Metal-enclosed interrupter switchgear type SIMOSEC, up to 27.6 kV

advertisement
Metal-Enclosed Interrupter Switchgear
Type SIMOSEC, up to 27.6 kV, ANSI,
Air-Insulated, Extendable
Medium-Voltage Switchgear
Catalog HA 41.31 · 2008
Answers for energy.
Application
Application, Requirements
Page
Typical uses, features
2 to 4
R-HA41-086 eps
Contents
Technical Data
Electrical data, pressure values,
temperature
Switchgear installation
Shipping data
5
6
7
Product Range
Product range overview, equipment
features
Panels
8 and 9
10 to 18
Design
Panel design
19
Components
Two/three-position switch-disconnector
Two/three-position switch
Busbars, HV CL (current-limiting)
fuse assembly
Operating mechanisms
Indicating and measuring equipment
Transformers
Cable connection
20
21
22 and 23
24
25
26 and 27
28 and 29
Dimensions (in mm/inch)
Panels
Floor openings, fixing points
30 to 38
39
Standards
Standards, specifications, guidelines
40 and 41
Notes
42
Invalid: Catalog HA 41.31 · 2007
SIMOSEC ANSI switchgear
© 2008 Siemens Power Transmission & Distribution, Inc.
SIEMENS is a registered trademark of Siemens AG.
2 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Application
R-HA41-110 eps
R-HA41-112 eps
R-HA41-085 eps
R-HA41-109 eps
Typical uses
R-HA41-111 eps
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 3
Application, Requirements
Features
SIMOSEC ANSI switchgear
is a factory-assembled, typetested, three-phase, metalenclosed, indoor switchgear
according to ANSI/IEEE
C37.20.3 * for single busbars.
Technical features
Reliability
• Air-insulated indoor
• Type (design) tested with
Typical uses
• Three-pole primary enclosure
SIMOSEC ANSI switchgear is
used for power distribution in
distribution systems with
feeder currents up to 1200 A.
• Phases arranged one behind
Modular space-saving design
allows use in
• Substations, customer trans-
fer substations, distribution
substations and switching
substations of power supply
and public utilities
• Public buildings, such as
high-rise buildings, railway
stations, hospitals
• Industrial plants
switchgear
• Gas-insulated, maintenance-
free switching functions for
the two/three-position switch
the other
• No cross-insulation between
phases
• Busbar system at the top or
bottom, as required by application
• Air-insulated busbar and cable
connection system
• Two/three-position switch,
metal-enclosed, with airinsulated primary terminals
and gas-insulated switching
functions
• Hermetically-sealed (welded)
• Sewage treatment plants
stainless-steel switchgear
vessel,
– For switching devices
– With welded-in bushings
(for electrical connections
and mechanical components)
– With insulating gas SF6
• Schools
• Metal-enclosed design
• Shopping centers
• Pressure relief
• Petroleum industry
• Chemical industry
– To the rear and upwards
– Separately for each
compartment
• Industrial plants
• Air-insulated cable connection
Typical examples
• Office parks
• Airports
• Underground railway stations
• Textile, paper and
food industry
Modular design
• Individual panels, for free
combination and extension
system for conventional cable
lugs
• Three-phase current trans-
former, factory-assembled on
the feeder bushings
• Integrated low-voltage niche
(standard) for installation
of low-voltage devices
– E.g. terminals, pushbuttons
– MCBs
• Option: Space heaters for
severe ambient conditions,
e.g. condensation
third-party witness
• Standardized and manu-
• Mechanical switch position
indications integrated in
mimic diagram
• Switchgear interlocking
factured using numerically
controlled machines
system with logical
mechanical interlocks
• Quality management system
Life-cycle cost-efficiency
according to ISO 9001
• More than 500,000 switchgear
panels in operation worldwide
for many years
• No cross-insulation between
phases
Personal safety
• All switching operations can
be performed with closed
panel front
• Metal-enclosed switchgear
• HV CL fuses and cable termi-
nations are only accessible
when the outgoing feeders
are grounded
• Logical mechanical inter-
locking
• Capacitive voltage detection
system for verification of safe
isolation from supply
• Grounding of outgoing feeders
by means of make-proof
grounding switches
Security of operation
• Components, e.g., operating
Extremely low life-cycle costs
and extremely high availability
throughout the entire product
service life cycle as a result of:
• Two/three-position switch
with gas-insulated quenching
principle
• Minimum space requirement
• Easy switchgear extension
Electrical features
• Rated voltages up to 27.6 kV
• Rated short-circuit current
(fused) up to 63 kA at 15 kV
and below, and 20 kA at
27.6 kV
• Rated short-time withstand
current up to 20 kA, 2 second
or 25 kA, 2 seconds
• Rated normal current of
feeders
– Up to 600 A (feeders)
– Up to 1200 A
(panel without switch)
• Rated normal current of
busbar up to 1200 A
mechanisms, three-position
switches proven for years
• Metal-enclosed panels plus
metal compartmentalization
between busbar and switching
device and between switching
device and cable connection
compartment
• Three-position switch metal-
enclosed with gas-insulated
switching functions
– Welded sealed-for-life
switchgear vessel
– No cross-insulation between
phases
– With welded-in bushings for
cable connection, busbar and
operating mechanism
• Switch operating mechanisms
outside switchgear vessel
• Maintenance-free operating
mechanism parts
* Standards see page 40
4 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Technical Data
Electrical data of panels, pressure values, temperature
Complete switchgear
Rated insulation level
Rated frequency fr
Rated continuous current Ir 1)
of busbar
Rated short-circuit current
Rated short-time withstand current Ik 6)
Rated peak withstand current Ip 6)
Rated filling pressure pre 2)
Minimum operating pressure pme 2)
Ambient temperature T
Rated voltage Ur
kV
Rated short-duration (one minute) power-frequency kV
withstand voltage Ud, rms
Rated lightning impulse withstand voltage Up, peak kV
Hz
On request
A
Standard
A
for switchgear with all feeders fused (panel type FS) kA (sym)
kA (asym)
kA (peak)
for switchgear with tk = 2 s rated duration
up to kA
up to kA
PSI (kPa)
at 20 °C/68 °F
(absolute)
for panels without secondary equipment
°C/°F
4.76
19
15
36
27.6
60
60
50/60
600
1200
63
101
164
20
25
52
65
21.8 (150)
18.9 (130)
95
125
63
101
164
20
52
20
32
52
20
52
25
65
-30 to +40 / -22 to +104
Cable switch panel type CS, cable connection panel type CC, cable grounding panel type CG
Rated voltage Ur
Rated continuous current Ir 1)
for panel type CS, CG
only for panel type CC
only for panel type CS
Rated fault closing current Ima 6)
kV
A
A
kA (asym)
kA (peak)
4.76
600
600, 1200
32
40
52
65
kV
A
up to kA
kA (asym)
kA (peak)
mm/inch
A
A
A
4.76
200, 600
164
101
164
537/21.1
450E
two 350E
three 200E
kV
kA (asym)
kA (peak)
4.76
32
52
kV
up to kA
kA (asym)
kA (peak)
4.76
52
32
52
kV
A
4.76
600, 1200
15
32
52
27.6
40
65
32
52
Fuse panel types FS, FU
Rated voltage Ur
Rated continuous current Ir 1) 4)
Rated peak withstand current Ip 5)
Rated fault closing current Ima 5)
Reference dimension “e“ 3)
Maximum fuse rating
for feeder
only for panel type FS
for HV CL (current limiting) fuses
for panel FS-1
for panel FS-2
for panel FS-3
15
27.6
164
101
164
52
32
52
200E
two 200E
three 200E
65E
two 65E
three 65E
40
65
15
32
52
40
65
27.6
32
52
65
40
65
15
52
32
52
65
40
65
27.6
52
32
52
Busbar grounding panel type BG
Rated voltage Ur
Rated fault closing current Ima 6)
Busbar voltage metering switch panel types MS2, MS3
Rated voltage Ur
Rated peak withstand current Ip 5)
Rated fault closing current Ima 5)
Metering panel types MT3, MC3, bus riser panel BR
Rated voltage Ur
Rated continuous current Ir 1)
15
27.6
1) The rated continuous currents apply to ambient temperatures of 40 °C/104 °F.
2) Pressure values for SF6-insulated vessels.
3) The fuse assembly is designed for a reference dimension “e” = 537 mm/21.1 inch.
With reference dimension “e” = 442 mm/17.4 inch, an extension tube
(95 mm/3.7 inch long) is required.
4) Depending on the HV CL fuse links.
