Central monitoring of self-contained luminaires

advertisement
Central monitoring
of self-contained luminaires
© 2014 Eaton, All Rights Reserved.
Categories for self-contained luminaires
"Unmonitored" luminaires
•
•
Only the battery charge circuit is tested –
if voltage exists  green LED lights up
Manual tests and inspection book management
Luminaires with automatic test - AT
•
•
•
The battery and light source circuit (LED) is continuously
monitored and the status displayed via LED
Automatic start of specified tests
•
•
Weekly function test
Annual duration test
Manual inspection book management
Centrally monitored luminaires: CGLine+ system
•
•
•
•
Luminaire monitoring and automatic tests: see AT
Central display of system status
Automatic inspection book management with digital memory
Web access – and visualization possible with CGVision
© 2014 Eaton, All Rights Reserved.
2
Self-contained luminaire System CGLine+
Simply the most flexible, reliable monitoring
for peace of mind
© 2014 Eaton, All Rights Reserved.
3
Installation, commissioning, operation
© 2014 Eaton, All Rights Reserved.
CGLine+ Web-Controller: Installation
1
•
•
•
Up to 800 luminaires per
CGLine+ Web-Controller
4 lines with up to 200 luminaires
(or 2 lines with up to 400 luminaires)
2
3
200
Line 4
ID: C0 0E A2 ID: EF A0 3D
2
3
ID: 46 FC A8
200
ID: DC 57 FA ID: BE EC 7B ID: 2F 24 BC
ID: ED 3C 8B
ID: A0 08 F0
1
Line 3
No manual addressing
(distinctive ID per luminaire)
1
2
3
200
Line 2
•
Automatic luminaire detection
ID: EE F8 CD ID: 9F F0 FC ID: 0F ED 2F
•
•
Easy assignment due to free
short address assignment
Individual name for each
luminaire
1
2
3
ID: CD 4F 7A
200
Line 1
ID: 4F E7 44
© 2014 Eaton, All Rights Reserved.
ID: F6 45 AB ID: 7D BD 1C
ID: 1C D0 EF
5
800 Luminaires per Controller
4 lines with up to 200 luminaires per line
Line 1
1
2
3
200
1
2
3
200
1
2
3
200
1
2
3
200
1
2
3
400
1
2
3
400
Line 2
Line 3
Line 4
or 2 lines with up to 400 luminaires per line
Line 1
Line 2
© 2014 Eaton, All Rights Reserved.
6
Distinctive ID per luminaire
Addressing of CGLine+ luminaires
•
Distinctive Address, six characters ID-Number in HEX-Code
•
No manual addressing
•
Numeric short address free programmable for each luminaire
•
Individual name (20 characters) for each luminaire
ID
A008F0
C00EA2
EFA03D
F645AB
46FCA8
ED3C8B
1
2
3
4
5
6
Exit 1st
floor north
Hall
1st floor front
Hall
1st floor, mid1
Hall
1st floor, mid2
Hall
1st floor, back
Exit
1st floor south
Line 1
Short digital
address
Individual
name
© 2014 Eaton, All Rights Reserved.
7
Web-Server
Safety under control worldwide
•
•
•
An integrated web server is available for convenient visualization, control and monitoring of
all connected CGLine+ luminaires.
From any PC with an IP connection and a regular web browser
Without requiring any special software
Line 1
1
2
3
200
1
2
3
200
1
2
3
200
1
2
3
200
Line 2
Line 3
Line 4
IP connection
© 2014 Eaton, All Rights Reserved.
8
Overview Zones
Maintain an overview:
Allocate the luminaires to zones
•
Up to 8 zones per line with 4 lines / 16 zones per line with max. of 2 lines
Zone 1
Zone 2
Zone 3
Line 1
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Line 2
© 2014 Eaton, All Rights Reserved.
