Type 585C Piston Actuators

advertisement
Product Bulletin
61.2:585C
August 2002
585C Actuator
Type 585C Piston Actuators
High Thrust Capability
With standard air supply, the Size 130 Type 585C
can produce up to 111,000 Newtons (25,000 lbs) of
force.
Wide Range of Sizes
The Type 585C family of actuators offers a wide
range of sizes, with piston areas of 168 sq cm (26 sq
in) up to 1,429 sq cm (221.5 sq in).
Rugged Construction
The Type 585C standard yoke material is ductile
iron, resulting in robust construction and increased
thrust capability.
Broad Travel Capability
Type 585C piston actuators provide standard travel
lengths of up to 203 mm (8 in). The 585C Long
Stroke version is capable of travels up to 610 mm
(24 in).
High Performance
Instrumentation
W7960 / IL
Figure 1. Type 585C Piston Actuator
D102086X012
Type 585C actuators are available with a variety of
positioners and accessories, including the DVC6000
Digital Valve Controller. The 377 Series Trip Valve
and tank system are available for fail-safe action.
www.Fisher.com
Product Bulletin
61.2:585C
August 2002
585C Actuator
Contents
Type 585C Features and Advantages . . . . . . . . . . 3
Principle of Operation—585C . . . . . . . . . . . . . . . . . . 4
Instrument Selection . . . . . . . . . . . . . . . . . . . . . . . . . 6
DVC6010/6020 Digital Valve Controller . . . . . . . . . 6
3600 Series Positioner . . . . . . . . . . . . . . . . . . . . . . . 7
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
585C Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Actuator Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Handwheel Specifications . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications—Type 585C Actuators
Sizes 25-130 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications—585C Long-Stroke Actuators . . .
Specifications—DVC6000 Series Digital Valve
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications—3600 Series Positioners . . . . . . .
SPRING
(SIZES 25 & 50)
CYLINDER
TRAVEL STOP
PISTON
STEM O-RING
PISTON O-RING
SEAL BUSHING
CAP SCREW
TRAVEL
INDICATOR
YOKE
STEM
CONNECTOR
ACTUATOR STEM
W7447-1 / IL
Figure 2. Type 585C Piston Actuator Components
2
17
18
22
23
24
26
Product Bulletin
61.2:585C
August 2002
585C Actuator
The Type 585C Linear Piston Actuator
The Type 585C linear piston actuator is a powerful,
double-acting actuator that provides accurate
throttling or on-off operation for sliding-stem control
valves.
The Type 585C piston actuator family is available in
sizes 25 to 130 to cover a wide range of thrust and
travel length requirements. It can be used with
switching valves for on-off control, or with the Fisher
DVC6000 Series digital valve controller or 3600
Series positioner for throttling applications.
The Type 585C has a wide-range of supply pressure
capabilities, up to 150 psig. As the Type 585C is
double-acting, the positioner supplies air to both
sides of the piston, resulting in stiff, precise
movement and control.
The 585C piston actuator is also available in a long
stroke version with travel capabilities up through 610
mm (24 inches).
Type 585C Features and Advantages
See table 1.
Table 1. Type 585C Features and Advantages
Features
High thrust capability
Long stroke
Wide range of sizes
Valve mounting
capability
Positioner mounting
capability
High frequency
response
Stiff construction
Handwheels
Bias springs
Advantages
With air supply capability of up to 150 psig, the Type 585C can produce up to
111,000 Newtons (25,000 pounds) thrust to overcome high valve unbalance. Special
constructions can produce thrusts of up to 137,000 Newtons (30,800 pounds).
Depending on size, strokes of up to 203 mm (8 inches) (standard) are available.
Longer travels of up to 610 mm (24 inches) are available upon request.
The Type 585C is available in standard sizes 25, 50, 60, 68, 80, 100, and 130.
Larger cylinder sizes are available for special applications.
Depending on size, the Type 585C can be mounted to yoke boss diameters of 2-1/8
inches through 5-inches, and valve stems of up to 1-1/4 inch diameter. Special
constructions will accommodate a 7-inch yoke boss and a 2-inch valve stem.
Universal NAMUR mounting provides a consistent mounting method for size 25
through 130 actuators. This mounting capability provides vibration resistance per
ISA-S75.13.
The double-acting construction of the Type 585C allows quick response to
instrument signals.
Pressure on both sides of the piston, plus the relatively small volume of air within the
cylinder, results in stiff, precise positioning.
Type 585C size 25 and 50 actuators are available with a top-mounted handwheel. All
other 585C actuator sizes can accommodate a side-mounted handwheel.
The sizes 25 and 50 are available with bias springs. A bias spring under the piston
fully retracts the actuator stem upon loss of supply air, while a bias spring on top of
the piston fully extends the actuator stem. The spring bias mode is easily reversed
without the need for additional parts.
3
Product Bulletin
61.2:585C
August 2002
585C Actuator
E0409 / IL
Figure 3. Type 585C Piston Actuator Without Springs
Principle of Operation – 585C
The Type 585C piston actuator (figures 2 and 3)
uses a piston that moves inside the actuator
cylinder. An O-ring (see figure 2) provides a seal
between the piston and the cylinder.
From an equilibrium state, the actuator reacts to a
force unbalance that is created by increasing supply
pressure on one side of the piston,and decreasing it
on the other. This moves the piston up or down, and
results in a repositioning of the valve control
element.
E0410 / IL
Figure 4. Type 585C Piston Actuator with Handwheel
Actuator with Handwheel (figures 4 and 13)
The handwheel version can be used to open or
close the valve manually (either during normal
operation or in an emergency), to position the valve
at any point in the stroke, or to act as a travel stop.
Size 25 and 50 actuators use an integral
top-mounted handwheel. See figure 13.
Size 60 to 130 actuators use a side-mounted
handwheel, and come with a spring-loaded ball
detent which prevents vibration from changing the
handwheel setting. Handwheels for most types are
either 203 mm (8 inches) in diameter with beveled
gears or 432 mm (17 inches) in diameter with worm
gears.
4
Product Bulletin
61.2:585C
August 2002
585C Actuator
W7447-1 / IL
Figure 5. Type 585C Piston Actuator with Spring Return
W2795–1/IL
Figure 6. Type 585C Long-Stroke Actuator
Actuator with Spring Return (figure 5)
Type 585C size 25 & 50 actuators are available with
bias springs. The Type 585C actuator with bias
spring has the spring under the piston and fully
retracts the actuator stem upon loss of cylinder
pressure. The bias spring in the Type 585CR
actuator is on top of the piston and fully extends the
actuator stem upon loss of cylinder pressure. No
additional parts are required to convert from one
actuator type to the other.
Type 585C Long-Stroke Construction
When especially high thrust or long stroke is
required, the Type 585C Long-Stroke piston actuator
is the answer (see figure 6). The versatility of the
Long-Stroke version allows accommodation of 16
different valve travels, up through 610 mm (24
inches). Available thrusts are impressive too, with
thrust capability of up to 137,800 newtons (30,800
lbs).
5
Product Bulletin
61.2:585C
August 2002
585C Actuator
Instrument Selection
An excellent selection of sensitive and accurate
instruments is available for Type 585C piston
actuators. These include the DVC6000 Series digital
valve controller, as well as the 3600 Series
pneumatic (P/P) and electro-pneumatic (I/P)
positioners.
DVC6010/6020 Digital Valve Controller
FIELDVUEr DVC6000 Series digital valve
controllers, figure 7, are communicating,
microprocessor-based current-to-pneumatic
instruments. In addition to the traditional function of
converting a current signal to a pressure signal,
DVC6000 Series digital valve controllers, using
HARTr communications protocol, give easy access
to information critical to process operation. This can
be done using a Model 275 HART Communicator at
the valve or at a field junction box, or by using a
personal computer or a system console within the
control room. Using HART communication protocol,
information can be integrated into a control system
or received on a single loop basis.
DVC6000 Series digital valve controllers can be
used on single- or double-acting actuators. The
digital valve controller receives feedback of the valve
travel position plus supply and actuator pneumatic
pressure. This allows the instrument to diagnose not
only itself, but also the valve and actuator to which it
is mounted. This provides you with very cost
effective maintenance information, so that required
maintenance can be performed on the instrument
and valve when there really is a need.
