Ganging and Derating Box-Mounted Lighting Controls Ganging is an installation practice where two or more lighting controls are mounted side-by-side using the required number of connected wallboxes. Ganging may require the removal of part of the fins on Architectural Dimmers or part of the mounting strap on strap-mounted devices. In Architectural Dimmers, the metallic fins help dissipate heat from within the device. Strap mounted dimmers use the mounting strap for the same purpose. Therefore, removing a portion of the fins or strap for ganging purposes will require derating the dimmers to prevent them from overheating. Maximum Load Per Dimmer for Multi-Ganging All Strap-Mounted Dimmers Chart 1 Dimmer Rating Single 2-Gang More than 2-Gang 600W 600W 500W 400W 1000W 1000W 800W 700W 600VA 600VA 500VA 400VA 1000VA 1000VA 800VA 700VA Maximum Bulb Wattage for Magnetic Low-Voltage Lighting Ganging and Derating Leviton Lighting Controls When ganging Mural, True Touch, TouchPoint, ToggleTouch and IllumaTech controls, the side sections of the mounting strap must be removed. Use pliers to carefully bend side sections back and forth until they break off. The side sections of the strap dissipate heat, so removing them requires derating the dimmer’s capacity. See Chart 1. Note that Leviton SureSlide and Trimatron lighting controls can be ganged without removing any sections of their mounting straps. However, SureSlide and Trimatron controls must also be derated when they’re ganged. Low-voltage lighting controls are rated in Volt-Amps (VA). The maximum bulb wattage is determined by the efficiency of the transformer in the low-voltage lighting system. Transformer efficiencies vary depending on the manufacturer, so consider 75% efficiency as average. Use Chart 2 to determine the maximum bulb wattage for typical transformer efficiency ratings. Maximum Bulb Wattage at 75% Efficiency Chart 2 Dimmer Rating Single 2-Gang More than 2-Gang 600VA 450VA 375VA 300VA 1000VA 750VA 600VA 525VA Ganging and Derating Leviton Renoir™ and Van Gogh™ Architectural Lighting Controls 6678-1, 6678-7, 6679-1, 6679-7, 61500, 62000, 71511, 71513, 81500, 81500-3, 81527, 82000, 82000-3, 86678-1, 86678-7, 86779-1, 86779-7 6676-1, 6676-7, 6677-1, 6677-7, 60800, 61000, 61000-3, 71111, 71113, 80800, 80800-3, 80827, 81000, 81000-3, 81127, 86676-1, 86676-7, 86777-1, 86777-7 To Double Gang Narrow Controls Break off right set of fins on one dimmer and left side of fins on the other dimmer. Two-gang outlet box is required. To Triple Gang Narrow Controls Break off right set of fins on first dimmer, both sets of fins on center dimmer, and left set of fins on third dimmer. Three-gang box is required. Double-Ganging Wide Controls Break off right set of fins on one dimmer and left set of fins on the other dimmer. Requires threegang outlet box. No derating necessary. Triple Ganging Wide Controls Break off right set of fins on first dimmer, both sets of fins on the middle dimmer, and left set of fins on third dimmer. Five gang outlet is needed. Switch boxes required for ganging Leviton architectural controls when no fins are removed: Switch boxes required for ganging Leviton architectural controls when all inside fins are removed: Number of Narrow Controls* Number of Wide Controls Cat. No’s. FIN BREAKOFF POINTS FOR NARROW CONTROLS 0 0 2 3 4 0 • • • • • 1 1 3 5 7 8 2 4 6 7 9 11 3 7 9 10 11 13 4 9 11 12 14 16 0 0 1 2 3 4 5 6 0 0 1 2 3 4 5 6 1 1 3 4 5 6 7 8 2 3 5 6 7 8 9 10 3 5 7 8 9 10 11 12 4 7 9 10 11 12 13 14 5 9 11 12 13 14 15 16 6 11 13 14 15 16 17 18 *Narrow controls must have fins broken off to be ganged. See ganging instructions for