Technical Data
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains
and Incoming Lines Dimension Reference
Catalog Number 2100
Topic
Page
Application Notes
1
Catalog Numbers
2
Incoming Lines
3
Fusible Disconnects
11
Circuit Breakers
27
Conduit Entry - Top
37
Conduit Entry - Bottom
40
Additional Resources
45
Application Notes
This guide contains cabling dimensions for main incoming line compartments, fusible disconnect switch mains, and circuit
breaker mains in Bulletin 2100 CENTERLINE motor control centers. Lug pad dimensions are included for main
incoming line compartments. The fusible disconnect and circuit breaker mains drawing include dimensions for standard
lugs, and optional lugs (if specified).
IMPORTANT
Although this guide is accurate at the time of printing, there are differences between these drawings and the actual product, due
to recent design enhancements. Always refer to the Job-specific Drawings (Form 385) for the most accurate drawings and
dimensions.
IMPORTANT
Reference dimensions include a tolerance of ±1/8 inches (±3.2 mm).
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Catalog Numbers
Every CENTERLINE motor control center unit is defined by a catalog number. For mains, these catalog numbers are of
the following form:
Type of Main
Catalog Bulletin Number
Catalog Number Example
Incoming Line
2191M
2191MT-CAC-54
Fusible Disconnect
2192M
2192MB-GAC-29R
Circuit Breaker
2193M
2193MT-FJC-54WT-83C500
The catalog numbers appear on the unit label, located on the unit bottom plate. For assembled motor control centers,
catalog numbers for each unit are also listed on the Job-specific Drawings (Form 385) that ship with the order.
2
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Incoming Lines
Figure 1 - 300 A Incoming Line Compartment, Top Entry,
1.0 Space Factor(1)
Figure 2 - 300 A Incoming Line Compartment, Bottom Entry,
1.0 Space Factor(1)
Figure 3 - 600 A Incoming Line Compartment, Top Entry,
1.0 Space Factor(1)
Figure 4 - 600 A Incoming Line Compartment, Bottom Entry,
1.0 Space Factor(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
3
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 5 - 800 A Incoming Compartment Top Entry, 1.5 Space
Factor(1)
Figure 6 - 800 A Incoming Compartment Bottom Entry,
1.5 Space Factor(1)
Figure 7 - 800 A Incoming Compartment Top Entry in Horizontal
Wireway
(additional 12 in. Pull Box required to meet NEC wire bending
requirements)(1)
Figure 8 - 800…1200 A Incoming Compartment Top Entry
1.0 Space Factor
(additional 12 in. Pull Box required to meet NEC wire
bending requirements)(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
4
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 9 - 800 A Incoming Line Compartment Top Entry,
1.5 Space Factor(1)
Figure 10 - 800 A Incoming Line Compartment Bottom Entry,
1.5 Space Factor(1)
Figure 11 - 800…1200 A Incoming Line Compartment Top Entry,
2.0 Space Factor(1)
Figure 12 - 800…1200 A Incoming Line Compartment Bottom
Entry, 2.0 Space Factor(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
5
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 12 - 600…1600 A Incoming Line Section Top Entry,
6.0 Space Factor(1)
Figure 13 - 600…1600 A Incoming Line Section Bottom Entry,
6.0 Space Factor(1)
Figure 14 - 2000 A Incoming Line Section Top Entry,
6.0 Space Factor(1)
Figure 15 - 2000 A Incoming Line Section Bottom
Entry, 6.0 Space Factor(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
6
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 17- 600…1200 A Corner Incoming Line Section
Top Entry, 6.0 Space Factor(1)
Figure 18 - 600…1200 A Corner Incoming Line Section
Bottom Entry, 6.0 Space Factor(1)
Figure 19 - 1600 A Corner Incoming Line Section Top
Entry, 6 Space Factor(1)
Figure 20 - 1600 A Corner Incoming Line Section
Bottom Entry, 6 Space Factor(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
7
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 21 - 600…1200 A, 10 in. Wide Incoming Line Section Top
Entry, 6.0 Space Factor (left-hand version shown)(1)
Figure 22 - 600…1200 A, 10 in. Wide Incoming Line Section
