Understanding Indoor Photometric Test Reports “Serving the lighting industry since 1989” 905 Harrison Street Allentown, PA 18103 Ph: 610.770.1044 Fax: 610.770.8912 www.luminairetesting.com Description Section The description section is the first section of an LTL indoor photometric test report. It provides the specific information about the luminaire being tested as well as the conditions of the test procedure. Here you will find the number of lamps, the model number, the manufacturer of the lamps, as well as the rated lumens for each lamp. Following the lamp information, the ballast manufacturer and model number are shown. The mounting position of the luminaire is noted, followed by the electrical characteristics recorded during the test. Finally, the orientation of the 0 plane is indicated (parallel with the lamps, perpendicular to the lamps, or neither in the case of luminaires with vertical lamps). LTL NUMBER: 04983 DATE: 1-1-2000 PREPARED FOR: LUMINAIRE TESTING LABORATORY, INC. CATALOG NUMBER: SAMPLE INDOOR TEST LUMINAIRE: FORMED STEEL HOUSING, FORMED WHITE ENAMEL STEEL REFLECTOR, 16 CELL, 3" DEEP, FORMED SEMI-SPECULAR ALUMINUM LOUVER. LAMPS: TWO SYLVANIA FBO31/31K RATED AT 2800 LUMENS EACH BALLAST: ONE MAGNETEK B232I120RH MOUNTING: RECESSED TOTAL INPUT WATTS = 54.7 AT 120.0 VOLTS THE 0 DEGREE PLANE IS PARALLEL WITH THE LAMPS. Luminaire Sketch The luminaire sketch is used to communicate pictorially any information about the luminaire that the description does not explain. This includes critical dimensions of the luminaire, lamp positioning, and orientation during testing. A circled plus sign ( ) indicates the photometric center of the luminaire as tested. #04983 21.500 10.250 20.875 23.750 Photometric Center Luminaire Testing Laboratory, Inc. -2- Candela Distribution Table The candela distribution table is a tabular listing of the candela readings at each given angle. These candela values are actually candelas per rated lamp lumens. This means these values do not take into consideration ballast factor, lamp depreciation, or temperature effects. By using candelas per rated lumen, it is more convenient to compare various test reports on a common ground. In standard indoor photometry, the 0 vertical angle denotes the measurement directly below the luminaire (also referred to as nadir). Following from this, 90 is at the equator, and 180 is directly above the luminaire (zenith). Vertical Angles Lateral Angles CANDELA DISTRIBUTION 0.0 22.5 45.0 0 1401 1401 1401 5 1399 1396 1393 15 1321 1313 1283 25 1198 1156 1124 35 1034 977 1050 45 803 789 979 55 508 557 706 65 82 103 123 75 18 20 21 85 0 0 0 90 0 0 0 67.5 1401 1391 1267 1170 1177 1167 823 107 21 0 0 90.0 1401 1390 1260 1199 1252 1277 921 97 21 0 0 FLUX 132 363 538 682 763 597 125 24 3 The lumens (flux) column is a summary of the lumens (flux) emitted within a zone centered around the corresponding vertical angle. Ex. The vertical angle 15 has 363 lumens in a cone ranging from 10 to 20 . 10 20 Luminaire Testing Laboratory, Inc. -3- Polar Candela Plot The polar candela plot is typically found in the lower right hand corner on the first page of an LTL test report. It is the graphical representation of the candela distribution table. The angles are vertical angles (again with 0 pointed straight down) and the deflection is in candelas per rated lumens. The lateral planes are represented by a solid line (0 plane) and a dot-dash line (90 plane). In the case of a completely symmetrical fixture, only the 0 plane is shown (see Figure 1). For a four quad symmetry fixture, the 0 and 90 plane is shown (see Figure 2). Finally, in both bilateral symmetry fixtures and asymmetrical fixtures, the plot shows the 