5) Fused
6) Without fuses
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 5
Technical Data
Switchgear installation
Room planning
Room planning (dimensions in mm/inch)
Switchgear installation
Wall-standing or free-standing
arrangement
– Single row
– Double row (for face-to-face
arrangement)
Door dimensions
1230/48.4
>950/37.5***
7
8
210
8.3
850/33.5
90/3.5
Cable basement
fixing points of the switchgear, see page 39
– Steel structure
– Steel-reinforced concrete
³2600/102.4
2550/100.5 *
2250/88.5
1080/42.5
5
1230/48.4
>950/37.5***
6
6
• For floor openings and
• Foundations:
4
9
210
8.3
10
90/3.5
Cable basement
Wall-standing arrangement (side view)
Free-standing arrangement (side view)
11
³50/2 150/6
850/33.5
600/23.5 **
Switchgear fastening
3
1080/42.5
600/23.5 **
The door dimensions
depend on the
– Number of panels in a
transport unit
– Height of the panel
1
³2600/102.4
2550/100.5 *
See opposite dimension
drawings
Switchgear
room
2
2250/88.5
Room dimensions
Switchgear
room
150/6
12
10/0.4
Weight
³50/2
Panel dimensions
See pages 30 to 38
10/0.4
1 Relief opening
2 Direction of pressure relief
3 Pressure relief of switchgear
4 Room height
5 Individual panel depth
6 Control aisle
7 Option: Floor cover
8 Cable
³50/2
HA41-2510a eps
Plan view
13
14
HA41-2511a eps
3
The weight of a panel depends
on the extent to which it is
equipped (e.g. with motor
operating mechanism, voltage
transformer). For details,
please refer to page 7.
Plan view
9 Foundation
10 Height of cable basement corresponding to
cable bending radius
11 Wall distance
12 Side wall distance
13 Panel width
14 End wall
15 Depth of pressure relief duct
* Switchgear height 2250 mm /
88.5" or 2550 mm / 100.5"
** Depending on bending radius of
cable
*** 950/37.5 distance shown is the
space required by the equipment.
The actual space must also
reflect requirements of applicable
codes (e.g. NEC) or standards
and regulations.
6 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
15
Technical Data
Shipping data
Transport of individual panels
Transport units
for shipping (plan view)
T2
1
T1
3
B1
2
B1
3
2
B2
B1
2
B3
4
5
2250 / 88.6
2250 / 88.6
1230 / 48.4
1230 / 48.4
Fuse switch panel
FS1
FS2
FS3
205/452
230/507
250/551
375 / 14.8
500 / 19.7
750 / 29.5
2250 / 88.6
2250 / 88.6
2250 / 88.6
1230 / 48.4
1230 / 48.4
1230 / 48.4
Fuse panel
FU1
FU2
FU3
160/353
185/408
210/463
375 / 14.8
500 / 19.7
750 / 29.5
2250 / 88.6
2250 / 88.6
2250 / 88.6
1230 / 48.4
1230 / 48.4
1230 / 48.4
Cable connection panel
CC1
CC2
145/320
170/375
375 / 14.8
500 / 19.7
2250 / 88.6
2250 / 88.6
1230 / 48.4
1230 / 48.4
Cable grounding panel
CG1
CG2
180/397
205/452
375 / 14.8
500 / 19.7
2250 / 88.6
2250 / 88.6
1230 / 48.4
1230 / 48.4
Metering panel
MT3
420/926
750 / 29.5
2250 / 88.6
1230 / 48.4
Metering cable panel
MC3
420/926
750 / 29.5
2250 / 88.6
1230 / 48.4
Metering switch panel
MS2
MS3
350/772
420/926
500 / 19.7
750 / 29.5
2250 / 88.6
2250 / 88.6
1230 / 48.4
1230 / 48.4
Bus riser panel
BR1
BR2
145/320
170/375
375 / 14.8
500 / 19.7
2250 / 88.6
2250 / 88.6
1230 / 48.4
1230 / 48.4
Busbar grounding panel
BG1
180/397
375 / 14.8
2250 / 88.6
1230 / 48.4
Transport of combinations of different individual panels
Overall width B3
Weight *
Width B2
mm / inch
kg/lb
Height H2 ** Depth T2
Volume
B2 x H2 x T2
B1
HA41-2513 eps
Depth T1
mm / inch
375 / 14.8
500 / 19.7
Transport unit
2
Height H1
mm / inch
180/397
205/452
1
T1
Width B1
mm / inch
CS1
CS2
With individual panel
T2
Weight
kg/lb
Cable switch panel
B2
HA41-2512 eps
Panel type
With combinations of different
individual panels
mm / inch
mm / inch
mm / inch
m3 / yd3
Transport unit
w 750 / 29.5
70/155
1100 / 43.3
2450 / 96.5
1400 / 56.1
3.8 / 5.0
Transport unit
w 1750 / 58.9
120/265
2200 / 86.6
2450 / 96.5
1400 / 56.1
7.6 / 10.0
Top case necessary for cable top entry, delivered in accessory bag
1 T1 = Depth of individual panel
2 Individual panel
dimension B1 x T1
3 Transport unit,
dimension B2 x T2
Packing, transport (examples)
Packing
Version
For supply
Transport
Panels mounted on wooden floor
and covered with protection sheeting
For container
Overseas
Ship + truck
4 B3 = Overall width of
combination of different
individual panels
5 B2 = Width of the
transport unit
* Additional packing weight in kg/lb (without weight of panels)
** Transport unit for air freight, height H2 2610 mm /102.8 inch
and width B2 1700 mm /66.9 inch
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 7
Product Range
Product range overview
Panel designation
Panel
type
Panel
width
CS1
375 mm / 14.8"
CS2
500 mm / 19.7"
FS1
375 mm / 14.8"
FS2
500 mm / 19.7"
FS3
750 mm / 29.5"
FU1
375 mm / 14.8"
FU2
500 mm / 19.7"
FU3
750 mm / 29.5"
CC1
375 mm / 14.8"
CC2
500 mm / 19.7"
Cable grounding panel
(= cable connection panel
with grounding switch)
CG1
375 mm / 14.8"
CG2
500 mm / 19.7"
Metering panel
MT3
750 mm / 29.5"
Metering cable panel
MC3
750 mm / 29.5"
Metering switch panel
MS2
500 mm / 19.7"
MS3
750 mm / 29.5"
BR1
375 mm / 14.8"
BR2
500 mm / 19.7"
BG1
375 mm / 14.8"
R-HA41-087 eps
Standard panels
Column No.
Cable switch panel
R-HA41-088 eps
Cable switch panel
type CS
Fuse switch panel
Fuse panel
Cable connection panel
R-HA41-089 eps
Fuse switch panel
type FS
Bus riser panel
Busbar grounding panel
Cable connection panel
type CC
8 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Product Range
Equipment features
se
fu
e
on
i
y
h
t
t
)
la
ca
if
ED
re
di
le
ism
ay vice e in
ib
ND
l
n
s
e
U
s
d
ha
de rvic
RO
po
e
a
ec se
ly
-G
im by
-se
m
en
t
a
n
r
)
N
p
w
y
e
o
o
E
o
by ing y-f
EN OP
el
rg
is
do ow
is
n
g
tr
h
p
d
in
ne
OP
d
)
pe oor
N)
w
itc
-e hun ppin trip rea
in
D- SED
E
o
D
d
n
P
E
E
d
w
s
is
e
sw
S
ri
O )
al
io
al
e
d
or
ND D-O
or
ct
by cal t nic tric
CL
LO
th ctor
re
st
d
a lec
i
pe fra
do e if
(C or ( PEN
OU OSE
h
r
e
e
s
h
t
r
R
t
t
e
i
n
l
e
a
in
in
G
L
ct
-O
ec
to
ec
w
th sib
er
on
e
(C
Nm ote
el
ne
ec
if
ED
ith
ith
m ism
bl
os disc
op
–
–
PE ism
w r w ing
nn con ND nis
p
m
n
r
ca
O
o
e
t
m ism ism
a
a
e
e
e
t
r
n
U
d
s
x
t
o
D
i
i
n
v
v
h
h
h
si c -dis
a
r
n
f
ta
n
t
ta
d
RO ec
SE
co
co ou
an
fo
an
an
ec
o
ch
h
g
g t
ow
os idis
hin
in tac
st
itc h (G g m g m ech ech ech O) e bl CLO me itch ent ent -gr
m
t
s
s
ti c
r
m
e
w
N
(
e
c
s
g
w rtm rtm
de
clo
clo in ble ack
sw n s wit ratin ratin y m y m y m (1
hu
th
fu itch
tin te s
–
–
– d
rg erg
rg itch tch
th e
th
e
e
br er
g
g d an ix ca
pa
pa ng
ra
on sitio g s
i
i
i
w
e
e
o
p
p
e
n
n
i
t
s
h
i
i
i
m om
n
n
n
w yp
w
o
in
si
l o al o
g ng
g
-e
-e l sw l sw iary r op rem co
-e
ck ock ock talle to f wit cov
c
po ee-p und ua
lt
in
in
i
lo
l
l
l
l
l
u
e
e
a
a
ed red
ed
o
oat eat eat ane
xil
er
er
er ins -rai -rai loor
bl
r
ca abl
o
ot
an tor
an
or ign ign
o
t
t
t
e
r
u
a
t
t
h
w
o
F
H
P
H
H
C
C
In is
In
In
C
C
L
M
A
S
S
S
S
S
M
M
G
T
T
1
2
3
°
°
°
°
°
–
•
–
•
–
•
–
•
–
•
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
•
•
–
–
–
–
–
–
–
•
•
–
–
–
–
°
°
–
–
°
°
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
•
–
–
•
–
–
–
–
–
•
–
–
•
–
–
–
°
°
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
•
•
–
–
–
–
•
•
•
•
•
•
4
5
°
°
°
°
°
6
7
8
–
–
9
10
11
12
17
18
°
°
°
°
°
°
°
°
°
°
°
°
°
°
–
°
°
–
° °
° ° –
° ° –
° – –
° – –
° – –
° – –
° – –
° – –
° – –
–
–
–
–
–
–
–
–
° °
–
–
–
° ° °
° ° °
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
°
–
°
–
–
–
–
–
–
–
–
°
°
° °
–
–
–
°
°
° °
° ° ° ° ° ° °
° ° –° ° ° ° °
° ° ° ° ° ° °
–
–
–
–
° – –
–
–
–
–
° – –
–
–
–
–
° – –
–
–
13
°
°
°
°
°
–
–
–
14
15
16
–
–
°
°
°
–
–
–
–
–
–
–
19
22
23
24
°
°
°
°
°
°
°
°
°
°
°
°
–7) –
–
°
° ° ° °
–
–
° °
–
–
° °
–
–
–
°
–
–
–
°
–
–
–
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
7
°)
20
21
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
°
CS1
CS2
FS1
FS2
FS3
FU1
FU2
FU3
CC1
CC2
CG1
CG2
MT3
MC3
MS2
MS3
BR1
BR2
BG1
Basic equipment
(optional) equipment
°– Additional
Not available
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 9
Product Range
Cable switch panel
Cable switch panel
as feeder panel
*
Cable switch panel
as transfer panel
HA41-2514 eps
HA41-2515 eps
HA41-22516 eps
Three-position
switch-disconnector
either... or
either... or
*
either... or
Three-position
switch-disconnector
Capacitve voltage
detection system
Surge arrester
either... or
Cable (not included
in the scope of supply)
Type CS
Type CS
Type CS
HA41-2608.eps
2nd cable
(not included in
the scope of supply)
Cable-type
current transformer
either... or
Type CS
Type CS
either... or
HA41-2519 eps
either... or
HA41-2518 eps
HA41-2517 eps
either... or
Type CS
* Switch-disconnector
Note: For detailed design, please
contact your local Siemens partner.