Bottom Entry, 6.0 Space Factor (left-hand version shown)(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
8
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 24 - #6-350 kcmil, Two Cable Mechanical Lug
Figure 23 - #6-350 kcmil, One Cable Mechanical Lug
Figure 25 - 350…800 kcmil, One Cable Mechanical Lug
Figure 27 - #4/0-600 kcmil, Two Cable Mechanical Lug
Figure 26 - #4/0-600 kcmil, One Cable Mechanical Lug
Figure 28 - #4/0-600 kcmil, Two Cable Mechanical Lug
2.562
(65.1)
3.00
(76.2)
1.875 ± 0.010
(47.63 ± 0.25)
3.310
(84.07)
5.687 ± 0 .031
(144.45 ±0.79)
0.75 ± 0.010
(19.10 ± 0.25)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
9
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 29 - 250 kcmil Panduit Crimp Lug
Figure 30 - 250 kcmil Burndy Crimp Lug
Figure 31 - 350 kcmil Panduit Crimp Lug
Figure 32 - 350 kcmil Burndy Crimp Lug
Figure 33 - 500 kcmil Panduit Crimp Lug
Figure 34 - 500 kcmil Burndy Crimp Lug
Figure 35 - 750 kcmil Panduit Crimp Lug
Figure 36 - 750 kcmil Burndy Crimp Lug
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
10
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Fusible Disconnects
Figure 37 - 30 A Main Fusible Disconnect Top Entry, 1.5 Space Factor Figure 38 - 30 A Main Fusible Disconnect Bottom Entry, 1.5 Space
Factor with #14…#8 AWG Mechanical Lugs, 1 per Phase(1)
with #14…#8 AWG Mechanical Lugs, 1 per Phase(1)
Figure 39 - 60 A Main Fusible Disconnect Top Entry, 1.5 Space
Factor with #14…#8 AWG Mechanical Lugs, 1 per Phase(1)
Figure 40 - 60 A Main Fusible Disconnect Bottom Entry, 1.5 Space
Factor with #14…#8 AWG Mechanical Lugs, 1 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
11
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 41 - 100 A Main Fusible Disconnect Top Entry, 1.5 Space Factor
with #8…1/0 AWG Mechanical Lugs, 1 per Phase(1)
Figure 42 - 100 A Main Fusible Disconnect Bottom Entry, 1.5 Space
Factor with #8…1/0 AWG Mechanical Lugs, 1 per Phase(1)
Figure 43 - 200 A Main Fusible Disconnect Top Entry, 2.0 Space Factor
with #6…4/0 AWG or #6…250 kcmil Mechanical Lugs, 1 per Phase(1)
Figure 44 - 200 A Main Fusible Disconnect Bottom Entry, 2.0 Space Factor
with #6…4/0 AWG or #6…250 kcmil Mechanical Lugs, 1 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
12
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 45 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor
with Two Cable 1/0…250 kcmil Mechanical Lugs, 1 per Phase(1)
Figure 46 - 400 A Main Fusible Disconnect Bottom Entry, 2.5 Space
Factor with Two Cable 1/0…250 kcmil Mechanical Lugs, 1 per Phase(1)
Figure 47 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor
with 250 kcmil Panduit Crimp Lugs, 2 per Phase(1)
Figure 48 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor
with 500 kcmil Panduit Crimp Lugs, 1 per Phase (additional 12 in. Pull
Box required to meet NEC wire bending requirements)(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
13
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 49 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor
with 250 kcmil Burndy Crimp Lugs, 2 per Phase(1)
Figure 50 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor
with 500 kcmil Burndy Crimp Lugs, 1 per Phase (additional 12 in. Pull
Box required to meet NEC wire bending requirements)(1)
Figure 51 - 600 A Main Fusible Disconnect Top Entry, 3.5 Space Factor
with #2…600 kcmil Mechanical Lugs, 2 per Phase(1)
Figure 52 - 600 A Main Fusible Disconnect Bottom Entry, 3.5 Space
Factor with #2…600 kcmil Mechanical Lugs, 2 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
14
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 53 - 600 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor Figure 54 - 600 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
with 500 kcmil Panduit Crimp Lugs, 2 per Phase(1)
Factor with 500 kcmil Panduit Crimp Lugs, 2 per Phase(1)
Figure 55 - 600 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor
with 500 kcmil Burndy Crimp Lugs, 2 per Phase(1)
Figure 56 - 600 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
Factor with 500 kcmil Burndy Crimp Lugs, 2 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
15