narrow controls on this page. Note: When ganging combinations of small and large controls without removing fin sections, mount small control on one end, large control on the other end. T7 1 Number of Narrow Controls Number of Wide Controls Cat. No’s. FIN BREAKOFF POINTS FOR WIDE CONTROLS When fins are broken off on wide and narrow controls for ganging purposes, the number of switch boxes required can be quickly determined by referring to the two charts below. For example, when ganging a 2000 watt Cat. No. 82000 with a 1000 watt Cat. No. 81000 and no fins are going to be removed, 3 switch boxes will be required as shown in the top chart. Likewise, you can refer to the bottom chart to determine how many switch boxes are required when all inside fins are being removed. To learn more about Leviton’s outstanding offering of devices visit our Website at: http://www.leviton.com Derating Any Architectural Dimmer that has had both sets of break-off fins removed to meet space requirements during installation must have its wattage specification derated as shown in the chart below. If no fins are removed, no derating is necessary, even when ganging. Incandescent Fluorescent Cat. No. Watts Derate To 61000, 81000 1000 800W When ganging these units, no derating is necessary, except as shown below when both sets of fins have been removed. 61500, 81500 1500 1300W 6677 – 16 lamps 86677 – 16 lamps 1800W 6679 – 36 lamps 86679 – 36 lamps 62000, 82000 2000 Ganging and Derating Leviton Monet™ Lighting Controls Multi-Gang Installation No Fins Broken Off CAUTION: Do not gang dimmers vertically (one directly above another). • It is recommended to install dimmers without breaking off fins whenever possible so that derating is not necessary, even when ganging. If an installation requires breaking off fins for space requirements, derating is required. • When ganging combinations of narrow and wide dimmers and ordering a custom wallplate, all narrow dimmers are required to be at one end of the gang, and all wide dimmers are required to be at the other end of the gang. • Adapter plates (Cat. No. MN0LA or MN0SA) available for multi-gang installations using any Leviton Decora®-style device. No Fins Broken Off Table 1 – Outlet Box Requirements Wide Narrow Controls (600W/VA, 1000W/VA, 7.5A) Controls 0 1 2 3 4 5 6 (1500W/VA,10A) 0 1 2 3 4 0 1 4 7 9 1 4 6 9 3 5 8 10 5 7 9 6 8 9 10 10 Fins Broken Off Table 2 – Outlet Box Requirements Wide Narrow Controls (600W/VA, 1000W/VA, 7.5A) Controls 0 1 2 3 4 5 6 7 8 9 (1500W/VA,10A) Refer to Table 1 for the size and number of outlet boxes required for multi-gang installations. A multi-gang masonry box or a multi-gang switch box with a raised cover are recommended for easy installation, although standard outlet boxes will work. No derating is necessary. Example of 5-Gang Outlet box with 3 Narrow Dimmers and No Wide Dimmers (note mounting holes). 0 1 2 3 4 5 0 1 3 5 7 9 1 3 5 7 9 2 4 6 8 10 3 5 7 9 4 6 8 10 5 7 9 6 8 10 7 9 8 10 9 Maximum Load Per Monet Dimmer Multi-Gang with Fins Broken Off Table 3 Fins Broken Off Refer to Table 2 for the size and number of outlet boxes required for multi-gang installations when all inside fins are removed. NOTE: The fins on the dimmers have special break-off points that allow removal of partial fin sections for ganging. Use pliers to carefully bend fin sides back and forth until they break off. (See Figure 2). These sections should only be removed at the break-off point to permit proper ventilation. DO NOT remove side sections on extreme ends of the gang. Example of 3-Gang Outlet box with 3 Narrow Dimmers and No Wide Dimmers (note mounting