10 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
as:
– two-position
switch-disconnector
– three-position
switch-disconnector
Product Range
Fuse switch panel
Fuse switch panel
as feeder panel
*
Fuse switch panel
as transfer panel
either... or
HA41-2522 eps
either... or
HA41-2521 eps
HA41-2520 eps
Three-position
switch-disconnector
either... or
either... or
*
either... or
either... or
Three-position
switch-disconnector
Capacitve voltage
detection system
Surge arrester
DS
DS
DS
either... or
Type FS
Discharge switch
Type FS
Type FS
HV CL fuse
2nd HV CL fuse
either... or
2nd and 3rd HV CL fuse
DS
either... or
either... or
either... or
either... or
HA41-2523 eps
Type FS
Type FS
HA41-2525 eps
either... or
HA41-2524 eps
either... or
Type FS
Cable (not included
in the scope of supply)
2nd cable
(not included in
the scope of supply)
2nd and 3rd cable
(not included in
the scope of supply)
HA41-2608.eps
DS
DS
Cable-type
current transformer
* Switch-disconnector
Note: For detailed design, please
contact your local Siemens partner.
as:
– two-position
switch-disconnector
– three-position
switch-disconnector
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 11
Product Range
Fuse panel
Fuse panel
as transfer panel
either... or
Capacitve voltage
detection system
HA41-2528 eps
HA41-2527 eps
HA41-2526 eps
Fuse panel
as feeder panel
either... or
Surge arrester
either... or
Grounding stud
HV CL fuse
either...
nd
2 HV CL fuse
... or
nd
rd
2 and 3 HV CL fuse
Type FU
Type FU
Type FU
Cable (not included
in the scope of supply)
either...
nd
2 cable
(not included in
the scope of supply)
... or
either... or
either... or
either... or
HA41-2608.eps
2nd and 3rd cable
(not included in
the scope of supply)
Type FU
Type FU
HA41-2531 eps
HA41-2530 eps
HA41-2529 eps
Cable-type
current transformer
Type FU
Note: For detailed design, please
contact your local Siemens partner.
12 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Product Range
Cable connection panel
Cable connection panel
as feeder panel
HA41-2532 eps
Capacitve voltage
detection system
Surge arrester
Grounding stud
Cable (not included
in the scope of supply)
2nd cable
(not included in
the scope of supply)
HA41-2608.eps
either... or
Type CC
Cable-type
current transformer
HA41-2535 eps
either... or
Type CC
Note: For detailed design, please
contact your local Siemens partner.
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 13
Product Range
Cable grounding panel, busbar grounding panel
HA41-2536 eps
HA41-2538 eps
Cable grounding panel/busbar grounding panel
(with grounding switch)
HA41-2537 eps
Cable grounding panel
(= cable connection panel
with grounding switch)
Capacitve voltage
detection system
Surge arrester
Grounding switch
Cable (not included
in the scope of supply)
either... or
nd
Type CG
Type CG
Type CG
HA41-2608.eps
2 cable
(not included in
the scope of supply)
Cable-type
current transformer
Type CG
Type CG
HA41-2541 eps
HA41-2540 eps
HA41-2539 eps
either... or
Type CG
Note: For detailed design, please
contact your local Siemens partner.
14 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Product Range
Metering panel
Metering panel
HA41-2542 eps
HA41-2543 eps
Capacitve voltage
detection system
either...
either...
... or
... or
Type MT3
HA41-2544 eps
either...
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
either...
... or
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
HA41-2608.eps
... or
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
HA41-2545 eps
Type MT3
Grounding stud
Type MT3
Type MT3
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
Note: For detailed design, please
contact your local Siemens partner.
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 15
Product Range
Metering panel with cable
Metering panel with cable
either... or
HA41-2548 eps
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
either... or
Type MC
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
Type MC
either... or
either... or
Grounding stud
either... or
Surge arrester
Cable (not included
in the scope of supply)
either... or
nd
HA41-2608.eps
either... or
HA41-2547 eps
either... or
HA41-2549 eps
HA41-2546 eps
Capacitve voltage
detection system
2 cable
(not included in
the scope of supply)
either... or
either... or
Type MC
HA41-2551 eps
HA41-2550 eps
Type MC
either... or
either... or
either... or
either... or
Type MC
Type MC
Note: For detailed design, please
contact your local Siemens partner.
16 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Product Range
Metering panel with cable (continued), metering switch panel
*
Metering panel with cable
Three-position
switch-disconnector
either... or
HA41-2553 eps
HA41-2552 eps
either... or
*
Three-position
switch-disconnector
either... or
Capacitve voltage
detection system
either... or
Grounding stud
either... or
either... or
Type MC
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
Type MC
Block-type
current-transformer
4MA and voltage
transformer 4MR
(both cast-resin
insulated)
HA41-2556 eps
HA41-2555 eps
HA41-2554 eps
Metering switch panel
Surge arrester
HV CL fuse ***
Option **
Option **
either... or
VT
either... or
CPT
Type MS
Option **
VT
Type MS
Voltage transformer 4MR
(cast-resin insulated)
either... or
CPT
VT
CPT
Control power transformer (CPT) make ITI
Type MS
HA41-2608.eps
Cable (not included
in the scope of supply)
2nd cable
(not included in
the scope of supply)
* Switch-disconnector as:
– two-position switch-disconnector
– three-position switch-disconnector
** Only in combination with VT or CPT
*** Fuses: Potential transformer fuses type CAV
Note: For detailed design, please
contact your local Siemens partner.
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 17
Product Range
Bus riser panel, busbar grounding panel
Bus riser panel
HA41-2557 eps
HA41-2558 eps
Capacitve voltage
detection system
HA41-2608.eps
Grounding stud
Grounding switch
Type BR
Type BR
Type BG
Type BG
HA41-2561 eps
HA41-2560 eps
Type BG
Type BG
HA41-2564 eps
HA41-2562 eps
Type BG
HA41-2563 eps
HA41-2559 eps
Busbar grounding panel
Type BG
18 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Note: For detailed
design, please
contact your local
Siemens partner.
