INSTALLATION MANUAL HORIZONTAL AND VERTICAL AIRSIDE ECONOMIZERS MODELS: D*SK & D*HH CONTENTS INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 COMPONENT LAYOUT . . . . . . . . . . . . . . . . . . . . . . . 4 DIMENSIONAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . 7 AIRFLOW CONFIGURATION. . . . . . . . . . . . . . . . . . . 9 SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . 12 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . 14 See following pages for a complete Table of Contents. NOTES, CAUTIONS AND WARNINGS The installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly. CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT. SAVE THIS MANUAL 036-21553-001-A-1203 036-21553-001-A-1203 TABLE OF CONTENTS INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Horizontal Economizers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Vertical Economizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 LIST OF FIGURES Fig. # 1 HORIZONTAL AIRSIDE ECONOMIZER 2 - 15 TON FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 HORIZONTAL AIRSIDE ECONOMIZER 2 - 15 TON FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3 VERTICAL AIRSIDE ECONOMIZER 3 - 25 TON FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Modulating Economizer with Electro - Mechanical Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 4 ECONOMIZER MIXING BOX VERTICAL AIR COOLED (VERTICAL RETURN/OUTSIDE AIR) . . . . . . . . . . . . . . 7 Powering the Thermostat (24vac) . . . . . . . . . . . . . . . . . . 12 5 ECONOMIZER MIXING BOX HORIZONTAL AIR COOLED (HORIZONTAL RETURN/OUTSIDE AIR) . . . 8 6 VERTICAL ECONOMIZERS - DAMPER AND ACTUATOR SETUP (FIG 1 AND 2) . . . . . . . . . . . . . . . . . . . . . . 9 7 HORIZONTAL ECONOMIZERS - DAMPER AND ACTUATOR SETUP (FIG 3 AND 4) . . . . . . . . . . . . . . . . . . . . . 10 8 HORIZONTAL ECONOMIZER - DAMPER AND ACTUATOR SETUP (FIG 5 AND 6) . . . . . . . . . . . . . . . . . . . . . 11 9 INTERCONNECTION DIAGRAM AIR SIDE ECONOMIZER, 3 - 20 TON T7300 PROGRAMMABLE THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 COMPONENT LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 DIMENSIONAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 AIRFLOW CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . 9 SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . 12 Powering the W7215 (24vac) . . . . . . . . . . . . . . . . . . . . . . 12 Night Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 High Enthalpy Sequence: . . . . . . . . . . . . . . . . . . . . . . . . . 12 Low Enthalpy Sequence: . . . . . . . . . . . . . . . . . . . . . . . . . 12 Damper Modulation: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Modulating Economizer with T7300 Thermostat . . . . . . . . . 13 Powering the W7215 (24vac) . . . . . . . . . . . . . . . . . . . . . . 13 Night Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 High Enthalpy Sequence: . . . . . . . . . . . . . . . . . . . . . . . . . 13 Low Enthalpy Sequence: . . . . . . . . . . . . . . . . . . . . . . . . . 13 Damper Modulation: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2 Pg. # 10 INTERCONNECTION DIAGRAM AIR SIDE ECONOMIZER, 3 - 20 TON T7300 ELECTRO-MECHANICAL THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 11 INTERCONNECTION DIAGRAM AIR SIDE ECONOMIZER, 25 TON T7300 PROGRAMMABLE THERMOSTAT - 3 STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Unitary Products Group 036-21553-001-A-1203 INSTALLATION HORIZONTAL ECONOMIZERS 1. Attach mixing box to unit evaporator return, using the flanges provided. This is intended to connect the units, and not to support the full weight of the economizer mixing box – EXTRA FIELD SUPPORT IS REQUIRED. This may be from the ceiling, or from beneath the unit. 2. Determine which inlet will be outside air, and which will be return air. If the normal open/closed position of the dampers needs to be reversed, remove the actuators, reset the damper positions so that the outside air damper is closed and the return air damper is open, and reattach the actuators so that they are rotating in the appropriate direction. 3. Mount the W7215 module and protective casing on the free side of the mixing box, using the brackets provided. For units between 8 and 15 tons, the module may be mounted between the economizer mixing box and the evaporator discharge ductwork on the air handler itself. 