Characterized Control Valves (CCV) Technical Documentation

advertisement
Characterized Control Valves™ (CCV)
Features and Benefits
EQUAL PERCENTAGE VALVE CHARACTERISTIC
In order to ensure good stability of control, it is essential
for a control valve to have an equal percentage
characteristic. This type of characteristic produces a
linear variation in thermal output according to the
amount of opening of the valve (also known as
the system characteristic). Under normal testing
conditions a conventional ball valve exhibits an
S-shaped characteristic. When it is installed in a
real system, however, this characteristic is
seriously deformed because, compared with its
nominal size, a ball valve possesses an extremely
high flow coefficient. Whether used with or without
pipe reducers or a reduced bore, they do not normally
allow stable regulation of the thermal capacity.
Patented Technology
BENEFIT OF THE BELIMO CHARACTERIZING DISC
● Equal percentage flow characteristic.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
● Excellent control stability assured with the characterizing disc.
● Cv values equal to Cv values of globe valves the same size.
● The need for multiple pipe reduction is usually eliminated.
● Better control prevents “hunting” of the control loop, increasing
life span of actuator and valve.
Belimo’s unique Characterized Control Valve™ (CCV) is very
different. A special characterizing disc inside the valve gives it an equal
percentage characteristic which is comparable with that of a globe valve
of the same nominal size. The flow (the Cv value) is reduced to the
required value by a combination of the hole in the ball and the shaped
aperture in the disc. The increase in flow as the valve is opened is very
slow and controlled.
This produces better part-load behavior and improved stability of
control while also optimizing energy consumption.
FEATURES
● Thermal isolating adapter between
flange and actuator.
● Easy direct coupling of actuator
with a single screw.
● Perpendicular mounting flange and
square drive head eliminate lateral
forces on the stem.
● Blow-out proof stem with thrust-bearing
Teflon® disc and double O-ring design
for long service life.*
● Non-corroding chrome-plated
brass or stainless ball.
● Vent holes reduce
condensation build-up.
● Forged brass valve body — no
pin-hole leaks.
● Characterizing disc — made of Tefzel®
known for excellent strength and
chemical resistance.
● Teflon® seats with O-rings provide
constant seating force against the ball
and reduce torque requirement.
● Actuator can be mounted in four
different positions.
* Designed for service life of over 100,000 full cycles.
Teflon® and Tefzel® are both registered trademarks of Dupont.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
1
Feature / Benefits
Characterized Control Valves™ (CCV)
COORDINATED MOTORIZED OPERATION
The optimum functionality of the Belimo CCV is assured by properly
coordinating its actuation with MFT. Specially developed rotary
actuators provide the necessary precision for modulating, floatingpoint, and on/off methods of control.
Flow Characteristics of Conventional Ball Valves
versus BELIMO CHARACTERIZED CONTROL VALVES
All CCVs are supplied with the appropriate rotary actuator to provide
the close-off and operation desired.
Stable
control is
hard to
achieve
OPTIMIZED FOR CONTROL
The Belimo CCV marries known technology with an innovative
development – the unique characterizing disc.
The marriage of CCV and MFT technologies has produced a range of
valuable features which surpass the capabilities of globe valves at a
very attractive price level:
●
●
●
●
B2 Series
Two-way ½” to 3”
B3 Series
Three-way ½” to 2”
Mixing*/Diverting
B6 Series
Two-way Flanged 2½” to 6”
Service:
Chilled/hot water, 60% glycol
Cv Range
0.3-240
Material:
Stainless trim or Brass trim
Control:
On/Off, Floating, 2-10 VDC
Desirable
valve
authority
is not
achieved
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
An equal-percentage valve characteristic
Unlike a globe valve, no sudden change in inlet flow upon opening
Excellent stability of control
Cv values comparable with those of globe valves of the same size
or larger
● Higher close-off ratings than standard globe valves
● 100% tight shut-off on two-way valves means NO leak-by unlike
globe valves that have ANSI IV shutoff (leakage rate of 0.01% of
the Cv rating)
● Three-way valve can be piped in mixing or diverting application
Multi-Function Technology®
Spring Return or Non-Spring Return
Mixing* (Not for use in change over applications)
Desirable Equal Percent Flow and resulting
heat output is achieved with linear results
800-543-9038 USA
2
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Sizing/Selection
Characterized Control Valves™ (CCV)
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
Cv
Maximum
Rating
Inches
DN
mm
2-Way
CCV
Pressure Drop Across the Valve
1 psi
2 psi
3 psi
4 psi
5 psi
6 psi
7 psi
8 psi
9 psi
10 psi
0.3
0.46
0.8
1.2
1.9
3
4.7
7.4
10
16
4.7
7.4
10
14
24
7.4
10
19
30
10
19
25
37
19
29
37
29
46
57
65
85
120
240
60
75
110
150
210
70
130
170
70
110
110
186
290
400
½”
½”
½”
½”
½”
½”
½”
½”
½”
½”
¾”
¾”
¾”
¾”
¾”
1”
1”
1”
1”
1¼”
1¼”
1¼”
1¼”
1½””
1½”
1½”
2”
2”
2”
2”
2”
2”
2”
2½”
2½”
2½”
2½”
2½”
3”
3”
3”
2½”
2½”
3”
4"
5"
6"
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
25
25
25
25
32
32
32
32
40
40
40
50
50
50
50
50
50
50
65
65
65
65
65
80
80
80
65
65
80
100
125
150
B207(B)
B208(B)
B209(B)
B210(B)
B211(B)
B212(B)
B213(B)
B214(B)
B215(B)*
B216(B)*
B217(B)
B218(B)
B219(B)
B220(B)*
B221(B)*
B222
B223
B224
B225*
B229
B230*
B231
B232*
B238
B239
B240*
B248
B249
B250*
B251
B252
B253
B254*
B261
B262
B263
B264
B265*
B277
B278
B280*
B6250S-070
B6250S-110
B6300S-110
B6400S-186
B6500S-290
B6600S-400
0.3
0.5
0.8
1.2
1.9
3.0
4.7
7.4
10
14
4.7
7.4
10
14
24
7.4
10
19
30
10
19
25
37
19
29
37
29
46
57
65
85
120
240
60
75
110
150
210
70
130
170
70
110
110
186
290
400
0.4
0.7
1.1
1.7
2.7
4.2
6.6
10
14
20
6.6
10
14
20
34
10
14
27
42
14
27
35
52
27
41
52
41
65
81
92
120
170
339
85
106
156
212
297
99
194
240
99
156
156
263
410
566
0.5
0.8
1.4
2.1
3.3
5.2
8.1
13
17
24
8.1
13
17
24
42
13
17
33
52
17
33
43
64
33
50
64
50
80
99
113
147
208
416
104
130
191
260
364
121
225
294
121
191
191
322
502
693
0.6
0.9
1.6
2.4
3.8
6.0
9.4
15
20
28
9.4
15
20
28
48
15
20
38
60
20
38
50
74
38
58
74
58
92
114
130
170
240
480
120
150
220
300
420
140
260
340
140
220
220
372
580
800
0.7
1.0
1.8
2.8
4.2
6.8
11
17
22
31
11
17
22
31
54
17
22
42
67
22
42
56
83
42
65
83
65
103
127
145
190
268
537
134
168
246
335
470
157
290
380
157
244
244
416
648
894
0.7
1.1
2.0
2.9
4.7
7.3
12
18
24
34
12
18
24
34
59
18
24
47
73
24
47
61
91
47
71
91
71
113
140
159
208
294
588
147
194
269
367
514
172
318
416
171
266
266
456
710
980
0.8
1.2
2.1
3.2
5.0
7.9
12
20
26
37
12
20
26
37
63
20
26
50
79
26
50
66
98
50
77
98
77
122
151
170
225
318
635
159
198
291
397
556
185
344
450
185
282
282
492
767
1058
0.8
1.3
2.3
3.4
5.4
8.5
13
21
28
40
13
21
28
40
68
21
28
54
85
28
54
71
105
54
82
105
82
130
161
194
240
339
679
170
212
311
424
594
198
368
481
198
296
296
526
820
1131
0.9
1.4
2.4
3.6
5.7
9.0
14
22
30
42
14
22
30
42
72
22
30
57
90
30
57
75
111
57
87
111
87
138
171
195
255
360
720
180
225
330
450
630
210
390
510
210
312
312
558
870
1200
0.9
1.5
2.5
3.8
6.0
9.5
15
23
32
44
15
23
32
44
76
23
32
60
95
32
60
79
117
60
92
117
92
145
180
206
269
380
759
190
237
348
474
664
221
411
538
221
320
320
588
917
1265
GPM = Cv x Δp
*Models with no characterizing disc.
The influence of the pipe geometry due to reduced flow is negligible for all valves 57 Cv and below with characterizing discs.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
3
Sizing/Selection
Characterized Control Valves™ (CCV)
3-Way Valve Flow Rate for Water Applications (Gallons Per Minute, GPM)
Inches
DN
mm
3-Way
CCV
Pressure Drop Across the Valve
1 psi
2 psi
3 psi
4 psi
5 psi
6 psi
7 psi
8 psi
9 psi
10 psi
0.3
0.46
0.8
1.2
1.9
3
4.7
10
16
4.7
7.4
14
24
7.4
10
30
10
19
25
19
29
37
46
29
37
46
57
68
83
½”
½”
½”
½”
½”
½”
½”
½”
½”
¾”
¾”
¾”
¾”
1”
1”
1”
1¼”
1¼”
1¼”
1½”
1½”
1½”
1½”
2”
2”
2”
2”
2”
2”
15
15
15
15
15
15
15
15
15
20
20
20
20
25
25
25
32
32
32
40
40
40
40
50
50
50
50
50
50
B307(B)
B308(B)
B309(B)
B310(B)
B311(B)
B312(B)
B313(B)
B315(B)*
B316(B)*
B317(B)
B318(B)
B320(B)*
B321(B)*
B222
B223
B325*
B329
B330
B331
B338
B339
B340
B341
B347
B348
B349
B350
B351
B352
0.3
0.5
0.8
1.2
1.9
3.0
4.7
10
14
4.7
7.4
14
24
7.4
10
30
10
19
25
19
29
37
46
29
37
46
57
68
83
0.4
0.7
1.1
1.7
2.7
4.2
6.6
14
20
6.6
10
20
34
10
14
42
14
27
35
27
41
52
65
41
52
65
81
96
117
0.5
0.8
1.4
2.1
3.3
5.2
8.1
17
24
8.1
13
24
42
13
17
52
17
33
43
33
50
64
80
50
64
80
99
118
144
0.6
0.9
1.6
2.4
3.8
6.0
9.4
20
28
9.4
15
28
48
15
20
60
20
38
50
38
58
74
92
58
74
92
114
136
166
0.7
1.0
1.8
2.8
4.2
6.8
11
22
31
11
17
31
54
17
22
67
22
43
56
43
65
83
103
65
83
103
128
152
186
0.7
1.1
2.0
2.9
4.7
7.3
12
24
34
12
18
34
59
18
24
73
25
47
61
47
71
91
113
71
91
113
140
167
204
0.8
1.2
2.1
3.2
5.0
7.9
12
26
37
12
20
37
63
20
26
79
27
50
66
50
77
98
122
77
98
122
151
180
220
0.8
1.3
2.3
3.4
5.4
8.5
13
28
40
13
21
40
68
21
28
85
28
54
71
54
82
105
130
82
105
130
161
192
235
0.9
1.4
2.4
3.6
5.7
9.0
14
30
42
14
22
42
72
22
30
90
30
57
75
57
87
111
138
87
111
138
171
204
249
0.9
1.5
2.5
3.8
6.0
9.5
15
32
44
15
23
44
76
23
32
95
32
60
79
60
92
117
146
92
117
146
180
215
263
GPM = Cv x Δp * = Models with no characterizing disc.
The influence of the pipe geometry due to reduced flow is negligible for all valves 83 Cv and below with characterizing discs.
800-543-9038 USA
4
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Cv
Maximum
Rating
Set-up and Wiring Instructions
Characterized Control Valves™ (CCV)
SET-UP
2-WAY VALVE
SPECIFY UPON ORDERING
Power to pin 2 will
drive valve CCW.
Power to pin 3 will
drive valve CW.
TR24-3-T US
TR24-3 US
Stays in Last Position
NON-SPRING RETURN
On/Off or
Floating Point Actuators
TR24-SR-T US
TR24-SR US
Note Fail Position
SPRING RETURN
Power to pin 2 will
drive valve CCW.
Power to pin 3 will
drive valve CW.
NC: Closed A to AB, will
open as voltage increases.
NO: Open A to AB, will close
as voltage increases.
(Can be chosen with
switch inside terminal
block of actuator.)
NC: Closed A to AB, will
open as voltage increases.
NO: Open A to AB, will close
as voltage increases.
(Can be chosen with
switch inside terminal
block of actuator.)
Power to pin 2 will drive
valve CW. Power to pin 3
will drive valve CCW. The
above will function when
the directional switch is in
the “1” position, to reverse
select the “0” position.
NO: Open A to AB, will close
as voltage increases or
power applied. (Can be
chosen with CW/CCW
switch.)
Power to pin 2 will drive
valve CW. Power to pin 3
will drive valve CCW. The
above will function when
the directional switch is in
the “1” position, to reverse
select the “0” position.
NO: Open A to AB, will close
as voltage increases or
power applied. (Can be
chosen with CW/CCW
switch.)
TFRB24
LF24 US
AFRB24
NO/FO Valve: Open A to AB
will drive closed.
Spring Action:
Will spring open A to AB
upon power loss.
NC/FC Valve: Closed A to AB
will drive open.
Spring Action:
Will spring closed A to AB
upon power loss.
NO/FO Valve: Open A to AB
will drive closed.
Spring Action:
Will spring open A to AB
upon power loss.
NC/FC Valve: Closed A to AB
will drive open.
Spring Action:
Will spring closed A to AB
upon power loss.
TF (-3), MFT, SR
LF (-3), MFT, SR
AF SR
AFR, MFT
NC/FO Valve: Closed A to AB
will drive open.
Spring Action:
Will spring open A to AB
upon power loss.
NC/FC or NO/FC
Valve: Closed A to AB or
Open A to AB.
(Can be chosen with
CW/CCW switch.)
Spring Action:
Will spring closed A to AB
upon power loss.
NC/FO Valve: Closed A to AB
will drive open
Spring Action:
Will spring open A to AB
upon power loss.
NC/FC or NO/FC
Valve: Closed A to AB
or Open A to AB.
(Can be chosen with
CW/CCW switch.)
Spring Action:
Will spring closed A to AB
upon power loss.
Proportional
Type Actuators
LRB24 (-3), MFT, SR
LRX24 (-3), MFT, SR
ARB24 (-3), MFT, SR
ARX24 (-3), MFT, SR
Floating Point or
Proportional Type Actuators
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
3-WAY VALVE
SPECIFY UPON ORDERING
Floating Point or
Proportional Type Actuators
NO/FO Valve: Open A to AB
Spring Action:
Will spring open A to AB
upon power loss.
(NO action can be chosen
with CW/CCW switch.)
NO/FO Valve: Open A to AB
Spring Action:
Will spring open A to AB
upon power loss.
(NO action can be chosen
with CW/CCW switch.)
GENERAL WIRING INSTRUCTIONS
WARNING The wiring technician must be trained and experienced with
electronic circuits. Disconnect power supply before attempting any
wiring connections or changes. Make all connections in accordance with
wiring diagrams and follow all applicable local and national codes.
Provide disconnect and overload protection as required. Use copper,
twisted pair, conductors only. If using electrical conduit, the attachment
to the actuator must be made with flexible conduit.
Always read the controller manufacturer's installation literature
carefully before making any connections. Follow all instructions in this
literature. If you have any questions, contact the controller manufacturer
and/or Belimo.