9
Zone segmentation
4 lines with up to 200 luminaires per line
Number
of
lines
No. of
zones /
line
Numbering
zones
Max. no.
luminaires
per zone
Numbering
luminaires
Total
number of
luminaires
4
2
1-2
100
1 - 100
800
4
4
1-4
50
1 - 50
800
4
5
1-5
40
1 - 40
800
4
8
1-8
25
1 - 25
800
2 lines with up to 400 luminaires per line
Number
of
lines
No. of
zones /
line
Numbering
zones
Max. no.
luminaires
per zone
Numbering
luminaires
Total
number of
luminaires
2
4
1-4
100
1 - 100
800
2
8
1-8
50
1 - 50
800
2
10
1 -10
40
1 - 40
800
2
16
1 - 16
25
1 - 25
800
© 2014 Eaton, All Rights Reserved.
10
Automatic Test
Never forgetting a test
•
Automatic function test and duration test of
luminaires
Testing at the right time
•
Up to 8 different test groups for FT and DT
Test
group 1
1
2
3
Test
group 2
© 2014 Eaton, All Rights Reserved.
4
5
6
11
Electronic Log book
Electronic log book saves the need for manual logging
•
•
•
•
•
Electronic inspection book for automatic saving of
results from function and duration tests
Stored for at least four years, in compliance with standards
Downloadable in TXT or DAT file format
DAT file can be transported using a regular USB stick
Efficient and convenient analysis of the log book using the
CGLine+ PC software
or
© 2014 Eaton, All Rights Reserved.
12
Automatic e-mail dispatch
Always informed
•
•
•
•
Automatic email dispatch if faults occur
Assignable events
2 recipient groups to implement hierarchical escalation
Acknowledgment function
Line 1
1
2
3
200
1
2
3
200
1
2
3
200
1
2
3
200
Line 2
Line 3
Line 4
Integrated
email function
IP connection
© 2014 Eaton, All Rights Reserved.
13
Control commands per luminaire
Selective assignment commends
•
•
•
•
Blocking / Release
Manual start or stopping of a
Function- or Duration test
Switch off / on of maintained
mode luminaires
All luminaires, per line, per
zone or per single luminaire
© 2014 Eaton, All Rights Reserved.
14
Floor layouts
Maintaining orientation in complex buildings
•
Luminaires visualised in up to 30 different floor layouts (across lines)
© 2014 Eaton, All Rights Reserved.
15
PC-Software
Compatibility with the CGLine 400 System
•
•
Extended CGLine+ functions only with
unmixed CGLine+ luminaires
Operation in CGLine 400 compatibility mode
with CGLine 400 luminaires
CGLine+
luminaires
CGLine 400
luminaires
CGLine+
Controller
CGLine+ mode
CGLine 400 mode
CGLine 400
Controller
CGLine 400 mode
CGLine 400 mode
USB
connection
Configuration with PC-Software
•
•
•
•
Short address and individual name
per luminaire
Zone assignment of luminaires
Defining of test groups
Entire system can be configured
in offline mode regardless of whether
the IT network is available
Line 1
1
2
3
200
1
2
3
200
1
2
3
200
1
2
3
200
Line 2
Line 3
Line 4
© 2014 Eaton, All Rights Reserved.
16
CGLine+ data line
2 wires are sufficient
•
Cross-section according to cable
lengths
•
No shielding required
Cable length per line (400 luminaires)
Crosssection
Length
With 4 lines in total
0.5 mm2
330 m
1320 m
1.0 mm2
660 m
2640 m
1.5 mm2
1000 m
4000 m
Free topology
•
Cabling can be with star, tree or line
Data per line
configurations
Robust against faults
•
Supply voltage on bus
25 V DC
Max. permissible voltage
drop
14 V
Bus current
400 mA
No shielding required
© 2014 Eaton, All Rights Reserved.
17
Overview CGLine+ System
LAN
LAN
LAN
LAN
LAN
© 2014 Eaton, All Rights Reserved.