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 57 - 600 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with #2…600 kcmil Mechincal Lugs, 2 per Phase(1)
Figure 58 - 600 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with #2…600 kcmil Mechincal Lugs, 2 per Phase(1)
Figure 59 - 600 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Panduit Crimp Lugs, 2 per Phase(1)
Figure 60 - 600 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with 500 kcmil Panduit Crimp Lugs, 2 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
16
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 61 - 600 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Burndy Crimp Lugs, 2 per Phase(1)
Figure 62 - 600 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with 500 kcmil Burndy Crimp Lugs, 2 per Phase(1)
Figure 63 - 800 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor
with #6…350 kcmil Mechanical Lugs, 3 per Phase(1)
Figure 64 - 800 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
Factor with #6…350 kcmil Mechanical Lugs, 3 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
17
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 65 - 800 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor
with 500 kcmil Panduit Crimp Lugs, 3 per Phase(1)
Figure 66 - 800 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
Factor with 500 kcmil Panduit Crimp Lugs, 3 per Phase(1)
Figure 67 - 800 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor
with 500 kcmil Burndy Crimp Lugs, 3 per Phase(1)
Figure 68 - 800 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
Factor with 500 kcmil Burndy Crimp Lugs, 3 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
18
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 69 - 800 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with #6…350 kcmil Mechanical Lugs, 3 per Phase(1)
Figure 70 - 800 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with #6…350 kcmil Mechanical Lugs, 3 per Phase(1)
Figure 71 - 800 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Panduit Crimp Lugs, 3 per Phase(1)
Figure 72 - 800 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with 500 kcmil Panduit Crimp Lugs, 3 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
19
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 73 - 800 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Burndy Crimp Lugs, 3 per Phase(1)
Figure 74 - 800 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with 500 kcmil Burndy Crimp Lugs, 3 per Phase(1)
Figure 75 - 1200 A Main Fusible Disconnect, Top Entry, 3.5 Space
Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(1)
Figure 76 - 1200 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
20
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 77 - 1200 A Main Fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(1)
Figure 78 - 1200 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(1)
Figure 79 - 1200 A Main Fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(1)
Figure 80 - 1200 A Main Fusible Disconnect, Bottom Entry, 3.5 Space
Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
21
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 81 - 1200 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(1)
Figure 82 - 1200 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(1)
Figure 83 - 1200 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(1)
Figure 84 - 1200 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
22
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 85 - 1200 A Main Non-fusible Disconnect, Top Entry, 3.5 Space
Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(1)
Figure 86 - 1200 A Main Non-fusible Disconnect, Bottom Entry, 3.5
Space Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(1)
Figure 87 - 1600 A Main Fusible or Non-fusible Disconnect, Top Entry,
6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 4 per Phase(1)
Figure 88 - 1600 A Main Fusible or Non-fusible Disconnect, Bottom
Entry, 6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 4 per
Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
23
