Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 4, Number 6 (2014), pp. 645-654 © Research India Publications http://www.ripublication.com/aeee.htm Voltage Sag Compensation Using Dynamic Voltage Restorer Mayank Paliwal, Rohit Chandra Verma and Shaurya Rastogi Department of Electronics, Electrical & Communication Engineering Galgotias University. Abstract This paper presents the modeling and simulation of a dynamic voltage restorer as a voltage sag mitigation device in electrical power distribution networks. The dynamic voltage restorer with its excellent dynamic capabilities, when installed between the supply and a critical load feeder, can compensate for voltage sags/swells, restoring line voltage to its nominal value within few milliseconds and hence avoiding any power disruption to the load. In this paper the technical aspect feasibility related to the use dynamic voltage restorer (DVR) of traditional DC storage systems are evaluated. This topology would ensure a constant DC voltage across the DC link during the process of voltage compensation. The modeling of dynamic voltage restorer is carried out component wise and their performances are analyzed using MATLAB software. The simulation results shows that the control technique is very effective and yields excellent compensation for voltage sag Mitigation. Keywords: Power Quality, Dynamic Voltage Restorer (DVR), Operating States. 1. Introduction In the early days of power transmission voltage deviation during load changes, power transfer limitation was observed due to reactive power unbalances. Modern power systems are complex networks, where hundreds of generating stations and thousand of load centers are interconnected through long power transmission and distribution networks. The main concern of customer is the quality and reliability of power supply at various load centers. Even though power generation in most well-developed countries is fairly reliable, the quality of supply is not. Power distribution system should ideally provide their customers an uninterrupted flow of energy with smooth 646 Mayank Paliwal et al sinusoidal voltage at the contracted magnitude and frequency. However, in practice power system especially the distribution system, have numerous non linear loads, which are significantly affect the quality of power supply. As a result, the purity of waveform of supply lost. This ends up producing many power quality problems. To improve power quality, custom power devices are used. In 1995 the concept of custom power is first explained by Hingorani[1]. The thought of custom power (CP) identifies with the utilization of electronic controllers for power system network. There are number of custom power units which are given below, Distribution Statcom (DSTATCOM), Dynamic Voltage Restorer (DVR), Unified power quality conditioner (UPQC), Active Power Filters, Battery Systems (BESS), Distribution Series Capacitors (DSC), Surge Arresters (SA), Un-interruptible Power Supplies (UPS), Solid State Fault Current Limiter (SSFCL), Solid-State Transfer Switches (SSTS), and Static Electronic Tap Changers (SETC)[2]. Dynamic Voltage Restoration (DVR) is a method and apparatus used to sustain, or restore, an operational electric load during sags, or spikes, in voltage supply. DVRs are a class of custom power devices for providing reliable distribution power quality. They employ a series of voltage boost technology using solid state switches for compensating sags/swells. 2. Power Circuits of DVR The power circuit of the DVR shown in Fig. 1 can be divided into four parts: a) Voltage source inverter (VSR) b) Three single-phase injection transformers c) Passive filters d) Energy storage. 2.1 Voltage Source Inverter (VSR) This may be 3-phase 3-wire VSI or 3-phase 4-wire VSI. The inverter rating is relatively low in voltage and high in current due to the use of step-up injection transformers. There is generally no need for extensive multilevel structures seen in Flexible AC Transmission system (FACTS). The most common inverter connections use either a three-level inverter or a conventional three-phase Graetz bridge inverter. 