18
Overview CGLine+ System
CGLine+ Web-Controller:
With integrated memory for
storing the configuration and
the log book
IP connection
Integrated e-mail
function
PC connected to the network or an
optional CGLine+ Wireless Monitoring
Set: Access using the integrated web
interface
USB stick: To
conveniently
assess the log
book on the PC
CGLine+ PC-Software
for configuration
© 2014 Eaton, All Rights Reserved.
Visualization of up to 800 luminaires
(4 lines with max. 200 lights each or 2 lines
with max. 400 lights each, in case of nonmixed installation of CGLine+ lights)
Printer: Printing out the log
book
19
Hardware, Software
© 2014 Eaton, All Rights Reserved.
CGLine+ Web-Controller
4 USB-1 host for
connecting a USB
stick
5 USB-2 device for
1
2
connection to PC
3
4
5
6 PE/L/N 230V 50/60Hz
7 Connection
CGLine+ bus
line 1-4
8 RS485
6
7
8
9
10
9 LAN (RJ45)
with LED displays:
Yellow = Link
Green = Traffic
1 LED displays Line 1 to Line 4
2 Status LED display of the device:
3 Push button:
10 S1/S2 = Block input
signalizes transmission to the
CGLine+ lines:
Green = receive;
Yellow = send
Power (green) = mains power O.K.
Test (yellow/green) = FT/DT indication
Failure (red) = sum failure
service = e.g. starting a FT
System = establish a USB
connection on USB2
In1, In2 = 2 x digital inputs
11, 12, 14, 21, 22, 24 =
2 x relay outputs
© 2014 Eaton, All Rights Reserved.
21
CGLine+ Web-Controller
© 2014 Eaton, All Rights Reserved.
22
CGLine+ Software: Starting screen
© 2014 Eaton, All Rights Reserved.
23
CGLine+ Software: Failure indication
© 2014 Eaton, All Rights Reserved.
24
CGLine+ Software: Failures per zone
© 2014 Eaton, All Rights Reserved.
25
CGLine+ Software: Overview luminaires
© 2014 Eaton, All Rights Reserved.
26
CGLine+ Software: Commands
© 2014 Eaton, All Rights Reserved.
27
CGLine+ Software: Test groups
© 2014 Eaton, All Rights Reserved.
28
CGLine+ Software: Email function
© 2014 Eaton, All Rights Reserved.
29
CGLine+ Software: Log book
© 2014 Eaton, All Rights Reserved.
30
CGLine+ Software: Layout
© 2014 Eaton, All Rights Reserved.
31
CGLine+ Wireless Monitoring Set
Mobile monitoring
•
•
•
•
•
•
•
Wireless visualization of up to 800 CGLine+ self-contained luminaires –
no wired network connection close to the luminaire required
Accessing detailed information of every luminaire – regardless of its installed location
Function test can be started on site to directly check that the luminaire is operative
Location-independent access to the electronic workbook
Integrated WiFi access point
Convenient operation via a web browser and touchscreen
Apple iPad Air, 32 GB, WiFi, grey included in the monitoring set
Line 1
1
2
3
200
1
2
3
200
1
2
3
200
1
2
3
200
Line 2
Line 3
Line 4
© 2014 Eaton, All Rights Reserved.
32
CGVision via CGLine+ Web-Controller
Comprehensive visualization
•
•
•
•
•
•
•
Up to 32 CGLine+ web controllers can be visualized at once
Both CGLine+ luminaire systems and other emergency lighting systems (for example ZB-S, LPSTAR, AT-S+) can be monitored with a single software
Central control and test functions
Comprehensive electronic log book for all
connected systems
State of the individual emergency lighting systems
can be presented on a site plan
Visualization of individual luminaires
in building layouts
Access to the webserver of the
Up to 32 Web-Controller
with max. 800 luminaires each
CGLine+ Web-Controller
= 25.600 luminaires
possible at the same time
Additional access to the WebController via a web browser
from any PC on the network
CGVision: Configuration und
complete visualization of all
luminaires
© 2014 Eaton, All Rights Reserved.
