CONTROL PANEL Using Smoke Power Reversal Module 6 The 333 PRM Polarity Reversing Module is used to reverse the polarity of the positive and negative voltages powering smoke detectors. The module is for use with 4-wire smoke detectors that employ a sounder and voltage-reversing feature. The module is triggered by a pulsing bell output. 333 PRM 5 + – 4-WIRE SMOKE DETECTORS + EOL POWER SUPERVISION RELAY MODULE A77-761B + - - SHOWN POWERED. RELAY OPENS WHEN POWER IS LOST -2 P1 +1 2000 OHM EOLR JUMPER HEAT DETECTOR JUMPER P1 ON 333 MODULE MUST BE IN "B" POSITION + - FOUR-WIRE DETECTOR CIRCUIT TO FIRE ZONE TERMINALS 2 3 4 12 C 333PRM-002-V0 1 NO NC 4204 Figure 3-12b: Wiring a 333PRM using a 4204 CONTROL PANEL 6 7 4 8 333 PRM Installing the 333 PRM Mount the 333 PRM inside the control panel’s cabinet or in a separate cabinet using the double-sided tape provided. Wire the 333PRM as shown in Figures 3-12a, b or c. Refer to the 333PRM Installation Instructions for detailed information on the installation of the module. 7 6 5 + 3 JUMPER P1 ON 333 MODULE MUST BE IN "B" POSITION P1 – 4-WIRE SMOKE DETECTORS 4 - -2 +1 JUMPER HEAT DETECTOR + EOL POWER SUPERVISION RELAY MODULE A77-761B + - SHOWN POWERED. RELAY OPENS WHEN POWER IS LOST 2000 OHM EOLR - 1 + FOUR-WIRE DETECTOR CIRCUIT 2 TO FIRE ZONE TERMINALS CONTROL PANEL 4 POWER SUPPLY 12 8 7 + USE A 12VDC, BATTERY-BACKED, UL LISTED POWER SUPPLY. 6 – 4-WIRE SMOKE DETECTORS 4 + 3 - -2 +1 JUMPER JUMPER P1 ON 333 MODULE MUST BE IN "B" POSITION HEAT DETECTOR + + EOL POWER SUPERVISION RELAY MODULE A77-761B + - SHOWN POWERED. RELAY OPENS WHEN POWER IS LOST 2000 OHM EOLR - TO FIRE ZONE TERMINALS FOUR-WIRE DETECTOR CIRCUIT 333PRM-001-V0 5 Figure 3-12a: Wiring a 333PRM to the Control Figure 3-12c: Wiring a 333PRM using a 4204 and a Power Supply 333PRM-003-V0 4204 3 4 NC MOMENTARY RESET SWITCH 333 PRM 6 3 The 333PRM reverses polarity to smoke detectors with Integral Temp-3 Sounders. Typically, in alarm, each draws 49-60mA of current. The control panel supplies only enough current for one smoke detector. In order to attach more than one, an external power supply and an external relay may be required. P1 7 4 The 333PRM may be used with the System Sensor 2112/24AT and similar models with the required operating features previously stated. 7 4 8 Smoke Detectors Compatible with the 333PRM 6 7