Transformer(s)
Belimo actuators require a 24 VAC class 2 transformer and draws a
maximum of 10 VA per actuator. The actuator enclosure cannot be opened
800-543-9038 USA
in the field, there are no parts or components to be replaced or repaired.
– EMC directive: 89/336/EEC
– Software class A: Mode of operation type 1
– Low voltage directive: 73/23/EEC
CAUTION It is good practice to power electronic or digital controllers
from a separate power transformer than that used for actuators or other
end devices. The power supply design in our actuators and other end
devices use half wave rectification. Some controllers use full wave
rectification. When these two different types of power supplies are
connected to the same power transformer and the DC commons are
connected together, a short circuit is created across one of the diodes in
the full wave power supply, damaging the controller. Only use a single
power transformer to power the controller and actuator if you know the
controller power supply uses half wave rectification.
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
5
Flow, Operation and Installation
Characterized Control Valves™ (CCV)
FLOW PATTERNS
2-way Characterized Control Valves™
(Belimo B2 Series)
(Belimo B6 Series)
Flow Direction
Two-way valves
should be installed
with the disc
upstream.
Upstream A
Downstream AB
3-way Characterized Control Valves™
MIXING (Not for use in change over applications
(Belimo B3 Series)
DIVERTING
The A-port must
be piped to the coil
to maintain proper
control.
INCORRECT PIPING
The A-port must be piped to the coil to maintain proper control.
Three-Way
y Div
Diverting Valve Piping
ping Diagram
(1 Input,
In
2 Outputs
uts)
A
Return
Return
B
Coil
Coil
AB
A
Supply
Supply
B
AB
Note Valve Porting!
The A-port must be piped to the coil! Not the B-port!
Flow is not possible from A to B. If AB-port is not piped as
the common port, the valve must be re-piped. It is good
practice to install a balancing valve in the bypass line. These
valves are intended for closed loop systems. Do not install
in an open loop system or in an application that is open to
atmospheric pressure.
OPERATION/INSTALLATION – CORRECT PIPING
2-way valves should be installed with the disc upstream. If installed with disc downstream, flow curve will be deeper. If installed “backwards” it is NOT necessary to
remove and change. No damage or control problems will occur.
3-WAY VALVES MUST BE PIPED CORRECTLY. They can be mixing or diverting. Mixing is the preferred piping arrangement.
Diverting* (Not for use in change over applications)
The BELIMO Characterized Control Valve is a CONTROL valve, not a manual valve adapted for actuation. The control port is the A-port. It is similar to the globe valve in that
the middle port is the B or bypass port. The common port AB is on the main opposite the A-port. These diagrams are for typical applications only. Consult engineering
specification and drawings for particular circumstances.
REDUCED B-PORT FLOW
Note: The B-port flow of the 3-way CCV is lower than that of the A-port. In most applications this is beneficial since the reduced flow compensates for the inexistent
pressure drop across the coil in the bypass mode. Therefore, proper sizing is important to avoid flow noise in particular when the system is designed with constant
speed pumps. Please refer to our valve sizing and selection guidelines.
The flow velocity in the pipe upstream and downstream of the valve should be considered as well. The typical HVAC design maximum flow is 4 to 8 ft/s to avoid noise
issues.
Also, the pipe reduction factor must be considered and can be found on pages 3 and 4. Pipe reducers decrease the Cv value of a valve and consequently increase the
pressure drop across the valve, a situation that could lead to noise or a lower than designed flow.
Diverting* (Not for use in change over applications)
800-543-9038 USA
6
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Three-Wa
Way Mixing
Mix
Valve Piping
ping Diagra
D
m
(2 Inpu
Inputs, 1 Outp
utput)
Nomenclature
Characterized Control Valve™ (CCV)
B2
09
B
LRX
24
-MFT
Valve
B2 = 2-way
B3 = 3-way
B6 = 2-way
Flanged
Valve Size
07-80 = ½”-3”
Control
Actuator Type Power Supply Blank = On/Off, Floating
Trim Material Non-Spring Return 24 = 24 VAC/DC -3 = Floating Point
120 = 120 VAC*
B = Brass
TR…
230 = 230 VAC
Blank = Stainless LRB…
Steel Trim LRX…
ARB…
ARX…
LRQ...
NRQ...
Spring Return
TFR…
LF…
AFR...
Electronic Fail-Safe
GK...
-SR = 2-10 VDC
-MFT = Multi-Function
Technology
-MFT95 = 0-135 Ω
-T = Terminal
Strip
-S = Built-in
Auxiliary
S it h
Switch
N4 = NEMA
4X, UL
Type 4X,
IP 66/67
Enclosure
ORDERING EXAMPLE
3
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
1
For MFT orders only - select programming code
Choose the valve actuator combination.
B209B+LRX24-MFT
+NO
+Tagging (if needed)
4
2
Specify preference or configuration.
Does order
require
tagging?
Set-Up
P-10001 (A01)
Non-Spring Models
NO = Normally Open
NC = Normally Closed
Spring Return Models
NO/FO = Normally Open/Fail Open
NO/FC = Normally Open/Fail Closed
NC/FO = Normally Closed/Fail Open
NC/FC = Normally Closed/Fail Closed
See settings
Refers to valve ports A to AB.
5
Complete Ordering Example:
P-100xx (Axx) Control voltage applications
P-200xx (Wxx) Pulse width modulation
applications
P-300xx (Fxx) Floating Point applications
P-400xx (Jxx) On/Off applications
X-XXXXX
Create custom MFT
configuration code
X-XXXXX
Create custom MFT
configuration in the field
with MFT-actuator PC software
Tagging:
Valves may be
tagged per customer
specification.
Example:
AHU-1
FCU-2
B209B+LRX24-MFT+NO+A01
*TF, LR and AR Series has 100 to 240 VAC nominal power supply.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
7
This Page Intentionally Left Blank
8
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
B2 Series, 2-Way, Characterized Control Valve
Chrome Plated Brass Ball and Brass Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable flow.
Suitable Actuators
Non-Spring
Spring
LF Series
forged brass, nickel plated
chrome plated brass
nickel plated brass
PTFE
Tefzel®
2 EPDM O-rings, lubricated
600 psi
0°F to 250°F [-18°C to 120°C]
200 psi
50 psi for typical applications
Type
2-way NPT
B207B
B208B
B209B
B210B
B211B
B212B
B213B
B214B
B215B
B216B
B217B
B218B
B219B
B220B
B221B*
TF Series
chilled or hot water, 60% glycol
A-port equal percentage
75°
½”, ¾”
NPT female ends
Valve Nominal Size
Inches DN [mm]
½
15
½
15
½
15
½
15
½
15
½
15
½
15
½
15
½
15
½
15
¾
20
¾
20
¾
20
¾
20
¾
20
LR Series
Cv
0.3
0.46
0.8
1.2
1.9
3
4.7
7.4
10
16
4.7
7.4
10
14
24
TR Series
Technical Data
Service
Flow characteristic
Controllable Flow Range
Sizes
Type of end fitting
Materials:
Body
Ball
Stem
Seats
Characterizing disc
Packing
Body pressure rating
Media temp. range
Close off pressure
Maximum differential
pressure (ΔP)
Leakage
External leakage
Cv rating
*Models without characterizing disc
0% for A to AB
according to EN 12266-1:2003
A-port: see product chart for values
Dimensions
2WayValve-B207-B220
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Tefzel® is a registered trademark of DuPont
Valve Body
B207B-B211B
B212B-B216B
B217B-B221B
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
Dimensions (Inches [mm])
A
B
2.38” [60.8]
1.39” [35.2]
2.38” [60.8]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
Flow Patterns
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
9
B3 Series, 3-Way, Characterized Control Valve
Chrome Plated Brass Ball and Brass Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
* (Not for use in change over applications)
*Models without characterizing disc
0% for A to AB
<2.0% for B to AB
according to EN 12266-1:2003
A-port: see product chart for values
B-port: 70% of A to AB Cv
Tefzel® is a registered trademark of DuPont
3WayValve-B307-B320
Dimensions
Valve Body
B307B-B311B
B312B-B316B
B317B-B321B
Valve Nominal Size
Dimensions (Inches [mm])
Inches DN [mm]
A
B
C
½”
15
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
½”
15
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
¾”
20
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
Flow Patterns
“B” Port must
be piped to the
bypass leg.
800-543-9038 USA
10
LF Series
TF Series
Suitable Actuators
Non-Spring
Spring
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
External leakage
Cv rating
forged brass, nickel plated
chrome plated brass
nickel plated brass
PTFE
Tefzel®
2 EPDM O-rings, lubricated
600 psi
0°F to 250°F [-18°C to 120°C]
200 psi
50 psi for typical applications
Type
3-way NPT
B307B
B308B
B309B
B310B
B311B
B312B
B313B
B315B
B316B
B317B
B318B
B320B
B321B
LR Series
Controllable Flow Range
Sizes
Type of end fitting
Materials:
Body
Ball
Stem
Seats
Characterizing disc
Packing
Body pressure rating
Media temp. range
Close off pressure
Maximum differential
pressure (ΔP)
Leakage
chilled or hot water, 60% glycol
A-port equal percentage
B-port modified for constant common port
flow
75°
½”, ¾”
NPT female ends
Valve Nominal Size
Inches DN [mm]
½
15
½
15
½
15
½
15
½
15
½
15
½
15
½
15
½
15
¾
20
¾
20
¾
20
¾
20
TR Series
Technical Data
Service
Flow characteristic
Cv
0.3
0.46
0.8
1.2
1.9
3
4.7
10
16
4.7
7.4
14
24
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
B2 Series, 2-Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
Tefzel® is a registered trademark of DuPont
Dimensions
Valve Body
B207-B211
B212-B216
B217-B221
B222-B225
B229-B230
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
1¼”
32
1½”
40
2”
50
2”
50
2½”
65
3”
80
800-543-9038 USA
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
LF Series
TF Series
AF Series
0% for A to AB
according to EN 12266-1:2003
A-port: see product chart for values
NR...N4 Series
½” - 2” (B250)
2” (B251) - 3”
50 psi for typical applications
AR...N4 Series
½” - 1¼” (B230)
1¼” (B231) - 3”
0°F to 250°F [-18°C to 120°C]
Suitable Actuators
Non-Spring
Spring
LR Series
forged brass, nickel plated
stainless steel
stainless steel
PTFE
Tefzel®
2 EPDM O-rings, lubricated
Valve Nominal Size
Type
Inches DN [mm] 2-Way NPT
½
15
B207
½
15
B208
½
15
B209
½
15
B210
½
15
B211
½
15
B212
½
15
B213
½
15
B214
½
15
B215
½
15
B216
¾
20
B217
¾
20
B218
¾
20
B219
¾
20
B220
¾
20
B221*
1
25
B222
1
25
B223
1
25
B224
1
25
B225*
1¼
32
B229
1¼
32
B230*
1¼
32
B231
1¼
32
B232*
1½
40
B238
1½
40
B239
1½
40
B240*
2
50
B248
2
50
B249
2
50
B250*
2
50
B251
2
50
B252
2
50
B253
2
50
B254*
2½
65
B261
2½
65
B262
2½
65
B263
2½
65
B264
2½
65
B265*
3
80
B277
3
80
B278
3
80
B280*
AR Series
chilled or hot water, 60% glycol
A-port equal percentage
75°
½”, ¾”, 1”, 1¼”, 1½”, 2”, 2½”, 3”
NPT female ends
Cv
0.3
0.46
0.8
1.2
1.9
3
4.7
7.4
10
16
4.7
7.4
10
14
24
7.4
10
19
30
10
19
25
37
19
29
37
29
46
57
65
85
120
240
60
75
110
150
210
70
130
170
TR Series
Technical Data
Service
Flow characteristic
Controllable Flow Range
Sizes
Type of end fitting
Materials:
Body
Ball
Stem
Seats
Characterizing disc
Packing
Body pressure rating
600 psi
400 psi
Media temp. range
Close off pressure
200 psi
100 psi
Maximum differential
pressure (ΔP)
Leakage
External leakage
Cv rating
2WayValve-B207-B220
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable flow.
*Models without characterizing disc
Flow Patterns
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
11
B3 Series, Three Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
* (Not for use in change over applications)
0% for A to AB
<2.0% for B to AB
according to EN 12266-1:2003
A-port: see product chart for values
B-port: 70% of A to AB Cv
*Models without characterizing disc
Flow Patterns
Tefzel® is a registered trademark of DuPont
“B” Port must
be piped to the
bypass leg.
3WayValve-B307-B320
Dimensions
Valve Nominal Size
Valve Body Inches DN [mm]
B307-B311
½”
15
B312-B316
½”
15
B317-B321
¾”
20
B322-B325
1”
25
B329-B331 1¼”
32
B338-B341 1½”
40
B347-B352
2”
50
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
800-543-9038 USA
12
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
AF Series
LF Series
TF Series
NR...N4 Series
AR...N4 Series
½” - 2”
50 psi for typical applications
LR Series
½” - 1”
1¼” - 2”
0°F to 250°F [-18°C to 120°C]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
External leakage
Cv rating
forged brass, nickel plated
stainless steel
stainless steel
PTFE
Tefzel®
2 EPDM O-rings, lubricated
Suitable Actuators
Non-Spring
Spring
AR Series
Controllable Flow Range
Sizes
Type of end fitting
Materials:
Body
Ball
Stem
Seats
Characterizing disc
Packing
Body pressure rating
600 psi
400 psi
Media temp. range
Close off pressure
200 psi
Maximum differential
pressure (ΔP)
Leakage
chilled or hot water, 60% glycol
A-port equal percentage
B-port modified for constant common port
flow
75°
½”, ¾”, 1”, 1¼”, 1½”, 2”
NPT female ends
Valve Nominal Size
Type
Inches DN [mm] 3-Way NPT
B307
½
15
½
15
B308
B309
½
15
½
15
B310
B311
½
15
½
15
B312
B313
½
15
½
15
B315
½
15
B316
¾
20
B317
¾
20
B318
¾
20
B320
¾
20
B321
1
25
B322
1
25
B323
1
25
B325*
1¼
32
B329
1¼
32
B330
1¼
32
B331
1½
40
B338
1½
40
B339
1½
40
B340
1½
40
B341
2
50
B347
2
50
B348
2
50
B349
2
50
B350
2
50
B351
2
50
B352
TR Series
Technical Data
Service
Flow characteristic
Cv
0.3
0.46
0.8
1.2
1.9
3
4.7
10
16
4.7
7.4
14
24
7.4
10
30
10
19
25
19
29
37
46
29
37
46
57
68
83
B6 Series, Two Way, Characterized Control Valve
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic system with variable or constant flow.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
400
6"
150
B6250S-070
B6250S-110
B6300S-110
B6400S-186
B6500S-290
B6600S-400
Electronic
Fail-Safe
GKR
Series
cast iron - GG25
stainless steel
stainless steel
PTFE
stainless steel
2 EPDM O rings, lubricated
according to ANSI 125, standard class B
0°F to 248°F [-18°C to +120°C]
100 psi
50 psi
2-way Flange Non-Spring Spring
AFR
Series
70
110
110
186
290
Suitable Actuators
AR
Series
Cv
chilled or hot water, 60% glycol
A-port equal percentage
75°
2½”, 3”, 4”, 5”, 6”
pattern to mate with ANSI 125 flange
Type
GR
Series
Technical Data
Service
Flow characteristic
Controllable Flow Range
Sizes
Type of end fitting
Materials:
Body
Ball
Stem
Seats
Characterizing disc
Packing
Body pressure rating
Media temp. range
Close off pressure
Maximum differential
pressure (ΔP)
Leakage
Cv rating
Valve Nominal
Size
DN
Inches
[mm]
2½"
65
2½"
65
3"
80
4"
100
5"
125
Flow Pattern
2-way B6250 to B6600 Characterized Control Valves™
Flow Direction
0% for A to AB
A-port: see product chart for values
Dimensions
Upstream A
Downstream AB
E
A
D
F
C
B
Valve
Body
Nominal
Pipe
Size
B6250S
2½" [65]
Top
Flange
Design
Flange
Diameter
Face-to-Face
Length
A
B
Height
Bolt Circle
Diameter
Flange
Thickness
Minimum
Bolt Hole
Diameter
Number of
Bolt Holes
C
D
E
F
7.50" [190.5] 5.50" [139.7]
8.10" [205.4]
5.50" [139.7]
0.75" [19.05]
0.75" [19.05]
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
6.00" [152.4]
0.75" [19.05]
0.75" [19.05]
4
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
7.50" [190.5]
0.94" [23.88]
0.75" [19.05]
8
4
B6300S
3" [80]
B6400S
4" [100]
B6500S
5" [125]
10.00" [254.0] 10.30" [261.6] 10.50" [266.4]
8.50" [215.9]
0.94" [23.88]
0.88" [22.35]
8
B6600S
6" [150]
11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
9.50" [241.3]
1.00" [25.40]
0.88" [22.35]
8
F05
NOTES:
1) Flange bolt pattern matches ANSI class 125 flanges (not ANSI/ASME rated)
2) Maximum allowable working pressure: 100 PSIG
3) It is not recommended to connect raised-face flanges to flat-faced flanges
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
13
Characterized Control Valve Product Range Overview
B2.., B3.., 2-way, 3-way, Stainless Steel Ball and Stem
Type
Suitable Actuators
3-way
NPT
Inches
0.3
½
15
B207(B)
B307(B)
0.46
½
15
B208(B)
B308(B)
0.8
½
15
B209(B)
B309(B)
1.2
½
15
B210(B)
B310(B)
1.9
½
15
B211(B)
B311(B)
3
½
15
B212(B)
B312(B)
4.7
½
15
B213(B)
B313(B)
7.4
½
15
B214(B)
10
½
15
B215(B)
14
½
15
B216(B)* B316(B)*
4.7
¾
20
B217(B)
B317(B)
7.4
¾
20
B218(B)
B318(B)
10
¾
20
B219(B)
14
¾
20
B220(B)*
14
¾
20
24
¾
20
B221(B)* B321(B)*
7.4
1
25
B222
B322
10
1
25
B223
B323
19
1
25
B224
30
1
25
B225*
10
1¼
32
B229
19
1¼
32
B230*
10
1¼
32
B329
19
1¼
32
B330
25
1¼
32
B231
37
1¼
40
B232*
19
1½
40
B238
B338
29
1½
40
B239
B339
37
1½
40
B240*
B340
46
1½
40
29
2
50
37
2
50
46
2
50
B249
B349
57
2
50
B250*
B350
65
2
50
B251
68
2
50
B351
83
2
50
B352
Non-Spring
Return
Spring
Return
NEMA
4X
CCV
Equal Percentage
Characteristic
NR Series
LF Series
LR Series
B315(B)
B320(B)
85
2
50
B252
2
50
B253
240
2
50
B254*
AR Series
B347
AFR Series
B331
B348
120
Valve Specifications
Service
Flow characteristic
AR Series
B248
Product Features
The equal-percentage characteristic of the flow is ensured
by the integral characterizing disc. This characteristic
provides linear heating or cooling output from the coil
improving energy efficiency and comfort.