2.2 Injection Transformers The three single-phase transformers can be connected to the distribution line with star/open star winding or delta/open star winding. The star/open star winding allows the injection of positive, negative and zero sequence voltages whereas the delta/open winding only allows the injection of positive and negative sequence voltages. However, the delta/open star winding maximizes the use of dc link voltage when compared to the star-open winding. The choice of injection transformer winding greatly depends on the manner in which the distribution line 132kV- 11 kV step down transformer is connected. If a A-Y with the neutral grounded is used, zero-sequence voltages and 11kV/O.415kV harmonics will not propagate through the transformer when unbalanced faults occur on the high voltage network. Therefore, there is no need to compensate for zero sequence voltages. However, this is not the case when a Y-Y with the neutral grounded connection is used. Hence, the choice of injection Voltage Sag Compensation Using Dynamic Voltage Restorer 647 transformer winding and the control algorithm adopted are dependent on the step-down transformer winding in the distribution system. Moreover, to avoid saturation under all conditions, the injection transformer must be sized to handle at least twice the normal steady-state flux requirement at maximum rms. Injection voltage, without saturation. Fig. 1: a) Equivalent electrical circuit diagram of the DVR Fig. 1: b) Block Diagram of General DVR 2.3 Passive Filters The filtering scheme in the dynamic voltage restorer can be placed either on the highvoltage-side or the inverter side of the series injection transformer. The advantage of the inverter-side filter is that it is on the low-voltage side of the series transformer and is closer to the harmonic source. Using this scheme, the high-order harmonic currents will be prevented from penetrating into the series transformer thus reducing the voltage stress on the transformer. However, when the DVR acts as a source the introduction of the filter inductor L causes voltage drop and a phase-angle shift in the fundamental component of the inverter output. This can affect the control scheme of the DVR. As the filter is located on the high-voltage side of the series transformer, high-order harmonic currents will penetrate into the series transformer, thus necessitating a higher rating of the transformer. However, the leakage reactance of the transformer can be used to aid the filtering characteristic. A common problem facing these two filtering schemes is that the filter capacitor will cause an increase in the inverter rating. 2.4 Energy Storage Energy storage is required to provide real power to the load when large voltage sags take place. Examples of energy storages are lead-acid batteries, flywheel, SMES, etc. The energy storage device used for this study is lead-acid batteries. Energy storage batteries are devices in which electric energy is stored in electrochemical form by creating electrically charged ions. Batteries provide rapid response for either charge or discharge, but the discharge rate is limited by chemical reaction rates so that the available energy depends on the discharge rate. Lead-acid battery technology is also a mature technology. 648 Mayank Paliwal et al 3. Control of the DVR The main considerations for the control system of a DVR include: detection of the start and finish of the sag, voltage reference generation, transient and steady-state control of the injected voltage, and protection of the system. The control system was used to control the DVR with a sampling and switching frequency. It requires measurement of four parameter groups. Three phase-voltages before the DVR to detect voltage sag and for feedforward control of the output voltage. Three-phase voltages after the DVR for feed-back control of the output voltage. Three currents in the converter to protect the DVR by both saturation control and over current. The dc-link voltage for dc voltage compensation (to decouple the controller from variations in the dc-link voltage), for converter protection, and to provide energy storage information. With the grid voltage in its normal level the DVR is held in a null state to keep the losses to a minimum [3]. Once voltage sag is detected the DVR converts into active mode to react as fast as possible and inject the required ac voltage to the grid. Table 1: Table showing System quantities/ parameter. S. No 1. System Quantities Inverter Specification 2. 3. Transmission Line Parameter PI Controller Standards IGBT based, 3 arms, 6 Pulse, Carrier frequency =1080 Hz, Sample Time= 5 μs R=0.001 ohms, L=0.005H KP=0.5, Ki=50, Sample time=50 μs Fig. 2: Single line diagram of test system for DVR. Voltage Sag Compensation Using Dynamic Voltage Restorer 649 4. Simulation Results System performance is analyzed for compensating voltage sag with different DC storage capacity so as to achieve rated voltage at a given load. Various cases of different load condition are considered to study [4] the impact DC storage on sag compensation. Case 1: A three-phase fault is created at point X via a resistance of 0.66 Ω which results in a voltage sag of 17.02 %. Transition time for the fault is