Design
Panel design (examples)
Fuse switch panel type FS
23
24
25
26
27
12
7
8
9
10
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
4
28
29
30
31
HA41-2566a eps
HA41-2565a eps
Cable switch panel type CS
23
24
25
26
27
12
7
8
9
10
11
12
13
14
15
16
17
18
19
1
2
3
4
5
6
4
32
20
28
29
30
32
36
34
36
34
35
21
21
22
21
33
Type CS1
20
21
33
22
Section
Type FS2
Section
Legend
HA41-2567a eps
Metering panel type MT
1 Indicator “Fuse intact/fuse
blown”
18 Feeder designation label
2 Switch position indicator
20 Cable termination
(not incl. in scope of supply)
3 View port for switch blade
position
23
24
7
22 Cable connection
compartment
5 Information label for view
port
23 Busbar
6
16
4
17
7 Warning label
8 Gas-insulated vessel for
switching device
35
9 Manual operation for the
mechanism of the load-breakdisconnecting function
18
29
19
32
37
37
38
38
33
Type MT3
Section
25 Bushing-type insulator for
busbar
26 Metal compartmentalization
of busbar compartment
27 Spring-operated mechanism
for three-position switch
28 Three-position switch
11 Manual operation for the
mechanism of the grounding
function
30 Bushing-type insulator for
feeder
12 Interlocking lever of cable
compartment cover (option)
14 Pressure relief device for
switching device
39
24 Insulating cap on busbar
(for > 15 kV)
10 “Ready-for-service” indicator
for switching device
13 Option: Locking device for
three-position switch
39
21 Cable bracket with clamps
4 Sockets for capacitive
voltage detection system
6 Mimic diagram
35
19 Pressure relief duct
15 Metal compartmentalization
of cable connection
compartment
29 Grounding busbar
31 Cable connection
32 Cable compartment:
As cover or door
(latched or screwed-on)
33 Grounding connection
34 Grounding switch to
discharge capacitance of
connected transformers
35 Post insulator
16 Rating and type plate
36 HV CL (current limiting) fuse
17 Option: Local-remote switch
and momentary-contact
rotary control switch
“CLOSED-OPEN” for the motor
operating mechanism
37 4MA7 block-type current
transformer
38 Fuse holder for VT fuse
39 4MR voltage transformer
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 19
Components
Two/three-position switch-disconnector
Three-position
switch-disconnector
• Switch positions:
– CLOSED-OPEN
or
– CLOSED-OPEN-GROUNDED
R-HA35-047 eps
Characteristics
Fixed contact
• Designed as a multi-chamber
Arcing chamber
switch incorporating the
following functions
– Switch-disconnector and
– Make-proof grounding switch
Moving contact, complete
Switch shaft
• Operation via gas-tight
Compression vane (with nozzle)
welded bushing at the front
of the switchgear vessel
• Switching functions as
general purpose switchdisconnector according to
ANSI/IEEE C37.20.3 *
Exploded view
Mode of operation
The switch shaft with the
moving contacts rotates inside
the chamber containing the
fixed contacts.
Interlocking is not necessary
as the CLOSED and GROUNDED
functions cannot be implemented simultaneously.
Control board with
switch position
indicators for
detachable lever
mechanism
R-HA41-092 eps
R-HA41-091 eps
R-HA41-090 eps
During the switching movement, the compression vanes
generate a pressure difference
between the subchambers.
The SF6 gas flows through a
nozzle, causes a directional
blow-out of the breaking arc
and quenches it rapidly.
Switch positions:
HA41-2568 eps
Compression vanes, which
rotate in conjunction with the
switch shaft, divide the arcing
chamber into two subchambers
each of which changes in conjunction with the rotation.
Switching functions
Three-position
switch-disconnector
– CLOSED
1
– OPEN
– GROUNDED
2
3
Switch positions
of three-position
switch-disconnector
CLOSED
OPEN
GROUNDED
Switch positions
of two-position
switch-disconnector
Legend
1 Moving contact
CLOSED
OPEN
2 Fixed contact for GROUNDED
3 Fixed contact for CLOSED
* Standards see page 40
20 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Components
Two/three-position switch as two/three-position switch-disconnector
Two/three-position
switch-disconnector 600 A
Common features
• Metal-enclosed
1
• Up to 600 A
• Located in a
• With gas-insulated,
gas-insulated
switchgear vessel
maintenance-free quenching principle
• Switch positions:
– CLOSED-OPEN
or
– CLOSED-OPENGROUNDED
Operating mechanism
2
5
• Spring-operated mechanism
• Manual operation with the
• No cross insulation
3
R-HA41-093 eps
with detachable lever
aid of a detachable lever
between phases
• Options:
• Two/three-position
– Mechanical ready-forservice indication
– Auxiliary switch
– Motor operating mechanism
for switch-disconnector
– Locking device
switch with air-insulated primary connections for busbar and
feeder
• Operation via a
gas-tight welded-in
metal bellows in the
front of the switchgear
vessel
• Spring-operated/stored-
energy mechanism for
transformer panel type FS
View port
Interlocks
The visual inspection of
the actual position of the
two/three-position switch
is possible via a view
port.
(Fig. shown on the right)
• Opening of panel cover or
cable compartment cover
only in “GROUNDED“
position
4
6
Three-position
switch-disconnector
600 A (side removed for photo)
1 Bushing-type insulator for busbar
2 Switchgear vessel for gas insulation
3 Three-position switch-disconnector
4 Bushing-type insulator for feeder
5 Spring-operated mechanism with detachable lever
6 View port
Operating cycles
• Capable of 100 operating
Switch positions of
three-position switch:
cycles at rated continuous
current 600 A
1000 operating cycles
7
HA41-2569a eps
• Mechanical endurance of
CLOSED
OPEN
GROUNDED
Detachable lever mechanism
with three-position switch-disconnector
7 Operating lever, inserted
Switching functions of the three-position switch-disconnector 600 A
• Switching and disconnecting under load
• General-purpose switching function
• Make-proof grounding function
View port
1
2
HA41-2570b eps
3
Legend for view port
1 Moving contact
2 Fixed contact for CLOSED
3 Fixed contact for GROUNDED
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 21
Components
Busbars, HV CL (current-limiting) fuse assembly
Busbars
HV CL fuse assembly
• Metal-enclosed busbar
• For fuse panel type FS
• Three-pole design,
bolted from panel to
panel
• Easy switchgear
extension
• Made of copper:
Round-edge copper for
up to 1200 A
Option:
Shrink-on sleeve
Busbars
• For busbar voltage meter-
ing panel type MS
1 Busbar
1
2 Bushing-type
insulator for busbar
• HV CL fuse links
acc. to ANSI/IEEE
C37.41/C37.46 *
– As short-circuit protection before transformers
– With selectivity (depending on correct selection)
to upstream and downstream connected equipment
2
R-HA41-094 eps
compartment
Busbar compartment extending over 2 panels, example (side view)
• Requirements fulfilled as
HV HRC fuse assembly
HV alternating current
switch fuse combination
Displays
• Selection of HV CL
fuses for transformers
Fuse intact
• Fuse replacement possi-
ble only when feeder is
grounded
Fuse blown
• Option: Shunt release on
operating mechanism of
two/three-position switchdisconnector
tion” of two/three-position
switch-disconnector in
transformer feeder (transformer switch) for remote
electrical indication with
one normally-open contact (1NO)
R-HA41-095 eps
• Option: “Tripped indica-
Control board of a fuse panel
“HV CL fuse tripped”
Following the tripping of an
HV CL fuse link, the mechanism for charging the spring
must be set to the “OPEN”
position
3 HV CL fuse
4 Lower fuse holder
Subsequently, grounding
can be implemented by
means of the two/threeposition switch-disconnector and e.g., the fuse can be
replaced.
Replacement of HV CL fuse
links
• Isolating and grounding
of the transformer feeder
5 Grounding stud
6 Cable termination
(not included in the
scope of supply)
3
4
• Subsequent manual
replacement of the
HV CL fuse links
5
R-HA41-096 eps
6
HV CL fuses in fuse panel type FS (side view, 2 sets of fuses shown)
* Standards see page 40
22 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Components
Allocation of HV CL fuses and transformers
The table opposite shows the
recommended fuse links (electrical data valid for ambient
temperatures of up to 40 oC/
104 °F) for the fuse protection
of transformers
Recommendation
The two/three-position switchdisconnector in the transformer feeder (transformer
switch) is combined with
Bussmann fuse links. Dimensions according to DIN standards (especially manufactured
for Siemens)
Standards
HV CL fuse links according to
ANSI/IEEE C37.41/C37.46 *
Bussmann fuses
Rated
voltage
Length
Diameter
Rated
current I1
Power
loss
A
W
Panel type **
FS1/FU1
FS2/FU2
FS3/FU3
Permissible continuous current
A
A
A
Code/reference
No. for SIMOSEC
ANSI
kV
mm / inch
mm / inch
5.5
5.5
5.5
442 / 17.4
442 / 17.4
442 / 17.4
51 / 2.0
51 / 2.0
51 / 2.0
10
15
20
8
11
11
10
15
20
18
27
36
24
36
48
55GDMSJ10ES
55GDMSJ15ES
55GDMSJ20ES
5.5
5.5
5.5
442 / 17.4
442 / 17.4
442 / 17.4
51 / 2.0
51 / 2.0
51 / 2.0
25
30
40
15
17
27
25
30
40
45
54
72
60
72
96
55GDMSJ25ES
55GDMSJ30ES
55GDMSJ40ES
5.5
5.5
5.5
442 / 17.4
442 / 17.4
442 / 17.4
51 / 2.0
51 / 2.0
51 / 2.0
50
65
80
36
44
53
50
65
80
90
117
144
120
156
192
55GDMSJ50ES
55GDMSJ65ES
55GDMSJ80ES
5.5
5.5
442 / 17.4
442 / 17.4
51 / 2.0
51 / 2.0
100
125
69
94
100
120
180
220
240
300
55GDMSJ100ES
55GDMSJ125ES
5.5
5.5
5.5
442 / 17.4
442 / 17.4
442 / 17.4
76 / 3.0
76 / 3.0
76 / 3.0
150
175
200
103
121
126
150
164
183
270
292
327
360
416
466
55GDMSJ150ES
55GDMSJ175ES
55GDMSJ200ES
5.5
5.5
5.5
442 / 17.4
442 / 17.4
442 / 17.4
76 / 3.0
76 / 3.0
76 / 3.0
250
300
350
139
147
161
220
241
269
390
429
478
555
598
600
55GDMSJ250ES
55GDMSJ300ES
55GDMSJ350ES
5.5
5.5
442 / 17.4
442 / 17.4
76 / 3.0
76 / 3.0
400
450
167
183
302
325
536
575
600
600
55GDMSJ400ES
55GDMSJ450ES
15.5
15.5
537 / 21.14 88 / 3.5