Actuator Specifications
Control type
on/off, floating point, 2-10 VDC,
multi-function technology (MFT)
Manual override
TR, LR, AR, NR, AFR series
Electrical connection
3 ft [1m] cable with ½”
conduit fitting or covered screw
terminal strip
B325*
B341
Mode of Operation
The Characterized Control Valve is operated by a rotary
actuator. The actuators are controlled by a standard voltage
for on/off control or a proportional signal or 3-point control
system which move the ball of the valve to the position
dictated by the control system.
Controllable flow range
Sizes
Type of end fitting
Materials
Body
Ball
Stem
Seats
Characterizing disc
½”- 1 ½” (2-way)
½”-1” (3-way)
2” (2-way)
1¼”- 2” (3-way)
Packing
Media temp range
Body pressure rating
½” - 1¼” (B230)
1¼”(B231) - 2”(B251)
Close-off pressure
Maximum differential
pressure (ΔP)
Leakage
chilled or hot water, 60% glycol
A-port equal percentage
B-port modified for constant
common port flow
75°
½” - 2”
NPT female ends
forged brass, nickel plated
stainless steel or chrome
stainless steel or chrome
Teflon® PTFE
Tefzel®
Tefzel®
stainless steel
stainless steel
2 EPDM O-rings, lubricated
0°F to 250°F [-18°C to 120°C]
600 psi
400 psi
200 psi
50 psi
0% for A to AB
< 2.0% for B to AB
Cv rating/GPM
A port: see product
chart above for values
B port: 70% of A to AB Cv
Tefzel® and Teflon® are registered trademarks of DuPont
* Models without characterizing discs.
(B) Models with chrome plated brass ball and brass stem
* 3-Way Valves not for use in change over applications
800-543-9038 USA
14
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2-way
NPT
TFR Series
Cv
DN
[mm]
TR Series
Valve Nominal Size
Characterized Control Valve Product Range Overview
B6.., 2-way, Stainless Steel Ball and Stem
DN
[mm]
2-way
NPT
70
2½
65
B6250S-070
110
2½
65
B6250S-110
110
3
80
B6300S-110
186
4
100
B6400S-186
290
5
125
B6500S-290
400
6
150
B6600S-400
Non-Spring
Return
Spring
Return
Electronic
Fail-Safe
AFR
Inches
GR
Cv
Suitable Actuators
CCV
GKR
Type
AR
Valve Nominal Size
Equal Percentage
Characteristic
Applications
Water-side control of heating and cooling systems for AHU supply,
cooling towers and chillers.
Mode of Operation
The Characterized Control Valve is operated by a rotary actuator. The
actuators are controlled by a standard voltage for on/off control or a
proportional signal or 3-point control system which move the ball of
the valve to the position dictated by the control system.
Product Features
The equal-percentage characteristic of the flow is ensured by the integral characterizing disc. This characteristic provides linear heating or
cooling output from the coil improving energy efficiency and comfort.
Actuator Specifications
Control type
On/Off, Floating Point, 2-10 VDC,
Multi-Function Technology (MFT)
Manual override
AR, GR, AFR and GKR series
Electrical connection
3 ft [1m] cable with ½”
conduit fitting or covered screw
terminal strip
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Valve Specifications
Service
Flow characteristic
Action
Sizes
Type of end fitting
Materials
Body
Ball
Stem
Seats
Characterizing disc
Packing
Body pressure rating
Media temp range
Close-off pressure
Maximum differential
pressure (ΔP)
Leakage
800-543-9038 USA
866-805-7089 CANADA
chilled or hot water, 60% glycol
A-port equal percentage
max 90° rotation
2½”, 3”, 4”, 5:, 6”
ANSI 125 flange pattern
cast iron (painted)
stainless steel
stainless steel
PTFE
stainless steel
2 EPDM O-rings, lubricated
According to ANSI 125, standard class B
0°F to 250°F [-18°C to +120°C]
100 psi
50 psi
0% for A to AB
203-791-8396 LATIN AMERICA / CARIBBEAN
15
TR24-3 Actuators, On-Off, Floating Point
2.50
[63.5]
D134
D1349
Dimensions with 2-Way Valve
3.25
[82.6]
2.82
[71.6]
D
C
E
B
F
A
Models
Input impedance
Angle of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing rating
Agency listing†
on/off, floating point
24 VAC 50/60 Hz
19.2…28.8 VAC
1W
1VA (class 2 power source)
screw terminals accessible after removal of
small cover (3 ft, 10 ft, 16 ft cables optional)
0.36 kΩ
90°
integrated into handle
push down handle
90 seconds @ 60 hz, 108 seconds @ 50 hz
5 to 95% non-condensing
-22°F to 122°F (-30°C to 50°C)
-40°F to 176°F (-40°C to 80°C)
NEMA 1/IP40
UL94-5V(B)
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
max. 35 db (A)
ISO 9001
† Rated impulse voltage 330V, Control pollution degree 2, Type of action 1
800-543-9038 USA
16
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
Dimensions with 3-Way Valve
2.50
[63.5]
3.25
[82.6]
2.82
[71.6]
D
E
F
C
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body
Inches DN [mm]
A
B
C
B307(B)-B311(B)
½”
15
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
B312(B)-B315(B)
½”
15
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
B317(B)-B321(B)
¾”
20
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
TR24-3-T US with 3 ft plenum rated cable
TR24-3-T US with 10 ft plenum rated cable
TR24-3-T US with 16 ft plenum rated cable
Technical Data
Control
Nominal voltage
Nominal voltage range
Power consumption
Transformer sizing
Electrical connection
Noise level
Quality standard
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
D135
D1350
TR24-3-T US
TR24-3 US
TR24-3/300 US
TR24-3/500 US
TR24-3 Actuators, On-Off, Floating Point
Wiring Diagrams
3
The common connection from the actuator must be
connected to the Hot connection of the controller.
Actuators with plenum rated cable do not have numbers on wires;
use color codes instead.
4
The actuator Hot must be connected to the control board Hot.
2
W187
NOTE:
E TR24-3(-T) US cannot be wired in parallel with
themselves or any other actuator.
WARNING Live Electrical Components!
Floating Control
W186
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off Control
You may not use one wire control.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
17
TR24-SR Actuators, Proportional
2.50
[63.5]
D1349
Dimensions with 2-Way Valve
3.25
[82.6]
2.82
[71.6]
D
C
E
B
F
A
Models
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing rating
Agency listing†
proportional
24 VAC 50/60 Hz, 24 VDC
19.2…28.8 VAC, 21.6…28.8 VDC
0.5 W
1VA (class 2 power source)
screw terminals accessible after removal of
small cover (3 ft, 10 ft, 16 ft cables optional)
100 kΩ
90°
reversible with switch under cover
integrated into handle
push down handle
90 seconds
5 to 95% non-condensing
-22°F to 122°F (-30°C to 50°C)
-40°F to 176°F (-40°C to 80°C)
NEMA 1/IP40
UL94-5V(B)
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
max. 35 db (A)
ISO 9001
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
Dimensions with 3-Way Valve
2.50
[63.5]
3.25
[82.6]
2.82
[71.6]
D
E
F
C
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body
Inches DN [mm]
A
B
C
B307(B)-B311(B)
½”
15
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
B312(B)-B315(B)
½”
15
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
B317(B)-B321(B)
¾”
20
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
† Rated impulse voltage 500V, Control pollution degree 2, Type of action 1
NOTE: Response sensitivity is 75mV
800-543-9038 USA
18
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
TR24-SR-T US with 3 ft plenum rated cable
TR24-SR-T US with 10 ft plenum rated cable
TR24-SR-T US with 16 ft plenum rated cable
Technical Data
Control
Nominal voltage
Nominal voltage range
Power consumption
Transformer sizing
Electrical connection
Noise level
Quality standard
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
D135
D1350
TR24-SR-T US
TR24-SR US
TR24-SR/300 US
TR24-SR/500 US
TR24-SR Actuators, Proportional
2
W190
Wiring Diagrams
Actuators with color coded wires are optional.
Wire numbers are provided for reference.
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
2 to 10 VDC Control of TR24-SR(-T) US
W191
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
4 to 20 mA Control of TR24-SR(-T) US
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Direct/Reverse acting switch is under wiring cover.
R = CW with decrease in signal
L = CCW with decrease in signal
No feedback
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
19
LR...24-3 Actuators, On/Off, Floating Point
D1351
Dimensions with 2-Way Valve
D
C
H1
H2
E
F
B
A
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
LRB24-3
LRX24-3
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
LRB24-3
LRX24-3
Humidity
Ambient temperature
Storage temperature
Housing type
Housing material
Agency listings†
Noise level
Quality standard
LR...24-3-T
Electrical connection
LR...24-3-S
Auxiliary switch
w/Terminal Block
w/3 ft. cable
w/built-in Aux. Switch
on/off, floating point
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 1.5 W
holding 0.2 W
2 VA (class 2 power source)
½” conduit connector
18 GA, plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
600 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
90 seconds, constant independent of load
150, 95, 60, 45, 35 seconds,
constant independent of load
5 to 95% RH, non-condensing (EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
less than 35 dB (A)
ISO 9001
Dimensions with 3-Way Valve
D
H1
C
H2
E
F
B
A
Valve Nominal Size
Valve Body
Inches DN [mm]
B307(B)-B311(B)
½”
15
B312(B)-B315(B)
½”
15
B317(B)-B321(B)
¾”
20
B322-B325
1”
25
Dimensions (Inches [mm])
A
B
C
2.06” [52.2] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
screw terminal (for 26 to 14 GA wire)
protected (NEMA 2, IP20)
1 SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 100°
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
800-543-9038 USA
20
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LRX24-3-T
LRX24-3
LRX24-3-S
Dimensions (Inches [mm])
A
B
1.39” [35.2]
1.39” [35.2]
1.78” [45.2]
1.78” [45.2]
1.87” [47.4]
1.87” [47.4]
1.87” [47.4]
1.87” [47.4]
1.87” [47.4]
1.87” [47.4]
D1352
Models
LRB24-3-T
LRB24-3
LRB24-3-S
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
B222-B225
B229-B231
LR...24-3 Actuators, On/Off, Floating Point
2
W193-LR-08
Wiring Diagrams
CAUTION Equipment damage!
3
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators are provided with color coded wires.
Wire numbers are provided for reference.
4
Actuators may also be powered by 24 VDC.
W123-LR-08
On/Off control
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Floating Point or On/Off control
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
21
LR...24-SR Actuators, Proportional
D1351
Dimensions with 2-Way Valve
D
C
H1
H2
E
F
B
A
Technical Data
Power supply
Power consumption
Transformer sizing
Electrical connection
LRB24-SR
LRX24-SR
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
LRB24-SR
LRX24-SR
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
LR...24-SR-T
Electrical connection
w/Terminal Block
w/3ft. cable
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 1.5 W
holding 0.4 W
3 VA (class 2 power source)
½” conduit connector
18 GA, plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA
1 to 10 VDC, max 0.5 mA
100 kΩ (0.1 mA), 500 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
constant independent of load
90 seconds
150, 95, 60, 45, 35 seconds
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<35 dB(A)
ISO 9001
Dimensions with 3-Way Valve
D
H1
C
H2
E
F
B
A
Valve Nominal Size
Valve Body
Inches DN [mm]
B307(B)-B311(B)
½”
15
B312(B)-B315(B)
½”
15
B317(B)-B321(B)
¾”
20
B322-B325
1”
25
Dimensions (Inches [mm])
A
B
C
2.06” [52.2] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
screw terminal (for 26 to 14 GA wire)
protected (NEMA 2/IP20)
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
800-543-9038 USA
22
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LRX24-SR-T
LRX24-SR
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1352
Models
LRB24-SR-T
LRB24-SR
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
B222-B225
B229-B231
LR...24-SR Actuators, Proportional
2
W265-LR-08
Wiring Diagrams
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (–) leg of control circuits.