Printing out
the log book
33
CGVision Anwendungsbeispiel
© 2014 Eaton, All Rights Reserved.
34
Comparison
CGLine+ / CGLine 400
CGLine+
CGLine 400
Max. 800 Luminaires
(4 x 200 or 2 x 400)
Max. 400 Luminaires
(4 x 100)
8 Zones per line with 4 lines / 16 Zones
with 2 lines
--
8 different test groups for FT und DT
free assignable
2 test groups (even / odd short address)
Blocking of the emergency lighting
function (All / per line / per zone or per
luminaire)
Blocking of the emergency lighting
function (All or per line)
Switch off / on of maintained mode
luminaires (All / per line / per zone / per
luminaire)
Switch off / on of maintained mode
luminaires (All / per line)
Visualization of the luminaires in up to
30 different floor plans via the WebServer
--
© 2014 Eaton, All Rights Reserved.
35
Comparison
CGLine+ / CGLine 400
CGLine+
CGLine 400
0,5 mm2 => 330 m
1,0 mm2 => 660 m
1,5 mm2 => 1000 m
0,5 mm2 => 450 m
1,0 mm2 => 900 m
1,5 mm2 => 1350 m
1 x S1/S2 Input (Blocking function with
differential loop monitoring)
1 x S1/S2 Input (Blocking function with
differential loop monitoring)
2 x Digital Input
--
2 x potential free contact
1 x potential free contact
Log book stored on internal storage
Log boog only on SD card (w/o SD card
no log book entries)
1 x USB Host, 1 x USB Device
SD card reader
Log book in TXT (pro Month) or in DAT
format (complete) via Intranet
downloadable. DAT file via PC Software
readable and analyzable
--
© 2014 Eaton, All Rights Reserved.
36
Comparison
CGLine+ / CGLine 400
CGLine+
CGLine 400
Log book on USB Stick storable and
transportable
Log book on SD card storable and
transportable
Configuration data via USB Device
loadable (cable connection USB – PC
necessary)
Configuration data via SD card loadable
(transportable)
For DIN rail; 12 TE
For DIN rail; 10 TE
Cross section / dimensions suitable for
Standard cut-outs for substations
--
Operating manual stored directly in the
Controller
--
© 2014 Eaton, All Rights Reserved.
37
CGLine+ / CGLine 400 mode
CGLine+ mode
•
Maximum of 800 CGLine+ luminaires (one type)
CGLine 400 mode
•
Hybrid operation of CGLine+ and CGLine luminaires in one line on a CGLine+ controller it is
possible. However, as soon as one CGLine luminaire is installed in a line, the controller only
operates in the older CGLine 400 mode! (the new features of the CGLine+ system are then
no longer available. e.g. only 4 lines at max. 100 luminaires)
•
CGLine+ can also be connected to the predecessor models "CGLine Web Interface" and
"CG-Controller CGLine 400".
© 2014 Eaton, All Rights Reserved.
38
Order codes
Order code
Type
40071361055
CGLine+ Web-Controller
40071361178
CGLine+ PC-Software
40071361184
CGLine+ Web-Controller connection box
Order code
Type
40071361275
CGLine+ WiFi connection box
CGLine+ Web-Controller + WLAN access point
in one wall connection box
40071361274
CGLine+ Wireless Monitoring Set
CGLine+ WiFi-connection box + iPad* Air, 32
GB, WiFi, grey
© 2014 Eaton, All Rights Reserved.
39
CGLine+ luminaires
© 2014 Eaton, All Rights Reserved.
Functional principle of the der luminaire
Mains
p - Controller
I
© 2014 Eaton, All Rights Reserved.
Charging unit
t
41
Portfolio luminaires CGLine+
GuideLed
GuideLed SL
Exit Cube LED
Atlantic Led,
IP65
3583 LED
Available from April 2015
© 2014 Eaton, All Rights Reserved.