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 89 - 1600 A Main Fusible or Non-fusible Disconnect, Top Entry,
6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 5 per Phase(1)
Figure 90 - 1600 A Main Fusible or Non-fusible Disconnect, Bottom
Entry, 6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 5 per
Phase(1)
Figure 91 - 1600 A Main Fusible or Non-fusible Disconnect, Top Entry,
6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 5 per Phase(1)
Figure 92 - 1600 A Main Fusible or Non-fusible Disconnect, Bottom
Entry, 6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 5 per Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
24
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 93 - 2000 A Main Fusible or Non-fusible Disconnect, Top Entry,
6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 6 per Phase(1)
Figure 94 - 2000 A Main Fusible or Non-fusible Disconnect, Bottom
Entry, 6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 6 per
Phase(1)
Figure 95 - 2000 A Main Fusible or Non-fusible Disconnect, Top Entry,
6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 6 per Phase(1)
Figure 96 - 2000 A Main Fusible or Non-fusible Disconnect, Bottom
Entry, 6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 6 per
Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
25
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 97 - 2000 A Main Fusible or Non-fusible Disconnect, Top Entry,
6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 6 per Phase(1)
Figure 98 - 2000 A Main Fusible or Non-fusible Disconnect, Bottom
Entry, 6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 6 per
Phase(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
26
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Circuit Breakers
Figure 99 - 150 A Main Circuit Breaker, Top Entry, 1.5 Space Factor,
with #14…#1/0 AWG Mechanical Lugs, 1 per Phase, 15…125 A
Trips(1)
Figure 100 - 150 A Main Circuit Breaker, Bottom Entry, 1.5 Space
Factor, with #14…#1/0 AWG Mechanical Lugs, 1 per Phase, 15…125
A Trips(1)
7.28
(185)
11.13
(283)
7.28
(185)
Figure 101 - 250 A Main Circuit Breaker, Top Entry, 1.5 Space Factor,
with #10…250 kcmil Mechanical Lugs, 1 per Phase, 70…250 A
Trips(1)
5.16
(131)
Figure 102 - 250 A Main Circuit Breaker, Bottom Entry, 1.5 Space
Factor, with #4…250 kcmil Mechanical Lugs, 1 per Phase, 70…250 A
Trips(1)
5.05
(128)
10.57
(268.5)
7.24
(184)
7.24
(184)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
27
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 103 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor,
with 250…500 kcmil Mechanical Lugs, 1 per Phase, 300 A(1)
Figure 104 - 400 A Main Circuit Breaker, Bottom Entry, 2.0 Space
Factor, with 250…500 kcmil Mechanical Lugs, 1 per Phase, 300 A
Trip(1)
6.90
(175.25)
16.88
(428.75)
6.90
(175.25)
Figure 105 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor,
with 2/0…250 kcmil Mechanical Lugs, 2 per Phase, 400 A Trip(1)
6.96
(177)
15.94
(405)
6.15
(156.2)
11.38
(289)
Figure 106 - 400 A Main Circuit Breaker, Bottom Entry, 2.0 Space
Factor,with 2/0…250 kcmil Mechanical Lugs, 2 per Phase, 400 A
Trip(1)
6.96
(177)
6.15
(156.2)
11.38
(289)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
28
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 107 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor,
with 250 kcmil Panduit Crimp Lugs, 2 per Phase, 300…400 A Trips
(optional Pull Box provides an additional 12 in. of bending space)(1)
Figure 108 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor,
with 250 kcmil Burndy Crimp Lugs, 2 per Phase, 300…400 A Trips
(optional Pull Box provides an additional 12 in. of bending space)(1)
7.64
(194)
7.64
(194)
6.12
(155.4)
6.12
(155.4)
11.68
(296.7)
11.16
(283.5)
Figure 109 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor,
with 500 kcmil Panduit Crimp Lugs, 1 per Phase, 300 A Trips (optional
Pull Box provides an additional 12 in. of bending space)(1)
Figure 110 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor,
with 500 kcmil Burndy Crimp Lugs, 1 per Phase, 300 A Trips (optional
Pull Box provides an additional 12 in of bending space)(1)
6.46
(164.1)
11.61