W265-LR-08
2 to 10 VDC control
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2
to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
4 to 20 mA control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
23
LR...120-3 Actuators, On/Off, Floating Point
D1353
Dimensions with 2-Way Valve
D
C
H2
H1
E
F
B
A
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
LRB120-3
LRX120-3
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
LRB120-3
LRX120-3
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
On/Off, Floating Point
100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
running 2 W
holding 0.5 W
4 VA (class 2 power source)
½” conduit connector
18 GA, plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
600 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
90 seconds, constant independent of load
150, 95, 60, 45, 35 seconds,
constant independent of load
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<35 dB(A)
ISO 9001
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Nominal Size
Valve Body
Inches DN [mm]
B307(B)-B311(B)
½”
15
B312(B)-B315(B)
½”
15
B317(B)-B321(B)
¾”
20
B322-B325
1”
25
Dimensions (Inches [mm])
A
B
C
2.06” [52.2] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
800-543-9038 USA
24
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LRB120-3
LRX120-3
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1354
Models
Noise level
Quality standard
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
B222-B225
B229-B230
LR...120-3 Actuators, On/Off, Floating Point
2
W405
Wiring Diagrams
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
On/Off
W406
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Floating Point or On/Off control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
25
LR...120-SR Actuators, Proportional
D1353
Dimensions with 2-Way Valve
D
C
H2
H1
E
F
B
A
Technical Data
Power supply
Power consumption
Transformer sizing
Electrical connection
LRB120-SR
LRX120-SR
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
LRB120-SR
LRX120-SR
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
running 2.5 W
holding 1 W
4.5 VA (class 2 power source)
½” conduit connector
18 GA, plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA
1 to 10 VDC, max 0.5 mA
100 kΩ (0.1 mA), 500 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
constant independent of load
90 seconds
150, 95, 60, 45, 35 seconds
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<35 dB(A)
ISO 9001
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Nominal Size
Valve Body
Inches DN [mm]
B307(B)-B311(B)
½”
15
B312(B)-B315(B)
½”
15
B317(B)-B321(B)
¾”
20
B322-B325
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
800-543-9038 USA
26
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LRB120-SR
LRX120-SR
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1354
Models
Noise level
Quality standard
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
B222-B225
B229-B230
LR...120-SR Actuators, Proportional
2
19
CAUTION Equipment damage!
N L1
1 Neutral
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
H L2
2 Hot +
6
6
Only connect common to neg. (–) leg of control circuits.
7
A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
1
15
LRB(X) can be supplied with both 120 VAC and 230 VAC.
19
All 120 VAC and 230 VAC actuators use appliance rated cables.
1 Common
7
(–)
Control Signal
VDC/mA (+)
2 to 10 VDC (–)
Feedback Signal (+)
2 Hot +
8
Cable 1
2
15
Cable 2
100 to 240 VAC
W365
Wiring Diagrams
3 Y Input, 2 to 10V
5 U Output, 2 to 10V
1
0
LR...120-SR
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
Proportional, 100 to 240V
WARNING Live Electrical Components!
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
27
LR...24-MFT Actuators, Multi-Function Technology
D1353
Dimensions with 2-Way Valve
D
C
H2
H1
E
F
B
A
Models
Flexible Version
Power consumption
Transformer sizing
Electrical connection
LRX24-MFT
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2 W
holding 1.2 W
6 VA (class 2 power source)
½” conduit connector
18 GA, plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
2 to 10 VDC (default)
4 to 20 mA
variable (VDC, PWM, floating point, on/off)
2 to 10 VDC, 0.5mA max
VDC variable
100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, floating point, on/off)
90° electronically variable
adjustable with mechanical stop
reversible with protected
handle
external push button
150 seconds (default)
Variable (35 to 150 secs)
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<35 dB(A)
ISO 9001
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
† Rated impulse voltage 800V, Control pollution degree 3,
Type of action 1 (1.B for -S models)
800-543-9038 USA
28
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Power supply
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1354
LRX24-MFT
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
LR...24-MFT Actuators, Multi-Function Technology
3
4
6
8
9
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection.
On/Off control
W538
2
W538
Wiring Diagrams
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components!
Floating Point
W538
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W538
VDC/4-20 mA
PWM
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
29
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
D1353
Dimensions with 2-Way Valve
D
C
H2
H1
E
F
B
A
Models
LRX24-PC
Transformer sizing
Electrical connection
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
800-543-9038 USA
30
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
866-805-7089 CANADA
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Power consumption
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2 W
holding 1.2 W
5 VA (Class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
0 to 20V phasecut
2 to 10 VDC, 0.5mA max
8 kΩ (50 mW)
90°, adjustable with mechanical stop
electronically variable
reversible with
handle
external push button
150 seconds (default)
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<35 dB(A)
ISO 9001
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1354
Technical Data
Power supply
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
LRX24-PC Actuators, 0 to 20V Phasecut, Proportional
W185
Wiring Diagrams
1
1
2
3
24 VAC Transformer
Blk (1) Common –
Line
Volts
Provide overload protection and disconnect as required.
Red (2) Hot +
CAUTION Equipment damage!
3
Pnk (6) Y Input, 0 to 20V phasecut
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Control Signal (–)
0 to 20 V Phasecut (+)
Actuators may also be powered by 24 VDC.
Org (5) U Output, 2 to 10V
…PC
WARNING Live Electrical Components!
2
LRX24-PC
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
31
LRX24-MFT95 Actuators, 0 to 135 Ω, Proportional
D1353
Dimensions with 2-Way Valve
D
C
H2
H1
E
F
B
A
Models
LRX24-MFT95
Technical Data
Power supply
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
Dimensions with 3-Way Valve
D1354
D
C
H2
H1
E
F
B
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
800-543-9038 USA
32
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 2 W
holding 1.2 W
Transformer sizing
5 VA (Class 2 power source)
Electrical connection
½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
Overload protection
electronic throughout 0 to 95° rotation
Operating range WRB
0 to 135 Ω Honeywell Electronic
Series 90, 0 to 135 Ω input
Feedback output U
2 to 10 VDC, 0.5mA max
100 kΩ (0.1 mW)
Input impedance
Angle of rotation
90°, adjustable with mechanical stop
electronically variable
Direction of rotation
reversible with
Position indication
handle
Manual override
external push button
150 seconds (default)
Running time
variable (35 to 150 seconds)
Humidity
5 to 95% RH non-condensing
(EN 60730-1)
Ambient temperature
-22°F to 122°F [-30°C to 50°C]
Storage temperature
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
Housing
UL94-5VA
Housing material
Agency listings†
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
Noise level
<35 dB(A)
Quality standard
ISO 9001
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
Wiring Diagrams
Switch A
Switch B
W_new60408_5
LRX24-MFT95 Actuators, 0 to 135 Ω, Proportional
Damper Position
Damper Open
Damper Closed
The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.
21 Provide overload protection and disconnect as required.
Line
Blk (1) Common
Volts
23
A
Wht (3) W
135 7
Resistor value depends on the type of controller and the
24
4 number of actuators. No resistor is used for one actuator.
Honeywell® resistor kits may also be used.
2
25
Red (2) + Hot
Consult controller instruction data for more detailed
information.
24
Wht (4) R
B
Wht (5) B
Wht (6) ‘U5’ Output 2 to 10 VDC
-MFT95 US
21 24 VAC Transformer
Line
Blk (1) Common
Volts
To reverse control rotation, use the reversing
switch.2524232221
Red (2) + Hot
23
A
Wht (3) W
W
Line
R
Volts
B
B
WARNING Live Electrical Components!
22
During installation, testing, servicing and troubleshooting
of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
24
Wht (4) R
Wht (5) B
Wht (6) ‘U5’ Output 2 to 10 VDC
Controller
-MFT95 US
24 VAC Transformer
21
S963A
Minimum Position
Potentiometer
Line
Volts
W019
23
W015
22
21 24 VAC Transformer
Actuators and controller must have separate transformers.
Blk (1) Common
Red (2) + Hot
25
Series 90
Controller
B
R
R
22
W
B
Wht (3) W
Wht (4) R
Wht (5) B
Wht (6) ‘U5’ Output 2 to 10 VDC
W
Shunting
Resistor
23
24
-MFT95 US
B
R
W
H205 Change- Occupied
over Controller Contact
21
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Line
Volts
Blk (1) Common
Red (2) + Hot
22
Wht (3)
Wht (4)
Wht (5)
Wht (6)
Wiring multiple actuators to a
Series 90 controller using a
minimum position potentiometer
To other
actuators
‘U5’ Output 2 to 10 VDC
W016
-MFT95 US
24 VAC Transformer
21
23
25
W
R
B
Line
Blk (1) Common
Volts
Red (2) + Hot
23
22
Series 90
Controller
R
W
W
Wht (3) W
B
R
Wht (4) R
B
Wht (5) B
Wht (6) ‘U5’ Output 2 to 10 VDC
-MFT95 US
W017
Series 90 low limit control
135 7 for 0 to 50% control
280 7 for 0 to 100% control
24
24 VAC Transformer
21
Line
Blk (1) Common
Volts
Red (2) + Hot
23
22
Series 90
Controller
Wht (3) W
W
B
24
Wht (4) R
R
R
W
B
Wht (5) B
Wht (6) ‘U5’ Output 2 to 10 VDC
Series 90 high limit control - 280 7
-MFT95 US
High Limit Control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
33
LRQ...24-1 Quick Running Actuators, On/Off
D1355
Dimensions with 2-Way Valve
D
C
H2
H1
B
F
A
Models
Basic Version
Flexible Version
Power consumption
Transformer sizing
Electrical connection
LRQB24-1
LRQX24-1
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
LRQB24-1
LRQX24-1
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
on/off
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 12 W
holding 1.5 W
18 VA (Class 2 power source)
20A @ 5ms max
½” conduit connector
18 GA plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
600 Ω
max 95°, adjustable with mechanical stop
reversible with
handle
external push button
5 seconds
constant of independent load
5 or 10 seconds
constant of independent load
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<52 dB(A)
ISO 9001
800-543-9038 USA
34
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
866-805-7089 CANADA
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Control
Power supply
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1356
LRQB24-1
LRQX24-1
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
LRQ...24-1 Quick Running Actuators, On/Off
W403-LRQ-08
Wiring Diagrams
1
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
LRQ...24-1
WARNING Live Electrical Components!
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
35
LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
D1371
Dimensions with 2-Way Valve
D
H1
C
H2
E
F
B
A
Models
Basic Version
Flexible Version
Power consumption
Transformer sizing
Electrical connection
LRQB24-MFT
LRQX24-MFT
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
LRQB24-MFT
LRQX24-MFT
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 12 W
holding 1.5 W
18 VA (Class 2 power source)
20A @ 5ms max
½” conduit connector
18 GA plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, on/off)
2 to 10 VDC, 0.5mA max
VDC variable
100 kΩ (0.1 mA), 500 Ω
1500 Ω (on/off)
max 95°, adjustable with mechanical stop
reversible with
reflective visual indicator (snap-on)
external push button
5 seconds
constant of independent load
5 or 10 seconds
constant of independent load
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<52 dB(A)
ISO 9001
800-543-9038 USA
36
Dimensions with 3-Way Valve
D
H1
C
H2
E
F
B
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
866-805-7089 CANADA
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Power supply
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1372
LRQB24-MFT
LRQX24-MFT
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
LRQ...24-MFT Quick Running Actuators, Multi-Function Technology
1
2
W399_08
Wiring Diagrams
Provide overload protection and disconnect as required.
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
W399_08
VDC/4-20 mA
The ZG-R01 500 Ω resistor may be used.
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
37
NRQ...24-1 Quick Running Actuators, On/Off
D1357
Dimensions with 2-Way Valve
D
C
H2
H1
E
B
F
A
Models
Basic Version
Flexible Version
Power consumption
Transformer sizing
Electrical connection
NRQB24-1
NRQX24-1
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
NRQB24-1
NRQX24-1
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
on/off
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 12 W
holding 1.5 W
18 VA (Class 2 power source)
½” conduit connector,
18 GA plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
600 Ω
max 95°, adjustable with mechanical stop
reversible with
reflective visual indicator (snap-on)
external push button
constant of independent load
5 seconds
5, 10 or 15 seconds
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<52 dB(A)
ISO 9001
Dimensions with 3-Way Valve
D
H1
C
H2
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
800-543-9038 USA
38
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Control
Power supply
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107]
2.27” [57.7]
D1358
NRQB24-1
NRQX24-1
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
Valve Body
B231-B232
B238-B240
B248-B250
NRQ...24-1 Quick Running Actuators, On/Off
W403-NRQ-08
Wiring Diagrams
1
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
NRQ...24-1
WARNING Live Electrical Components!
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
39
NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
D1357
Dimensions with 2-Way Valve
D
C
H2
H1
E
B
F
A
Models
Basic Version
Flexible Version
Power consumption
Transformer sizing
Electrical connection
NRQB24-MFT
NRQX24-MFT
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
NRQB24-MFT
NRQX24-MFT
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 12 W
holding 1.5 W
18 VA (Class 2 power source)
½” conduit connector,
18 GA plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, on/off)
2 to 10 VDC, 0.5mA max
VDC variable
100 kΩ (0.1 mA), 500 Ω, 1500 Ω
(on/off)
max 95°, adjustable with mechanical stop
electronically variable
reversible with
reflective visual indicator (snap-on)
external push button
constant of independent load
5 seconds
5, 10 or 15 seconds
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<52 dB(A)
ISO 9001
Dimensions with 3-Way Valve
D
H1
C
H2
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
800-543-9038 USA
40
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Power supply
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107]
2.27” [57.7]
D1358
NRQB24-MFT
NRQX24-MFT
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
Valve Body
B231-B232
B238-B240
B248-B250
NRQ...24-MFT Quick Running Actuators, Multi-Function Technology
1
2
W399_08
Wiring Diagrams
Provide overload protection and disconnect as required.
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
W399_08
VDC/4-20 mA
The ZG-R01 500 Ω resistor may be used.
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
41
NRB24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
6.77
[172]
D1363
Dimensions with 2-Way Valve
12.98
[330]
10.29
[261]
6.02
[153]
D
E
C
F
B
A
Models
w/built in heater
Power consumption
Transformer sizing
Electrical connection
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing type
Housing material
Agency listings†
Quality standard
on/off, floating point
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2.0 W / heater 24 W
holding 0.2 W
4 VA (class 2 power source) / heater 19 VA
screw terminal (for 26 to 14 GA wire)
electronic throughout 0° to 95° rotation
600 Ω
90°, adjustable with mechanical stop
reversible with
visual pointer
external push button
90 seconds constant independent of load
100% RH
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
UL Type 4X/NEMA 4X/IP66 & IP67
Polypropylene
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No. 24-93,
CE according to 89/336/EEC.
ISO 9001
*Cannot be used with the CCV-EXT-KIT
† Rated impulse voltage 800V, Control pollution degree 3,
Type of action 1.
800-543-9038 USA
42
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
Dimensions with 3-Way Valve
D1364
Technical Data
Control
Power supply
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
6.77
[172]
12.98
[330]
10.29
[261]
6.02
[153]
C
D
E
B
F
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
866-805-7089 CANADA
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
NRB24-3-T N4
NRB24-3-T N4H
NRB24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
2
W193-NR-08
Wiring Diagrams
CAUTION Equipment damage!
3
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators are provided with color coded wires.
Wire numbers are provided for reference.
4
Actuators may also be powered by 24 VDC.
W123-NR-08
On/Off control
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Floating Point control
with actuator types ..-3
N
L
L
1
2
3
N
L
M = actuator
T (°C) = Thermostat
H = Heating
T
H
(°C)
M
1
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2
Note
The follo
f wing points must be taken into account
with independent, external wiring:
• All contact between the cables or wires that
are introduced and the heating element is to be
avoided.
• Where necessary, use cables with sufficient
numbers of wires, e.g. so that the heating and the
actuator can be supplied separately with voltage.
Heater wiring
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
43
NRB24-SR-T N4 NEMA 4X Actuators, Proportional
D1363
Dimensions with 2-Way Valve
12.98
[330]
6.77
[172]
10.29
[261]
6.02
[153]
D
E
C
F
B
A
w/built in heater
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing type
Housing material
Agency listings†
Quality standard
2 to 10 VDC, 4 to 20 mA
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2.5 W / heater 24 W
holding 0.4 W
5 VA (class 2 power source) / heater 20 VA
screw terminal (for 26 to 14 GA wire)
electronic throughout 0° to 95° rotation
100 kΩ (0.1mA), 500Ω
90°, adjustable with mechanical stop
reversible with
visual pointer
external push button
90 seconds constant independent of load
100% RH
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
UL Type 4X/NEMA 4X/IP66 & IP67
Polypropelene
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No. 24-93,
CE according to 89/336/EEC.