4. The module is connected to the unit wiring via wiring harness. Connect the thermostat wiring as indicated in the Installation Instruction for Ceiling Mounted Ducted Air Conditioners. 5. With the power to the module, the actuator springs will wind and lock. The enthalpy changeover setting may be altered, and the minimum outside air damper position set. See the attached Honeywell information for details. VERTICAL ECONOMIZERS 1. Attach mixing box to unit evaporator return, using the metal securing strip provided. Fasteners may also be used around the perimeter of the mixing box, at the location of the filter frame, for additional security. This is intended to connect the units, and not to support the full weight of the economizer mixing box – EXTRA FIELD SUPPORT IS REQUIRED. This may be from the ceiling, or from beneath the unit. Unitary Products Group 2. Determine which inlet will be outside air, and which will be return air. If the normal open/closed position of the dampers needs to be reversed, remove the actuator, reset the damper positions so that the outside air damper is closed and the return air damper is fully open. Adjust the linkage rod to these normal positions, and secure. Reattach the actuator so that it is rotating in the appropriate direction. 3. The module is connected to the unit wiring via wiring harness. The harness is connected at the plug located on the corner post of the air conditioning unit. Connect the thermostat wiring as indicated in the Installation Instruction for Vertical Air Conditioners. 4. With the power to the module, the actuator springs will wind and lock. The enthalpy changeover setting may be altered, and the minimum outside air damper position set. See the attached Honeywell information for details. Prior to installing or servicing the unit, lock all electrical power supply switches in the off position. Failure to disconnect power supply may result in electrical shock or even death. Additional field support of the mixing box is required. Failure to provide adequate support for the unit may result in injury or even death. Exercise care when working around the sharp metal edges of door panels or flanges. These edges are sharp and can cause injury. 3 036-21553-001-A-1203 COMPONENT LAYOUT FIGURE 1 - HORIZONTAL AIRSIDE ECONOMIZER 2 - 15 TON FEATURES 4 Unitary Products Group 036-21553-001-A-1203 FIGURE 2 - HORIZONTAL AIRSIDE ECONOMIZER 2 - 15 TON FEATURES Unitary Products Group 5 036-21553-001-A-1203 FIGURE 3 - VERTICAL AIRSIDE ECONOMIZER 3 - 25 TON FEATURES 6 Unitary Products Group 036-21553-001-A-1203 DIMENSIONAL DATA Vertical Unit Model Number Economizer Model Number WEIGHT/ LBS. A B C D E F G 15.00 DSK 036-060 2EE04704024 122 36.00 24.00 24.00 31.00 14.00 8.00 DSK 096-120 2EE04704124 192 49.50 28.00 26.50 44.00 19.50 8.00 15.00 DSK 144 2EE04704224 216 59.25 29.00 26.50 54.00 19.50 8.00 15.00 DSK 180 2EE04704324 238 69.25 29.00 26.50 64.00 19.50 8.00 15.00 DSK 240 2EE04704424 306 75.00 40.25 32.00 69.00 25.00 8.00 15.00 DSK 300 2EE04704524 310 78.00 40.25 32.00 69.00 25.00 8.00 15.00 FIGURE 4 - ECONOMIZER MIXING BOX VERTICAL AIR COOLED (VERTICAL RETURN/OUTSIDE AIR) Unitary Products Group 7 036-21553-001-A-1203 Vertical Unit Model Number Economizer Model Number WEIGHT/ LBS. A B C D E F G DHH 024-036 DHH 048-060 2EE04704624 74 22.63 18.25 22.63 17.00 14.00 8.00 15.00 2EE04704724 102 29.63 20.25 29.63 24.00 14.00 8.00 15.00 DHH 096-120 2EE04704824 137 33.63 25.25 33.63 28.00 19.50 8.00 15.00 DHH 144-180 2EE04704924 176 41.63 27.25 41.63 36.00 23.00 8.00 15.00 FIGURE 5 - ECONOMIZER MIXING BOX HORIZONTAL AIR COOLED (HORIZONTAL RETURN/OUTSIDE AIR) 8 Unitary Products Group 036-21553-001-A-1203 AIRFLOW CONFIGURATION FIGURE 6 - VERTICAL ECONOMIZERS - DAMPER AND ACTUATOR SETUP (FIG 1 AND 2) Unitary Products Group 9 036-21553-001-A-1203 FIGURE 7 - HORIZONTAL ECONOMIZERS - DAMPER AND ACTUATOR SETUP (FIG 3 AND 4) 10 Unitary Products Group 036-21553-001-A-1203 FIGURE 8 - HORIZONTAL ECONOMIZER - DAMPER AND ACTUATOR SETUP (FIG 5 AND 6) Unitary Products Group 11 036-21553-001-A-1203 SEQUENCE OF OPERATION MODULATING ECONOMIZER WITH ELECTRO MECHANICAL THERMOSTAT The Honeywell W7215 module, ML series