Wiring is economical because DVC6000 Series
digital valve controllers use two-wire 4 to 20 mA loop
power. This provides for low cost replacement of
existing analog instrumentation. The DVC6000
Series digital valve controller’s two-wire design
avoids the high cost of running separate power and
signal wiring.
Principle of Operation—DVC6010/6020
DVC6000 Series instruments receive a set point and
position the valve where it needs to be. See figure 8.
D The input signal provides electrical power and
the set point simultaneously. It is routed into the
terminal box through a twisted pair of wires.
6
W7960 / IL
Figure 7. Type DVC6010 Digital Valve Controller Mounted on
Type 585C Piston Actuator
D The input signal is then directed to the printed
wiring board assembly where the microprocessor
runs a digital control algorithm resulting in a drive
signal to the I/P converter.
D The I/P converter assembly is connected to
supply pressure and converts the drive signal into a
pressure output signal.
D The I/P output is sent to the pneumatic relay
assembly. The relay is also connected to supply
pressure and amplifies the small pneumatic signal
from the I/P converter into a single larger pneumatic
output signal used by a single-acting actuator. For
double-acting actuators, the relay accepts the
pneumatic signal from the I/P converter and provides
two pneumatic output signals.
D The change in relay output pressure to the
actuator causes the valve to move.
D Valve position is sensed through the feedback
linkage by the instrument’s travel sensor. The travel
sensor (or potentiometer) is electrically connected to
the printed wiring board to provide a travel feedback
signal used in the control algorithm.
The valve continues to move until the correct
position is attained.
Product Bulletin
61.2:585C
August 2002
585C Actuator
4–20 mA
INPUT SIGNAL
+
HART
AUXILIARY
TERMINALS
TERMINAL BOX
VALVE TRAVEL
FEEDBACK
PRINTED
WIRING BOARD
DRIVE
SIGNAL
OUTPUT A
I/P
CONVERTER
PNEUMATIC
RELAY
SUPPLY
PRESSURE
OUTPUT B
VALVE AND ACTUATOR
E0408 / IL
Figure 8. DVC6000 Series Digital Valve Controller Block Diagram
3600 Series Positioner
3600 Series pneumatic (P/P) and electro-pneumatic
(I/P) positioners are used in combination with either
single or double acting actuators to accurately
position control valves used in throttling applications.
These accurate and vibration-resistant positioners
provide a valve position proportional to a pneumatic
or a dc current input signal. Low steady-state air
consumption contributes to efficient operation.
The Type 585C piston actuator can be controlled
with the Type 3610JP or 3611JP pneumatic (P/P)
positioner, and the 3620JP or 3621JP
electro-pneumatic (I/P) positioner.
Principle of Operation—3600 Series
A switching device is required to control the loading
and unloading of supply pressure. A 4-way solenoid
or a 3600 Series positioner can be used for throttling
service. The P/P positioner accepts a pneumatic
input signal, whereas the I/P positioner accepts a dc
current signal from a control device.
W4919 / IL
Figure 9. Type 3620JP/3621JP Electro-Pneumatic (I/P)
Positioner Assembly
7
Product Bulletin
61.2:585C
August 2002
585C Actuator
FINE SPAN
ADJUSTMENT
MINOR
LOOP GAIN
ADJUSTMENT
COARSE
SPAN
ADJUSTMENT
CROSSOVER
ADJUSTMENT
ZERO
ADJUSTMENT
summing beam, pivoting the summing beam
clockwise and causing relay B to exhaust upper
actuator cylinder pressure to atmosphere and relay
A to increase lower actuator cylinder pressure. As a
result, the actuator stem retracts and the feedback
arm pivots counterclockwise reducing the force
applied to the summing beam by the range spring.
As the actuator stem retracts, the range spring force
to the summing beam continues to reduce until the
summing beam torques are in equilibrium. At this
point, the actuator stem is in the correct position for
the specific input signal applied.
The I/P positioner is a combination of a P/P
positioner with a current-to-pressure converter. The
converter provides a 0.2 to 1.0 bar (3 to 15 psig)
output pressure proportional to the 4 to 20
milliampere input signal. The 0.2 to 1.0 bar (3 to 15
psig) output pressure becomes the input signal
pressure to the P/P pneumatic positioner.
W4901–1*/IL
Figure 10. Adjustment for 3600 Series Positioners
The P/P positioner is a force-balanced instrument
that provides an actuator stem position proportional
to the pneumatic input signal, as shown in figure 11.
For direct action, input signal pressure from a
pneumatic instrument is channeled to cavity A in the
input module. An increase in input signal pressure
results in a downward force on the summing beam,
pivoting the summing beam counterclockwise. This
moves the flapper slightly toward the nozzle,
increasing the nozzle pressure. As nozzle pressure
increases, the relay beam pivots clockwise, causing
relay B to increase upper cylinder pressure and
Relay A to exhaust lower cylinder pressure of the
actuator.
As a result, the actuator stem extends and the force
applied to the summing beam by the range spring
increases as the feedback lever rotates clockwise.
This force, which opposes the downward force on
the summing beam caused by the increasing input
signal pressure, continues to increase until the
summing beam torques are in equilibrium. At this
point, the actuator stem is in the correct position for
the specific input signal applied.
For reverse action, input signal pressure is
channeled to both cavities A and B. An increase in
signal pressure results in an upward force on the
8
Accessories
Type 304 Electrical Valve Stem Position Switch—
A cam operated limit switch assembly that can
house from one to six snap-acting switches. The
position switch shaft is rotated by linear motion of
the valve stem and each cam can be adjusted to
activate its switch at the proper travel.
377 Series Trip Valve—Used when a specific valve
fail action is required when supply pressure falls
below a specified pressure. Should supply pressure
fall below the trip point, the trip valve can be set to
cause the actuator piston to fail up, fail down or
lock-in-last position.
4200 Series Electronic Position Transmitter—The
position transmitter provides an electrical signal that
is proportional to the valve stem position. Depending
on the type of transmitter ordered, it provides a
transmitter signal only, position switches only, or a
transmitter signal with position switches for accurate
valve position indication.
GO Series Limit Switches (Size 60 to 130
only)—Can be mounted on the yoke cover plate to
electrically indicate open or closed positions of the
valve.
Product Bulletin
61.2:585C
August 2002
585C Actuator
CROSS-OVER
ADJ
RELAY BEAM
SUPPLY PRESSURE
NOZZLE PRESSURE
INPUT SIGNAL
RELAY
B
RELAY
A
OUTPUT SIGNAL
OUTPUT SIGNAL
MINOR LOOP
GAIN ADJ
AIR
SUPPLY
RANGE SPRING
ZERO ADJ
FINE
SPAN
ADJ
COARSE
SPAN
ADJ
SUMMING BEAM
COUNTER SPRING
PIVOT A
FLAPPER
INPUT MODULE
NOZZLE
CAVITY A
CAVITY B
AIR SUPPLY
FIXED
RESTRICTION
INPUT SIGNAL
PRESSURE
PIVOT B
FEEDBACK
LEVER
PISTON
ACTUATOR
TYPE 3610JP/3611JP PNEUMATIC (P/P) POSITIONER
38A8902-B
B1846-1/IL
38A6592-A
B2157/IL
TYPE 3620JP/3621JP ELECTROĆPNEUMATIC (I/P) POSITIONER
Figure 11. 3600 Series Principle of Operation
9
Product Bulletin
61.2:585C
August 2002
585C Actuator
tables 4, 5, 6, 7, 8, and 9 for actuator thrust
capabilities.
