ETHEKWINI ELECTRICITY Substations: Section 1.3 Medium Voltage Certificate of Compliance Page 1 of 5 FOR OFFICE USE ONLY Application No. Official Date Stamp of EE Meter No. Tariff CERTIFICATE OF COMPLIANCE FOR 11 kV INSTALLATIONS Note: This compliance form shall be submitted to the Clerk of Works or Superintendant prior to energisation of the installation. The form shall be captured by Customer Services and sent to the Chief Technologist: Test Division CONSUMERS DETAILS Consumers name: Consumers address: Description of land: (Lot and Block) Date installation completed: Suburb: Date supply required: ELECTRICAL CONTRACTORS DETAILS Dear Sir/Madam, This is to certify that the work in connection with the electrical installation, additions, alterations, etc., carried out by me/us, is strictly in accordance with the Electricity Supply By-Laws and SANS 10142-2, Item 1 has been supplied to eThekwini Electricity’s Metering Division for wiring and Items 2 and 3 were supplied to the eThekwini Electricity’s Test Division for approval. 1 2 3 Meter panel door Current Transformers (CT’s) Voltage Transformers (VT’s) YES YES YES NO NO NO If NO is indicated for 2 and 3 above, then the original equipment manufacturers test reports shall be attached to this certificate of compliance. Name of Contracting Company: Address: Signature on behalf of Contracting Company Contact Number DETAILS OF MAIN INCOMMING SWITCHGEAR Make of Switch Rated Voltage (kV) Rated short time withstand current (kA) Type of Switch Rated current (A) Rated short power frequency withstand voltage (kV) ETHEKWINI ELECTRICITY Substations: Section 1.3 Medium Voltage Certificate of Compliance Page 2 of 5 DETAILS OF ELECTRICAL PROTECTION AND INSTRUMENT TRANSFORMERS Overcurrent Earth Fault Sensitive Earth Fault Ratio: CT details VT details Protection: If None, indicate how current monitoring is done: Metering: Ratio: Ratio: Class: Burden: Class: Class: Burden: Burden: DETAILS OF CHECK, INSPECTION AND/OR TEST This check, inspection and test shall be carried out by a competent person. Each item on the list shall be checked and if found to be satisfactory a tick (√) shall be used in the YES column, or if found to be unsatisfactory a tick (√) shall be used in the NO column. A tick (√) shall be inserted against items which are not applicable in the NA column. Where an item is ticked in the NO or NA column, reasons shall be stated in the Remarks and Comments section. No. 1.0 1.1 1.2 1.3 2.0 2.1 2.2 2.3 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.6.1 3.6.2 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.14 3.15 Description General inspection Designation of consumer incoming switch correct Cable boxes and glands in order and ready for terminating Meter wiring in accordance with Drawing DL 9631A1 General checks on each Switchgear Panel Paint work on switchgear satisfactory CT information and rating plates inside relay compartment Manufacturer’s rating plate affixed with information Mechanical Checks on each Switchgear Panel (for withdrawable switchgear) Panel bolted down Busbar shutters red Cable shutters yellow Busbar and cable shutter holding device operational Busbar and cable shutter locking facilities functional Position selector easily manipulated “FREE” position easily selected “LOCKED” position easily selected “ISOLATED” indicator on truck and housing Interlock “FREE” indicator on truck “ENGAGED” indicator on truck and housing Cannot close CB with racking handle fitted Cannot close CB with interlocking in “FREE” position Can only close CB with interlock in “LOCKED” position Cannot isolate CB when closed “OFF” position clearly displayed and visible “ON” position clearly displayed and visible YES NO NA ETHEKWINI ELECTRICITY Substations: Section 1.3 No. 3.16 3.16.1 3.16.2 3.16.3 3.16.4 3.16.5 3.16.6 3.17 3.17.1 3.17.2 3.17.3 3.17.4 3.17.5 3.17.6 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.10.1 4.10.2 4.10.3 4.10.4 4.10.5 4.10.6 4.11 4.11.1 4.11.2 4.11.3 4.11.4 4.11.5 5.0 5.1 5.2 Medium Voltage Certificate of Compliance Description Circuit earth Circuit earth position easily selected and indicated Only circuit shutters open for busbar earth position Close CB in circuit earth position CB can be locked off in circuit earth position CB electrical trip inhibited in circuit earth position Open CB via mechanical trip Service position Service position easily selected and indicated Both cables and busbar shutters open for service position Close CB by mechanical lever or push-button Close CB by electrical push-button Open CB by mechanical lever or push button Open CB by electrical push-button Mechanical Checks on each Switchgear Panel (for fixed pattern switchgear) Panel bolted down Position selector easily manipulated “OFF” position clearly displayed and visible "ON" position clearly displayed and visible Can only close with interlock in “LOCKED” position Cannot close with interlock in “FREE” position Close by mechanical lever or push-button Cannot operate isolator when CB is closed Open by mechanical lever or push-button Circuit earth Circuit earth position easily selected and indicated Only circuit shutters open for busbar earth position Close CB in circuit earth position CB can be locked off in circuit earth position CB electrical trip inhibited in circuit earth position Open CB via mechanical trip Service position Service position easily selected and indicated Close CB by mechanical lever or push-button Close CB by electrical push-button Open CB by mechanical lever or push button Open CB by electrical push-button Electrical tests on each Switchgear Panel Circuit Breaker open Circuit Breaker closed Page 3 of 5 YES NO NA ETHEKWINI ELECTRICITY Substations: Section 1.3 6.0 6.1 6.2 6.3 6.4 6.5 7.0 No. Medium Voltage Certificate of Compliance Power frequency voltage withstand test – Test voltage 24kV, duration 1 minute From To Leakage current (mA) Red phase earth White phase earth Blue phase earth Across open point Across other point Earth resistance measurement of installation Description Remarks and Comments Page 4 of 5 ETHEKWINI ELECTRICITY Substations: Section 1.3 To: Medium Voltage Certificate of Compliance Page 5 of 5 eThekwini Municipality Head: Electricity Notice of Completion of Medium Voltage Installation Consumers Name: Consumers Address: Further to the attached notice of completion I hereby certify that: a) All personnel involved have been removed from the above mains/apparatus and have been warned that all relevant equipment is now to be treated as “alive”. b) All earths have been removed. All circuits are isolated and locked in the off position. c) The mains/apparatus is in a safe condition and may be energised from the eThekwini Electricity without further notice. Name: Date: Designation of Person: Signed: The above designated person shall be competent in accordance with Annexure A of SANS 10142-2