42
Portfolio luminaires CGLine+
Alte Sachnummer/
Old part number
Neue Sachnummer/
GuideLed CGLine+ 20m/ 30m
New part number
40071353080
40071353260
Wall mounting, surface 10811/11811 CGLine+
40071353060
40071353261
Wall mounting, recessed 10812 CGLine+
40071353070
40071353262
40071353081
40071353263
Wall mounting, recessed 11812 CGLine+
Ceiling mounting, rope, recessed
10826/11826 CGLine+
Alte Sachnummer/
Old part number
Neue Sachnummer/
GuideLed CGLine+ 20m
New part number
40071353061
40071353264
Ceiling mounting 10821 CGLine+
40071353062
40071353265
Ceiling moun., pendant 0,5m 10822 CGLine+
40071353063
40071353266
Ceiling moun., pendant 1,5m 10823 CGLine+
40071353064
40071353267
Ceiling mounting, recessed 10824 CGLine+
40071353065
40071353268
Ceiling mounting, rope 10825 CGLine+
Alte Sachnummer/
Old part number
Neue Sachnummer/
GuideLed CGLine+ 30m
New part number
40071353071
40071353269
Ceiling mounting 11821 CGLine+
40071353072
40071353270
Ceiling moun., pendant 0,5m 11822 CGLine+
40071353073
40071353271
Ceiling moun., pendant 1,5m 11823 CGLine+
40071353074
40071353272
Ceiling mounting, recessed 11824 CGLine+
40071353075
40071353273
Ceiling mounting, rope 11825 CGLine+
© 2014 Eaton, All Rights Reserved.
43
Portfolio luminaires CGLine+
Alte Sachnummer/
Old part number
40071353092
40071353093
40071353090
40071353091
40071353417
40071353418
Neue Sachnummer/
New part number
40071353274
40071353275
40071353278
40071353279
40071353280
40071353282
Alte Sachnummer/
Old part number
40071354970
40071354971
40071354972
40071354973
40071354974
40071354975
40071354976
40071354977
40071354978
40071354979
Neue Sachnummer/
New part number
40071354870
40071354871
40071354872
40071354873
40071354874
40071354875
40071354876
40071354877
40071354878
40071354879
Alte Sachnummer/
Old part number
40071350190
Neue Sachnummer/
Andere Typen/ Other luminaires
New part number
40071353365
3583 1-8h/D LED CGLine+
--
40071353420
© 2014 Eaton, All Rights Reserved.
GuideLED SL CGLine+
GuideLed SL 13821 CGLine+
GuideLed SL 13811 CGLine+
GuideLed SL 13822 CGLine+
GuideLed SL 13812 CGLine+
GuideLed SL 13851 CGLine+ 5 Lux
GuideLed SL 13852 CGLine+ 5 Lux
Atlantic LED CGLine+
Atlantic LED S 1-8H/D CGLine+
Atlantic LED D 1-8H/D CGLine+
Atlantic LED R 1-8H/D CGLine+
Atlantic LED O 1-8H/D CGLine+
Outdoor Wall 1-8H/D CGLine+
Atlantic LED S 1-8H/D CGLine+ H
Atlantic LED D 1-8H/D CGLine+ H
Atlantic LED R 1-8H/D CGLine+ H
Atlantic LED O 1-8H/D CGLine+ H
Outdoor Wall 1-8H/D CGLine+ H
Exit Cube 33822 CGLine+
44
Portfolio luminaires CGLine+ (Q3 / 2015)
Style Variant LED
Style Industrie
28011 / 28021
48011 LED
58011 / 58021
Aluminium
71811 / 71821
6811 IP 65
Brillant LED
1883, 1884, 1984
© 2015 Eaton, All Rights Reserved.
