RR1 Polarity Reversal Relay Module

advertisement
INSTALLATION AND MAINTENANCE INSTRUCTIONS
RR1 Polarity Reversal
Relay Module
Specifications
Operating Voltage Range:
Maximum Operating Current:
Relay Contacts:
Operating Temperature Range:
Operating Humidity Range:
Dimensions:
Wire connections:
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
9.5 to 32 VDC
29mA
2A at 30 VDC, 0.5A at 120 VAC
0˚ to 55˚ C (32° to 131° F)
5% to 95%
11/2″ x 13/4″
18 AWG stranded, tinned, 16″ long
General Description
The RR1 polarity reversing relay module is intended for
use with 2-wire and 4-wire detectors with built-in
sounder, such as System Sensor 2100AT, 2112/24ATR
and 2112/24AITR, and other compatible models. It is designed to allow all the detectors in the same loop to
sound when one of the detectors goes into alarm.
2.
3.
NOTICE: This manual shall be left with the owner/user of
this equipment.
4.
NOTE: If your panel configuration does not match any of
the provided wiring diagrams, please contact System Sensor technical services at 1-800-SENSOR2 for assistance.
Installation
Choose a mounting location in the control panel within
reach of the provided wire leads. Use a water/isopropyl alcohol mixture (50/50) to clean the mounting surface. Allow
surface to dry and remove paper backing from the Velcro
and catch. Stick the Velcro in the panel and the catch on
the back of the module, then mount the module inside the
control panel. Route terminals to the appropriate terminals
as noted below.
5.
The RR1 cannot be used with a coded (or
pulsed) power supply. For proper RR1 operation, distinct wiring methods are required. See
page 4 for specifics.
wire detectors.
2) Connect the red wire to other end of alarm relay
contact output.
Connect the outgoing wires of the relay module to the
smoke detector power-in terminals (brown to positive,
white to negative).
Connect the blue and purple wires of the RR1 to any of
the power sources as specified in the applicable wiring
diagram (see Figures 1-4).
2-wire models:
Connect the yellow and orange wires to the positive and
negative of the initiating loop, respectively.
4-wire models:
Connect the yellow and orange wires to the positive and
negative of power to detectors, respectively.
Connect the smoke detector initiating circuit to the
alarm loop.
WARNING
When calculating total current draw of the control panel,
remember to add current consumption (29mA) for the
power reversal relay module (RR1).
Testing
Before testing, notify the proper authorities that the system
is undergoing maintenance and will temporarily be out of
service.
Wiring
1. Connect the relay module trigger wires to the fire alarm
output terminals.
IMPORTANT: Polarity must be observed!
A. Continuous alarm/bell output: (Figures 1 and 2)
Connect red wire to positive and black wire to negative.
B. Alarm relay, normally open contact output: (Figures 3
and 4)
1) Connect one end of the alarm relay contact output
and the black wire to positive and negative of
power, respectively. Auxiliary power supply is used
as a power source for 2-wire detectors and power
to the detectors is used as a power source for 4M500-12-00
NOTE: If using a power supervision relay, be
aware of the following: In an alarm condition, a
wiring-fault trouble state may also register at
the panel when the RR1 is used.
Test in accordance with NFPA 72 Chapter 7 test methods,
inspections, and testing frequency.
1. To test the RR1 module, confirm that the smoke detectors do not sound without an alarm.
2. Initiate an alarm with smoke or approved test method
on any detector connected to the control panel via the
RR1 module. In alarm, all the detectors that are installed
in the corresponding loop shall sound.
3. Reset the detectors by removing power to the loop.
1
I56-1168-02
NOTE: If your panel configuration does not match any of the following wiring diagrams, please contact System Sensor
technical services at 1-800-SENSOR2 for assistance
Figure 1. RR1 module with 2-wire smoke detectors:
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
UL LISTED
CONTROL
PANEL
POWER REVERSAL
RELAY MODULE (RR1)
EOL
CONTINUOUS
+
BELL/
ALARM
OUTPUT –
RED
T1
BLK
+ P
+ W
– R
A+
A-
T2
T8
ORG
T7
BLUE
WHITE
T6
INITIATING
LOOP
+
–
T3
+
RA400Z
YELLOW
–
T4
PURPLE T5
+
Not
Used
+ P
+ W
– R
A+
A-
+
–
Not
Used
RA400Z
BROWN
–
To auxiliary power/IAC/Bell output or
any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
A78-2336-10
NOTE: If optional Class A wiring is used, second power reversal relay module (RR1) must be added to enable concurrent
loop polarity reversal.