537 / 21.14 88 / 3.5
175
200
177
238
167
165
310
305
420
430
175GXQSJ175ES
175GXQSJ200ES
17.5
17.5
17.5
442 / 17.4
442 / 17.4
442 / 17.4
51 / 2.0
51 / 2.0
51 / 2.0
10
15
20
22
30
32
10
15
20
18
27
36
24
36
48
175GDMSJ10ES
175GDMSJ15ES
175GDMSJ20ES
17.5
17.5
442 / 17.4
442 / 17.4
51 / 2.0
51 / 2.0
25
30
41
47
25
30
45
54
60
72
175GDMSJ25ES
175GDMSJ30ES
17.5
17.5
17.5
442 / 17.4
442 / 17.4
442 / 17.4
76 / 3.0
76 / 3.0
76 / 3.0
40
50
65
79
95
130
40
50
59
72
90
104
69
120
149
175GFMSJ40ES
175GFMSJ50ES
175GFMSJ65ES
17.5
17.5
442 / 17.4
442 / 17.4
76 / 3.0
88 / 3.5
80
100
126
169
73
85
131
155
186
225
175GXMSJ80ES
175GXMSJ100ES
17.5
17.5
537 / 21.14 88 / 3.5
537 / 21.14 88 / 3.5
125
150
203
221
112
123
207
238
292
336
175GXQSJ125ES
175GXQSJ150ES
25.8
25.8
25.8
537 / 21.14 51 / 2.0
537 / 21.14 51 / 2.0
537 / 21.14 51 / 2.0
10
15
20
27
41
44
10
15
20
18
27
36
24
36
48
258GDQSJ10ES
258GDQSJ15ES
252GDQSJ20ES
25.8
25.8
537 / 21.14 51 / 2.0
537 / 21.14 51 / 2.0
25
30
50
67
25
30
45
54
60
72
252GDQSJ25ES
252GDQSJ30ES
25.8
25.8
25.8
537 / 21.14 88 / 3.5
537 / 21.14 88 / 3.5
537 / 21.14 88 / 3.5
40
50
65
87
103
140
40
50
65
72
90
117
96
120
156
252GDQSJ40ES
252GDQSJ50ES
252GDQSJ65ES
* Standards see page 40
** FS1/FU1: Single fuse
FS2/FU2: Two fuses in parallel
FS3/FU3: Three fuses in parallel
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 23
Components
Operating mechanisms for two/three-position switches
• Spring-operated mecha-
nism
– For cable-switch panel
type CS
– For all two/three-position
switches (except in panel
type FS)
• Spring-operated /stored-
energy mechanism
For fuse panel type FS as
well as for busbar voltage
metering switch panel
type MS
The two/three-position
switch is operated via a
rocker with metal bellows
which is gas-tight and
welded at the switchgear
vessel.
Motor operating
mechanism (option)
The manual operating mechanisms can be equipped with
motor operating mechanisms
for the two/three-position
switch-disconnector.
Operating voltages for motor
operating mechanisms:
– 24, 48, 60, 125 V DC
– 50/60 Hz 120 and 240 V AC
Electrical operation:
R-HA41-098 eps
As detachable lever
mechanism
Operating mechanisms
Spring-operated/storedenergy mechanisms can be
equipped with a shunt release. Remote electrical
tripping of the two/threeposition switch-disconnector
is possible via the magnetic
coil of the shunt release,
e.g., transformer overtemperature tripping.
To avoid thermal overloading
of the shunt release in the
event of a continuous signal
that may be applied, the
shunt release is switched off
via an auxiliary switch which
is mechanically coupled with
the three-position switchdisconnector.
Detachable lever mechanism
as spring-operated/
stored-energy mechanism
Detachable lever mechanism
as spring-operated mechanism
R-HA41-099 eps
• Standard:
Shunt release (option)
R-HA41-097 eps
Manual operating
mechanism
Auxiliary switch (option)
Each operating mechanism
of the two/three-position
switch-disconnector can be
optionally equipped with an
auxiliary switch for the
switch position indication:
– Function switch-disconnector or disconnector:
CLOSED and OPEN:
2NO + 2NC
– Function grounding
switch at the two/threeposition switch:
CLOSED and OPEN:
2NO + 2NC
2 Auxiliary switch
3 Switch position
indicator for the
three-position
switch-disconnector
1
2
4 Locking device
(standard for motor
operating mechanism)
3
5 Operating mechanism
for the three-position
switch-disconnector
coupled with the motor
operating mechanism
4
5
6 Low-voltage niche
7 Terminal strip located
in the low-voltage
niche
6
7
8 M.c.b. (option)
in the low-voltage
niche
8
9 Local-remote switch
(option)
9
10 Actuation for the
motor operating
mechanism of the
three-position
switch-disconnector
• Standard: Remote opera-
tion (applied to terminal)
1 Ready-for-service
indicator
• Option: Local operation
by momentary-contact
rotary control switch
10
Operating mechanism parts in
panel types FS… (transformer feeders)
Technical data of the auxiliary switch
Rated switching capacity
Breaking capacity
AC operation at
50 Hz to 60 Hz
DC operation
Rated insulation
voltage 250 V AC/DC
Operating Normal
voltage
current
Operating Normal current
voltage
resistive inductive:
T=20 ms
V
A
A
24
10
10
48
10
9
60
9
7
110
5
4
125
5
4
240
2.5
2
Insulation group
C to VDE 0110
V
A
up to 240 10
Abbreviations:
NO = normally-open contact
NC = normally-closed contact
24 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Continuous current
10 A
Making capacity
50 A
Components
Indicating and measuring equipment
• Self-monitoring; easy to
read
• Independent of tempera-
Voltage detection systems
Indicating and measuring equipment
(examples)
For voltage detection
according to IEC 61 243-5 /
VDE 0682-415
Plug-in voltage
detection systems
ture and pressure variations • Standard: HR system
• Independent of site altitude
Features of the
• Only responds to changes
HR system
in gas density
R-HA41-100 eps
Ready-for-service indicator
(option for three-position
switch)
1
• Voltage indicator
HR system (standard)
“1NO contact”
• Verification of safe isolation
Mode of operation
For the ready-for-service indicator, a gas-tight measuring
box is installed on the inside
of the switchgear vessel.
A coupling magnet, which
is fitted to the bottom end
of the measuring box, transmits its position to an outside
armature through the stainless steel switchgear vessel.
This armature moves the
ready-for-service indicator of
the switchgear.
While changes in the gas
density during the loss of
gas, which are decisive for
the insulating capacity, are
displayed, temperaturedependent changes in the
gas pressure are not. The gas
in the measuring box has the
same temperature as that in
the switchgear.
from supply phase by
phase through insertion in
each socket pair
• Voltage indicator flashes
if high voltage is present
• For continuous operation
• Safe-to-touch
• Measuring system and
voltage indicator can be
tested
• Fixed-mounted capacitive
2
voltage divider in bushings
• Without auxiliary power
Mounting of voltage
detection systems
See “Product range”
pages 10 to 18
Control board of a ring-main panel
(example)
Verification of correct
terminal-phase connections
Mounting locations in the control
board for
• Possible by means of a
1 Ready-for-service indicator
(option)
phase comparison test unit
(optional)
2 Voltage indicator, HR system,
plugged-in (standard)
• Safe-to-touch handling of
the phase comparison test
unit by inserting it into the
capacitive taps (socket
pairs) of the switchgear
Voltage indicator,
HR system (standard)
HA41-2571 eps
The temperature effect is
compensated via the same
pressure change in both gas
volumes.
2
R-HA40-088 eps
• Option: Alarm switch
3 Measuring box
4 Magnetic coupling
3
5
4
5 Red indication:
not ready for service
6 Green indication:
ready for service
6
Stainless-steel vessel
filled with SF6 gas,
gauge pressure
50 kPa (7.25 psi) at 20 °C
Ready-forservice
indicator
Principle of operation of gas monitoring
with ready-for-service indicator
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 25
Components
4MC70 33 cable-type current transformers
• For cable panel
types CS, CC, CG
• For fuse panel
types FS, FU
R-HA41-102 eps
Application
Features
• According to
ANSI / IEEE C57.13
• Designed as a single-pole
R-HA41-024 eps
ring-core current transformer
• Only for shielded cables
H
• Climate-independent
4MC70 33 cable-type
current transformer,
4 different overall heights
• Free of dielectrically
stressed cast-resin parts
(due to design)
• Inductive type
• Secondary connection by
means of a terminal strip
inside the panel
Installation
• Arranged on the cable at
the panel connection
• Transformers mounted on
a supporting plate at the
factory; final assembly on
the cables at site
4MC70 33 cable-type current transformers
on the cable at the panel connection **
Technical data
MC70 33 cable-type current transformer
Primary data
Max. equipment operating voltage Um
0.60 kV
Rated current IN
30 A to 600 A
Rated short-duration power-frequency
withstand voltage (winding test)
3 kV
Rated thermal short-time withstand current Ith
25 kA
Rated continuous thermal current ID
1.0 x IN
option: 1.2 x IN
Rated peak withstand current Idyn
unlimited
Secondary data
Rated current
Measuring core
Protection core
5A
Class ***
0.3
Burden
0.2 VA to 1.8 VA
Class ***
C10 ... C200
0.6
1.2
Dimensions
Overall height H
mm
50* 100* 170* 285*
Outside diameter
Ø 145 mm / 5.7 inch
Inside diameter
Ø 55 mm / 2.2 inch
For cable diameter
Ø 36 ... 50 mm / 1.4 ... 2.0 inch
* Depending on the core data
** Assembly normally under the
panel floor
*** Accuracy class varies according
Other values available on request
to CT data
26 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Components
4MA7 block-type current transformers and 4MR voltage transformers
Application
types MT, MS, MC
Features
R-HA41-030a eps
R-HA41-101 eps
• For metering panel
• 4MA7 current transformer
• According to
ANSI / IEEE C57.13
• Dimensions according to
DIN 42 600-8
4MA7 blocktype current
transformer,
single-pole
• Designed as a single-pole
indoor block-type current
transformer
• Cast-resin insulated
• Secondary connection by
means of screw-type
terminals
4MR voltage transformer
• According to
ANSI / IEEE C57.13
• Dimensions according to
R-HA41-029a eps
DIN 42 600-9 (small model)
• Designed as an indoor
voltage transformer:
– Type 4MR, single-pole
– Option: Type 4MR, two-pole
• Cast-resin insulated
4MR14 voltage
transformer,
single-pole
• Secondary connection by
means of screw-type
terminals
4MR voltage transformer and
4MA7 block-type current transformer installed in metering panel
Technical data
4MA7 single-pole block-type current transf.