ISO 9001
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3
*Cannot be used with the CCV-EXT-KIT
800-543-9038 USA
44
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
Dimensions with 3-Way Valve1363
6.77
[172]
12.98
[330]
10.29
[261]
6.02
[153]
C
D
E
B
F
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
866-805-7089 CANADA
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
NRB24-SR-T N4
NRB24-SR-T N4H
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
D1364
Models
NRB24-SR-T N4 NEMA 4X Actuators, Proportional
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (–) leg of control circuits.
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to 2
to 10 VDC, up to 2 actuators may be connected in parallel.
2 to 10 VDC control
W265-NR-08
2
W265-NR-08
Wiring Diagrams
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Wiring Diagrams
with actuator types ..-3
N
L
L
1
2
3
N
L
M = actuator
T (°C) = Thermostat
H = Heating
T
4 to 20 mA control
H
(°C)
M
1
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2
Note
The follo
f wing points must be taken into account
with independent, external wiring:
• All contact between the cables or wires that
are introduced and the heating element is to be
avoided.
• Where necessary, use cables with sufficient
numbers of wires, e.g. so that the heating and the
actuator can be supplied separately with voltage.
Heater wiring
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
45
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
D1363
Dimensions with 2-Way Valve
12.98
[330]
6.77
[172]
10.29
[261]
6.02
[153]
D
E
C
F
B
A
w/built in heater
Technical Data
Control
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 3.5 W (1.25 W) / heater 24 W
holding 1.25 W
6 VA (class 2 power source) / heater 21 VA
Transformer sizing
Electrical connection
screw terminal (for 26 to 14 GA wire)
Overload protection
electronic throughout 0° to 95° rotation
Input impedance
100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, floating point, on/off)
Angle of rotation
95°, adjustable with mechanical stop
electronically variable
Direction of rotation
reversible with
Position indication
visual pointer
Manual override
external push button
Running time
150 seconds (default)
constant independent of load
variable (75 to 350 seconds)
Humidity
100% RH
Ambient temperature
-22°F to 122°F [-30°C to 50°C]
Storage temperature
-40°F to 176°F [-40°C to 80°C]
Housing type
UL Type 4X/NEMA 4X/IP66 & IP67
Housing material
Polypropelene
Agency Listings†
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1, CSA C22.2 No. 24-93, CE according to 89/336/EEC.
Quality standard
ISO 9001
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
Dimensions with 3-Way Valve1363
6.77
[172]
12.98
[330]
10.29
[261]
6.02
[153]
C
D
E
B
F
A
Valve Body
B307-B311
B312-B315
B317-B321
B322-B325
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3
*Cannot be used with the CCV-EXT-KIT
800-543-9038 USA
46
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
NRX24-MFT-T N4
NRX24-MFT-T N4H
Valve Body
B207-B211
B212-B215
B217-B221
B222-B225
B229-B230
D1364
Models
NRX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
3
4
6
8
9
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection.
On/Off control
W538
2
W538
Wiring Diagrams
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components!
Floating Point
W538
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
with actuator types ..-3
N
L
L
1
2
3
N
L
M = actuator
T (°C) = Thermostat
H = Heating
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
T
W538
VDC/4-20 mA
H
(°C)
M
1
2
Note
The follo
f wing points must be taken into account
with independent, external wiring:
• All contact between the cables or wires that
are introduced and the heating element is to be
avoided.
• Where necessary, use cables with sufficient
numbers of wires, e.g. so that the heating and the
actuator can be supplied separately with voltage.
PWM
Heater wiring
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
47
AR...24-3 Actuators, On/Off, Floating Point
D1359
Dimensions with 2-Way Valve
C
D
H1
H2
E
F
B
A
Models
w/built-in Aux. Switch
Flexible
Flexible w/built-in Aux. Switch
Dimensions (Inches [mm])
A
B
3.72” [94.6]
1.98” [50.4]
3.88” [98.5]
1.98” [50.4]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
Dimensions with 3-Way Valve
D1360
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
ARB24-3...
ARX24-3...
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
ARB24-3...
ARX24-3...
on/off, floating point
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2.5 W
holding 0.2 W
5.5 VA (class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft. [1m]
3 ft. [1m] 10 ft. [3m] 16 ft. [5m]
electronic throughout 0° to 95° rotation
600 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
AR...24-3-S
Auxiliary switch (-S models)
C
D
H1
H2
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
B347-B352
2”
50
4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
90 seconds
300, 150, 90 seconds,
constant independent of load
5 to 95% RH non-condensing (EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<45 dB(A)
ISO 9001
1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0 to 90°
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
800-543-9038 USA
48
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
ARB24-3
ARB24-3-S
ARX24-3
ARX24-3-S
ARB24-3-5-14
ARX24-3-5-14
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
AR...24-3 Actuators, On/Off, Floating Point
Wiring Diagrams
3.46"
[88]
8.5" [216]
CAUTION Equipment damage!
2
2.49"
[63.4]
3.3"
[84]
D
D1373
Dimensions
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
For end position indication, interlock control, etc.,
ARB24-3-S incorporates one built-in auxiliary switches:
1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
1.35"
[35]
I
3
C
Actuators may also be powered by 24 VDC.
4
G
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
B
A
E
F
WARNING Live Electrical Components!
B6250
2½" [65]
B6300
3" [80]
B6400
4" [100]
Top
Flange
Design
F05
Flange
Diameter
Face-to-Face
Length
A
B
Height
C
7.50" [190.5] 5.50" [139.7]
8.10" [205.4]
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
W409
Valve
Body
Nominal
Pipe
Size
2
24 VAC Transformer
4
Blk (1) Common –
Line
Volts
Red (2) +
a open
a closed
a
Wht (3) +
The indication of direction
is valid for switch position 1.
1
0
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
ARB24-3
24 VAC Transformer
W411
On/Off control
2
4
Blk (1) Common –
Line
Volts
Red (2) +
Wht (3) +
The indication of direction
is valid for switch position 1.
1
0
ARB24-3
W410
Floating Point or On/Off control
3
S1
NC
S2
S3
NO
0° to 95°
ARB24-3-S
Auxiliary switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
49
AR...24-SR Actuators, Proportional
D1359
Dimensions with 2-Way Valve
C
D
H1
H2
E
F
B
A
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
Valve Body
B231-B232
B238-B240
B248-B250
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
Models
Power consumption
Transformer sizing
Electrical connection
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Torque
Direction of rotation
Position indication
Manual override
Running time
ARB24-SR...
ARX24-SR...
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2.5 W
holding 0.4 W
5 VA (class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA
1 to 10 VDC, max 0.5 mA
100 kΩ (0.1 mA), 500 Ω
90°, adjustable with mechanical stop
180 in-lb [20 Nm]
reversible with protected
handle
external push button
C
D
H1
H2
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
90 seconds
300, 150, 90 seconds,
constant independent of load
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to +122°F [-30°C to +50°C]
-40°F to +176°F [-40°C to +80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<45 dB(A)
ISO 9001
† Rated impulse voltage 800V, Control pollution degree 3, Type of action 1
(1.B for -S models)
800-543-9038 USA
50
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Power supply
Noise level
Quality standard
Dimensions with 3-Way Valve
Flexible Version
D1360
ARB24-SR
ARX24-SR
AR...24-SR Actuators, Proportional
24 VAC Transformer
2
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (–) leg of control circuits.
2
Blk (1) Common –
Line
Volts
CAUTION Equipment damage!
W408
Wiring Diagrams
Red (2) Hot +
3
Wht (3) Y Input, 2 to 10V
Control Signal (–)
2 to 10 VDC (+)
Org (5) U Output, 2 to 10V
1
2 to 10 VDC (–)
Feedback Signal (+)
0
ARB24-SR
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
24 VAC Transformer
WARNING Live Electrical Components!
2
Blk (1) Common –
Line
Volts
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
W408
2 to 10 VDC control
4 to 20 mA
Control Signal
(–)
(+)
Ω
500Ω
Red (2) Hot +
3
Wht (3) Y Input, 2 to 10V
Org (5) U Output, 2 to 10V
1
5
To other
actuators
0
ARB24-SR
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
4 to 20 mA control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
51
AR...120-3 Actuators, On/Off, Floating Point
D1361
Dimensions with 2-Way Valve
D
C
H1
H2
E
B
F
A
Models
Flexible Version
Power consumption
Transformer sizing
Electrical connection
ARB120-3
ARX120-3
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
ARB120-3
ARX120-3
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Servicing
Quality standard
on/off, floating point
100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
running 3 W
holding 0.6 W
7 VA (class 2 power source)
½” conduit connector
18 GA appliance rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
600 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
90 seconds
300, 150, 90 seconds,
constant independent of load
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<45 dB(A)
maintenance free
ISO 9001
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
800-543-9038 USA
52
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Control
Power supply
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
D1362
ARB120-3
ARX120-3
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
AR...120-3 Actuators, On/Off, Floating Point
Wiring Diagrams
3.46"
[88]
8.5" [216]
Provide overload protection and disconnect as required.
1
2.49"
[63.4]
3.3"
[84]
D
D1373
Dimensions
1.35"
[35]
CAUTION Equipment damage!
2
I
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
C
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
G
WARNING Live Electrical Components!
B
Valve
Body
Nominal
Pipe
Size
B6250
2½" [65]
B6300
3" [80]
B6400
4" [100]
E
Top
Flange
Design
F05
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
F
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
7.50" [190.5] 5.50" [139.7]
8.10" [205.4]
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
W414
A
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W415
On/Off control
Floating Point or On/Off control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
53
AR...120-SR Actuators
D1361
Dimensions with 2-Way Valve
D
C
H1
H2
E
B
F
A
Models
ARB120-SR
ARX120-SR
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
Valve Body
B231-B232
B238-B240
B248-B250
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
Flexible Version
Power consumption
Transformer sizing
Electrical connection
ARB120-SR
ARX120-SR
Overload protection
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
ARB120-SR
ARX120-SR
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Servicing
Quality standard
on/off, floating point
100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
running 3 W
holding 0.6 W
7.5 VA (class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft [1m]
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0° to 95° rotation
1 to 10 VDC, max 0.5 mA
600 Ω
90°, adjustable with mechanical stop
reversible with protected
handle
external push button
90 seconds
300, 150, 90 seconds,
constant independent of load
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<45 dB(A)
maintenance free
ISO 9001
D
C
H2
H1
E
F
B
A
Valve Body
B329-B331
B338-B341
B347-B352
Valve Nominal Size
Dimensions (Inches [mm])
Inches DN [mm]
A
B
C
1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
800-543-9038 USA
54
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Control
Power supply
D1362
Dimensions with 3-Way Valve
AR...120-SR Actuators
2
19
CAUTION Equipment damage!
N L1
1 Neutral
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
H L2
2 Hot +
6
6
Only connect common to neg. (–) leg of control circuits.
7
A 500 Ω resistor converts the 4 to 20 mA control signal to 2 to 10 VDC.
1
15
ARB(X) can be supplied with both 120 VAC and 230 VAC.
19
All 120 VAC and 230 VAC actuators use appliance rated cables.
1 Common
7
(–)
Control Signal
VDC/mA (+)
2 to 10 VDC (–)
Feedback Signal (+)
2 Hot +
3 Y Input, 2 to 10V
5 U Output, 2 to 10V
1
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
8
Cable 1
2
15
Cable 2
100 to 240 VAC
W365
Wiring Diagrams
0
Proportional, 100 to 240V
WARNING Live Electrical Components!
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
55
AR...24-MFT Actuators, Multi-Function Technology
D1361
Dimensions with 2-Way Valve
D
C
H1
H2
E
B
F
A
Models
ARX24-MFT
ARX24-MFT-5-14
Transformer sizing
Electrical connection
ARX24-MFT
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
ARB24-MFT
ARX24-MFT
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
B347-B352
2”
50
4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
150 seconds
variable (90 to 350 seconds)
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according
to 2004/108/EC and 2006/95/EC for line
voltage and/or –S versions
<45 dB(A)
ISO 9001
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
800-543-9038 USA
56
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Power consumption
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 4 W
holding 1.25 W
6 VA (class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
2 to 10 VDC, 0.5 mA max
VDC variable
100 kΩ (0.1 mA), 500 Ω
1500 Ω (PWM, floating point, on/off)
95° electronically variable
reversible with protected
handle
external push button
Dimensions (Inches [mm])
A
B
3.72” [94.6]
1.98” [50.4]
3.88” [98.5]
1.98” [50.4]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
D1362
Technical Data
Power supply
Noise level
Quality standard
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
AR...24-MFT Actuators, Multi-Function Technology
D1374
W538
Dimensions
3.46"
[88]
D
I
C
W538
On/Off control
G
B
Nominal
Pipe
Size
Valve
Body
B6250
2½" [65]
B6300
3" [80]
B6400
4" [100]
E
Top
Flange
Design
F05
F
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
7.50" [190.5] 5.50" [139.7]
8.10" [205.4]
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
Floating Point
W538
A
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Wiring Diagrams
2
CAUTION Equipment damage!
3
Actuators may also be powered by 24 VDC.
6
8
9
VDC/4-20 mA
W538
4
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection.
PWM
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components. Have a
qualified licensed electrician or other individual who has been properly trained
in handling live electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical components could
result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
57
ARX24-PC Actuators, Phasecut
D1361
Dimensions with 2-Way Valve
D
H1
H2
E
B
F
A
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
Models
ARX24-PC
Transformer sizing
Electrical connection
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
800-543-9038 USA
58
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Power consumption
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 4 W
holding 1.25 W
5.5 VA (Class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
electronic throughout 0 to 95° rotation
0 to 20V phasecut
2 to 10 VDC, 0.5mA max
VDC variable
8 kΩ (50 mW)
90°, adjustable with mechanical stop
electronically variable
reversible with
handle
external push button
150 seconds (default)
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<45 dB(A)
ISO 9001
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
D1362
Technical Data
Power supply
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
ARX24-PC Actuators, Phasecut
W185
Wiring Diagrams
1
1
2
3
24 VAC Transformer
Blk (1) Common –
Line
Volts
Provide overload protection and disconnect as required.
Red (2) Hot +
CAUTION Equipment damage!
3
Pnk (6) Y Input, 0 to 20V phasecut
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Control Signal (–)
0 to 20 V Phasecut (+)
Actuators may also be powered by 24 VDC.
Org (5) U Output, 2 to 10V
…PC
WARNING Live Electrical Components!
2
0 to 20V Phase Cut
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
59
ARX24-MFT95 Actuators, 0 to 135 Ω
D1361
Dimensions with 2-Way Valve
D
C
H1
H2
E
B
F
A
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
Models
ARX24-MFT95
Dimensions with 3-Way Valve
D
C
H2
H1
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
†Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3.
800-543-9038 USA
60
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 4 W
holding 1.25 W
6 VA (Class 2 power source)
Transformer sizing
Electrical connection
½” conduit connector
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
Overload protection
Operating range WRB
0 to 135 Ω Honeywell Electronic
Series 90, 0 to 135 Ω input
Feedback output U
2 to 10 VDC, 0.5mA max
Input impedance
100 kΩ (0.1 mW)
Angle of rotation
90°, adjustable with mechanical stop
electronically variable
Direction of rotation
reversible with
Position indication
handle
external push button
Manual override
Running time
150 seconds (default)
variable (90 to 350 seconds)
Humidity
5 to 95% RH non-condensing
(EN 60730-1)
Ambient temperature
-22°F to 122°F [-30°C to 50°C]
Storage temperature
-40°F to 176°F [-40°C to 80°C]
Housing
NEMA 2/IP54
Housing material
UL94-5VA
Agency listings†
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
Noise level
<45 dB(A)
Quality standard
ISO 9001
D1362
Technical Data
Power supply
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
ARX24-MFT95 Actuators, 0 to 135 Ω
Wiring Diagrams
Switch A
Switch B
Damper Position
Damper Open
Damper Closed
The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.
