Retail Interior Finish Code Compliance Brickell City Centre SLS CONSULTING,INC. 1825 PONCE DE LEON BLVD #565 CORAL GABLES,FL 33134 TEL: 786-528-7611 FAX: 305-441-6622 www.slsfi re.com October 29, 2013 VIA EMAIL Ms. Garciela Escalante Project Manager Swire Properties 1779 Brickell Plz., Suite 802 Miami, Florida 33131 INTERIOR FINISH CODE COMPLIANCE REQUIREMENTS BRICKELL CITYCENTRE - MIAMI, FLORIDA Dear Grace: SLS Consulting, Inc. (SLS) has prepared this letter for Swire Properties and the Brickell CityCentre project team in order to outline the required fire testing requirements associated with furniture, fabrics, equipment and interior finishes within the three (3) Brickell CityCentre blocks currently under construction (i.e. BCCW, BCCE and BCCN). The intent of this letter is to assist the project team in proactively identifying the minimum performance criteria and associated testing that will need to be either demonstrated or completed as part of the project's certificate of occupancy process. The interior finishes are required to comply with the requirements outlined in the 2007 Florida Prevention Code (FFPC), which is an amended version of the 2006 Edition of NFPA 1, Uniform Fire Code and 101, Life Safety Code (FFPC). This letter has been structured to outline the applicable interior finish code compliance requirements and to summarize the associated testing required in order to determine the fire performance of interior finished (e.g. flame spread, smoke developed ratings, heat release rates, specimens sizes, etc.). It is recommended that SLS Consulting , Inc. serve a third-party fire protection engineer responsible for reviewing all submittals of the FF&E book(s) for the project.