Actuator Data
See table 2 for piston cylinder clearance volumes,
table 3 for yoke boss and valve stem diameters, and
Table 2. Type 585C Piston Cylinder Clearance Volumes
PISTON AT TOP OF CYLINDER (SPRINGS BELOW PISTON FOR SIZE 25 AND 50)
Actuator
Size
Piston Area
Maximum Actuator Travel
Upper Clearance Volume
(figure 12)
cm3
Inches3
Volume Below Piston
(figure 12)
cm3
Inches3
cm2
Inches2
cm
Inches
25
168
26
2.9
1-1/8
104
6.3
1750
107
50
303
47
5.1
2
330
20
5200
320
5.1
2
310
19
2700
163
10
4
310
19
4400
270
20
8
310
19
8200
500
5.1
2
1230
75
7500
460
10.2
4
1230
75
7500
460
20.3
8
1230
75
13300
810
10.2
4
1230
75
7500
460
20.3
8
1230
75
13300
810
10.2
4
1700
104
10700
650
20.3
8
1700
104
19200
1170
10.2
4
4600
280
18500
1130
20.3
8
4600
280
33000
2000
60
68
80
358
55.5
571
88.5
571
88 5
88.5
100
842
130 5
130.5
130
1430
221 5
221.5
PISTON AT BOTTOM OF CYLINDER (SPRINGS ABOVE PISTON FOR SIZE 25 AND 50)
Actuator
Size
Piston Area
Maximum Actuator Travel
Volume Above Piston
(figure 12)
cm3
Inches3
cm2
Inches2
cm
Inches
25
168
26
2.9
1-1/8
77
4.7
1790
109
50
303
47
5.1
2
350
22
5200
320
585C Installation
The actuator may be installed in any orientation but
normal installation is with the actuator vertical above
the valve. Actuator and positioner dimensions are
shown in figures 13, 14, 15, and 16.
If the supply source is capable of exceeding the
maximum actuator operating pressure or instrument
supply pressure, appropriate steps must be taken
10
Lower Clearance Volume
(figure 12)
cm3
Inches3
during installation to protect the instrument and all
connected equipment against overpressure.
Note
Fisher does not assume responsibility
for the selection, use, or maintenance
of any product. Responsibility for
proper selection, use, and
maintenance of any Fisher product
remains solely with the purchaser and
end-user.
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 3. Yoke Boss and Valve Stem Diameters
ACTUATOR SIZE
YOKE BOSS DIAMETER
VALVE STEM DIAMETER
mm
Inches
mm
Inches
25
54
71
2-1/8
2-13/16
9.5
12.7
3/8
1/2
50
71
90
2-13/16
3-9/16
12.7
19.1
1/2
3/4
60
90
3-9/16
19.1
3/4
68
90
3-9/16
19.1
3/4
1
1-1/4
1
1-1/4
80
127
5, 5H
25.4
31.8
100
127
5, 5H
25.4
31.8
130
127
5, 5H
31.8
1-1/4
Long Stroke
127
178
5H(1)
7
25.4 or 31.8
50.8
1 or 1-1/4
2
1. Heavy actuator to bonnet bolting.
UPPER
CLEARANCE
VOLUME
VOLUME
ABOVE
PISTON
VOLUME
BELOW
PISTON
LOWER
CLEARANCE
VOLUME
44B7217-C
44B7218-C
Figure 12. Clearance Volumes
11
Product Bulletin
61.2:585C
August 2002
585C Actuator
Actuator Thrust Capabilities
See tables 4, 5, 6, 7, 8, and 9.
Table 4. Type 585C Size 25 and 50 Actuator Thrust Capabilities, U.S. Units (spring retracts stem)
ACTU- SPRING
ATOR
RATE,
SIZE
lb/in
ACTUATOR
STEM
TRAVEL
TRAVEL,
INCHES
SPRING THRUST,
POUNDS
Stem
Retracted
d
NET THRUST FOR TYPE 585C WITH ACTUATOR STEM FULLY
EXTENDED AT FULL TRAVEL
Operating Pressure, psig(1)
Stem
Extended
d d
40
50
60
70
80
100
110
125
150
SPRING
COLOR
Force, Pounds
0
0
1040
1300
1560
1820
2080
2340
2600
2860
3250
3900
Springs
Not Used
9/16
3/4
7/8
1-1/8
200
200
200
200
313
350
375
425
730
690
660
610
990
950
920
870
1250
1210
1180
1130
1510
1470
1440
1390
1760
1730
1700
1650
2020
1990
1960
1910
2280
2250
2220
2170
2540
2510
2480
2430
2930
2900
2870
2820
3580
3550
3520
3470
Gold
400
9/16
3/4
7/8
1-1/8
400
400
400
400
625
700
750
850
410
340
290
190
670
600
550
450
930
860
810
710
1190
1120
1070
970
1450
1380
1330
1230
1710
1640
1590
1490
1970
1900
1850
1750
2230
2160
2110
2010
2620
2550
2500
2400
3270
3200
3150
3050
Light
Green
500
9/16
3/4
7/8
1-1/8
500
500
500
500
781
875
938
1063
260
160
100
X
520
420
360
240
780
680
620
500
1040
940
880
760
1300
1200
1140
1010
1560
1460
1400
1270
1820
1720
1660
1530
2080
1980
1920
1790
2460
2370
2310
2180
3110
3020
2960
2830
White
700
9/16
3/4
7/8
1-1/8
700
700
700
700
1094
1225
1313
1488
X
X
X
X
200
70
X
X
460
330
250
70
720
590
510
330
980
850
760
590
1240
1110
1020
850
1500
1370
1280
1110
1760
1630
1540
1370
2150
2020
1930
1760
2800
2670
2580
2410
Gold &
White
900
9/16
3/4
7/8
1-1/8
900
900
900
900
1406
1575
1688
1913
X
X
X
X
X
X
X
X
150
X
X
X
410
240
130
X
670
500
390
160
930
760
650
420
1190
1020
910
680
1450
1280
1170
940
1840
1670
1560
1330
2490
2320
2210
1980
Light Green
& White
0
All
0
0
1840
2300
2760
3220
3680
4140
4600
5060
5750
6900
Springs
Not Used
330
3/4
7/8
1-1/8
1-1/2
2
330
330
330
330
330
578
619
701
825
990
1310
1270
1180
1060
900
1780
1740
1660
1530
1370
2250
2210
2130
2000
1840
2720
2680
2600
2470
2310
3190
3150
3070
2950
2780
3660
3620
3540
3420
3250
4140
4090
4010
3890
3720
4610
4570
4480
4360
4190
5310
5270
5190
5070
4900
6490
6450
6370
6250
6080
Pink
600
3/4
7/8
1-1/8
1-1/2
2
600
600
600
600
600
1050
1125
1275
1500
1800
840
760
610
390
90
1310
1230
1080
860
560
1780
1700
1550
1330
1030
2250
2170
2020
1800
1500
2720
2650
2500
2270
1970
3190
3120
2970
2740
2440
3660
3590
3440
3210
2910
4130
4060
3910
3680
3380
4840
4770
4620
4390
4090
6020
5950
5800
5570
5270
Light
Blue
930
3/4
7/8
1-1/8
1-1/2
2
930
930
930
930
930
1628
1744
1976
2325
2790
260
140
X
X
X
730
610
380
30
X
1200
1080
850
500
40
1670
1560
1320
970
510
2140
2030
1790
1450
980
2610
2500
2270
1920
1450
3090
2970
2740
2390
1920
3560
3440
3210
2860
2390
4260
4150
3910
3570
3100
5440
5330
5090
4750
4280
Pink &
Light Blue
1550
3/4
7/8
1-1/8
1-1/2
2
1550
1550
1550
1550
1550
2710
2906
3294
3875
4650
X
X
X
X
X
X
X
X
X
X
110
X
X
X
X
580
385
X
X
X
1050
855
465
X
X
1520
1325
935
355
X
1990
1795
1405
825
50
2460
2265
1875
1295
520
3165
2970
2580
2000
1225
4345
4150
3760
3180
2405
Green
1880
3/4
7/8
1-1/8
1-1/2
2
1880
1880
1880
1880
1880
3290
3525
3995
4700
5640
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
470
235
X
X
X
940
705
235
X
X
1410
1175
705
X
X
1880
1645
1175
470
X
2585
2350
1880
1175
235
3765
3530
3060
2355
1415
Pink &
Green
0
All
200
25
50
X indicates where the listed supply pressure is not sufficient to overcome the opposing bias spring effect.