4MR single-pole voltage transformer
Primary data
Max. equipment
operating voltage Um
15.5 kV 27.6 kV
Rated short-duration
power-frequency
withstand voltage
34 kV
1)
36 kV
2)
Rated lightning impulse
withstand voltage Up
95 kV
Rated current IN
50 A to 600 A
> 600 A: on
request
Rated thermal short-time
withstand current Ith
up to 25 kA
Rated continuous thermal
current ID
up to 1.0 x IN
option: 1.2 x IN
1)
40 kV
60 kV 2)
125 kV
Max. equipment 5.6 kV 9.52 kV
operating voltage
Um
15.5 kV 25.5 kV
16 kV 1) 26 kV 1)
34 kV 1) 40 kV 1)
Rated shortduration powerfrequency withstand voltage
20 kV
2)
Rated lightning
60 kV
impulse withstand
voltage Up
B
28 kV 2)
36 kV 2) 60 kV 2)
75 kV
95 kV
125 kV
R. peak withst. current Idyn max. 2.5 x Ith
Secondary data
B On request: operating voltage
Um > 25.5 kV, e.g. 27.6 kV
1) Acc. to ANSI/IEEE C57.13
(standard)
Rated current
5A
Measuring core Class 3)
0.3
1.2
Burden
0.2 to 1.8 VA
Protection core Class 3)
C10 ... C200
2) Option: on request
3) Accuracy class varies according
to CT data
0.6
Other values available on request
Rated voltage
100/ 3 V
110/ 3 V
120/ 3 V
Rated voltage for
auxiliary winding
100/3 V
110/3 V
120/3 V
Burden
25 ... 200 VA
Class
0.3
0.5
1.2
Other values available on request
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 27
Components
Cable connection
General features
• Cable termination points are
Cable connection (examples)
arranged one behind the other
• Uniform cable connection
L3
height per panel (see dimension
drawings)
L2
L1
L3
L2
L1
• With cable bracket or cable
clamps and grounding points
for cable shields
1
3
• Access to the cable connection
compartment only when
feeder has been grounded
4
Features for cable terminals
• For thermoplastic-insulated
R-HA41-103 eps
R-HA41-105 eps
cables
• For paper-insulated mass-
impregnated cables
• For connection cross-
sections (cable size) * up to
300 mm2 (600 kcmil)
• Cable bottom entry from
below (standard)
Cable connection compartment
with cable termination
Cable switch panel type CS
Cable connection compartment as delivered
• Cable top entry from above
(optional)
2
R-HA41-104 eps
R-HA41-106 eps
5
Fuse panel type FS
Cable connection compartment as delivered
Cable connection compartment
with cable termination
Legend
1 As delivered condition for
cable termination
4 Cable termination brand 3M or
Tyco Electronics Raychem
2 As delivered condition,
prepared for cable termination
5 Cable termination brand 3M or
Tyco Electronics Raychem
(with cold shrink brand 3M)
3 Cold shrink brand 3M
* Larger connection cross-sections
on request.
28 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Components
Selection data for various cable terminations
Panel type
FS1 + 2 + 3
FU1 + 2 + 3
CC1 + 2
Panel
height
in
mm/inch
Cable
termination
height in
mm/inch
Panel
height
in
mm/inch
Cable
termination
height in
mm/inch
Panel
height
in
mm/inch
Cable
termination
height in
mm/inch
2550/
100.4
490/
19.3
2550/
100.4
490/
19.3
2550/
100.4
490/
19.3
not
not
available available
490/
19.3
2550/
100.4
not
not
available available
not
not
available available
not
not
available available
2250/
88.6
not
not
available available
940/
37
2250/
88.6
940/
37
2250/
88.6
940/
37
2250/
88.6
not
not
available available
2250/
88.6
not
not
available available
1240/
48.8
2250/
88.6
1240/
48.8
2250/
88.6
1240/
48.8
2250/
88.6
not
not
available available
2250/
88.6
not
not
available available
not
not
available available
not
not
available available
490/
19.3
490/
19.3
490/
19.3
CS1 + 2
Cable
termination
height in
mm/inch
Panel
height
Main switch or vertical copper
bar in upper position
(fuse assembly in lower position)
490/
19.3
Main switch or vertical copper
bar in lower position
(fuse assembly in upper position)
not
not
available available
to top
940/
37
to bottom
1240/
48.8
CG1 + 2
MC3
Panel
height
in
mm/inch
Cable
termination
height in
mm/inch
Panel
height
in
mm/inch
Cable
termination
height in
mm/inch
2550/
100.4
490/
19.3
2550/
100.4
530/
20.8
2250/
88.6
in
mm/inch
Top cable entry
Middle cable connection
Bottom cable entry
Main switch or vertical copper
bar in upper position
(fuse assembly in upper position)
not
not
available available
not
not
available available
490/
19.3
Main switch or vertical copper
bar in upper position
(fuse assembly in lower position)
490/
19.3
490/
19.3
not
not
available available
2250/
88.6
2250/
88.6
2250/
88.6
2250/
88.6
2250/
88.6
Principle of cable connection (dimensions in mm/inch)
(e.g. for panel type CS)
Æ100/3.9
L=max. 420/16.5
125/4.9
Æ130/5.1
HA41-2574 eps
L=max. 420/16.5
Æ130/5.1
HA41-2573 eps
HA41-2572 eps
L=max. 420/16.5
125/4.9
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 29
Dimensions
370.5/14.6
2250/88.6
148
5.8
1
187.5
7.4
375/14.8
187.5
7.4
205
8.1
500/19.7
Type CS1
50/2
Type CS2
187.5
7.4
210
8.3
1000/39.4
1230/48.4
205
8.1
210
8.3
210
8.3
1
148
5.8
443/17.4
187.5
7.4
HA41-2576a eps
2250/88.6
187.5
7.4
150
5.9
210
8.3
940/37
187.5
7.4
2250/88.6
HA41-2575a eps
1240/48.8
2250/88.6
Cable switch panel types CS… (dimensions in mm/inch)
Legend
1 Available mounting depth
in the LV niche
375/14.8
Type CS1
500/19.7
Type CS2
50/2
150
5.9
1000/39.4
1230/48.4
30 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Dimensions
Fuse switch panel types FS… (dimensions in mm/inch)
2
500/19.7
2250/88.6
HA41-2578a eps
187.5
7.4
375/14.8
443/17.4
50/2
Type FS3
187.5
7.4
187.5
7.4
500/19.7
=
=
150
5.9
210
8.3
210
8.3
1000/39.4
1230/48.4
148
5.8
187.5
7.4
205
8.1
750/29.5
50/2
Type FS3
Type FS2
Type FS1
205
8.1
187.5
7.4
750/29.5
Type FS2
187.5
7.4
=
370.5/14.6
Type FS1
=
490/19.3
187.5
7.4
2250/88.6
375/14.8
2250/88.6
2250/88.6
187.5
7.4
1
150
5.9
210
8.3
2
1
490/19.3
187.5
7.4
2250/88.6
HA41-2577a eps
2250/88.6
148
5.8
210
8.3
1000/39.4
1230/48.4
3
187.5 =
7.4
187.5
7.4
=
187.5
7.4
205
8.1
210
8.3
210
8.3
490/19.3
187.5
7.4
187.5
7.4
2
1
443/17.4
2250/88.6
2550/100.4
2550/100.4
2550/100.4
148
5.8
Legend
HA41-2579b eps
1 Available mounting depth
in the LV niche
2 Screwed-on door
(fuse compartment)
3 Top case for cable top entry
375/14.8
Type FS1
500/19.7
Type FS2
750/29.5
Type FS3
50/2
150
5.9
1000/39.4
1230/48.4
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 31
Dimensions
Fuse panel types FU… (dimensions in mm/inch)
187.5
7.4
375/14.8
187.5
7.4
187.5
7.4
500/19.7
Type FU1
457/18
2250/88.6
2250/88.6
187.5
7.4
=
2
= 187.5
7.4
205
8.1
750/29.5
Type FU2
Type FU3
187.5
7.4
187.5
7.4
1
50/2
150
5.9
210
8.3
490/19.3
HA41-2580a eps
2250/88.6
108/4.3
210
8.3
1000/39.4
1230/48.4
3
187.5
7.4
=
= 187.5
7.4
205
8.1
210
8.3
210
8.3
490/19.3
187.5
7.4
457/18
2250/88.6
2550/100.4
2550/100.4
HA41-2581b eps
2550/100.4
108/4.3
2
1
375/14.8
500/19.7
750/29.5
Type FU1
50/2
Type FU3
Type FU2
150
5.9
1000/39.4
1230/48.4
2
1
457/18
2250/88.6
2250/88.6
2250/88.6
108/4.3
205
8.1
210
8.3
210
8.3
Legend
HA41-2582a eps
1 Available mounting depth
in the LV niche
2 Screwed-on door
(fuse compartment)