1
Provide overload protection and disconnect as required.
2
CAUTION Equipment damage!
24 VAC Transformer
1
Actuators and controller must have separate transformers.
3
4
5
1 Common
Line
Volts
3
2 + Hot
A
Consult controller instruction data for more detailed installation
information.
Resistor value depends on the type of controller and the number of
actuators. No resistor is used for one actuator. Honeywell resistor
kits may also be used.
4
3 W
135
4 R
B
5 B
6 ‘U5’ Output 2-10 VDC
…MFT95
24 VAC Transformer
1
1 Common
Line
Volts
3
2 + Hot
To reverse control rotation, use the reversing switch.
4
A
WARNING Live Electrical Components!
W
3 W
Line
Volts
R
4 R
2
Controller
B
5 B
B
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
6 ‘U5’ Output 2-10 VDC
…MFT95
Override
24 VAC
Transformer
1
S963A
Minimum Position
Potentiometer
1 Common
Line
Volts
2 + Hot
5
Series 90
Controller
R
B
B
W
3 W
4 R
R
2
5 B
W
Shunting
Resistor
6 ‘U5’ Output 2-10 VDC
3
4
…MFT95
B
R
W
H205 Changeover Controller
Occupied
Contact
1
1 Common
Line
Volts
3
2 + Hot
5
2
3 W
4 R
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
5 B
6 ‘U5’ Output 2-10 VDC
To other
actuators
…MFT95
Wiring multiple actuators to a
Series 90 controller using a
minimum position potentiometer.
24 VAC Transformer
1
1 Common
Line
Volts
2 + Hot
W
Series 90
Controller
3
5
2
W
B
R
3 W
R
4 R
B
5 B
Series 90 low limit control
135 for 0 to 50% control
280 for 0 to 100% control
6 ‘U5’ Output 2-10 VDC
…MFT95
Low Limit Control
1
24 VAC Transformer
1 Common
Line
Volts
2 + Hot
3 W
W
Series 90
Controller
3
5
2
4 R
R
B
R
W
B
5 B
6 ‘U5’ Output 2-10 VDC
Series 90 high limit control - 280
…MFT95
High Limit Control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
61
ARB24-3-T N4, ARX24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
D1363
Dimensions with 2-Way Valve
D
E
w/built in heater
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing type
Housing material
Agency listings†
Quality standard
on/off, floating point
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2.5 W / heater 23 W
holding 0.5 W
5.5 VA (class 2 power source) / heater 20.5 VA
screw terminal (for 26 to 14 GA wire)
electronic throughout 0° to 95° rotation
600 Ω
90°, adjustable with mechanical stop
reversible with
visual pointer
external push button
90 seconds constant independent of load
100% RH
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
UL Type 4X/NEMA 4X/IP66 & IP67
Polypropelene
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No. 24-93,
CE according to 89/336/EEC.
ISO 9001
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
A
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
Dimensions with 3-Way Valve1363
C
D
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3
*Cannot be used with the CCV-EXT-KIT
800-543-9038 USA
62
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
w/built in heater
B
D1364
ARB24-3-T N4
ARB24-3-T N4H
ARX24-3-T N4
ARX24-3-T N4H
F
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
Models
C
ARB24-3-T N4, ARX24-3-T N4 NEMA 4X Actuators, On/Off, Floating Point
2
24 VAC Transformer
2
3
4
4
Blk (1) Common –
Line
Volts
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
For end position indication, interlock control, etc.,
ARB24-3-S incorporates one built-in auxiliary switches:
1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
W409
Wiring Diagrams
Red (2) +
a
a open
a closed
Wht (3) +
The indication of direction
is valid for switch position 1.
1
0
ARB24-3
Actuators may also be powered by 24 VDC.
On/Off control
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
24 VAC Transformer
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
2
4
Blk (1) Common –
Line
Volts
WARNING Live Electrical Components!
W411
y
Red (2) +
Wht (3) +
The indication of direction
is valid for switch position 1.
1
0
ARB24-3
Floating Point or On/Off control
with actuator types ..-3
N
L
L
1
2
3
N
L
M = actuator
T (°C) = Thermostat
H = Heating
T
H
(°C)
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
M
1
2
Note
The follo
f wing points must be taken into account
with independent, external wiring:
• All contact between the cables or wires that
are introduced and the heating element is to be
avoided.
• Where necessary, use cables with sufficient
numbers of wires, e.g. so that the heating and the
actuator can be supplied separately with voltage.
Heater wiring
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
63
ARB24-SR-T N4, ARX24-SR-T N4 NEMA 4X Actuators, Proportional
D
D1363
Dimensions with 2-Way Valve
D
E
C
F
B
A
ARB N4, ARX N4, NRB N4, NRX N4
w/built in heater
w/built in heater
Technical Data
Power supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Operating range Y
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing type
Housing material
Agency listings†
Quality standard
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 2.5 W / heater 23 W
holding 0.4 W
5 VA (class 2 power source) / heater 20 VA
screw terminal (for 26 tp 14 GA wire)
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA
600 Ω
90°, adjustable with mechanical stop
reversible with
visual pointer
external push button
90 seconds constant independent of load
100% RH
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
UL Type 4X/NEMA 4X/IP66 & IP67
Polypropelene
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No. 24-93,
CE according to 89/336/EEC.
ISO 9001
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
Dimensions with 3-Way Valve1363
D1364
ARB24-SR-T N4
ARB24-SR-T N4H
ARX24-SR-T N4
ARX24-SR-T N4H
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
C
D
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
†Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3
*Cannot be used with the CCV-EXT-KIT
800-543-9038 USA
64
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models
ARB24-SR-T N4, ARX24-SR-T N4 NEMA 4X Actuators, Proportional
Wiring Diagrams
Wiring Diagrams
with actuator types ..-3
2
CAUTION Equipment damage!
N
L
L
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
1
2
3
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (–) leg of control circuits.
N
L
M = actuator
T (°C) = Thermostat
H = Heating
T
H
(°C)
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
M
1
2
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Note
The follo
f wing points must be taken into account
with independent, external wiring:
• All contact between the cables or wires that
are introduced and the heating element is to be
avoided.
• Where necessary, use cables with sufficient
numbers of wires, e.g. so that the heating and the
actuator can be supplied separately with voltage.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W408-SR-T
Heater wiring
W408-SR-T
2 to 10 VDC control
4 to 20 mA control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
65
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
D1363
Dimensions with 2-Way Valve
12.98
[330]
6.77
[172]
10.29
[261]
6.02
[153]
D
E
C
F
B
A
w/built in heater
Technical Data
Control
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
Power supply
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption running 3.5 W / heater 24 W
holding 1.25 W
6 VA (class 2 power source) / heater 21 VA
Transformer sizing
Electrical connection
screw terminal (for 26 tp 14 GA wire)
Overload protection
electronic throughout 0° to 95° rotation
Input impedance
100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for PWM, floating point and
on/off control
95°, adjustable with mechanical stop
Angle of rotation
electronically variable
Direction of rotation
reversible with
Position indication
visual pointer
Manual override
external push button
150 seconds (default)
Running time
constant independent of load
variable (75 to 350 seconds)
Humidity
100% RH
Ambient temperature
-22°F to 122°F [-30°C to 50°C]
Storage temperature
-40°F to 176°F [-40°C to 80°C]
Housing type
UL Type 4X/NEMA 4X/IP66 & IP67
Polypropelene
Housing material
Agency listings†
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1, CSA C22.2 No. 24-93, CE according to 89/336/EEC.
Quality standard
ISO 9001
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.27” [57.7]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
Dimensions with 3-Way Valve1363
6.77
[172]
12.98
[330]
10.29
[261]
6.02
[153]
C
D
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
† Rated impulse voltage 4kV, Control pollution degree 3, Type of action 1
*Cannot be used with the CCV-EXT-KIT
800-543-9038 USA
66
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
ARX24-MFT-T N4
ARX24-MFT-T N4H
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
D1364
Models
ARX24-MFT-T N4 NEMA 4X Actuators, Multi-Function Technology
3
4
6
8
9
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A& B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection.
On/Off control
W538
2
W538
Wiring Diagrams
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
WARNING Live Electrical Components!
Floating Point
W538
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
with actuator types ..-3
N
L
L
1
2
3
N
L
M = actuator
T (°C) = Thermostat
H = Heating
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
T
W538
VDC/4-20 mA
H
(°C)
M
1
2
Note
The follo
f wing points must be taken into account
with independent, external wiring:
• All contact between the cables or wires that
are introduced and the heating element is to be
avoided.
• Where necessary, use cables with sufficient
numbers of wires, e.g. so that the heating and the
actuator can be supplied separately with voltage.
PWM
Heater wiring
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
67
ARQX24-1 Quick Running Actuators, On/Off
D1375
Dimensions with 2-Way Valve
8.30”
[210.8]
3.84”
[97.4]
D
C
H1
H2
E
F
A
Models
Flexible Version
Dimensions with 3-Way Valve
Power consumption
Transformer sizing
Electrical connection
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
on/off
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 15 W
holding 1.5 W
26 VA (Class 2 power source)
½” conduit connector,
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
100 Ω
max 95°, adjustable with mechanical stop
reversible with
reflective visual indicator (snap-on)
external push button
constant of independent load
10 or 15 seconds
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<52 dB(A)
ISO 9001
8.30”
[210.8]
3.84”
[97.4]
D
H1
C
H2
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B330-B332 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B340 1½”
40
4.39” [111.6] 2.51” [63.7] 2.90” [61.1]
B348-B352
2”
50
4.95” [124.5] 2.73” [69.5] 2.74” [69.7]
Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
800-543-9038 USA
68
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Control
Power supply
Noise level
Quality standard
Dimensions (Inches [mm])
A
B
4.21” [107]
2.27” [57.7]
D1376
ARQX24-1
Valve Nominal Size
Inches DN [mm]
50
2”
Valve Body
B248-B280
ARQX24-1 Quick Running Actuators, On/Off
W403-ARQ-08
Wiring Diagrams
1
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
ARQ...24-1
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
ARQX24-1
WARNING Live Electrical Components!
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
69
ARQX24-MFT Quick Running Actuators, Multi-Function Technology
D149-2A
Dimensions with 2-Way Valve
Flexible Version
Technical Data
Power supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Operating range Y
Feedback output U
Input impedance
Angle of rotation
Direction of rotation
Position indication
Manual override
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Quality standard
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 15 W
holding 1.5 W
26 VA (Class 2 power source)
½” conduit connector,
18 GA plenum rated cable
3 ft [1m], 10 ft [3m], 16 ft [5m]
electronic throughout 0 to 95° rotation
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, on/off)
2 to 10 VDC, 0.5mA max
VDC variable
100 kΩ (0.1 mA), 500 Ω, 1500 Ω
(on/off)
max 95°, adjustable with mechanical stop
electronically variable
reversible with
reflective visual indicator (snap-on)
external push button
constant of independent load
10 or 15 seconds
5 to 95% RH non-condensing
(EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EC and 2006/95/EC for line voltage
and/or –S versions
<52 dB(A)
ISO 9001
Dimensions (Inches [mm])
A
B
3.72” [94.6]
2.04” [51.9]
3.88” [98.5]
2.04” [51.9]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
Dimensions with 3-Way Valve
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B330-B332 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B340 1½”
40
4.39” [111.6] 2.51” [63.7] 2.90” [61.1]
B348-B352
2”
50
4.95” [124.5] 2.73” [69.5] 2.74” [69.7]
Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
800-543-9038 USA
70
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
ARQX24-MFT
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
D149A
Models
Valve Body
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
ARQX24-MFT Quick Running Actuators, Multi-Function Technology
1
2
W399_08
Wiring Diagrams
Provide overload protection and disconnect as required.
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
5
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
W399_08
VDC/4-20 mA
The ZG-R01 500 Ω resistor may be used.
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
71
GRB24-3, GRX24-3 Actuators, On/Off, Floating Point
D1377
Dimensions
8.30”
[210.8]
3.84”
[97.4]
D
C
I
G
B
E
A
Nominal
Pipe
Size
B6400
4” [100]
B6500
5" [125]
B6600
6" [150]
GRB24-3-5-14
GRX24-3-5-14
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
Manual override
Ambient temperature
Housing
Agency listings †
Noise level
Quality standard
on/off, floating point
24 VAC ± 20% 50/60 Hz
running 4 W
holding 2 W
6 VA (Class 2 power source)
3 ft,18 GA plenum rated cable
½” conduit connector
GRX
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
electronic throughout 0° to 95° rotation
600 Ω
max. 95°, adjustable with mechanical stop
Top
Flange
Design
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
F05
10.00" [254] 10.30" [261.6] 10.50" [266.4]
11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models
Valve
Body
F
reversible with
visual indicator
150 seconds, constant independent of load
external push button
-22°F to 122°F [-30°C to 50°C]
NEMA 2/IP54, Enclosure Type 2
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EEC and 2006/95/EC.
<45 dB(A)
ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
800-543-9038 USA
72
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
GRB24-3, GRX24-3 Actuators, On/Off, Floating Point
W254_08
Wiring Diagrams
1
Provide overload protection and disconnect as required.
3
Actuators may also be powered by 24 VDC.
Meets cULus requirements without the need of an electrical ground
connection.
WARNING
G Live Electrical Components!
On/Off control
W255_08
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Floating Point or On/Off control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
73
GRB120-3, GRX120-3
D1377
Dimensions
8.30”
[210.8]
3.84”
[97.4]
D
C
I
G
B
E
A
Nominal
Pipe
Size
B6400
4” [100]
B6500
5" [125]
B6600
6" [150]
GRB120-3
GRX120-3
Technical Data
Power Supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Control
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
Humidity
Ambient temperature
Housing
Housing material
Agency listings †
Noise level
Quality standard
100 to 240 VAC, 50/60 Hz (nominal)
85 to 265 VAC, 50/60 Hz (tolerance)
running 4 W
holding 2 W
7 VA (Class 2 power source)
18 GA appliance rated cable
½” conduit connector
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
electronic throughout 0° to 95° rotation
on/off, floating point
600 Ω
max. 95°, adjustable with mechanical stop
Top
Flange
Design
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
F05
10.00" [254] 10.30" [261.6] 10.50" [266.4]
11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Models
Valve
Body
F
reversible with
external push button
150 seconds, constant independent of load
5 to 95% RH non condensing (EN 60730-1)
-22°F to 122°F [-30°C to 50°C]
NEMA 2/IP54, Enclosure Type 2
UL94-5VA
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EEC and 2006/95/EC.
<45 dB(A)
ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
800-543-9038 USA
74
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
GRB120-3, GRX120-3
W375_08
Wiring Diagrams
1
Provide overload protection and disconnect as required.
2
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Meets cULus requirements without the need of an electrical ground
connection.
WARNING
G Live Electrical Components!