1. The maximum design pressure for size 25 and 50 actuator is 150 psig. Maximum rating for applications is 125 psig.
12
90
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 5. Type 585C Size 25 and 50 Actuator Thrust Capabilities, Metric Units (spring retracts stem)
ACTUACTU- SPRING ATOR
STEM
ATOR RATE,
N/mm TRAVEL,
SIZE
mm
SPRING
THRUST, N
Stem
Red
tracted
NET THRUST FOR TYPE 585C WITH ACTUATOR STEM FULLY
EXTENDED AT FULL TRAVEL
Operating Pressure, bar(1)
Stem
Exd d
tended
2.8
3.4
4.1
4.8
5.5
6.2
6.9
7.6
8.6
10.3
SPRING
COLOR
Force, N
0
0
4626
5783
6939
8096
9252
10,409
11,565
12,722
14,457
17,348
Springs
Not
Used
14.3
19.1
22.2
28.6
890
890
890
890
1393
1558
1669
1891
3247
3069
2936
2713
4404
4226
4092
3870
5560
5382
5249
5026
6717
6539
6405
6183
7829
7695
7562
7340
8985
8852
8718
8496
10,142
10,008
9875
9653
11,298
11,165
11,032
10,809
13,033
12,900
12,766
12,544
15,925
15,791
15,658
15,435
Gold
70.1
14.3
19.1
22.2
28.6
1780
1780
1780
1780
2781
3115
3338
3783
1824
1512
1290
845
2980
2669
2447
2002
4137
3825
3603
3158
5293
4982
4760
4315
6450
6139
5916
5471
7606
7295
7073
6628
8763
8452
8229
7784
9919
9608
9386
8941
11,654
11,343
11,121
10,676
14,546
14,234
14,012
13,567
Light
Green
87.6
14.3
19.1
22.2
28.6
2225
2225
2225
2225
3475
3894
4174
4730
1156
712
445
X
2313
1868
1601
1068
3470
3025
2758
2224
4626
4181
3914
3381
5783
5338
5071
4493
6939
6494
6227
5649
8096
7651
7384
6806
9252
8807
8541
7962
10,943
10,542
10,275
9697
13,834
13,434
13,167
12,588
White
122.6
14.3
19.1
22.2
28.6
3115
3115
3115
3115
4868
5451
5843
6622
X
X
X
X
890
311
X
X
2046
1468
1112
311
3203
2624
2269
1468
4359
3781
3381
2624
5516
4938
4537
3781
6672
6094
5694
4938
7829
7251
6850
6094
9564
8985
8585
7829
12,455
11,877
11,476
10,720
Gold &
White
157.7
14.3
19.1
22.2
28.6
4005
4005
4005
4005
6257
7009
7512
8513
X
X
X
X
X
X
X
X
667
X
X
X
1824
1068
578
X
2980
2224
1735
712
4137
3381
2891
1868
5293
4537
4048
3025
6450
5694
5204
4181
8185
7428
6939
5916
11,076
10,320
9831
8807
Light
Green &
White
0
All
0
0
8180
10,200
12,300
14,300
16,400
18,400
20,500
22,500
25,600
30,700
Springs
Not
Used
57.8
19.1
22.2
28.6
38.1
50.8
1468
1468
1468
1468
1468
2571
2753
3118
3670
4404
5827
5649
5249
4715
4003
7918
7740
7384
6806
6094
10,008
9831
9475
8896
8185
12,099
11,921
11,565
10,987
10,275
14,190
14,012
13,656
13,122
12,366
16,280
16,102
15,747
15,213
14,457
18,416
18,193
17,837
17,303
16,547
20,506
20,328
19,928
19,394
18,638
23,620
23,442
23,086
22,552
21,796
28,869
28,691
28,335
27,801
27,045
Pink
105.1
19.1
22.2
28.6
38.1
50.8
2669
2669
2669
2669
2669
4671
5004
5671
6672
8007
3736
3381
2713
1735
400
5827
5471
4804
3825
2491
7918
7562
6895
5916
4582
10,008
9653
8985
8007
6672
12,099
11,788
11,121
10,097
8763
14,190
13,878
13,211
12,188
10,854
16,280
15,969
15,302
14,279
12,944
18,371
18,060
17,392
16,369
15,035
21,529
21,218
20,551
19,528
18,193
26,778
26,467
25,800
24,777
23,442
Light
Blue
162.9
19.1
22.2
28.6
38.1
50.8
4137
4137
4137
4137
4137
7242
7758
8790
10,342
12,410
1157
623
X
X
X
3247
2713
1690
133
X
5338
4804
3781
2224
178
7428
6939
5872
4315
2269
9519
9030
7962
6450
4359
11,610
11,121
10,097
8541
6450
13,745
13,211
12,188
10,631
8541
15,836
15,302
14,279
12,722
10,631
18,949
18,460
17,392
15,880
13,789
24,198
23,709
22,641
21,129
19,038
Pink &
Light
Blue
271.4
19.1
22.2
28.6
38.1
50.8
6894
6894
6894
6894
6894
12054
12925
14652
17236
20683
X
X
X
X
X
X
X
X
X
X
489
X
X
X
X
2580
1712
X
X
X
4670
3803
2068
X
X
6761
5894
4159
1579
X
8852
7984
6249
3670
222
10942
10075
8340
5760
2313
14078
13211
11476
8896
5449
19,328
18,460
16,725
14,145
10,698
Green
329.2
19.1
22.2
28.6
38.1
50.8
8362
8362
8362
8362
8362
14634
15679
17770
20906
25087
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2091
1045
X
X
X
4181
3136
1045
X
X
6272
5226
3136
X
X
8362
7317
5226
2091
X
11498
10453
8362
5226
1045
16,748
15,702
13,612
10,476
6294
Pink &
Green
0
All
35.0
25
50
X—Indicates where the listed supply pressure is not sufficient to overcome the opposing bias spring effect.
1. The maximum design pressure for size 25 and 50 actuator is 10.3 bar. Maximum rating for applications is 8.6 bar.
13
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 6. Type 585C Size 25 and 50 Actuator Thrust Capabilities, U.S. Units (spring extends stem)
SPRING
THRUST W/
SPRING
ACTUATOR
ACTUATOR
RATE,
STEM
SIZE
lb/in
EXTENDED,
POUNDS
25(2)
50((3))
TOTAL THRUST FOR TYPE 585CR WITH ACTUATOR STEM FULLY
EXTENDED
Operating Pressure, psig(1)
40
50
60
70
80
90
100
110
125
150
SPRINGS USED, BY
COLOR
Force, Pounds
Springs
Not Used
0
0
1040
1300
1560
1820
2080
2340
2600
2860
3250
3900
200
200
1240
1500
1760
2020
2280
2540
2800
3060
3450
X
Gold
400
400
1440
1700
1960
2220
2480
2740
3000
3260
3650
X
Light Green
500
500
1540
1800
2060
2320
2580
2840
3100
3360
3750
X
White
700
700
1740
2000
2260
2520
2780
3040
3300
3560
X
X
Gold & White
900
900
1940
2200
2460
2720
2980
3240
3500
3760
X
X
Light Green
& White
0
0
1840
2300
2760
3220
3680
4140
4600
5060
5750
6900
Springs
Not Used
330
330
2210
2680
3150
3620
4090
4560
5030
5500
6205
X
Pink
600
600
2480
2950
3420
3890
4360
4830
5300
5770
6475
X
Light Blue
Pink & Light Blue
930
930
2810
3280
3750
4220
4690
5160
5630
6100
6805
X
1550
1550
3430
3900
4370
4840
5310
5780
6250
6720
X
X
Green
1880
1880
3760
4230
4700
5170
5640
6110
6580
7050
X
X
Pink & Green
X indicates where the listed supply pressure is not sufficient to overcome the opposing bias spring effect.
1. The maximum design pressure for size 25 and 50 actuator is 150 psig.
2. Maximum thrust is 3900 lbs.
3. Maximum thrust is 6900 lbs.
Table 7. Type 585C Size 25 and 50 Actuator Thrust Capabilities, Metric Units (spring extends stem)
SPRING
THRUST W/
SPRING
ACTUATOR
ACTUATOR
RATE,
STEM
SIZE
N/mm
EXTENDED,
N
0
25(2)
50((3))
TOTAL THRUST FOR TYPE 585CR WITH ACTUATOR STEM FULLY
EXTENDED
Operating Pressure, bar(1)
2.8
3.4
4.1
4.8
5.5
6.2
7.6
8.6
10.3
SPRINGS USED, BY
COLOR
Force, N
Springs
Not Used
0
4626
5782
6939
8095
9251
10408
11565
12721
14456
17347
35.0
890
5516
6672
7828
8985
10141
11298
12454
13610
15346
X
Gold
70.0
1780
6405
7562
8718
9874
11031
12188
13344
14500
16235
X
Light Green
87.6
2225
6850
8006
9163
10319
11476
12632
13789
14945
16680
X
White
122.6
3115
7740
8896
10052
11209
12365
13655
14678
15835
X
X
Gold & White
157.6
4005
8629
9786
10942
12099
13255
14412
15568
16724
X
X
Light Green
& White
0
0
8180
10200
12300
14300
16400
18400
20500
22500
25600
30700
Springs
Not Used
57.8
1468
9830
11921
14011
16102
18192
20282
22373
24464
27600
X
Pink
105.1
2670
11031
13122
15212
17303
19393
21484
23574
25665
28800
X
Light Blue
162.8
4135
12499
14589
16680
18770
20861
22952
25042
27133
30269
X
Pink & Light Blue
271.4
6894
15256
17347
19438
21528
23619
25709
27800
29891
X
X
Green
329.2
8362
16724
18815
20906
22996
25087
27177
29268
31358
X
X
Pink & Green
X indicates where the listed supply pressure is not sufficient to overcome the opposing bias spring effect.