45
Portfolio luminaires CGLine+ (Q3 / 2015)
Alte Sachnummer/
Old part number
Neue Sachnummer/
New part number
40071352221
40071354815
28011 1-8h/D LED CGLine+
40071352223
40071354816
28021 1-8h/D LED CGLine+
--
40071354817
28011 1-8h/D LED CGLine+ (SET)
--
40071354818
28021 1-8h/D LED CGLine+ (SET)
40071354820
58011 1-8h/D LED CGLine+
40071354721
40071354821
Alte Sachnummer/
Old part number
Neue Sachnummer/
New part number
40071352811
40071354822
48011 1-8h/D LED CGLine+
40071352812
40071354823
48011 1-8h/D LED CGLine+
Alte Sachnummer/
Old part number
Neue Sachnummer/
New part number
40071352806
40071354824
1883 1-8h/D LED CGLine+
40071352807
40071354825
1884 1-8h/D LED CGLine+
40071352808
40071354826
1984 1-8h/D LED CGLine+
Alte Sachnummer/
Old part number
Neue Sachnummer/
New part number
Aluminium LED CGLine+
40071352802
40071354827
71811 1-8h/D LED CGLine+
40071352803
40071354828
71821 1-8h/D LED CGLine+ WM
40071352804
40071354829
71821 1-8h/D LED CGLine+ DM
40071352805
40071354830
71821 1-8h/D LED CGLine+ PM
Alte Sachnummer/
Old part number
Neue Sachnummer/
New part number
40071354750
40071354831
© 2014 Eaton, All Rights Reserved.
58021 1-8h/D LED CGLine+
Style Industry LED CGLine+
Brillant LED CGLine+
Available from
Q3 2015
40071354720
Available from
Q3 2015
STYLE LED CGLine +
6811 LED CGLine+
6811 1-8h/D LED CGLine+
46
Operation in AT mode
1
2
3
200
Line 4
ID: A0 08 F0
ID: C0 0E A2 ID: EF A0 3D
ID: 46 FC A8
Automatic function test (weekly)
and duration test (every 3 months)
even with interrupted bus line.
© 2014 Eaton, All Rights Reserved.
47
New indication CGLine+ luminaires
Intelligent self-contained luminaires with microprocessor control
•
On-going monitoring of the
Indication of Bicolour-LED
battery circuit
•
Operating mode
Fully automated function test
and duration test
•
Status indication at the luminaire
l
LED
No failure
l
lights up green
Emergency mode

LED is off
Delay of mains return
/
Function test active /
Duration test active

Luminaire blocked
/
Error messages
LED
blinks green/yellow
alternately at 0.5 Hz
blinks green 1 Hz
blinks green/yellow
alternately at 1 Hz
Charge fault / Function test
failed / Duration test failed

yellow light blinks slowly
at 0.5 Hz
Luminaire fault

yellow light blinks rapidly
at 2 Hz
© 2014 Eaton, All Rights Reserved.
48
OLD indication CGLine 400 luminaires
Intelligent self-contained luminaires with microprocessor control
•
Indication of Bicolour-LED
On-going monitoring of the
Operating mode
battery circuit
•
Fully automated function test
LED
Emergency standby
l
lights up green
Emergency

LED is off
Delay of mains return
l/l
and duration test
•
Status indication at the luminaire
blinks green/yellow in
rotation
Function test
l
blinks green
Duration test

flashes green
Luminaire is blocked

blinks yellow

flashes red
Failure indication
Charging failure
l
Function test failed
l/l
blinks green/red in rotation
Duration test failed
l/l
blinks green/red in rotation
Lamp failure
l/l
blinks yellow/red in rotation
No duration test during last 12
month
© 2014 Eaton, All Rights Reserved.
l
lights up yellow
49
CEAG Notlichtsysteme GmbH, Senator-Schwartz-Ring 26, D-59494 Soest
www.ceag.de
© 2014 Eaton, All Rights Reserved.
50
Related documents