actuators, York damper sections and wiring harness comprise an integrated economizer. Economizers are used to provide ventilation and free cooling for the York series of vertical and horizontal through the wall air handlers. The Honeywell W7215 accepts inputs from a room thermostat, outdoor and return air enthalpy sensors a discharge air sensor as well as an optional CO2 sensor. Additional contact inputs and outputs are available on the module to enable a variety of ventilation strategies; through the activation of supply and exhaust fans. Powering the Thermostat (24vac). Power to the electromechanical thermostat is provided from R terminal of the York unit’s low voltage terminal strip. Electromechanical thermostats do not require a 24 vac common connection. Powering the W7215 (24vac). The W7215 is designed to be powered from the York air handler when the fan of the air handler is operating. To ensure that the W7215 is powered the fan switch on the thermostat subbase should be left on at all times. In this way the economizer will be powered from the G terminal on the thermostat. When the outside air enthalpy exceeds the enthalpy setpoint on the W7215 the NO contacts of relays 1K and 2K close. First Stage Cooling: A cooling signal from the thermostat Y1, first stage cooling is routed through NO contact 1K to engage the first compressor of the York unit. Second Stage Cooling: A second call for cooling Y2 is routed through the NO contact 2K to engage the second compressor. During this sequence the outside dampers are held at a preset minimum position. The minimum may be overridden from a remote potentiometer. Low Enthalpy Sequence: To prevent operation of mechanical cooling at low temperatures during the economizer cycle, a low ambient outdoor thermostat LL-1 can be installed if desired. The contacts are connected to TB-3. If the outdoor temperature is below the set point of LL-1, and the N.O. FREE COOLING contacts of the W7215 are closed, 24 vac will be supplied to the holding coil of R3 opening their NC contacts so that mechanical cooling will be disabled. First Stage Cooling: During the low enthalpy sequence relays 1K and 2K are not energized. The first call for cooling Y1 powers relay IS through the NC contact 1K. When IS is powered IS1 closes enabling the discharge sensor C7046 to modulate the outside air and return air damper. Night Operation. Night set back or set up of hvac equipment utilizing electromechanical thermostats requires two thermostats one each for day and night set points. Switching between thermostats is accomplished utilizing a time clock and switching relay. Typically the outside air dampers are held closed during night time operation. Contacts SD1 and SD2 of the W7215 will maintain the dampers in the closed position when jumpered. Contacts SD1 and SD2 are wired through the economizer wiring harness to terminals A1 and A2 located on the low voltage terminal strip. Do not provide 24 vac to these terminals. High Enthalpy Sequence: 12 Second Stage Cooling: A second call for cooling Y2 is routed through the NC contact 2K of the W7215 to energize the first compressor. Damper Modulation: On York units as well as most rooftop hvac units the C7046 should be located in the discharge air duct. Because of short duct runs effective sensing and control of the mixed air temperature is not possible. Locating the sensor in the discharge air provides effective sensing and control. The outside air damper remains at minimum position if the discharge air temperature is below 50° F or 10° C. If the discharge air temperature is between 50° to 56° F or 10° to 13.3° C the outside air damper will not modulate. Above 56° F or 10° C the dampers will modulate. Unitary Products Group 036-21553-001-A-1203 MODULATING ECONOMIZER WITH T7300 THERMOSTAT The Honeywell W7215 module, ML series actuators, York damper sections and wiring harness comprise an integrated economizer. Economizers are used to provide ventilation and free cooling for the York series of vertical and horizontal through the wall air handlers. The Honeywell W7215 accepts inputs from a room thermostat, outdoor and return air enthalpy sensors, a discharge air sensor, as well as an optional CO2 sensor. Additional contact inputs and outputs are available on the module