0 , 90 ,180 , and 270 ,planes (see Figure 3). In the bilateral symmetry plot, the 270 plane is a mirror image of the 90 plane. Figure 1 180 165 150 135 Figure 2 120 180 165 150 105 135 120 105 90 Candelas 75 6520 60 9780 13040 Vertical Angles 3260 90 15 75 600 60 900 1200 45 0 300 45 0 30 15 30 0 Deg. Plane 0 Deg. Plane 90 Deg. Plane Figure 3 120 135 150 165 180 165 150 135 120 105 105 90 90 60 75 75 120 60 60 180 240 45 45 300 30 0 15 180 Deg. Plane 270 Deg. Plane 15 0 Deg. Plane Luminaire Testing Laboratory, Inc. -4- 30 90 Deg. Plane Zonal Lumen Summary The zonal lumen summary is a brief description of the flux (flow of light) emitted from the luminaire within a specific zonal range. The ranges represent vertical angles and the flux found within the area of the cone. The 0-30 zone represents the flux found within the cone through 0 and 30 . This area is shown in gray shading 10 ZONAL LUMEN SUMMARY ZONE LUMENS 0- 30 1034 0- 40 1716 0- 60 3076 0- 90 3228 90-180 0 0-180 3228 Vertical Angle Range 20 30 40 %LAMP 18.5 30.6 54.9 57.6 0.0 57.6 The lumens column shows how many lumens are produced within the given zone. This column gives the lumen sum within the given zone as a p e r c e n t a g e o f t h e t o t a l r a t e d l a m p l u m e n s. (Lumens in given zone/rated lumens). This column gives the lumen sum within the given zone as a percentage of the total luminaire lumen output. (Lumens in Given Zone/Lumens 0-180) Luminaire Testing Laboratory, Inc. -5- %FIXT 32.0 53.2 95.3 100.0 0.0 100.0 Total Luminaire Efficiency The total luminaire efficiency is simply the ratio between the lumen output of the luminaire and the lumen output of the bare lamps. This value is the percentage of the bare lamp’s light that exits the luminaire. TOTAL LUMINAIRE EFFICIENCY: TOTAL REFLECTANCE OF PAINT: 57.6% 92.4% CIE TYPE: DIRECT PLANE: 0-DEG 90-DEG SPACING CRITERIA: 1.2 1.4 SHIELDING ANGLES: 30 35 LUMINOUS LENGTH: 20.875 20.875 The average of 4 diffuse reflectance samples taken from varying sections of the reflector. CIE Type: A classification system specified by the International Commission on Illumination (CIE) which uses luminous intensity or flux distribution of the indoor luminaire to categorize it in one of the following 5 classifications. These classifications are based o n t h e a m o u n t o f f l u x t h a t i s d i r e c t e d u pwa r d o f d ow n wa r d . (1) Direct- 90-100%of flux is directed downward (2) Semi-Direct - 60-90% of the flux is directed downward. The remainder of the flux is above the 90 vertical angle (horizon). (3) General Diffuse- both upward and downward flux are comparable. (4) Semi-Indirect-60-90% of flux is directed upward (5) Indirect-90-100% of flux is directed upward above the 90 vertical angle (horizon). Shielding Angle The shielding angle is the angle between the first sight of the bare lamp and a horizontal line through the lamp center. This is expressed on the test report for both the 0 and 90 horizontal planes. 35 Spacing Criteria (Criterion) is a ratio used to estimate the farthest spacing of luminaires that will still yield a relatively u n i f o r m i l l u m i n a n c e o n t h e f l o o r. This ratio is presented in units of spacing per mounting height. EX: Mounted at 8 feet, this luminaire should be mounted: 8 * 1.4=11.2 crosswise from the next luminaire 8 * 1.2=9.6 lengthwise from the next luminaire Luminaire Testing Laboratory, Inc. -6- Luminance Table The luminance table is a tabular listing of the average brightness when viewed from specific viewing angles. Average luminance is measured in candela per square meter and is very important in glare calculations. Two light sources may produce the same candela value at a given angle. If we suppose one is a small projector lamp and the other is a two foot by four foot recessed luminaire, the luminance of the projector lamp will be much greater than that of the two foot by four foot luminaire. Essentially, the average luminance describes whether a luminaire is small and bright, or large and dim. LUMINANCE IN CANDELA PER SQUARE METER Lateral Angles ANGLE IN DEG 0 45 Vertical Angles 55 65 75 85 AVERAGE AVERAGE AVERAGE 0-DEG 45-DEG 90-DEG 4983. 