Multi-Application Peripherals and Accessories ULC Listed* 4901 Series Insuite Silenceable Devices; Silence Switch and Silenceable Mini-Horn Features Insuite Silenceable Devices: Allows manual 10 minute Silence for local mini-horn; or for switched 24 VDC or 25/70 VAC audio notification appliances After 10 minutes, automatic resound occurs for code compliance if the fire alarm panel has not been silenced Touching the two Silence contacts activates the Silence feature and an LED indicator activates to indicate local Silence is in process Models 4901-9838CA and 4901-9839CA operate as a Silence Switch for connected slave appliances Models 4901-9851C and 4901-9852C have a built-in mini-horn Units mount flush using a single gang electrical box Electrically polarized input with color coded #18 AWG wire leads for in/out wiring Compatible with 4905 Series Insuite Device Distribution Modules; refer to data sheet S4905-0009 for additional information Insuite Silenceable Device (Silence Switch 4901-9839CA is shown with LED on) Description Description (Continued) 4901 Series Insuite Silenceable Devices are specifically designed to meet applications that require compliance with building codes which state that an audible signal device located within a dwelling unit shall incorporate a means that enables the device to be silenced for a period of not more than 10 minutes. Typical applications would include hotel rooms, dormitories, and apartments. Mini-horn models. Models 4901-9851C and 4901-9852C have a built-in piezoelectric mini-horn that allows a high level signal to be generated in a small package. These units operate as part of a 24 VDC NAC and can be used with or without the Simplex® 4905 Series Distribution Modules. These silenceable devices mount flush to the wall in a single gang electrical box and are available in red or off-white. In/Out wiring and electrical polarization allows for system wiring supervision when connected to a listed compatible Fire Alarm notification appliance circuit. Operation Switch models. The 4901-9838CA and 4901-9839CA are used to silence audible DC or speaker appliances that are located in a suite. They operate as part of either a 24 VDC, or 25 or 70 VRMS Audio NAC. In 24 VDC and 25 VRMS Audio applications these units can be used with or without the 4905 Series Distribution Modules. Silence Switches require separate 24 VDC power from the Fire Alarm Control Panel. This power must be interrupted during the use of the fire alarm paging microphone when the switch modules are used to silence 25 or 70 VRMS speakers. Audible appliances in the suite are silenced by touching the two Silence contacts on the faceplate of the silenceable device which also causes the LED indicator to activate. Within ten minutes after touching the contacts to silence the alarm, the notification appliances will re-sound (assuming the Fire Alarm panel has not been silenced). Additional Reference Refer to Installation Instructions 579-1009 for additional information. * Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. S4901-0015-2 11/2011 Product Selection Table Audio Operation 25/70 VAC DC Operation 24 VDC Operating Voltage (Nominal) Alarm Signal Current (DC) Alarm Silenced Current (DC) Supervisory Signal Current (DC) Sound Pressure Level On Axis @ 3m Silence Switch Yes Yes 24 VDC Regulated 22 mA 22 mA 0 mA NA Silenceable Mini-Horn Device No Yes 24 VDC Regulated 82 mA 4 mA 0 mA 87 dBA (Temporal), 79 dBA (Steady) Model Color Description 4901-9838CA Red OffWhite 4901-9839CA 4901-9851C 4901-9852C Red OffWhite Product Dimensions and Electrical Box Requirements Electrical Box Requirements: Single-Gang Box 2-1/2” minimum depth, 3” recommended 2 S4901-0015-2 11/2011 Application Diagrams 25V Audio Application Using Distribution and Insuite Silence Modules Class B