to enable a variety of ventilation strategies; through the activation of supply and exhaust fans. R4 and the NC contact of R3 (4-5) to the third compressor. During this sequence the outside dampers are held at a preset minimum position. The minimum may be overridden from a remote potentiometer. Low Enthalpy Sequence: To prevent operation of mechanical cooling at low temperatures during the economizer cycle, a low ambient outdoor thermostat LL-1 can be installed if desired. The contacts are connected to TB-3. If the outdoor temperature is below the set point of LL-1, and the N.O. FREE COOLING contacts of the W7215 are closed, 24 vac will be supplied to the holding coil of R3 opening the NC contacts so that mechanical cooling will be disabled. Powering the W7215 (24vac). The W7215 is designed to be powered from the York air handler when the fan of the air handler is operating. To ensure that the W7215 is powered the fan operation mode should be left in the T7300 default setting. In this way the economizer will be powered from the G terminal on the thermostat. Night Operation. The blower operates continuously during occupied periods and intermittently during unoccupied periods. Since this would cause the economizer to open during unoccupied periods, N.O. contacts A3 and A2 on the T7300 subbase are wired to the air handlers low voltage terminal strip. When contacts A3 and A2 on the thermostat subbase make at night, SD1 and SD2 are effectively jumpered and the outside dampers of the economizer remain closed during night operation of the blower. First Stage Cooling: During the low enthalpy sequence relays 1K and 2K are not energized. The first call for cooling Y1 powers relay IS through the NC contact 1K. When IS is powered IS1 closes enabling the discharge sensor C7046 to modulate the outside air and return air damper. Second Stage Cooling: A second call for cooling Y2 is routed through the NC contact 2K of the W7215 to energize the first compressor. Third Stage Cooling: Twenty-five ton units only: The holding coil of R4 is energized whenever a low enthalpy condition is sensed by the W7215. The third call for cooling Y3 is routed through the NO contacts of R4 (which are now closed) through the NC contact of R3 (2-1) to terminal 4 of the W7215 and from there to the second compressor. At this time the outside damper will modulate in response to the discharge sensor, Y2 will engage the first compressor and Y3 will engage the second compressor. High Enthalpy Sequence: Damper Modulation: When the outside air enthalpy exceeds the enthalpy setpoint, the NO contacts of relays 1K and 2K close. First Stage Cooling: A cooling signal from the thermostat Y1, first stage cooling is routed through NO contact 1K to engage the first compressor of the York unit. Second Stage Cooling: A second call for cooling Y2 is routed through the NO contact 2K to engage the second compressor. Third Stage Cooling: Twenty-five ton units only: A third call for cooling is routed directly from the thermostat via the wiring harness to through the NC contact of Unitary Products Group On York units as well as most rooftop hvac units the C7046 should be located in the discharge air duct. Because of short duct runs effective sensing and control of the mixed air temperature is not possible. Locating the sensor in the discharge air provides effective sensing and control. The outside air damper remains at minimum position if the discharge air temperature is below 50° F or 10° C. If the discharge air temperature is between 50° to 56° F or 10° to 13.3° C the outside air damper will not modulate. Above 56° F or 10° C the dampers will modulate. 13 036-21553-001-A-1203 WIRING DIAGRAMS FIGURE 9 - INTERCONNECTION DIAGRAM AIR SIDE ECONOMIZER, 3 - 20 TON T7300 PROGRAMMABLE THERMOSTAT 14 Unitary Products Group 036-21553-001-A-1203 FIGURE 10 - INTERCONNECTION DIAGRAM AIR SIDE ECONOMIZER, 3 - 20 TON T7300 ELECTROMECHANICAL THERMOSTAT Unitary Products Group 15 FIGURE 11 - INTERCONNECTION DIAGRAM AIR SIDE ECONOMIZER, 25 TON T7300 PROGRAMMABLE THERMOSTAT - 3 STAGE Subject to change without notice. Printed in U.S.A. Copyright © 2003 by Unitary Products Group. All rights reserved. Unitary Products Group 036-21553-001-A-1203 Supersedes: Nothing 5005 York Drive Norman OK 73069