4983. 4983. 4039. 4924. 6423. 3150. 4378. 5711. 690. 1035. 816. 247. 289. 289. 0. 0. 0. Candela Distribution & Zonal Lumen Summary This section presents the same information found on the summary tables on the front page of the report, however the data is shown in finer degree increments. The candela distribution table displays candela values in finer increments. The ver tical angles are in 5 increments instead of 10 increments. CANDELA DISTRIBUTION 0.0 22.5 45.0 0 1401 1401 1401 5 1399 1396 1393 10 1365 1363 1360 15 1321 1313 1283 20 1263 1245 1195 25 1198 1156 1124 30 1121 1067 1078 35 1034 977 1050 40 925 881 1019 45 803 789 979 50 668 694 898 55 508 557 706 60 248 322 391 65 82 103 123 70 38 43 44 75 18 20 21 80 10 10 10 85 0 0 0 90 0 0 0 67.5 1401 1391 1343 1267 1199 1170 1173 1177 1191 1167 1033 823 352 107 44 21 9 0 0 The Zonal Lumen Summary found here represents the lumen values at given zonal ranges. The zonal ranges now are in 5 increments beginning at 0 vertical. ZONAL LUMEN SUMMARY 0- 5 33. 5- 10 99. 10- 15 157. 15- 20 207. 20- 25 249. 25- 30 289. 30- 35 325. 35- 40 357. 40- 45 382. 45- 50 382. 50- 55 351. 55- 60 246. 60- 65 92. 65- 70 33. 70- 75 16. 75- 80 7. 80- 85 3. 85- 90 0. 90.0 1401 1390 1332 1260 1204 1199 1222 1252 1307 1277 1133 921 298 97 42 21 10 0 0 Luminaire Testing Laboratory, Inc. -7- Coefficients of Utilization The coefficients of utilization table is a listing of the luminaire’s efficiency relative to room surface reflectances and space configuration. The top numbers in the “RC” row represent the reflectance of the ceiling. The next row of numbers in the “RW” row represent the reflectance of the walls. The column on the left hand side of the table is the “room cavity ratio” or RCR. The RCR is a factor that is calculated to classify the room proportions. A high RCR means that the room has either a high ceiling or a large perimeter length relative to its square foot area (ex. hallway/corridor). A low RCR would indicate a low ceiling or a small perimeter length relative to its square foot area (ex. square room). Each value in the table is the percentage of the barelamp’s light that can be used to illuminate a horizontal work plane. LTL NUMBER: 04983 DATE: 1-1-2000 PREPARED FOR: LUMINAIRE TESTING LABORATORY, INC. COEFFICIENTS OF UTILIZATION - ZONAL CAVITY METHOD EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20 “RCR” Room Cavity Ratio RC RW 80 70 50 30 10 70 70 50 30 10 50 50 30 10 30 50 30 10 10 50 30 10 0 0 0 1 2 3 4 5 6 7 8 9 10 69 64 60 56 51 47 44 40 37 34 31 67 63 59 54 50 46 43 39 36 33 31 64 59 53 48 44 39 35 32 28 25 23 61 56 52 47 42 38 34 31 28 25 22 59 54 50 46 41 37 34 30 27 24 22 58 52 46 41 36 31 27 23 20 17 15 69 62 56 51 46 41 37 33 29 26 24 69 60 53 47 42 36 32 28 25 22 19 69 59 51 44 38 33 29 25 22 19 16 67 61 55 50 45 40 36 33 29 26 24 67 59 53 47 41 36 32 28 25 22 19 67 58 50 44 38 33 29 25 22 19 16 “RC” indicates the Reflectance of the Ceiling 64 57 51 45 40 36 31 28 24 21 19 64 56 49 43 38 33 29 25 21 18 16 61 55 50 44 39 35 31 27 24 21 19 61 54 48 42 37 32 28 25 21 18 16 “RW” indicates the Reflectance of theWalls Luminaire Testing Laboratory, Inc. -8- 59 54 48 43 39 34 30 27 24 21 19 59 53 47 42 37 32 28 25 21 18 16