1. The maximum design pressure for size 25 and 50 actuator is 10.3 bar.
2. Maximum thrust is 17347 N.
3. Maximum thrust is 30700 N.
14
6.9
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 8. Type 585C Thrust (springless construction)
TOTAL THRUST FOR TYPE 585C(1)
PISTON
ACTUATOR AREA
SIZE
Operating Pressure, bar(3)
2.8
3.4
4.1
4.8
5.5
cm2
6.2
6.9
7.6
8.6
10.3
Force, Newtons(2)
MAXIMUM ALLOWABLE
THRUST
Newtons
25
168
4630
5780
6940
8100
9260
10400
11600
12700
14500
17300
17300
50
303
8180
10200
12300
14300
16400
18400
20500
22500
25600
30700
31400
60(3)
358
9880
12300
14800
17300
19800
22200
24700
27200
30900
36900
36900
68(3)
571
15700
19700
23600
27600
31500
35400
39400
43300
49200
55600
55600(4)
80(3)
571
15700
19700
23600
27600
31500
35400
39400
43300
49200
58700
58700
100(3)
842
23200
29000
34800
40600
46400
52200
58000
63900
72600
X
86700
130(3)
1430
39400
49300
59100
69000
78700
88500
98800
108100
X
X
111200
PISTON
AREA
40
50
60
70
80
110
125
150
MAXIMUM ALLOWABLE
THRUST
ACTUATOR
SIZE
Operating Pressure, psig(3)
Inches2
90
100
Force, Pounds(2)
Pounds
25
26
1040
1300
1560
1820
2080
2340
2600
2860
3250
3900
3900
50
47
1840
2300
2760
3220
3680
4140
4600
5060
5750
6900
7050
60(3)
55.5
2220
2780
3330
3890
4440
5000
5550
6110
6940
8300
8300
68(3)
88.5
3540
4430
5310
6200
7080
7970
8850
9740
11100
12500
12500(4)
80(3)
88.5
3540
4430
5310
6200
7080
7970
8850
9740
11100
13200
13200
100(3)
130.5
5220
6530
7830
9140
10440
11700
13100
14400
16300
19500
19500
130(3)
221.5
8860
11100
13300
15500
17700
19900
22200
24300
X
X
25000
X indicates where the listed supply pressure will exceed the maximum thrust allowable.
1. The maximum design pressure for size 25 through 100 actuators is 10.3 bar (150 psig). Size 68 and 130 actuators are limited to 9.7 and 7.8 bar (140 and 113 psig) respectively.
2. The size 25 and 50 data is for the construction without a bias spring.
3. Minimum operating pressure for sizes 60-130 actuators is 2.4 bar (35 psig).
4. The size 68 actuator with a handwheel is limited to 40000 Newtons (9000 lb) thrust.
15
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 9. Type 585C Long-Stroke Thrust
PISTON
DIAMETER
STROKE
mm
TOTAL THRUST FOR TYPE 585C LONG-STROKE ACTUATORS(1)
PISTON
ROD
SIZE
PISTON
AREA
mm
mm2
Operating Pressure, bar
2.8
4.1
5.5
8.3
9.7
10.3
127
127
3500
5250
6980
8720
10500
12200
13100
152
182
5030
7560
10100
12600
15100
17600
18900
203
323
8940
13400
17900
22400
26800
31300
33500
507
14000
21000
27900
34900
41900
48900
52500
305
730
20100
30200
40300
50300
60500
70300
75600
356
993
27400
41100
54700
68500
82300
96100
103000
127
111
3060
4580
6140
7650
9210
10700
11500
152
167
4580
6890
9210
11500
13800
16100
17300
254
203
Push
Pull
---
44 5
44.5
309
8500
12800
17000
21300
25500
29800
31900
254
491
13600
20300
27100
33900
40700
47600
50700
203
293(2)
8050
12100
16100
20200
24200
28200
30200
254
475(3)
13100
19700
26200
32700
39300
45800
48900
698
19300
28900
38500
48000
57800
67200
72100
961
26500
39800
52900
66300
79600
93000
99600
120
140
150
305
Pull
63 5
63.5
356
PISTON
DIAMETER
STROKE
Inches
PISTON
ROD
SIZE
Inches
PISTON
AREA
Operating Pressure, psig
40
60
80
Inches2
100
Force, Pounds
5
19.6
786
1180
1570
1960
2360
2750
2950
6
28.3
1130
1700
2260
2830
3390
3960
4240
8
50.3
2010
3020
4020
5030
6030
7040
7540
78.5
3140
4710
6280
7850
9420
11000
11800
12
113.1
4520
6790
9050
11300
13600
15800
17000
14
153.9
6160
9240
12300
15400
18500
21600
23100
5
17.2
689
1030
1380
1720
2070
2410
2580
6
25.9
1030
1550
2070
2590
3100
3620
3880
47.9
1910
2870
3830
4790
5740
6700
7180
10
76.1
3050
4570
6090
7610
9140
10700
11400
8
45.4(2)
1810
2720
3630
4540
5440
6350
6800
10
73.6(3)
2950
4420
5890
7360
8840
10300
11000
108.2
4330
6490
8660
10800
13000
15100
16200
149.0
5960
8940
11900
14900
17900
20900
22400
10
8
12
14
Push
Pull
Pull
---
1 3/4
1-3/4
2 1/2
2-1/2
1. For operating pressures above 10.3 bar (150 psig), consult your Fisher sales office.
2. For travels greater than 406 mm (16 inches) with 10.3 to 17.3 bar (150 to 250 psig) operating pressure.
3. For travels greater than 406mm (16 inches).
16
6.9
Force, Newtons
Product Bulletin
61.2:585C
August 2002
585C Actuator
Handwheel Specifications
See table 10 for handwheel specifications.