(283.5)
6.4
(162.6)
10.94
(278)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
29
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 111 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space
Factor, with 3/0…350 kcmil Mechanical Lugs, 2 per Phase, 600 A
Trips(1)
Figure 112 - 800 A Frame Main Circuit Breaker, Bottom Entry, 2.0
Space Factor, with 3/0…350 kcmil Mechanical Lugs, 2 per Phase,
600 A Trips(1)
6.90
(175.26)
14.36
(364.7)
5.15
(130.8)
14.44
(366.8)
5.15
(130.8)
6.90
(175.26)
Figure 113 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space
Factor, with 250…500 kcmil Mechanical Lugs, 2 per Phase, 600 A
Trips(1)
Figure 114 - 800 A Frame Main Circuit Breaker, Bottom Entry, 2.0
Space Factor, with 250…500 kcmil Mechanical Lugs, 2 per Phase,
600 A Trips(1)
6.90
(175.26)
14.36
(364.7)
5.15
(130.8)
14.44
(366.8)
5.15
(130.8)
6.90
(175.26)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
30
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 115 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space
Factor, with 500 kcmil Panduit Crimp Lugs, 2 per Phase, 600 A Trips
(additional 12 in. Pull Box required to meet NEC wire bending
requirements)(1)
Figure 116 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space
Factor, with 500 kcmil Burndy Crimp Lugs, 2 per Phase, 600 A Trips
(additional 12 in. Pull Box required to meet NEC wire bending
requirements)(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
31
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 117 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor,
with #2/0…250 kcmil Mechanical Lugs, 3 per Phase, 800 A Trips(1)
Figure 118 - 800 A Main Circuit Breaker, Bottom Entry, 2.5 Space
Factor, with #2/0...350 kcmil Mechanical Lugs, 3 per Phase,
800 A Trips(1)
5.62
(143)
16.90
(430)
4.93
(125)
17.40
(442)
5.06
(129)
5.81
(148)
Figure 119 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor,
with #2/0 - 400 kcmil Mechanical Lugs, 3 per Phase, 800 A Trips(1)
Figure 120 - 800 A Main Circuit Breaker, Bottom Entry, 2.5 Space
Factor, with #2/0 - 400 kcmil Mechanical Lugs, 3 per Phase, 800 A
Trips(1)
6.12
(156)
5.43
(138)
16.90
(430)
4.81
(123)
17.40
(442)
4.81
(123)
5.43
(138)
6.12
(156)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
32
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 121 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor,
with 500 kcmil Panduit Crimp Lugs, 3 per Phase, 800 A Trips
(additional 12 in. Pull Box required to meet NEC wire bending
requirements)(1)
7.62
(194)
6.00
(153)
4.53
(115)
4.18
(107)
Figure 122 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor,
with 500 kcmil Burndy Crimp Lugs, 3 per Phase, 800 A Trips
(additional 12 in. Pull Box required to meet NEC wire bending
requirements)(1)
7.62
(194)
6.00
(153)
4.53
(115)
3.94
(100)
Figure 123 - 1200 A Main Circuit Breaker, Top Entry, 3.5 Space Factor,
with #4/0 - 500 kcmil Mechanical Lugs, 4 per Phase, 400…1200
Trips(1)
Figure 124 - 1200 A Main Circuit Breaker, Bottom Entry, 3.5 Space
Factor, with #4/0 - 500 kcmil Mechanical Lugs, 4 per Phase,
400…1200 Trips(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
33
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 125 - 1200 A Main Circuit Breaker, Top Entry, 3.5 Space Factor,
with 500 kcmil Panduit Crimp Lugs, 3 or 4 per Phase, 400…1200
Trips(1)
9.23
(235)
16.20
(412)
Figure 126 - 1200 A Main Circuit Breaker, Bottom Entry, 3.5 Space
Factor, with 500 kcmil Panduit Crimp Lugs, 3 or 4 per Phase,
400…1200 Trips(1)
7.73
(197)
6.30
(160)
4.80
(122)
16.34
(415)
4.80
(122)
6.30
(160)
7.73
(197)
9.23
(235)
Figure 127 - 1200 A Main Circuit Breaker, Top Entry, 3.5 Space Factor,
with 500 kcmil Burndy Crimp Lugs, 4 per Phase, 600…1200 Trips(1)
Figure 128 - 1200 A Main Circuit Breaker, Bottom Entry, 3.5 Space
Factor, with 500 kcmil Burndy Crimp Lugs, 4 per Phase, 600…1200
Trips(1)
9.23
(235)
15.54
(395)
7.73
(197)
6.30
(160)
4.80
(122)
15.68
(398)
4.80
(122)
6.30
(160)
7.73
(122)
9.23
(235)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
34
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 129 - 3000 A R-frame Main Circuit Breaker, Top Entry, 8 Cables
