity 3 –20 to +60 °C S 7-1 KS 0338/1 2 x 0.75 to 1.5 mm² / 2 x 0.75 to 2.5 mm² 1 or 2 x 0.5 to 1.5 mm² 0.8 to 1 Nm 0.3 kg – Subject to change without further notice