Table 10. Type 585C Handwheel Specifications
HANDWHEEL
DIAMETER
mm
TURNS PER mm
TRAVEL
MAXIMUM RIM
FORCE REQUIRED
Newtons
HANDWHEEL
OUTPUT FORCE
Newtons
HANDWHEEL
WEIGHT
kg
356
0.5
325
12,810
17
482
0.5
445
23,790
20
60
203
0.6
276
40000
28
68
203
0.6
276
40000
30
432
0.4
423
50000
35
100
432
0.4
623
75600
94
130
432
0.4
623
75600
123
HANDWHEEL
OUTPUT FORCE
Pounds
HANDWHEEL
WEIGHT
Pounds
ACTUATOR SIZE
25
50
80
ACTUATOR SIZE
25
HANDWHEEL
MOUNTING
Top Mounted
Top-Mounted
Side-Mounted
Side
Mounted
HANDWHEEL
MOUNTING
HANDWHEEL
DIAMETER
Inches
MAXIMUM RIM
TURNS PER INCH FORCE REQUIRED
TRAVEL
Pounds
14
12
73
2880
37
19
12
100
5350
45
60
8
16
62
9000
61
68
8
16
62
9000
66
80
17
10
95
11250
77
100
17
10
140
17000
208
130
17
10
140
17000
272
50
Top Mounted
Top-Mounted
Side-Mounted
Side
Mounted
17
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 11. Type 585C Dimensions—Size 25 and 50 Actuator with Type 3611 Pneumatic (P/P) Positioner
ACTUATOR SIZE
YOKE
BOSS
SIZE
E
H
C
AR(1)
54.0
324.4
693.7
205.2
71.4
352.3
720.9
71.4
464.3
90.5
503.4
F
Jc
L
P
T
X
127.0
259.6
355.6
47.8
255.8
19.1
114.3
205.2
176.3
259.6
355.6
19.8
255.8
23.9
139.3
841.5
257.0
176.3
265.4
482.6
13.7
281.7
23.9
152.4
881.1
257.0
225.6
265.4
482.6
---
281.7
35.1
193.5
mm
25
50
Inches
25
50
2-1/8
12.77
27.31
8.08
5.00
10.22
14.00
1.88
10.07
0.75
4.50
2-13/16
13.87
28.38
8.08
6.94
10.22
14.00
0.78
10.07
0.94
5.50
2-13/16
18.28
33.13
10.12
6.94
10.45
19.00
0.54
11.09
0.94
6.00
3-9/16
19.82
34.69
10.12
8.88
10.45
19.00
---
11.09
1.38
7.62
1. Actuator removal clearance
18B5463-A
H
17B3436-B
Figure 13. Type 585C Dimensions—Size 25 and 50 Actuator with Type 3611 Pneumatic (P/P) Positioner (also see table 11)
18
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 12. Type 585C Dimensions—Size 25 and 50 Actuator with Type 3621 Electro-Pneumatic (I/P) Positioner
ACTUATOR SIZE
YOKE BOSS
SIZE
E
H
C
54.0
322.1
681.0
71.4
350.0
71.4
90.5
AR(1)
F
Jc
L
P
205.2
127.0
216.7
355.6
96.0
303.5
720.9
205.2
176.3
216.7
355.6
68.1
303.5
462.0
836.4
257.0
176.3
222.5
482.6
62.5
329.4
501.1
875.6
257.0
225.6
222.5
482.6
23.4
329.4
mm
25
50
Inches
25
50
2-1/8
12.68
26.81
8.08
5.00
8.53
14.00
3.78
11.95
2-13/16
13.78
28.38
8.08
6.94
8.53
14.00
2.68
11.95
2-13/16
18.19
32.93
10.12
6.94
8.76
19.00
2.46
12.97
3-9/16
19.73
34.47
10.12
8.88
8.76
19.00
0.92
12.97
1. Actuator removal clearance
17B3435-B
H
18B6671-A
Figure 14. Type 585C Dimensions—Size 25 and 50 Actuator with Type 3621 Electro-Pneumatic (I/P) Positioner (also see table 12)
19
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 13. Type 585C Dimensions—Size 60 to 130 Actuator
ACTUATOR
SIZE
60
68
80
100
130
B
DIAMETER
A
C(1)
AR
D
F
DIAMETER
E
ARH
TRAVEL
mm
Inch
mm
Inch
mm
Inch
mm
Inch
mm
Inch
mm
Inch
mm
Inch
mm
Inch
2
462
18.2
267
10.5
305
12.0
226
8.9
734
28.9
206
8.1
203
8.0
273
10.8
4
564
22.2
267
10.5
305
12.0
226
8.9
785
30.9
206
8.1
203
8.0
273
10.8
8
782
30.8
267
10.5
305
12.0
232
9.1
1074
42.3
206
8.1
356
14.0
279
11.0
2
597
23.5
325
12.8
330
13.0
226
8.9
853
33.6
206
8.1
203
8.0
273
10.8
4
729
28.7
325
12.8
330
13.0
226
8.9
853
33.6
206
8.1
203
8.0
273
10.8
8
828
32.6
325
12.8
330
13.0
232
9.1
1143
45.0
206
8.1
356
14.0
279
11.0
4
714
28.1
325
12.8
330
13.0
295
11.6
1245
49.0
305
12
432
17.0
295
11.6
8
965
38.0
325
12.8
330
13.0
295
11.6
1344
52.9
305
12
432
17.0
295
11.6
4
714
28.1
381
15.0
361
14.2
321
12.6
1245
49.0
305
12
432
17.0
321
12.6
8
958
37.7
381
15.0
361
14.2
321
12.6
1346
53.0
305
12
432
17.0
321
12.6
4
833
32.8
483
19.0
411
16.2
321
12.6
1410
55.5
305
12
432
17.0
321
12.6
8
1006
39.6
483
19.0
411
16.2
321
12.6
1725
67.9
305
12
432
17.0
321
12.6
1. The “C” dimension shown is for FIELDVUE DVC5000 or DVC6000 digital valve controllers. Add 38.1 mm (1.5 inches) to this dimension for Type 3620JP positioners.
Subtract 12.7 mm (0.5 inches) to this dimension for Type 3610JP positioners.
B
AR
F
D
A
B
ARH
E
1
C
A
WITH MANUAL OPERATOR
WITH DVC5000 OR DVC6000
DIGITAL VALVE CONTROLLER
1
THE “C” DIMENSION LISTED IN THE TABLE IS
FOR THE ACTUATOR WITH THE FIELDVUE
DIGITAL VALVE CONTROLLER. ADD TO THIS
DIMENSION FOR TYPE 3620JP POSITIONERS.
SUBTRACT FROM THIS DIMENSION FOR TYPE
3610JP POSITIONERS. REFER TO THE FOOTNOTE IN THE TABLE.
1
C
WITH TYPE 3610 OR 3620 POSITIONER
Figure 15. Type 585C Dimensions—Size 60 to 130 Actuator (also see table 13)
20
Product Bulletin
61.2:585C
August 2002
585C Actuator
Table 14. Type 585C Long Stroke Dimensions (Fabricated
Yoke)
DIMENSION
TRAVEL
E
(w/o Handwheel)
B
E
(w/ Handwheel)
mm
In.
mm
In.
mm
In.
mm
In.
229
254
279
305
9
10
11
12
762
762
762
762
30
30
30
30
1217
1242
1267
1293
47.9
48.9
49.9
50.9
1722
1748
1773
1798
67.8
68.8
69.8
70.8
330
356
381
406
13
14
15
16
864
864
864
864
34
34
34
34
1420
1445
1471
1496
55.9
56.9
57.9
58.9
2027
2052
2078
2103
79.8
80.8
81.8
82.8
432
457
483
508
17
18
19
20
965
965
965
965
38
38
38
38
1623
1648
1674
1699
63.9
64.9
65.9
66.9
2332
2357
2383
2408
91.8
92.8
93.8
94.8
533
559
584
610
21
22
23
24
1067
1067
1067
1067
42
42
42
42
1826
1852
1877
1902
71.9
72.9
73.9
74.9
2637
2662
2687
2713
103.8
104.8
105.8
106.8
Table 15. Type 585C Long Stroke Dimensions (Fabricated
Yoke)
Cylinder
Diameter
mm (Inch)
E Dimension
Correction
Factor
mm (Inch)
152
(6)
203
(8)
254
(10)
305
(12)
356
(14)
84
(3.3)
69
(2.7)
82
(3.2)
46
(1.8)
33
(1.3)
0
(0)
191
(7.50)
194
(7.62)
MAX
1
127
(5)
E
54
(2.12)
B
1
E
B
42A4726-A / IL
TYPE 585C LONG STROKE ACTUATOR
NOTE:
THE E DIMENSIONS SHOWN ARE FOR A 356 mm (14-INCH)
1
DIAMETER PISTON. THE E DIMENSION FOR SMALLER PISTONS
WILL BE SLIGHTLY LESS. SUBTRACT THE FOLLOWING VALUE
FROM THE E DIMENSION FOR SMALLER CYLINDERS.
B2522 / IL
52A4727-A / IL
324
(12.75)
TYPE 585C LONG STROKE ACTUATOR WITH HANDWHEEL
Figure 16. Type 585C Long Stroke Dimensions (Fabricated Yoke) (also see tables 14 and 15)
21
Product Bulletin
61.2:585C
August 2002
585C Actuator
Specifications - Type 585C Actuators (sizes 25-130)
Operating Pressure
Sizes 25-50:
Maximum Allowable: 10.3 bar (150 psig)
Minimum Recommended: 1.4 bar (20 psig)
Sizes 60-130:
Maximum Allowable: See table 8.
Minimum Recommended: 2.4 bar (35 psig)
Travel
See table 2
Sizes 50-60:
J 1/4 inch NPT female (standard), or J 1/2 inch
NPT female (optional)
Sizes 68-130:
J 1/2 inch NPT female (standard)
Instrument Mounting
The Type 585C actuator has NAMUR mounting
capability on sizes 25 through 130.