On/Off control
W376_08
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Floating Point or On/Off control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
75
GRX24-MFT Actuators, Multi-Function Technology
D1377
Dimensions
8.30”
[210.8]
3.84”
[97.4]
D
C
I
G
B
E
A
Nominal
Pipe
Size
B6400
4” [100]
B6500
5" [125]
B6600
6" [150]
Top
Flange
Design
Models
GRX24-MFT-5-14
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
Overload protection
Feedback output
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
Manual override
Ambient temperature
Housing
Housing material
Agency listings †
Noise level
Quality standard
2 to 10 VDC, 4 to 40 mA (default)
variable (VDC, PWM, floating point, on/off)
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 4.5 W
holding 1.5 W
7 VA (Class 2 power source)
3 ft,18 GA plenum rated cable
½” conduit connector
3 ft. [1m], 10 ft. [3m], 16 ft. [5m]
electronic throughout 0° to 95° rotation
2 to 10 VDC, 0.5 mA max, VDC variable
100 kΩ (0.1 mA, 500 Ω)
1500 Ω (PWM, floating point , on/off)
max. 95°, adjustable with mechanical stop
electronically variable
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
F05
10.00" [254] 10.30" [261.6] 10.50" [266.4]
11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Valve
Body
F
reversible with
visual indicator
150 seconds (default)
variable (75 to 300 seconds)
external push button
-22°F to 122°F [-30°C to 50°C]
NEMA 2/IP54, Enclosure Type 2
UL94-5V (flammability rating)
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EEC and 2006/95/EC.
<45 dB(A)
ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
800-543-9038 USA
76
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
GRX24-MFT Actuators, Multi-Function Technology
2
3
4
5
8
9
Provide overload protection and disconnect as required.
CAUTION Equipment Damage!
Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance
must be observed.
Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection of the controller.
VDC/4-20 mA
W399_08
1
W399_08
Wiring Diagrams
Meets UL requirements without the need of an electrical ground
connection.
The ZG-R01 500 Ω resistor may be used.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
PWM
M
W399_08
WARNING
G Live Electrical Components!
W399_08
On/Off
Off controll
Floating Point control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
77
TFRB(X) Actuators, On/Off
3.05"
[76.2]
6.28"
[159.55]
2.40"
[61]
2.93"
[74.5]
D
E
D136
65
Dimensions with 2-Way Valve
F
C
B
A
Models
TFRB(X)120
TFRB(X)120-S
on/off
Power consumption
motor
spring
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
TFRB(X)...-S
Auxiliary switch
6.28"
[159.55]
24VAC ± 20%, 50/60Hz
24VDC ± 10%
(nominal) 100 to 240 VAC, 50/60 Hz
(tolerance) 85 to 265 VAC, 50/60 Hz
running 2.5 W
holding 1.3 W
Transformer sizing
TFRB(X)24(-S)
TFRB(X)120(-S)
Electrical connection
(-S models have 2 cables)
TFRB(X)24...
TFRB(X)120
Overload protection
Angle of rotation
Direction of rotation
Position indication
Running time
3.05"
[76.2]
running
spring return
D
2.40"
[61]
2.93"
[74.5]
C
5 VA (class 2 power source)
5 VA (class 2 power source)
½” conduit connector
18 GA appliance cable
3 ft [1m]
10 ft [3m]
16 ft [5m]
electronic throughout 0° to 95° rotation
95°
reversible with protected
visual indicator, 0° to 95°
<75 seconds (0 to 18 in-lb)
<75 sec @ -22°F to 122°F [-20°C to 50°C]
5 to 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA type 2/IP42
UL94 - 5VA
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
<40 db (A)
<40 dB (A)
ISO 9001
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body
Inches DN [mm]
A
B
C
B307(B)-B311(B)
½”
15
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
B312(B)-B315(B)
½”
15
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
B317(B)-B321(B)
¾”
20
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
800-543-9038 USA
78
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
TFRB(X)120(-S)
Quality standard
w/built-in Aux. Switch
Dimensions with 3-Way Valve
Technical Data
Control
Power supply
TFRB(X)24(-S)
Noise level (max)
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
D136
66
TFRB(X)24
TFRB(X)24-S
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
TFRB(X) Actuators, On/Off
Wiring Diagrams
24 VAC Transformer
1 Common
2
3
3
2 + Hot
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
TFX24 US
Actuators may also be powered by 24 VDC.
2
On/Off Wiring
100 to 240 VAC
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
N L1
1 Neutral
H L2
2 Hot
WARNING Live Electrical Components!
TFX120 US 2
On/Off Wiring
W248
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
S1
NC
S2
S3
NO
0° to 95°
TFX…-S US
2
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary Switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
79
TFRB(X)24-3 Actuators, Floating Point
3.05"
[76.2]
6.28"
[159.55]
2.40"
[61]
2.93"
[74.5]
D
E
D136
65
Dimensions with 2-Way Valve
F
C
B
A
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
Models
TFRB(X)24-3
TFRB(X)24-3-S
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
w/built-in Aux. Switch
Transformer sizing
Electrical connection
(-S models have 2 cables)
TFRB(X)24-3...
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
spring
motor
motor
spring
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level (max)
running
spring return
Quality standard
TFRB(X)24-3-S US
Auxiliary switch
3.05"
[76.2]
6.28"
[159.55]
D
2.40"
[61]
2.93"
[74.5]
C
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body
Inches DN [mm]
A
B
C
B307(B)-B311(B)
½”
15
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
B312(B)-B315(B)
½”
15
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
B317(B)-B321(B)
¾”
20
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
800-543-9038 USA
80
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
running
holding
floating point
24VAC ± 20%, 50/60Hz
2.5 W
1.0 W
4 VA (class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft [1m]
10 ft [3m]
16 ft [5m]
electronic throughout 0° to 95° rotation
1000 Ω (0.6w) control inputs
95°
reversible with CW/CCW mounting
reversible with built-in
visual indicator, 0° to 95°
95 sec constant, independent of load
<25 sec @ -4°F to 122°F [-20°C to 50°C]
<60 sec @ -22°F [-30°C]
5 to 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA type 2/IP42
UL94 - 5VA
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
<35 db (A)
62 dB (A)
ISO 9001
D136
66
Dimensions with 3-Way Valve
Technical Data
Control
Power supply
Power consumption
TFRB(X)24-3 Actuators, Floating Point
24 VAC Transformer
7
a
Wht (W3)
~
~
xx
xx
xx
b
Or
~
xx
xx
xx
xx
xx
xx
xx
xx
xx
x
x
CCW
Switch
Positions
a
(3)
b
(4)
CW
W
C
CCW
CW
C
CCW
stop
stop
stop
stop
TF24-3 (-S) US
The actuator Hot must be connected to the control board common.
For end position indication, interlock control, fan startup, etc.,
TF24-3-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A
(0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
Actuators with plenum rated cable do not have numbers on wires; use
color coded instead. Actuators with appliance rated cable use numbers.
(W4)
Direction of Rotation Switch
The indication of direction is valid
for switch position CW.
Floating point control
W242
5
xx
xx
4
Common
Red (2)
e
xx
xx
3
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
The common connection from the actuator must be
connected to the Hot connection of the controller.
Blk (1)
xx
xx
2
7
Line
Volts
CAUTION Equipment damage!
W240
Wiring Diagrams
24 VAC Transformer
Line
Volts
2
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
Hot
Com
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
7
Blk (1)
Common
Red (2)
~ Hot
Wht (W3)
~
~
Or
(W4)
TF24-3 (-S) US
Controller
The indication of direction
is valid for switch position CW.
W243
Triac source
24 VAC Transformer
Line
Volts
2
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Hot
Com
7
Blk (1)
Common
Red (2)
~ Hot
3
Wht (W3)
~
~
4
Or
(W4)
TF24-3 (-S) US
Controller
The indication of direction is valid for switch position CW.
W241
Triac sink with separate transformers
5
S1
NC
S2
S3
NO
0° to 95°
TF24-3-S US
Auxiliary switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
81
TFRB(X)24-SR Actuators, Proportional
3.05"
[76.2]
6.28"
[159.55]
2.40"
[61]
2.93"
[74.5]
D
E
D136
65
Dimensions with 2-Way Valve
F
C
B
A
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B221(B)
Models
TFRB(X)24-SR
TFRB(X)24-SR-S
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
w/built-in Aux. Switch
Power consumption
running
holding
Transformer sizing
Electrical connection
(-S models have 2 cables)
TFRB(X)24-SR...
Electrical protection
Overload protection
Operating range Y
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
spring
motor
motor
spring
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level (max)
Quality standard
TFRB(X)24-SR-S
Auxiliary switch
running
spring return
proportional
24 VAC ± 20%, 50/60 Hz
24 VDC ± 10%
2.5 W
1.0 W
4 VA (class 2 power source)
½” conduit connector
18 GA plenum rated cable
3 ft [1m]
10 ft [3m]
16 ft [5m]
actuators are double insulated
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA
100k Ω (0.1mA), 500 Ω
95°
reversible with CW/CCW mounting
reversible with built-in
visual indicator, 0° to 95°
95 sec constant, independent of load
<25 sec @-4°F to 122°F [-20°C to 50°C]
<60 sec @-22°F [-30°C]
5 to 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA type 2/IP42
UL94 - 5VA
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
<35 db (A)
<62 dB (A)
ISO 9001
3.05"
[76.2]
6.28"
[159.55]
D
2.40"
[61]
2.93"
[74.5]
C
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body
Inches DN [mm]
A
B
C
B307(B)-B311(B)
½”
15
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
B312(B)-B315(B)
½”
15
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
B317(B)-B321(B)
¾”
20
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95°
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
800-543-9038 USA
82
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Control
Power supply
D136
66
Dimensions with 3-Way Valve
TFRB(X)24-SR Actuators, Proportional
24 VAC Transformer
4
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Up to 4 actuators may be connected in parallel. With 4 actuators wired
to one 500 Ω resistor, a +2% shift of control signal may be required.
Power consumption must be observed.
3
Actuators may also be powered by 24 VDC.
5
Only connect common to neg. (—) leg of control circuits.
6
7
Blk (1) Common
Line
Volts
CAUTION Equipment damage!
6
Red (2) + Hot
3
Wht (3) Y1 Input, 2 to 10V
Control Signal (–)
2 to 10 VDC (+)
2
TF24-SR US
2 to 10 VDC control
24 VAC Transformer
Actuators with plenum rated cable do not have numbers on wires;
use color codes instead.
For end position indication, interlock control, fan startup, etc.,
TF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 3A
(0.5A ) @250 VAC, UL listed, adjustable 0° to 95°.
W246
2
W245
Wiring Diagrams
6
Blk (1) Common
Line
Volts
(–)
4 to 20 mA
Control Signal (+)
Ω
500Ω
Red (2) + Hot
3
Wht (3) Y1 Input, 2 to 10V
4
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
5
WARNING Live Electrical Components!
2
To other
actuators
TF24-SR US
4 to 20 mA control
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
7
S1
NC
S2
S3
NO
0° to 95°
TF24-SR-S US
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
83
TFRX24-MFT Actuators, Multi-Function Technology
3.05"
[76.2]
6.28"
[159.55]
2.40"
[61]
2.93"
[74.5]
D
E
D136
65
Dimensions with 2-Way Valve
F
C
B
A
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
Valve Body
B207-B211
B212-B215
B217-B221
Models
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
TFRX24-MFT
running
holding
Transformer sizing
Electrical connection
Overload protection
Operating range Y*
Feedback output U*
Input impedance
Mechanical angle of rotation*
Angle of rotation adaptation*
Direction of rotation
spring
motor
Position indication
Override control*
Running time
motor*
spring
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level (max)
Quality standard
running
spring return
3.05"
[76.2]
6.28"
[159.55]
D
2.40"
[61]
2.93"
[74.5]
C
E
F
B
A
Valve Body
B307-B311
B312-B315
B317-B321
Valve Nominal Size
Dimensions (Inches [mm])
Inches DN [mm]
A
B
C
½”
15
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
½”
15
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
¾”
20
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
* Variable when configured with MFT options
† Rated impulse voltage 0.8 kV, Control pollution degree 3, Type of action 1.AA.
800-543-9038 USA
84
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Power consumption
MFT
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
2.5 W
1.0 W
4 VA (class 2 power source)
½” conduit connector
3 ft [1m], 18 GA plenum rated cable
electronic throughout 0° to 95° rotation
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
2 to 10 VDC, 0.5 mA max
100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for PWM, floating point and
on/off control
95°
Off (Default)
reversible with CW/CCW mounting
reversible with built-in
visual indicator, 0° to 95°
Min. (Min Position) = 0%
- ZS (Mid. Position) = 50%
- Max. (Max. Position) = 100%
95 seconds constant independent of load
<25 seconds @-4°F to 122°F [-20°C to 50°C]
<60 seconds @-22°F [-30°C]
5 to 95% RH, non-condensing
-22 to 122° F (-30 to 50° C)
-40 to 176° F (-40 to 80° C)
NEMA 2/IP42
UL 94-5VA
cULus according to UL 60730-1A/-2-14, CAN/
CSA E60730-1:02, CE according to 2004/108/
EC and 2006/95/EC for line voltage and/or –S
versions
<35 dB (A)
<65 dB (A)
ISO 9001
D136
66
Dimensions with 3-Way Valve
Technical Data
Control
Power supply
TFRX24-MFT Actuators, Multi-Function Technology
1
2
W024
Wiring Diagrams
Provide overload protection and disconnect as required.
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
Actuators may also be powered by 24 VDC.
4
ZG-R01 may be used.
WARNING Live Electrical Components!
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W025
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
2 to 10 VDC Control Signal
4 to 20 mA Control Signal
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
85
LF Actuators, On/Off
3.625"
[92]
D1367
Dimensions with 2-Way Valve
7.64"
[194]
2.28"
[58]
3.7"
[94]
D
E
C
B
F
A
Models
w/built-in Aux. Switch
w/built-in Aux. Switch
Technical Data
Control
Power supply
LF24(-S) US
LF120(-S) US
Dimensions with 3-Way Valve
D1368
on/off, floating point
LF120(-S) US
Power consumption
LF24(-S) US
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
120 VAC ± 10% 50/60 Hz
running
holding
running
holding
5W
2.5 W
5.5 W
3.5 W
D
Transformer sizing
LF24(-S) US
LF120(-S) US
Electrical connection
(-S models have 2 cables)
Electrical protection
Overload protection
Angle of rotation
Spring return direction
Position indication
Running time
motor
spring
7 VA, class 2 power source
7.5 VA, class 2 power source
½” conduit connector
3 ft [1m], 18 GA appliance cable
120V actuators double insulated
electronic throughout rotation
95°
reversible with CW/CCW mounting
visual indicator 0° to 90°
<40 to 75 seconds (on/off)
<25 sec. @-4°F to 122°F [-20°C to 50°C]
<60 sec. @-22°F [-30°C]
Ambient temperature
-22° F to 122° F [-30° C to 50° C]
NEMA 2
Housing
Agency listings†
cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93
Noise level (max)
running <30 db(A)
spring return 62 dB(A)
Quality standard
ISO 9001
LF...-S US
Auxiliary switch
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
E
F
C
B
A
Valve Nominal Size
Valve Body
Inches DN [mm]
B307(B)-B311(B)
½”
15
B312(B)-B315(B)
½”
15
B317(B)-B320(B)
¾”
20
B322-B325
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
† Rated impulse voltage 800V (4kV for 120V model), Control pollution degree 3,
Type of action 1.AA (1.AA.B for -S models)
800-543-9038 USA
86
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LF24 US
LF24-S US
LF120 US
LF120-S US
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B220(B)
B222-B225
B229-B230
LF Actuators, On/Off
W047
Wiring Diagrams
24 VAC Transformer
2
Provide overload protection and disconnect as required.
CAUTION Equipment damage!
1 Common
2 + Hot
LF24 US
Actuators may be connected in parallel.
Power consumption must be observed.
3
2
On/Off wiring for 24 VDC
3
Actuator may also be powered by 24 VDC.
4
For end position indication, interlock control, fan startup, etc.,
LF24-S US and LF120-S US incorporates a built-in auxiliary switch:
1 x SPDT, 6A (1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
W049-LF-08
1
Line
Volts
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
WARNING Live Electrical Components!