3 Top case for cable top entry
375/14.8
Type FU1
500/19.7
Type FU2
750/29.5
Type FU3
50/2
150
5.9
1000/39.4
1230/48.4
32 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Dimensions
Cable connection panel types CC… (dimensions in mm/inch)
2
1
HA41-2583b eps
457/18
1240/48.8
2250/88.6
2250/88.6
108/4.3
187.5
7.4
187.5
7.4
375/14.8
187.5
7.4
205
8.1
500/19.7
Type CC1
50/2
150
5.9
210
8.3
210
8.3
1000/39.4
1150/45.3
Type CC2
2
210
8.3
210
8.3
1
108/4.3
457/18
205
8.1
940/37
187.5
7.4
2250/88.6
187.5
7.4
2250/88.6
187.5
7.4
HA41-2584b eps
Legend
1 Available mounting depth
in the LV niche
2 Screwed-on cover
375/14.8
Type CC1
500/19.7
Type CC2
50/2
150
5.9
1000/39.4
1150/45.3
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 33
Dimensions
Cable grounding panel types CG… (dimensions in mm/inch)
370.5/14.6
2250/88.6
148
5.8
1
HA41-2585b eps
1240/48.8
2250/88.6
2
187.5
7.4
187.5
7.4
375/14.8
187.5
7.4
205
8.1
500/19.7
Type CG1
50/2
150
5.9
210
8.3
210
8.3
1000/39.4
1150/45.3
Type CG2
2
210
8.3
210
8.3
1
148
5.8
443/17.4
205
8.1
940/37
187.5
7.4
2250/88.6
187.5
7.4
2250/88.6
187.5
7.4
HA41-2586b eps
Legend
1 Available mounting depth
in the LV niche
2 Screwed-on cover
375/14.8
Type CG1
500/19.7
Type CG2
50/2
150
5.9
1000/39.4
1150/45.3
34 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Dimensions
Metering panel type MT3, metering switch panel types MS (dimensions in mm/inch)
2
2
1
108/4.3
1
457/18
250
9.8
165
6.5
250
9.8
250
9.8
HA41-2588b eps
250
9.8
HA41-2587b eps
165
6.5
2250/88.6
2250/88.6
457/18
108/4.3
750/29.5
50/2
750/29.5
1000/39.4
1150/45.3
150
5.9
Type MT3
50/2
1000/39.4
1150/45.3
150
5.9
Type MT3
2
1
2250/88.6
457/18
108/4.3
250
9.8
250
9.8
HA41-2589b eps
165
6.5
Legend
1 Available mounting depth in the LV niche
2 Screwed-on cover
750/29.5
50/2
1000/39.4
1150/45.3
150
5.9
Type MT3
2
205
8.1
250
9.8
250
9.8
148
5.8
370/14.6
205
8.1
210
8.3
210
8.3
1
148
5.8
1
HA41-2590b eps
210
8.3
HA41-2591b eps
165
6.5
210
8.3
2250/88.6
2250/88.6
370/14.6
2
750/29.5
50/2
150
5.9
1000/39.4
1150/45.3
Type MS2 (with voltage transformer 4MR)
750/29.5
50/2
150
5.9
1000/39.4
1150/45.3
Type MS3 (with control power transformer make ITI)
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 35
Dimensions
297.5
11.7
250
9.8
250
9.8
2250/88.6
457/18
165
6.5
530/20.8
Metering cable panel type MC3 (dimensions in mm/inch)
108/4.3
1
HA41-2592b eps
2
750/29.5
50/2
1000/39.4
1150/45.3
150
5.9
Type MC3
1
2250/88.6
457/18
108/4.3
297.5
11.7
165
6.5
750/29.5
50/2
165
6.5
250
9.8
250
9.8
2250/88.6
457/18
307.5
12.1
250
9.8
1000/39.4
1150/45.3
150
5.9
Type MC3
297.5
11.7
250
9.8
580/22.8
307.5
12.1
530/20.8
HA41-2593b eps
2
108/4.3
HA41-2594b eps
1
2
Legend
1 Available mounting depth in the LV niche
2 Screwed-on cover
750/29.5
Type MC3
50/2
150
5.9
1000/39.4
1150/45.3
36 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Dimensions
Bus riser panel types BR… (dimensions in mm/inch)
457/18
2250/88.6
2250/88.6
2
108/4.3
HA41-2595b eps
1
375/14.8
500/19.7
Type BR1
50/2
150
5.9
Type BR2
1000/39.4
1150/45.3
2
1
457/18
2250/88.6
HA41-2596b eps
2250/88.6
108/4.3
375/14.8
500/19.7
50/2
150
5.9
Type BR2
Type BR1
1000/39.4
1150/45.3
457/18
2250/88.6
2250/88.6
2
108/4.3
HA41-2597b eps
1
Legend
1 Available mounting depth in the LV niche
2 Screwed-on cover
375/14.8
Type BR1
500/19.7
Type BR2
50/2
150
5.9
1000/39.4
1150/45.3
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 37
Dimensions
Busbar grounding panel type BG1 (dimensions in mm/inch)
2
1
HA41-2598b eps
2250/88.6
443/17.4
148
5.8
375/14.8
50/2
150
5.9
Type BG1
1000/39.4
1150/45.3
1
HA41-2599b eps
2250/88.6
443/17.4
148
5.8
375/14.8
50/2
150
5.9
Type BG1
1000/39.4
1150/45.3
2250/88.6
370.5/14.6
2
148
5.8
HA41-2600b eps
1
Legend
1 Available mounting depth in the LV niche
2 Screwed-on cover
375/14.8
Type BG1
50/2
150
5.9
1000/39.4
1150/45.3
38 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Dimensions
Floor openings (dimensions in mm/inch in red) and fixing points
60/2.4
58/2.3
857/33.7
4 Position of the cables for the feeder
5 Fixing points
6 Floor opening if required for panels
without cable connection
28 x 14/
1.1 x 0.6
255/10
250/9.8
60/2.4
58/2.3
14 x 28/
0.6 x 1.1
Panel
type
857/33.7
BR2
MS2
380/15
60/2.4
28 x 14/
1.1 x 0.6
58/
2.3
18/0.7 169.5/6.7 375/14.8
60/2.4
58/2.3
Panel
type
MT3
MS3
857/33.7
385/15.2 80 20
3.1 0.8
110/4.3 385/15.2
150/5.9 50/2
HA41-2606 eps
187.5/7.4 375/14.8
14 x 28/
0.6 x 1.1
60/2.4
18/0.7 232/9.1
630/24.8
1000/39.4
850/33.5
58/
2.3
1000/39.4
850/33.5
385/15.2 80 20
3.1 0.8
110/4.3 385/15.2
3 Floor opening for high-voltage cables and,
where applicable, control cables
1000/39.4
850/33.5
385/15.2 80 20
3.1 0.8
150/5.9 50/2
HA41-2602 eps
HA41-2604 eps
60/2.4
58/2.3
58/
2.3
6
1000/39.4
850/33.5
857/33.7
2 Fixing frame (base)
of an individual panel or panel block
BG1
BR1
60/2.4
150/5.9 50/2
60/2.4
1000/39.4
850/33.5
1 Wall distance
28 x 14/
1.1 x 0.6
60/2.4
14 x 28/
0.6 x 1.1
Panel
type
857/33.7
18/0.7 169.5/6.7 375/14.8
630/24.8
1000/39.4
850/33.5
MC3
58/
2.3
60/2.4
Panel
type
28 x 14/
1.1 x 0.6
58/2.3
187.5/7.4 375/14.8
110/4.3 385/15.2
60/2.4
58/2.3
857/33.7
630/24.8
Panel
type
750/29.5
14 x 28/
0.6 x 1.1
750/29.5
385/15.2 80 20
3.1 0.8
150/5.9 50/2
5
58/2.3
385/15.2 80 20
3.1 0.8
150/5.9 50/2
150/5.9 50/2
385/15.2 80 20
3.1 0.8
60/2.4
187.5/7.4
18/0.7 169.5/6.7
6
FS3
FU3
18/0.7 169.5/6.7 375/14.8
110/4.3 385/15.2
3
4
187.5/7.4 375/14.8
58/
2.3
1
2
CS2
FS2
FU2
CC2
CG2
28 x 14/
1.1 x 0.6
380/15
14 x 28/
0.6 x 1.1
500/19.7
Panel
type
750/29.5
110/4.3 385/15.2
HA41-2605 eps
5
HA41-2607 eps
For panel width 750 mm/29.5"
3
4
250/9.8
18/0.7 232/9.1
60/2.4
6
14 x 28/
0.6 x 1.1
58/
2.3
1
2
255/10
500/19.7
110/4.3 385/15.2
5
HA41-2603 eps
For panel width 500 mm/19.7"
3
4
CS1
FS1
FU1
CC1
CG1
28 x 14/
1.1 x 0.6
18/0.7 169.5/6.7
60/2.4
Panel
type
1000/39.4
850/33.5
58/
2.3
1
2
187.5/7.4
375/14.8
14 x 28/
0.6 x 1.1
857/33.7
150/5.9 50/2
5
385/15.2 80 20
3.1 0.8
3
4
375/14.8
110/4.3 385/15.2
2
HA41-2601 eps
For panel width 375 mm/14.8"
1
28 x 14/
1.1 x 0.6
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 39
Standards
Standards, specifications, guidelines
Overview of standards
Table – Insulating capacity
SIMOSEC ANSI switchgear complies with the following relevant standards and specifications as applicable:
Rated voltage (rms value)
Insulating capacity
kV
8.25
15
27.6
Rated short-duration (1 minute) power-frequency withstand voltage (rms value)
• ANSI/IEEE Std. C37.20.3-2001
– Across isolating distances
– Between phases and to ground
kV
kV
39.6
36
39.6
36
66
60
• ANSI/IEEE Std. C37.20.4-2001
Rated lightning impulse withstand voltage (peak value)
• ANSI/IEEE Std. C37.57-2003
– Across isolating distances
kV
105
105
138
• ANSI/IEEE Std. C37.58-2003
– Between phases and to ground
kV
95
95
125
• EEMAC G11-1
(measurement of Corona)
• IEC 62 271-105
Third-party listing
SIMOSEC ANSI is available for
most configurations with UL
or C-UL listing.