Construction Materials
Thrust Capabilities
See tables 4, 5, 6, 7, and 8
Part
Stroking Speeds
Varies with actuator size, actuator spring, travel,
and supply pressure. If stroking speed is critical,
consult your Fisher sales office
Piston Area
See table 8
Cylinder Volumetric Displacement
See table 2
Operative Temperature Limits
For All Sizes:
With Nitrile O-Rings: –50 to 80_C (–58 to 175_F),
standard
With Fluoroelastomer O-Rings: –18 to 150_C
(0 to 300_F), optional
Ductile Iron
Piston
Aluminum
Cylinder
Aluminum
Bolting and Fasteners
NCF (non-corroding finish)
Springs (sizes 25 & 50 only)
Alloy Steel
O-Rings
Nitrile (std), Fluoroelastomer, or
EPDM
Actuator Stem
Chrome-plated Steel
Stem Connection
Stainless Steel
Travel Indicator Scale
Stainless Steel
Paint
Polyester Powder
Actuator Stem
(sizes 60-130 only)
S41600 (416) SST, Chrome Plate
Cylinder Seal Bushings
(sizes 60-130 only)
Brass
Approximate Weights (less positioner and
handwheel)
Size 25:
2-1/8 inch yoke boss, 7 kg (16 pounds)
2-13/16 inch yoke boss, 8 kg (17 pounds)
Size 50:
2-13/16 inch yoke boss, 20 kg (45 pounds)
3-9/16 inch yoke boss, 22 kg (48 pounds)
Size 60: 31 kg (68 pounds)
Size 68: 54 kg (120 pounds)
Size 80: 102 kg (225 pounds)
Size 100: 113 kg (250 pounds)
Size 130: 188 kg (415 pounds)
Yoke Boss and Valve Stem Diameters
See table 3
Pressure Connections
Size 25:
J 1/4 inch NPT female (standard), or J 3/8 inch
NPT female (optional)
- continued -
22
Material
Yoke
Product Bulletin
61.2:585C
August 2002
585C Actuator
Specifications - Type 585C Actuators (sizes 25-130) (continued)
Options
Sizes 25 and 50:
J Top-mounted handwheel, see figures 13 and
14 and table 10.
J Cylinder bypass valve J Limit switches J 4200
Series position transmitter
Sizes 60-80:
J Side-mounted handwheel
Sizes 60-130:
J FIELDVUEr mounting options
J 377 Series trip valve system to fail actuator
J up or J down or J lock in last position
J Type 304 electrical valve stem position switch
J Micro-Switch limit switches
Dimensions
See figures 13 and 14
Specifications - Type 585C Long-Stroke (Fabricated Yoke) Actuators
Cylinder Pressure
Minimum Recommended: For valves with low
thrust requirements—2.4 bar (35 psig); for all
other valves—3.4 bar (50 psig)
Maximum Allowable: 127 mm (5-inch) to 305
mm (12-inch) Diameter Cylinders—17.2 bar (250
psig) unless limited by maximum allowable supply
pressure of positioner or switching devices; 356
mm (14-inch) diameter cylinder—13.8 bar (200
psig) unless limited by maximum allowable supply
pressure of positioner or switching device
With Fluoroelastomer O-Rings: –18 to 150_C
(0 to 300_F), optional
Piston Diameters and Areas
See table 9
Yoke Boss and Valve Stem Diameters
See table 3
Pressure Connections
Standard is 1/4-inch NPT. For larger sizes,
consult your sales office
Travel Information
All Types: 229 mm (9 inches) through 610 mm
(24 inches) in 25 mm (1-inch) increments as
shown in figure 16.
Travel Ratio for Handwheel Construction: 10
complete revolutions of wheel moves stem 25 mm
(1 inch)
Thrust Information
See table 9
Operative Ambient Temperature(2)
For All Sizes:
With Nitrile O-Rings: –50 to 80_C (–58 to 175_F),
standard
Construction Materials
Part
Material
Cylinder Body: 127 mm through 356 mm
(5-inch through 14-inch)
Steel, chrome plated
Piston Rod
Steel, chrome plated
Yoke
Structural Steel
Options
J High temperature piston seals to 177_C
(350_F), J 377 Series trip valves to fail actuator
up, down, or lock in last position, J Limit
switches, J Side-mounted handwheel
Dimensions
See figure 16
1. Scfh - Standard cubic feet per hour (60_F and 14.7 psia); normal m3/hr - normal cubic meters per hour (0_C and 1.01325 bar, absolute)
2. These terms are defined in ANSI/ISA S51.1
23
Product Bulletin
61.2:585C
August 2002
585C Actuator
Specifications - DVC6000 Series Digital Valve Controllers
(refer to bulletin 62.1:DVC6000 for complete DVC6000 information)
Available Configurations
DVC6010: Sliding-stem applications with travels
of 101.6 mm (4 inches) or less
DVC6020: Sliding-stem applications with greater
than 101.6 mm (4 inches) travel
At 5.5 bar (80 psig) supply pressure: Less than
1.3 normal m3/hr (47 scfh)
Maximum Output Capacity(2)(3)
Input Signal(1)
Point-to-Point:
Analog Input Signal: 4–20 mA dc, nominal; split
ranging available
Minimum Voltage Available at Instrument
Terminals must be 10.5 volts dc for analog
control, 11 volts dc for HART communication (see
instrument instruction manual for details)
Minimum Control Current: 4.0 mA
Minimum Current w/o Microprocessor Restart: 3.5
mA
Maximum Voltage: 30 volts dc
Overcurrent Protection: Input circuitry limits
current to prevent internal damage
Reverse Polarity Protection: No damage occurs
from reversal of loop current
Multi-drop:
Instrument Power: 11 to 30 volts dc at
approximately 8 mA
Reverse Polarity Protection: No damage occurs
from reversal of loop current
At 1.4 bar (20 psig) supply pressure: 10.7
normal m3/hr (400 scfh)
At 5.5 bar (80 psig) supply pressure: 33.2
normal m3/hr (1240 scfh)
Independent Linearity(1)(4)
+/–0.5% of output span
Electromagnetic Interference (EMI)
These instruments have the CE mark in
accordance with the Electromagnetic
Compatibility (EMC) Directive. They meet the
requirements of EN61326-1 (emissions for light
industry, immunity for industrial environment).
Electrical Classification
Hazardous Area: Approvals are pending from
certifying agencies. Refer to Hazardous Area
bulletins.
Electrical Housing: Designed to meet NEMA 4X,
IEC 60529 IP65 (approvals pending)
Connections
Output Signal(1)
Pneumatic signal as required by the actuator, up
to full supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: J Double, J Single Direct, and J Single
Reverse
Supply Pressure
Minimum Recommended: 0.3 bar (5 psig)
higher than maximum actuator requirements
Maximum: 10.3 bar (150 psig) or maximum
pressure rating of the actuator, whichever is lower
Supply Pressure: 1/4-inch NPT female and
integral pad for mounting 67CFR regulator
Output Pressure: 1/4-inch NPT female
Tubing: 3/8-inch metal, recommended
Vent (pipe-away): 1/4-inch NPT female
Electrical: 1/2-inch NPT female conduit
connection, M20 adaptor optional
Operating Ambient Temperature Limits
–40 to 85_C (–40 to 185_F)
Construction Materials
Steady-State Air Consumption(1)(2)(3)
At 1.4 bar (20 psig) supply pressure: Less than
0.38 normal m3/hr (14 scfh)
- continued -
24
Housing, module base and terminal box: ANSI
B360.0 low copper aluminum alloy
Cover: Valox
Elastomers: J Nitrile (standard), or
J Fluoroelastomer (optional)
Product Bulletin
61.2:585C
August 2002
585C Actuator
Specifications - DVC6000 Series Digital Valve Controllers
(refer to bulletin 62.1:DVC6000 for complete DVC6000 information) (continued)
Stem Travel
DVC6010: 0 to 102 mm (4 inches) maximum
0 to 9.5 mm (3/8 inches) minimum
DVC6020: 0 to 606 mm (23-7/8 inches) maximum
Weight
Mounting
Designed for direct actuator mounting. For
weatherproof housing capability, the instrument
must be mounted upright to allow the vent to
drain.
