Installation Instructions Models CC-5 / CC-2 System Cardcage CC-5 (500-633037 / S24235-B123-A1) System Cardcage CC-2 (500-633440 / S24235-B122-A1) INTRODUCTION The SIEMENS Model CC-5 Cardcage (see Figure 1) has five card slot s and fits in two positions on the Mounting Plate. The SIEMENS Model CC-2 Cardcage (see Figure 2) has two card slot s and fits in one position on the Mounting Plate. The CC-5 and CC-2 are used for mounting all system circuit card assemblies. They each have two removable terminal block connectors at the top and one removable terminal block connector at the bottom of each card slot. All field-wiring connections are made directly to the top of the cardcage while internal power is connected to the bottom of the cardcage. The two removable terminal block connectors at the top of each slot are arranged in two rows. The lower row is labeled 1 through 8 and the upper row is labeled 9 through 16. These removable terminal block connectors are used for connecting power limited external equipment. The removable terminal block connector located at the bottom of each slot is labeled 17 through 24 and is used for connecting internal power. UPPER ROW (9-16) UPPER ROW (9-16) LOWER ROW (1-8) LOWER ROW (1-8) Note: Boards shown without card guides installed. Figure 1 CC-5 Card Cage OPERATION P/N 315-033035-3 A24205-A334-B815 Figure 2 CC-2 Card Cage The CC-5 and CC-2 provide a central point for mounting circuit card assemblies. If a card requires power, it is applied through the removable terminal block at the bottom of the cardcage. All external devices for the card are connected to the card through the two removable terminal blocks at the top of the cardcage. The circuit card assemblies are connected to the HNET and CAN bus through the connectors on the cardcage. Siemens Building Technologies Fire Safety PRE-INSTALLATION The CC-5 and CC-2 are shipped with the card guides removed. The card guides are keyed to assist in installation. They can be installed either before or after the cardcage is installed in the enclosure. For ease of installation, the card guides have been designed to be installed after the field wiring has been completed. Card Guide Installation (Figure 3) The upper and lower card guides are keyed differently and are not interchangeable. Ensure that the card guide keys fit easily into the holes in the motherboard to prevent damage. 1. The upper card guide has a label on each slot that can be used to identify the module installed in the slot. If desired, complete the label before inserting the upper card guide. 2. Insert the upper card guide and secure with the captive screws. 3. Insert the lower card guide and secure with the captive screws. UPPER CARD GUIDE LABELS GUIDE PIN LOWER CARD GUIDE CAPTIVE SCREWS GUIDE PIN HOLE CAPTIVE SCREW RETAINERS Figure 3 Card Guide Installation (CC-5 Shown) INSTALLATION Disconnect BATTERY and AC prior to working on equipment. The CC-5 and CC-2 mount on the Mounting Plate. The Mounting Plate may be located either “IN” or “OUT” of the enclosure to perform this inst allation procedure. If the Mounting Plate is located “IN” the enclosure you will have to gain access to it Siemens Building Technologies Fire Safety 2 P/N 315-033035-3 A24205-A334-B815 by opening the enclosure Inner and Outer doors. If the Mounting Plate is located outside of the enclosure, place it in front of you so that the word “T OP” is at the top and away from you. Each Mounting Plate can hold a maximum of two CC-5 cardcages. There are three possible locations for mounting the CC-5 on the Mounting Plate. 1. Flush left on the Mounting Plate in positions 1-2. 2. In the center of the Mounting Plate in positions 2-3. 3. Flush right on the Mounting Plate in positions 3-4. The CC-2 is most effectively used to add two more card slots in a row that already has one CC-5 and another 1-position module (i.e., PSC-12). It is best inst alled in a position adjacent to the CC-5. In all of the possible mounting locations, the top and bottom of the CC-5 and CC-2 will be flush with the top and bottom of the Mounting Plate. When only one CC-5 cardcage is to be installed, it is normally installed on the left side of the Mounting Plate. There is a top and bottom to the Mounting Plate. The top is where the word “T OP” is stamped on the Mounting Plate. When the cardcage is mounted correctly on the Mounting Plate it will be flush on the top, bottom, and lef t with the Mounting Plate and the two screw holes in the center of the cardcage motherboard will be over threaded post s. Siemens Building Technologies Fire Safety 1. Install four 10-32 scr ews (M5) in the threaded post s at the top lef t of Position 1, top right of Position 2, bottom lef t of Position 1, and the bottom right of Position 2 on the Mounting Plate. Screw each of the 10-32 screws (M5) into the threaded post s 5-6 turns. (Refer to Figure 3.) 