holes). Cat. No. Single 2-Gang More than 2-Gang MNI06 600W 500W 400W MNI10 1000W 800W 700W MNI15 1500W 1250W 1000W MNM06 600VA 500VA 400VA MNM10 1000VA 800VA 700VA MNM15 1500VA 1250VA 1000VA MNX10 1000VA 800VA 700VA MNF07 7.5A 6A 5.3A MNF10 10A 8A 7A Break-Off Fins (Side Sections) Light Bar Slider Mounting Strap Figure 1 – Dimmer Function For answers to technical questions, call Leviton’s Techline at 1-800-824-3005 Figure 2 – Break-Off Fin Removal T8 Ordering Monet™ Multi-Gang Wallplates No Fins Broken Off Table 1 – Outlet Box Requirements Wide Narrow Controls (600W/VA, 1000W/VA, 7.5A) Controls 0 1 2 3 4 5 6 (1500W/VA,10A) 0 1 2 3 4 0 1 4 7 9 1 4 6 9 3 5 8 10 5 7 9 6 8 9 10 10 Monet™ Multi-Gang Wallplates for Installations with No Fins Broken Off Fins Broken Off Table 2 – Outlet Box Requirements Wide Narrow Controls (600W/VA, 1000W/VA, 7.5A) Controls 0 1 2 3 4 5 6 7 8 9 (1500W/VA,10A) 0 1 2 3 4 5 0 1 3 5 7 9 The second digit represents the number of large-fin devices in the combination: MNW24 = 4 large-fin Monet Dimmers In the suffix, FB indicates that fins have been broken off: MNW24-FB = Fins Broken Off The last letter in the suffix indicates the color of the wallplate: MNW24-FBE = Black wallplate 1 3 5 7 9 2 4 6 8 10 3 5 7 9 4 6 8 10 5 7 9 6 8 10 7 9 8 10 9 Monet multi-gang wallplates are available for every permissible combination of small fin and large fin dimmers. Tables 1 and 2 can be used to determine if a specific combination of devices is possible. When small and large fin devices are combined, all the large fin devices must be placed to one side and all the small fin devices must be placed to the other side. In an installation where all the fins are broken off, do not remove the fins from the dimmers at each of the extreme ends of the installation. Monet multi-gang wallplates are ordered using the following catalog number system. Example: Cat. No. MNW31-00W MNW = Monet Wallplate The first digit represents the number of small-fin devices in the combination: MNW3 = 3 small-fin Monet Dimmers The second digit represents the number of Large Fin devices in the combination: MNW31 = 1 large-fin Monet Dimmer In the suffix, the double-zero indicates that no fins have been removed: MNW31-00 = No fins removed The last letter in the suffix indicates the color of the wallplate: MNW31-00W = White wallplate Multi-gang wallplates ar available in the following colors (add letter to suffix as indicated): Ivory (-I), White (-W), Almond (-A), Gray (-G), Black (-E) and Brown (-B). Catalog Number (Add suffix to indicate color): Ivory (-I), White (-W), Almond (-A), Gray (-G), Black (-E) and Brown (-B). MNW10-00 MNW20-00 MNW30-00 MNW40-00 MNW50-00 MNW60-00 MNW01-00 MNW02-00 MNW03-00 MNW04-00 MNW11-00 MNW21-00 MNW31-00 MNW41-00 MNW51-00 MNW12-00 MNW22-00 MNW13-00 MNW32-00 MNW23-00 Monet™ Multi-Gang Wallplates for Installations with Fins Broken Off Catalog Number (Add suffix to indicate color): Ivory (-I), White (-W), Almond (-A), Gray (-G), Black (-E) and Brown (-B). MNW20-FB MNW30-FB MNW40-FB MNW50-FB MNW60-FB MNW70-FB MNW80-FB MNW90-FB MNW11-FB MNW21-FB MNW31-FB MNW41-FB MNW51-FB MNW61-FB MNW71-FB MNW81-FB MNW02-FB MNW12-FB MNW22-FB MNW32-FB MNW42-FB MNW52-FB MNW62-FB MNW03-FB MNW13-FB MNW23-FB MNW33-FB MNW43-FB MNW04-FB MNW14-FB MNW24-FB MNW05-FB An example of ordering Monet multi-gang wallplates when fins are broken off. Example: Cat. No. MNW24-FBE MNW = Monet Wallplate The first digit represents the number of small-fin devices in the combination: MNW2 = 2 small-fin Monet Dimmers T9 To learn more about Leviton’s outstanding offering of devices visit our Website at: http://www.leviton.com