Supervision Simplex 4100U/4100ES 25 VAC Audio SIG CCT Corridor 4905-9996CA (2 Circuit Supervised) Notification Appliance Suites 24 VDC * 4901-9838CA 4901-9839CA Silence Switch 4901-9838CA 4901-9839CA Silence Switch Speaker 25 VAC Speaker 25 VAC Speaker 25 VAC Speaker 25 VAC Speaker 25 VAC Speaker 25 VAC Speaker 25 VAC Suite #1 Suite #2 4901-9838CA 4901-9839CA Silence Switch 4901-9838CA 4901-9839CA Silence Switch Speaker 25 VAC 24 VDC * 24 VDC * Suite #3 25 V Audio Operation To non-Insuite Fire Alarm Device or 4905-9996CA Device or E.O.L. Resistor (10K Ohms) 4905-9996CA (2 Circuit Supervised) Notification Appliance 24 VDC * Suite #4 25 V Audio Operation * When the 4901-9838CA/4901-9839CA silence switch is used in conjunction with slave speakers, this 24 VDC power source provided by the Fire Alarm Control Panel must be interrupted during use of the f ire alarm microphone. This diagram provides an applications overview, not all wiring is shown. For detailed wiring connection inf ormation ref er to Installation Instructions 5791008 (Distribution Modules) and 579-1009 (Insuite Silenceable Devices). Note: The 4905-9996CA does not accept an input f rom a 70V Audio NAC. DC Application Using Distribution and Insuite Silence Modules Class B Supervision Simplex 4100U/4100ES 24 VDC SIG CCT Corridor Notification Appliance Suites 24 VDC * 4905-9996CA (2 Circuit Supervised) 4901-9838CA 4901-9839CA Silence Switch Notification Appliance 4901-9851C 4901-9852C Silenceable Mini-horn Device 24 VDC * 4905-9996CA (2 Circuit Supervised) 4901-9838CA 4901-9839CA Silence Switch DC Audible Appliance DC Audible Appliance DC Audible Appliance DC Audible Appliance Suite #1 Suite #2 Suite #3 To non-Insuite Fire Alarm Device or 4905-9996CA Device or E.O.L. Resistor (10K Ohms) 4901-9851C 4901-9852C Silenceable Mini-horn Device Suite #4 DC Operation DC Operation This diagram provides an applications overview, not all wiring is shown. For detailed wiring connection inf ormation ref er to Installation Instructions 5791008 (Distribution Modules) and 579-1009 (Insuite Silenceable Devices). 3 S4901-0015-2 11/2011 Application Diagrams (Continued) 4901-9838CA/9839CA Silence Switch Modules Without Distribution Modules (No Short-Circuit Isolation) Wiring Diagram Simplex 4100U/4100ES 25/70 VAC Audio Corridor SIG + Class A Circuit f or NAC to Suites Class B Circuit f or Corridor NAC Notification Appliance CCT- To Notification Appliance or E.O.L. Resistor (10K Ohms) Notification Appliance Suites 25/70 VAC To next Suite with Silence Switch or return loop circuit SIG + CCT- 24 VDC from Fire Alarm Control Panel* + - 24 VDC from Fire Alarm Control Panel* + Red White Yellow Red Black 4901-9838CA 4901-9839CA Silence Switch White White Black 4901-9838CA 4901-9839CA Silence Switch Yellow Yellow + - Speaker 25 /70VAC + - + - Speaker 25 /70VAC White Yellow + Speaker + - 25 /70VAC - + - + Speaker + - 25 /70VAC - Note: When the 4901-9838CA/4901-9839CA silence switch is used in conjunction with slave speakers, this 24 VDC supply must be interrupted during use of the f ire alarm microphone. 4901-9851C/9852C Silenceable Mini-horn Device Without Distribution Modules (No Short-Circuit Isolation) Wiring Diagram Simplex Fire Alarm Control Panel 24 VDC Corridor SIG + Notification Appliance CCT- Class A Circuit f or NAC to Suites Class B Circuit f or Corridor NAC To Notification Appliance or E.O.L. Resistor (10K Ohms) Notification Appliance Suites 24 VDC To next Suite with Silence Switch or return loop circuit SIG + CCT- Red Black 4901-9851C 4901-9852C Silenceable Mini-horn Device Red Black Red Black 4901-9851C 4901-9852C Silenceable Mini-horn Device Red Black TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA www.simplexgrinnell.com S4901-0015-2 11/2011 © 2011 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.