considered from 0.4 sec to 0.6 DVR performance in presence of capacitor rating of 750×10-6 F with energy storage devices via 3.1KV. Fig. 3: a) Three Phase, Phase to Phase Voltage without DVR Energy Storage Fig. 3: b) Voltage p.u. at the Load Point without DVR System Fig. 3: c) Voltage p.u. at the Load Point with DC storage of 3.1 kV Case 2: A three-phase fault is created at point X via a resistance of 0.60 Ω which results in a voltage sag of 19 %. Transition time for the fault is considered from 0.4 s to 0.6 s DVR performances in presence of capacitor rating of 750×10-6 F with energy storage devices via. 3.3 kV. 650 Mayank Paliwal et al Fig. 4: a) Three Phase, Phase to Phase Voltage without DVR Energy Storage Fig. 4: b) Voltage p.u. at the Load Point without DVR System Fig. 4: c) Voltage p.u. at the Load Point with DC storage of 3.3 kV Case 3: A three-phase fault is created at point X via a resistance of 0.50 Ω which results in a voltage sag of 23 %. Transition time for the fault is considered from 0.4 s to 0.6 s. DVR performance in presence of capacitor rating of 750×10-6 F with energy storage devices via. 3.5 kV. Fig. 5: a) Three Phase, Phase to Phase Point without DVR System Fig. 5: b) Voltage p.u. at the Load Point without DVR System Voltage Sag Compensation Using Dynamic Voltage Restorer 651 Fig. 5: c) Voltage p.u. at the Load Point with DC storage of 3.5 kV Case 4: A three-phase fault is created at point X via a resistance of 0.45 Ω which results in a voltage sag of 26 %. Transition time for the fault is considered from 0.4 s to 0.6 s. DVR performance in presence of capacitor rating of 750×10-6 F with different energy storage devices via. 3.7KV. Fig. 6: a) Three Phase, Phase to Phase Point without DVR System Fig. 6: b) Voltage p.u. at the Load Point without DVR System Fig. 6: c) Voltage p.u. at the Load Point with DC storage of 3.7 kV 652 Mayank Paliwal et al Case 5: A three-phase fault is created at point X via a resistance of 0.40 Ω which results in a voltage sag of 29 %. Transition time for the fault is considered from 0.4 s to 0.6 s. DVR performance in presence of capacitor rating of 750×10-6 F with different energy storage devices viz. above 3.7KV. Fig. 7: a) Three Phase, Phase to Phase Voltage without DVR Energy Storage Fig. 7: b) Voltage p.u. at the Load Point without DVR System Fig. 7: c) Voltage p.u. at the Load Point with DC storage of 4.3 kV Table 2: Comparison of desired % voltage sag at DC voltage S. No. 1. 2. 3. 4. 5. % Voltage Sag 17.02 19 23 26 29 Required DC Voltage (KV) 3.1 3.3 3.5 3.7 Above 3.7 Voltage Sag Compensation Using Dynamic Voltage Restorer 653 In the above table it is shown that required DC storage values are not same for different voltage sag conditions [5]. When the load is fixed on 11 KV feeders, the amount of DC energy storage is increased with increase in the percentage voltage sag. It is observed that when percentage voltage sag is increased above 28%. The per unit voltage fall below 1 per unit value and it is continuously decreases with increase in percentage voltage sag for 11 kV feeder [6]. 5. Conclusion Fig. 8 shows the variation of DC storage voltage with the increase percentage voltage sag. DC storage value can be estimated from the following equation: = 0.0012 − 0.008 + 1.8 − 10 Where Y= DC Voltage (kV) and X= % Voltage sag Voltage sag values are major factors in estimating the DC storage value. The effectiveness of a DVR system mainly depends upon the rating of DC storage rating and the percentage voltage sag. In the test system it is observed that after a particular amount of voltage sag, the voltage level at the load terminal decreases. Fig. 8: % voltage sag verses DC storage (KV) References [1] [2] C.C. Zhan, M. Barnes, V.K. Ramachandaramurthy, and N. Jenkis, “Dynamic Voltage Restorer with Battery Energy Storage for Voltage Dip Mitigation” Power Electronics and Variable Speed Drives, 18-19, Conference Publication No. 475, IEEE September 2000. Francisco Jurado, Manul Valverde, and Jose Carpio, “Voltage Sag Correction by Dynamic Voltage Restorer Based on Fuzzy Logic Control” IEEE 2003. 654 [3] [4] [5] [6] Mayank Paliwal et al Kasuni Perera, Daniel Salomon son, Arulampaiam, Atputharajah, Sanath Alahakoon, “Automated Control Technique for A Single Phase Dynamic Voltage Restorer” IEEE, 2006. S. V Ravi Kumar, S. Siva Nagaraju, “Simulation of D-Statcom and DVR in Power Systems” ARPN Journal of Engineering and Applied Sciences Vol. 2, No. 3, June 2007. Changjian Zhan,V.K. Ramachandrara murthy, A. Arulampalam, M.Barnes, G.Strbac N.Jekin, “Dynamic Voltage Restorer Based on Voltage Space Vector PWM Control”, IEEE 2001. P Kundur, “Power System Stability and Control”, McGraw-Hill 1994.