per Phase
Figure 130 - 3000 A R-frame Main Circuit Breaker, Bottom Entry, 8
Cables per Phase
15.05
(382.3)
13.40
(340.4)
11.75
(298.5)
10.10
(256.5)
24.82
(630.4)
24.72
(627.9)
10.10
(256.5)
11.75
(298.5)
13.40
(340.4)
15.05
(382.3)
Figure 131 - 2500 A R-frame Main Circuit Breaker, Top Entry, 100%, 7
Cables per Phase
Figure 132 - 2500 A R-frame Main Circuit Breaker, Bottom Entry,
100%, 7 Cables per Phase
15.05
(382.3)
13.40
(340.4)
11.75
(298.5)
10.10
(256.5)
24.82
(630.4)
25.81
(655.6)
25.71
(653.0)
24.72
(627.9)
10.10
(256.5)
11.75
(298.5)
13.40
(340.4)
15.05
(382.3)
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
35
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 133 - 2500 A R-frame, Top Entry, 80% 7 Cables per Phase
Figure 134 - 2500 A R-frame, Bottom Entry, 80% 7 Cables per Phase
8.47
(215.1)
5.77
(146.6)
4.61
(117.1)
24.86
(631.4)
25.85
(656.6)
24.82
(630.4)
25.81
(655.6)
4.61
(117.1)
5.77
(146.6)
8.47
(215.1)
Figure 135 - 2000 A and Less R-frame, Top Entry, 6 Cables per Phase
Figure 136 - 2000 A and Less R-frame, Bottom Entry, 6 Cables per
Phase
5.77
(146.6)
4.61
(117.1)
24.86
(631.4)
24.82
(630.4)
4.61
(117.1)
5.77
(146.6)
36
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Conduit Entry - Top
Figure 137 - Top Horizontal Ground Bus Location Front View(1)
Figure 138 - Standard and Incoming Line Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Single Section, Top View(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
37
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 139 - Standard and Incoming Line Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Back-to-Back Construction, Top View(1)
Figure 140 - Standard and Incoming Line Corner Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Top View
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
38
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 141 - 10 in. Wide Incoming Line Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Top View
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
39
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Conduit Entry - Bottom
Figure 142 - Bottom Horizontal Ground Bus Location, Front View(1)
Figure 143 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1(with gasket), or 12, Single Section, Top View(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
40
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 144 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, Back-to-Back Construction, Top View(1)
Figure 145 - Standard and Incoming Line Corner Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, Top View
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
41
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 146 - 10 in. Wide Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12 Top View
42
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 147 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, with Optional External
Mounting Channels, Single Section, Top View(1)
Figure 148 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, with Optional External
Mounting Channels, Back-to-Back Construction, Top View(1)
(1) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
43
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Figure 149 - Standard and Incoming Line Corner Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, with Optional
External Mounting Channels, Top View
Figure 150 - 10 in. Wide Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with
gasket), or 12, with Optional External Mounting Channels, Top View
44
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource
Description
Form 385 - Motor Control Center Layout and Specification
Specific drawings and dimensions for your MCC.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Rockwell Automation Publication 2100-TD018B-EN-P - March 2015
45
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Software, Rockwell Automation, CENTERLINE, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 2100-TD018B-EN-P - March 2015
Supersedes Publication 2100-4.2 - October 1998
Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.