Options
3.5 kg (7.7 lbs)
J Supply and output pressure gauges or J tire
valves, J integral mounted filter regulator,
J Fluoroelastomer O-rings
1. These terms are defined in ISA Standard S51.1.
2. Normal m3/hr - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute; Scfh - Standard cubic feet per hour at 60_F and 14.7 psia.
3. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
4. Not applicable for Type DVC6020 digital valve controllers in long-stroke applications.
25
Product Bulletin
61.2:585C
August 2002
585C Actuator
Specifications - 3600 Series Positioners
Available Configurations
J Pneumatic (P/P) Positioner: Type 3610JP
and 3611JP
J Electro-Pneumatic (I/P) Positioner: Type
3620JP and 3621JP
steady-state deviation is less than +/–1% at an
electromagnetic field strength of 30 V/m from 20
to 1000 MHz. Positioner is tested with cover on
and with external wiring in rigid metal conduit.
Maximum Supply Air Demand(3)
Type 3610JP, 3620JP, 3611JP, and 3621JP:
5.2 Bar (75 Psig) Supply: 37 normal m3/hour
(1380 scfh)
6.9 Bar (100 Psig) Supply: 46 normal m3/hour
(1700 scfh)
Application by Size
J Size 25 and 50: Type 3611JP and 3621JP
J Size 60-130 and Type 585C Long-Stroke:
Type 3610JP and 3620JP
Input Signal(1)
Type 3610JP and 3611JP:
Standard: J 0.2 to 1.0 bar (3 to 15 psig), J 0.4 to
2.0 bar (6 to 30 psig), or J split range, see table
16.
Adjustable: Zero is adjustable from 0.07 to 1.5 bar
(1 to 22 psig) for standard valve travels. Span is
adjustable from 0.2 to 2.0 bar (3.2 to 28.8 psi) for
standard valve travels.
Type 3620JP and 3621JP:
4 to 20 mA dc constant current with 30 V dc
maximum compliance voltage. Minimum terminal
voltage is 2.4 V dc at 20 mA. Split range is also
available, see table 16.
Supply Pressure(1)
Minimum Recommended: 0.3 bar (5 psig) above
actuator requirement
Maximum: 10.3 bar (150 psig) or maximum
pressure rating of the actuator, whichever is lower
Steady-State Air Consumption(3)
Type 3610JP: 0.64 normal m3/hour (24 scfh) at
6.9 bar (100 psig) supply pressure
Type 3620JP: 0.93 normal m3/hour (35 scfh) at
6.9 bar (100 psig) supply pressure
Operative Temperature Limits(1)
–40 to 82_C (–40 to 180_F)
Equivalent Circuit
Type 3620JP and 3621JP: 120 ohms shunted by
three 5.6 V zener diodes
Housing Classification for 3620JP and 3621JP
Output Signal(1)
Pneumatic pressure as required by the actuator
up to full supply pressure
Action(2): Field-reversible between J direct and
J reverse within the pneumatic positioner
Electrical Classification for 3620JP and 3621JP
Typical Performance
(Refer to table 17 for typical performance for
Type 3611JP and 3621JP Positioners)
Independent Linearity(1)
Direct-Acting Type 3610JP and 3620JP: ±1.25%
of output span
Reverse-Acting Type 3610JP and 3620JP: ±0.5%
of output span
Hysteresis(1)
Type 3610JP: 0.5% of output span
Type 3620JP: 0.6% of output span
Deadband(1): 0.1% of input span
Electromagnetic Interference (EMI)(1) for
3620JP and 3621JP:
When tested per IEC 60801-3 (1984),
NEMA 3, IEC 60529 IP54; Instrument should be
mounted with vent on side or bottom to meet
weatherproofing classification
Refer to the Hazardous Area Classification
bulletin for specific approvals
Construction Materials
All Positioners:
Case: Low copper aluminum alloy
Cover: Polyester plastic
Feedback Lever: Stainless steel
Range Spring: Zinc-plated steel
Input Module and Relay Diaphragms: Nitrile and
Dacron
Relay Valve Plugs and Seats: Stainless steel
Tubing: Copper (standard)
Fittings: Brass (standard)
Gauges: Chrome-plated brass connection with
plastic case
Type 3620JP and 3621JP:
Housing and Cap: Low copper aluminum alloy
-continued-
26
Product Bulletin
61.2:585C
August 2002
585C Actuator
Specifications—3600 Series Positioners (continued)
Pressure Connections
Options
Type 3610JP, 3611JP, 3620JP, and 3621JP:
J Supply pressure gauge, J tire valves, or
J plugs
1/4-inch NPT female
Conduit Connection for Type 3620JP and 3621JP
Approximate Weight
3610JP and 3611JP: 2.5 kg (5.6 pounds)
3620JP and 3621JP: 3.6 kg (8.0 pounds)
1/2-inch NPT female (standard), M20 or PG13
adaptor (optional)
1. These terms are defined in ISA Standard S51.1
2. For direct action, an increasing input signal extends the actuator rod. For reverse action, an increasing input signal retracts the actuator rod.
3. Normal m3/hr - normal cubic meters per hour (0_C and 1.01325 bar absolute). Scfh - standard cubic feet per hour (60_F and 14.7 psia).
Table 16. Split-Ranging Capabilities
TYPE 3610JP/3611JP PNEUMATIC (P/P) POSITIONER
Split
0.2 to 1.0 Bar (3 to 15 Psig) Input Signal
0.4 to 2.0 Bar (6 to 30 Psig) Input Signal
Bar
Psig
Bar
Psig
Two-way
0.2 to 0.6
0.6 to 1.0
3 to 9
9 to 15
0.4 to 1.2
1.2 to 2.0
6 to 18
18 to 30
Three-way
0.2 to 0.5
0.5 to 0.7
0.7 to 1.0
3 to 7
7 to 11
11 to 15
0.4 to 0.9
0.9 to 1.5
1.5 to 2.0
6 to 14
14 to 22
22 to 30
TYPE 3620JP/3621JP ELECTRO-PNEUMATIC (I/P) POSITIONER(1)
Split
4 to 20 Milliampere Input Signal
Two-way
4 to 12
12 to 20
Three-way
4 to 9.3
9.3 to 14.7
14.7 to 20
1. Hazardous area approvals are not available with split range applications.
Table 17. Typical Performance Specifications (1) for Type 3611JP and Type 3621JP Positioners with Size 25 and 50 Actuators
Size 25 Actuator(8)
Characteristic
Size 50 Actuator(8)
Deadband(1,2)
0.1% of input span
0.1% of input span
Step Response(1,3,5)
0.3 seconds
0.3 seconds
Steady-State Air Consumption(2,4,7)
0.64 normal m3/hr (24 scfh)
0.64 normal m3/hr (24 scfh)
Hysteresis(3)
0.5% of output span
0.5% of output span
Terminal-Based Linearity(2,6)
1% of output span
1% of output span
Frequency Response(1,2) (–6 dB)
2 Hz
2 Hz
Supply Pressure Sensitivity
10% change in supply pressure changes the actuator stem position less than 0.1%
1. Performance tests are based on 6.9 bar (100 psig) supply pressure and lightest actuator springs. Performance will vary with other pressures and springs.
2. These terms are defined in ISA Standard S51.1.
3. Step response is the time for the actuator to reach 63 percent of expected travel after a 10 percent step change in input signal.
4. At 6.9 bar (100 psig) supply pressure. Scfh—standard cubic feet per hour (60_F and 14.7 psia). Normal m3/hr-cubic meters per hour (0_C and 1.01325 bar).
5. Type 3621JP positioner step response equals 0.4 seconds.
6. Type 3621JP positioner terminal-based linearity equals +/–2.25%.
7. Type 3621JP positioner steady-state air consumption equals 0.93 normal m3/hr (35 scfh).
8. Size 25 and 50 actuators tested with appropriate parallel flexure (key 179).
27
Product Bulletin
61.2:585C
August 2002
585C Actuator
FIELDVUE and Fisher are marks owned by Fisher Controls International, Inc., a business of Emerson Process Management. The Emerson
logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy,
they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use
or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Fisher does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and
maintenance of any Fisher product remains solely with the purchaser and end-user.
Emerson Process Management
Fisher
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
www.Fisher.com
28
EFisher
Controls International, Inc. 1994, 2002; All Rights Reserved
Printed in USA
Download