Figure 2. RR1 module with 4-wire smoke detectors:
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
UL LISTED
CONTROL
PANEL
POWER REVERSAL
RELAY MODULE (RR1)
CONTINUOUS
+
BELL/
ALARM
OUTPUT
RED
T1
+ P
+ W
– R
BLK
–
T2
ORG
T8
T7
WHITE
BLUE
T6
T3
POWER +
YELLOW
TO
DETECTORS –
PURPLE T5
+
T4
BROWN
A
A
NC
C
NO
A
U
X
+ P
+ W
– R
A
A
NC
C
NO
} INITIATING
LOOP
A
U
X
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
–
To auxiliary power/detector power/IAC/Bell
output or any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
INITIATING
LOOP
OPTIONAL CLASS A WIRING
A78-2336-09
M500-12-00
2
I56-1168-02
Figure 3. RR1 module with alarm relay and 2-wire smoke detectors:
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
UL LISTED
CONTROL
PANEL
POWER REVERSAL
RELAY MODULE (RR1)
EOL
RED
ALARM
RELAY
(N/O contact)
OUTPUT
AUX.
POWER
SUPPLY
INITIATING
LOOP
T1
BLK
+ P
+ W
– R
A+
A-
T2
T8
ORG
+
T7
BLUE
–
T6
+
T3
–
+
–
Not
Used
RA400Z
BROWN
T4
PURPLE T5
+
Not
Used
RA400Z
YELLOW
–
+
WHITE
+ P
+ W
– R
A+
A-
–
To auxiliary power/IAC/Bell output or
any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
A78-2336-12
NOTE: If optional Class A wiring is used, second power reversal relay module (RR1) must be added to enable concurrent
loop polarity reversal.
Figure 4. RR1 module with alarm relay and 4-wire smoke detectors:
The power reversal relay module does not provide supervision.
All supervision is provided by the interconnected control unit.
UL LISTED
CONTROL
PANEL
POWER REVERSAL
RELAY MODULE (RR1)
RED
ALARM
RELAY
(N/O contact)
OUTPUT
T1
+ P
+ W
– R
BLK
T2
ORG
T8
T7
A
A
NC
C
NO
WHITE
BLUE
T6
T3
POWER +
TO
DETECTORS –
YELLOW
PURPLE T5
+
T4
BROWN
A
U
X
+ P
+ W
– R
A
A
NC
C
NO
} INITIATING
LOOP
A
U
X
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
–
To auxiliary power/detector power/IAC/Bell
output or any UL listed regulated power supply
listed for fire protective signaling use.
(polarity shown with panel in alarm).
INITIATING
LOOP
OPTIONAL CLASS A WIRING
A78-2336-11
M500-12-00
3
I56-1168-02
Minimum Conditions Required for Proper Operation of the RR1 Upon Fire Alarm
For 2-Wire Model Smoke Detectors (Model 2100AT)
Auxiliary power supply for smoke detector sounders upon alarm and one of the following:
1. Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required
–or–
2. Auxiliary power supply for RR1 and auxiliary relay with normally open contact activated by fire alarm only
For 4-Wire Model Smoke Detectors (Models 2112/24AT, 2112/24ATR, 2112/24AITR)
1. Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required
–or–
2. Auxiliary relay with normally open contact activated by fire alarm only
NOTE: Outputs must be continuous (non-coded, non-pulsed.) The RR1 will not function properly in panels that provide
only single combined burglary and fire alarm output unless the minimum conditions noted above are present.
Three-Year Limited Warranty
System Sensor warrants its enclosed relay module to be free from defects
in materials and workmanship under normal use and service for a period
of three years from date of manufacture. System Sensor makes no other
express warranty for this relay module. No agent, representative, dealer, or
employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the
relay module which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing
with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair DepartM500-12-00
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
4
I56-1168-02
© System Sensor 1998
Download