2. Place the cardcage over the four screws on the Mounting Plate and slide it down or towards you to rest on the four screws. (Refer to Figure 4.) When the cardcage is in the correct position it will be flush with the top, bottom, and left side of the Mounting Plate. 3. Install the two 10-32 screws (M5) in the center of the cardcage motherboard near the left and right edge. 4. Tighten the six screws. 3 P/N 315-033035-3 A24205-A334-B815 Figure 4 Location Of The CC-5 and CC-2 On The Mounting Plate Figure 5 Mounting The CC-5 and CC-2 On Mounting Plate Siemens Building Technologies Fire Safety 4 P/N 315-033035-3 A24205-A334-B815 WIRING To Connect External Wiring To The Card Slots: At the top and bottom of the CC-5 and CC-2 and adjacent to each card slot are removable terminal blocks. The removable terminal blocks are color-coded to each slot and have a white cover over the top. The wiring to the two terminal block connectors at the top of the CC-5 and CC-2 is power limited. The wiring to the terminal block connector at the bottom of the CC-5 and CC-2 is non-power limited. (Figure 6) 1. On the removable terminal block, open the white cover . 2. Insert the wire to be connected in the desired opening in the side of the removable terminal block. 3. Tighten the appropriate locking screw. WHITE COVER LOCKING SCREWS 1 2 3 4 5 6 7 8 REMOVABLE TERMINAL BLOCK OPENING IN SIDE FOR WIRE CONNECTION Figure 6 Removable Terminal Block On The CC-5 and CC-2 To Connect The Data Bus: The Data bus connectors on the cardcage motherboard are P1 and P2. (Refer to Figure 7.) They are 60 pin, keyed, male connectors with connector extractors. 1. Open the connector ejectors out of the vertical position and away from the connector body. 2. Insert the female cable connector into the male connector (P1 or P2) on the cardcage motherboard. Gently press the cable connector into the motherboard connector. As the cable connector is pressed in, the connector ejectors will begin to move to the vertical position. When the cable connector is fully seated the connector ejectors will be vertical. Use the 60 pin bus cable - long, P/N 500-633997 / C24235-A1-K9 when the PSC-12C/ PSX-12C is located on a different Mounting Plate Siemens Building Technologies Fire Safety 5 P/N 315-033035-3 A24205-A334-B815 To Connect The CAN Bus: The CAN bus (P3) is a six pin connector located just above P1 on the cardcage motherboard. (Refer to Figure 7.) It is used to supply CAN communications and power to the Switch Control Modules (SCM-8S), LED, Fan Control Modules (FCM-6S), Live Voice Microphone Module (LVM) and Firefighters Master Telephone (FMT). The connector is keyed and requires no special instructions for cable connection. Use cable CCL, P/N 500-634214 / C24235-A1-K6 to connect from CAN bus (P3) on CC-5 and CC-2 to the desired module. CAN power must be supplied to E11 (CC-5) or E5 (CC-2) Refer to Figure 8 for wiring det ails. E5 E4 (GR EEN E) (BLU ) J5 ) W LLO (YE E3 E2 (OR AN GE J4 ) P2 J3 ) E1 CONNECTOR EJECTORS IN VERTICAL POSITION J10 J2 (RED -5 P4 P3 J9 CC J1 J8 J7 P1 17 J6 17 60 17 17 17 18 19 20 21 22 23 24 18 19 20 21 22 23 24 18 19 20 21 22 23 24 18 19 20 21 22 23 24 18 19 20 21 22 23 24 T5 SLO T4 SLO T3 SLO T2 SLO T1 SLO Figure 7 Location Of Connectors (CC-5 Shown) Figure 8 Connecting Power For CAN Bus Siemens Building Technologies Fire Safety 6 P/N 315-033035-3 A24205-A334-B815 SPECIFICATIONS Physical Specifications: CC-5 10.58”W x 14.25” H (26.87cm x 36.20cm) CC-2 4.78”W x 14.25”H (12.14cm x 36.20cm) Electrical Ratings: Data CC-2. The given The PSC-12C supplies the power to the two 60-pin bus connectors (P1 and P2) in the CC-5 and total rating on P1 and P2 for all CC-5s in any enclosure is as follows: 24 VDC, 2 Amps max 6.2 VDC, 2 Amps max See PSC-12C Installation Instructions, P/N 315-033060 / A24205-A334-B819 and the PSX-12C Installation Instructions, P/N 315-034050 / A24205-A334-B818, for complete power supply loading calculations. Siemens Building Technologies Fire Safety 7 P/N 315-033035-3 A24205-A334-B815 For CE applications in Cerberus E100 systems refer to Installation Instruction A24205-A334-B844 (English) orA24205-A334-A844 (German). Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. Siemens AG 8 Fernwood Road 2 Kenview Boulevard I BT DE FS SYS Florham Park, New Jersey 07932 Brampton, Ontario L6T 5E4 CN D-81379 München P/N 315-033035-3 A24205-A334-B815