For site altitudes
above 1000 m/
3281 ft, the altitude correction
factor Ka is recommended, depending on the actual
site altitude above
sea level.
1.30
1.20
1.00
1000/ 1500/
3281 4921
SIMOSEC ANSI switchgear can
be used as an indoor installation in accordance with NEC
(NFPA70)
service locations at places
which are not accessible to
the public. Enclosures of
switchgear can only be
removed with tools.
m=1
A
1.40
1.10
Type of service location
• Outside lockable electrical
Ka
1.50
HA40-2037a am eps
• CSA C22.2 No. 31-04
Altitude correction factor Ka
Altitude correction factor
• CSA C22.2 No. 193-M 1983
2000/
6562
2500/
8202
3000/
9842
3500/ 4000/
11483 13123
Site altitude in m/ft above sea level
to sea level and to normal
atmospheric conditions
14.7 PSI, 68 °F, 0.00068 lb/ft3
humidity in accordance with
IEC 60 071/VDE 0111 and
ANSI/IEEE.
• The insulating capacity
decreases with increasing
altitude.
For site altitudes above
1000 m/3281 ft (above sea
level) the standards do not
provide any guidelines for the
insulation rating. Instead,
special regulations apply to
these altitudes.
Site altitude
• As the altitude increases, the
Rated short-duration power-frequency withstand voltage to be selected
W Rated short-duration power-frequency withstand voltage · Ka
insulating capacity of insulation in air decreases due to
the decreasing air density.
• For site altitudes above
Rated lightning impulse withstand voltage to be selected
W Rated lightning impulse withstand voltage · Ka
• Inside lockable electrical
service locations. A lockable
electrical service location is
a place outdoors or indoors
that is reserved exclusively
for housing electrical equipment and which is kept under lock and key. Access is restricted to authorized personnel and persons who have
been properly instructed in
electrical engineering.
Untrained or unskilled persons may only enter under
the supervision of authorized
personnel or properly instructed persons.
fied by testing the switchgear
with rated values of shortduration power-frequency
withstand voltage and lightning impulse withstand voltage according to IEC 60 694/
VDE 0670-1000 and
ANSI/IEEE C37.20.3.
• The rated values are referred
• ANSI/IEEE Std. 1247-2005
• ANSI/IEEE Std. C37.22-1997
• The insulating capacity is veri-
Example:
Result:
3000 m/9842 ft site altitude above sea level
15 kV switchgear rated voltage
95.0 kV rated lightning impulse withstand voltage
According to the above
table, a switchgear for a
rated voltage of 27.6 kV is
to be selected.
1000 m/3281 ft a higher
insulation level must be
selected. This results from
the multiplication of the
rated insulation level for
0 mm/0 ft to 1000 m/3281 ft
(above sea level) with altitude correction factor Ka.
Rated lightning impulse withstand voltage
to be selected 95 kV · 1.28 = 122 kV
Terms
• “Make-proof grounding
switches” are grounding
switches with short-circuit
making capacity according to
IEC 62 271-102
• Switch-disconnector corre-
sponds to interrupter switch
• HV CL are high-voltage
current limiting fuse links
40 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
Standards
Standards, specifications, guidelines
Cable testing
• For cable testing
– the installation and
operating instructions of
the switchgear
– the information on manufacturer-dependent cable
sealing ends
– the cable version
(e.g. paper-insulated massimpregnated cables, PVC
cables or XLPE cables)
must be observed.
• For switch-disconnector
feeders
• DC voltage test
before the test:
Remove or disconnect any
voltage transformers at the
cable connection in SIMOSEC
ANSI switchgear.
SIMOSEC ANSI switchgear
for rated voltages up to
27.6 kV can be subjected to
cable tests at a max. DC test
voltage of 70 kV. The voltage
at the busbar may be 27.6 kV
in this case.
Test voltages:
VLF* test voltage
cosine-rectangular
waveform rms
(peak) voltage
VLF* test voltage
sinusoidal
waveform rms
(peak) voltage
Rated voltage
of switchgear
DC test voltage,
maximum value
kV
15
kV
55
kV
kV
22 (22)
16 (22)
27.6
72
33 (33)
23 (33)
Aseismic capacity (optional)
Switchgear color
SIMOSEC ANSI switchgear can
be upgraded for regions at risk
from earthquake.
Light grey No. 61
according to ASTM D1535 97
(Munsell notation
8.3 G6.10/0.54)
For upgrading, earthquake
qualification testing has been
carried out in accordance with
the following standards as
applicable:
– IEC 60 068-3-3, 1993
– IEC 60 068-2-6, 1195
– IABG TA13-TM-002/98
(guide)
– NFPA 5000 and IBC Level
Seismic Simulation
Within the range of the prevailing earthquake frequencies
from 1 to 35 Hz, the required
response spectrum to IBC
200 % and 300 % covers the
following response spectra:
– Uniform Building Code zone 4
– Seismic Requirements
Spec. 9067; Department of
Water & Power, Los Angeles
– GTS-1.1013 ENDES, Chile
– VDE 0670-111
– IABG TA13-TM-002/98
category 2
• Metal enclosure of switching
Climate and ambient
conditions
SIMOSEC ANSI switchgear may
be used, subject to possible additional measures – e.g. panel
heaters or floor covers –
under the following ambient
conditions and operating
temperatures:
• Ambient conditions
– Natural foreign materials
– Chemically active pollutants
– Small animals
• Operating temperatures
The operating temperatures
are classified according to
ANSI/IEEE C37.20.3
SIMOSEC ANSI switchgear is
largely insensitive to climate
and ambient conditions by
virtue of the following features:
• No cross insulation for
isolating distances between
phases
* VLF = Very Low Frequency.
Refer to IEEE Standard 400.2-2004
“IEEE Guide for Field Testing of
Shielded Power Cable Systems
Using Very Low Frequency (VLF)”.
For cosine-rectangular waveform,
the rms value is taken as equal to
the peak value. For sinusoidal
waveform, the rms value is 0.707
times the peak value, if distortion is
less than 5 %.
devices (e.g. three-position
switch) in gas-filled stainlesssteel switchgear vessel
• Dry-type bearings in
operating mechanism
• Essential parts of the operat-
ing mechanism made of
corrosion-proof materials
• Use of climate-independent
cable-type current transformers
• All contacts (switch discon-
nector and make-proof
grounding switch) are maintenance-free
• Joints of the energized
copper bars are silver plated
• Under indoor operating
conditions, SIMOSEC ANSI
requires low maintenance
Protection against solid
foreign bodies, electric shock
and ingress of water
SIMOSEC ANSI switchgear
fulfills acc. to the standards
ANSI/IEEE C37.20.3 the
following type of protection:
All openings in the enclosure
prevent the entrance of a rod
with a diameter of 3.2 mm/
0.13 inch.
Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008 41
Responsible for
Technical contents:
Siemens AG, Dept. PTD M 2 PPM
Erlangen, Germany
General editing:
Siemens AG, Dept. E CC MCC R
Erlangen, Germany
42 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable · Siemens HA 41.31 · 2008
All statements, technical information and recommendations
contained herein are based on information and tests we
believe to be reliable. The accuracy hereof is not guaranteed.
Since conditions of use are outside our control, the user should
determine the suitability of the product for its intended use and
assumes all risk and liability whatsoever in connection herewith.