On/Off wiring for 120 VDC
W048-AUX
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary Switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
87
LF24-3 Actuators, Floating Point
D1367
Dimensions with 2-Way Valve
3.625"
[92]
7.64"
[194]
2.28"
[58]
3.7"
[94]
D
E
C
B
F
A
Technical Data
Power supply
Power consumption
running
holding
Transformer sizing
Electrical connection
(-S models have 2 cables)
Overload protection
Input impedance
Angle of rotation
spring
Direction of rotation
motor
Position indication
Running time
motor
spring
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings
Noise level (max)
Servicing
Quality standard
LF24-3-S US
Auxiliary switch
running
spring return
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
2.5 W
1W
5 VA (class 2 power source)
½” conduit connector
3 ft [1m], 18 GA appliance cable
electronic throughout 0° to 95° rotation
1000 Ω (0.6w) control inputs
95°
reversible with CW/CCW mounting
reversible with built-in
visual indicator 0° to 90°
150 seconds constant independent of load
<25 seconds @ -4°F to 122°F [-20°C to 50°C]
<60 seconds @ -22°F [-30°C]
5 to 95% RH non-condensing
-22° F to 122° F [-30° C to 50° C]
-40° F to 176° F [-40° C to 80° C]
NEMA type 2/IP54
zinc coated metal
cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93
<30 db(A)
62 dB(A)
maintenance free
ISO 9001
D
E
F
C
B
A
Valve Nominal Size
Valve Body
Inches DN [mm]
B307(B)-B311(B)
½”
15
B312(B)-B315(B)
½”
15
B317(B)-B320(B)
¾”
20
B322-B325
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
800-543-9038 USA
88
Dimensions with 3-Way Valve
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
w/built-in Aux. Switch
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1368
Models
LF24-3 US
LF24-3-S US
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B220(B)
B222-B225
B229-B230
LF24-3 Actuators, Floating Point
W054
Wiring Diagrams
24 VAC Transformer
Line
Volts
CAUTION Equipment damage!
Actuators may be connected in parallel.
Power consumption must be observed.
3
Actuators may also be powered by 24 VDC.
4
The common connection from the actuator must be connected to the
Hot connection of the controller.
5
The actuator Hot must be connected to the control board common.
8
Hot
nents!
ting,
hooting
be
h live
Have
ectrician
o has
n
Com
Blk (1) Common
Red (2) + Hot
Wht (3) +
Grn (4) +
CW
hese
all
utions
electrical
ult in
For end position indication, interlock control, fan startup, etc.,
LF24-3-S US incorporates one built-in auxiliary switch: 1 x SPDT, 6A
(1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
Actuators with plenum rated cable do not have numbers on wires;
use color coded instead. Actuators with appliance rated cable use
numbers.
8
CCW
LF24-3(-S) US
The indication of direction is
valid for switch position CW.
Controller
Triac source
W055
2
6
2
NG
24 VAC Transformer
Line
Volts
G
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
8
2
nts!
ng,
ooting
e
ive
Have
trician
has
Hot
Com
Blk (1) Common 4
Red (2) + Hot
5
Wht (3) +
Grn (4) +
WARNING Live Electrical Components!
ese
ll
ons
ectrical
t in
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
3
2
8
LF24-3(-S) US
Controller
The indication of direction is valid for switch position CW.
s!
Line
Volts
W056
24 VAC Transformer
Line
Volts
24 VAC Transformer
2
8
Blk (1) Common
Line
Volts
Blk (1) Common
ing
Red (2) +
a
e
ve
cian
s
Wht (3) +
Grn (4) +
Hot
Com
Red (2) + Hot
e
CW
CCW
The indication of direction
is valid for switch position CW.
5
Wht (3) +
Grn (4) +
a open
a closed
s
rical
n
LF24-3(-S) US
On/Off control
CW
CCW
LF24-3(-S) US
Controller
The indication of direction is valid for switch position CW.
24 VAC Transformer
W052
Triac sink with separate transformers
8
Blk (1) Common
Line
Volts
Red (2) +
a
Wht (3) +
b
Grn (4) +
Installation Side
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
x
x
CCW
Switch
Positions
a
(3)
b
(4)
Direction of Rotation Switch
CW
W
C W
CC
CW
C W
CC
stop
stop
stop
stop
CW
CCW
LF24-3(-S) US
The indication of direction
is valid for switch position CW.
Floating Point control
W053
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
CCW
Triac sink
W061
24 VAC Transformer
CW
6
S1
NC
S2
S3
NO
0° to 95°
LF24-3-S US
Auxiliary switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
89
LF24-SR Actuators, Proportional
3.625"
[92]
D1367
Dimensions with 2-Way Valve
7.64"
[194]
2.28"
[58]
3.7"
[94]
D
E
C
B
F
A
Technical Data
Control
Control signal
Power consumption
running
holding
Transformer sizing
Electrical connection
(-S models have 2 cables)
Overload protection
Feedback output
Input impedance
Angle of rotation
spring
Direction of rotation
motor
Position indication
Running time
motor
spring
Ambient temperature
Housing
Agency listings
Noise level (max)
Quality standard
LF24-SR-S US
Auxiliary switch
running
spring return
proportional
2 to 10 VDC
4 to 20 mA (with 500 Ω resistor)
2.5 W
1W
5 VA, class 2 power
½” conduit connector
3 ft [1m], 18 GA appliance cable
electronic throughout 0° to 95° rotation
2 to 10 VDC
100 kΩ
95°
reversible with CW/CCW mounting
reversible with built-in
visual indicator
150 sec. independent of load (proportional)
<25 seconds @ -4°F to 122°F [-20°C to 50°C]
<60 seconds @ -22°F [-30°C]
-22° F to 122° F [-30° C to 50° C]
NEMA 2
cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93
<30 db(A)
62 dB(A)
ISO 9001
D
E
F
C
B
A
Valve Nominal Size
Valve Body
Inches DN [mm]
B307(B)-B311(B)
½”
15
B312(B)-B315(B)
½”
15
B317(B)-B320(B)
¾”
20
B322-B325
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
800-543-9038 USA
90
Dimensions with 3-Way Valve
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
w/built-in Aux. Switch
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
D1368
Models
LF24-SR US
LF24-SR-S US
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207(B)-B211(B)
B212(B)-B215(B)
B217(B)-B220(B)
B222-B225
B229-B230
LF24-SR Actuators, Proportional
4
24 VAC Transformer
2
Blk (1) Common
Line
Volts
CAUTION Equipment damage!
Actuators may be connected in parallel. Up to 4 actuators may be
connected in parallel. With 4 actuators wired to one 500 Ω resistor, a
+2% shift of control signal may be required. Power consumption
must be observed.
Red (2) + Hot
Actuators may also be powered by 24 VDC.
4
Actuators with plenum rated cable do not have numbers on wires;
use color codes instead.
5
Only connect common to neg. (–) leg of control circuits.
6
For end position indication, interlock control, fan startup, etc.,
LF24-SR-S US incorporates one built-in auxiliary switch: 1 x SPDT, 6A
(1.5A) @ 250 VAC, UL listed, adjustable 0° to 95°.
7
Control Signal (–)
2 to 10 VDC (+)
Grn (5) U Output, 2 to 10V
7
CCW
2
LF24-SR US
2 to 10 VDC control
24 VAC Transformer
4
Blk (1) Common
Line
Volts
(–)
4 to 20 mA
Control Signal (+)
The LF24-SR-S US wire 5 is white.
Ω
500Ω
5
Red (2) + Hot
3
Wht (3) Y1 Input, 2 to 10V
2 to 10 VDC (–)
Feedback Signal (+)
Grn (5) U Output, 2 to 10V
To other
actuators
CW
CCW
2
LF24-SR US
4 to 20 mA control
W058
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
3
Wht (3) Y1 Input, 2 to 10V
CW
3
W057
Wiring Diagrams
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
6
S1
NC
S2
S3
NO
0° to 95°
LF24-SR-S US
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary switch
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
91
LF24-MFT Actuators, Multi-Function Technology
3.625"
[92]
D1367
Dimensions with 2-Way Valve
7.64"
[194]
2.28"
[58]
3.7"
[94]
D
E
C
B
F
A
Models
w/built-in Aux. Switch
running
holding
Transformer sizing
Electrical connection
(-S models have 2 cables)
Overload protection
Feedback output
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
spring
motor
motor
spring
Ambient temperature
Housing
Agency listings
Noise level (max)
Quality standard
LF24-MFT-S US
Auxiliary switch
running
spring return
MFT
2 to 10 VDC
2.5 W
1W
5 VA (class 2 power source)
½” conduit connector
3 ft [1m], 18 GA appliance cable
electronic throughout 0° to 95° rotation
2 to 10 VDC, 0.5 mA max
100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20mA
750 Ω for PWM
500 Ω for on/off and floating point
95°
reversible with CW/CCW mounting
reversible with built-in
visual indicator
150 seconds independent of load
(proportional, default)
<25 seconds @-4°F to 122°F [-20°C to 50°C]
<60 seconds @-22°F [-30°C]
-22° F to 122° F [-30° C to 50° C]
NEMA 2
cULus according to UL 873 and CAN/CSA
C22.2 No. 24-93
<30 db(A)
62 dB(A)
ISO 9001
D
E
F
C
B
A
Valve Body
B307-B311
B312-B315
B317-B320
B322-B325
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
Dimensions (Inches [mm])
A
B
C
2.41” [61.1] 1.39” [35.2] 1.20” [30.6]
2.38” [60.4] 1.78” [45.2] 1.29” [32.8]
2.73” [69.3] 1.87” [47.4] 1.47” [37.3]
3.09” [78.4] 1.87” [47.4] 1.59” [40.3]
1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
800-543-9038 USA
92
Dimensions with 3-Way Valve
D1368
Technical Data
Control
Control signal
Power consumption
Dimensions (Inches [mm])
A
B
2.41” [61.1]
1.39” [35.2]
2.38” [60.4]
1.78” [45.2]
2.73” [69.3]
1.87” [47.4]
3.09” [78.4]
1.87” [47.4]
3.72” [94.6]
1.87” [47.4]
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
LF24-MFT US
LF24-MFT-S US
Valve Nominal Size
Inches DN [mm]
½”
15
½”
15
¾”
20
1”
25
1¼”
32
Valve Body
B207-B211
B212-B215
B217-B220
B222-B225
B229-B230
Wiring Diagrams
24 VAC/DC Transformer
Line
Volts
CAUTION Equipment damage!
Actuators may be connected in parallel if not mechanically mounted to
the same shaft. Power consumption and input impedance must be
observed.
Actuators may also be powered by 24 VDC.
4
IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).
5
Triac A and B can also be contact closures.
7
Common
(2)
Hot
(3)
Y Input
(5)
U Output
a
(–)
Feedback VDC (+)
CCW CW
3
6
Position
(1)
…MFT
On/Off control
W041
2
W043
LF24-MFT Actuators, Multi-Function Technology
24 VAC Transformer (AC only)
Control signal may be pulsed from either the Hot (Source) or
Common (Sink) 24 VAC line.
Position feedback cannot be used with Triac sink controller.
The actuators internal common reference is not compatible.
(1)
Line
Volts
7
6
Position
(–)
Feedback VDC (+)
Common
(2)
+ Hot
(3)
Y Input
(5)
U Output
CCW CW
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
…MFT
PWM, triac source and sink
WARNING Live Electrical Components!
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W302
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
Floating Point control
Proportional 2 to 10 or 4 to 20 mA control signal
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
93
AFRB24(-S), AFRX24(-S) Actuators, On/Off
D1369
Dimensions
9.77”
[248.2]
3.93”
[99.9]
2.50”
[63.5]
4.04”
[102.7]
C
D
E
B
F
A
Models
AFRX24...
Overload protection
Control
Direction of rotation
Angle of rotation
Running time
Position indication
Manual override
Ambient temperature
Storage temperature
Housing
Agency listings †
Noise level
Quality standard
3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance
cables with 1/2” conduit connectors
3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
1/2” conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or
16 ft. [5m] appliance cables, with or without
1/2" conduit connectors
electronic throughout 0 to 95° rotation
on/off
spring reversible with CW/CCW mounting
95°
motor < 75 seconds
spring 20 seconds @ -4°F to 122°F [-20°C to 50°C];
< 60 seconds @ -22°F [-30°C]
visual indicator, 0° to 95°
(0° is full spring return position)
5 mm hex crank (3/16" Allen), supplied
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2, IP54, Enclosure Type2
cULus according. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according. to
2004/108/EC & 2006/95/EC
<50dB(A) motor @ 75 seconds
<62dB(A) spring return
ISO 9001
Dimensions
9.77”
[248.2]
4.04”
[102.7]
C
D
E
B
F
A
Valve Nominal Size
Valve Body Inches DN [mm]
B312-B316
½”
15
B317-B321
¾”
20
B322-B325
1”
25
B329-B331 1¼”
32
B338-B341 1½”
40
B347-B352
2”
50
Dimensions (Inches [mm])
A
B
C
2.38” [60.4] 1.72” [43.7] 1.26” [32.1]
2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
AFRB24-S, AFRX24-S
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
94
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Transformer sizing
Electrical connection
AFRB24...
D1370
Power consumption
24 VAC ± 20% 50/60 Hz
24 VDC +20% / -10%
running 5 W
holding 2.5 W
7.5 VA (class 2 power source)
Dimensions (Inches [mm])
A
B
2.38” [60.4]
1.72” [43.7]
2.73” [69.3]
1.81” [45.9]
3.09” [78.4]
1.81” [45.9]
3.72” [94.6]
1.81” [45.9]
3.72” [94.6]
1.98” [50.4]
3.88” [98.5]
1.98” [50.4]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
2.50”
[63.5]
Technical Data
Power supply
Valve Nominal Size
Inches DN [mm]
½”
15
¾”
20
1”
25
1¼”
32
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B212-B216
B217-B221
B222-B225
B229-B230
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
3.93”
[99.9]
AFRB24
AFRB24-S
AFRX24
AFRX24-S
AFRB24(-S), AFRX24(-S) Actuators, On/Off
1
2
3
4
24 VAC Transformer
1 Common
Line
Volts
Provide overload protection and disconnect as required.
CAUTION Equipment Damage!
2 + Hot
3
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
AFB24, AFB24-S
AFX24, AFX24-S
Actuators may also be powered by 24 VDC.
For end position indication, interlock control, fan startup, etc.,
AFRB24-S and AFRX24-S incorporates two built-in auxiliary switches:
2 x SPDT, 3A (0.5A) @250 VAC, UL Approved, one switch is fixed at
+10°, one is adjustable 10° to 90°.
2
On/Off wiring for AFRB24, AFRX24
W064_AFB(X)_-S
1
W063_AFB(X)
Wiring Diagrams
Meets cULus requirements without the need of an electrical ground
connection.
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFB24-S
AFX24-S
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary Switches for AFRB24-S, AFRX24-S
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
95
AFRBUP(-S), AFRXUP(-S) Actuators, On/Off
D1369
Dimensions
9.77”
[248.2]
3.93”
[99.9]
2.50”
[63.5]
4.04”
[102.7]
C
D
E
B
F
A
Models
Electrical connection
AFRBUP...
AFRXUP...
Overload protection
Control
Direction of rotation
Angle of rotation
Running time
Position indication
Manual override
Ambient temperature
Storage temperature
Housing
Agency listings †
Noise level
Quality standard
3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance
cables with 1/2” conduit connectors
3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
1/2” conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or
16 ft. [5m] appliance cables, with or without
1/2" conduit connectors
electronic throughout 0 to 95° rotation
on/off
spring reversible with CW/CCW mounting
95° (adjustable with mechanical end stop, 35°
to 95°)
motor < 75 seconds
spring 20 seconds @ -4°F to 122°F [-20°C to 50°C];
< 60 seconds @ -22°F [-30°C]
visual indicator, 0° to 95°
(0° is full spring return position)
5 mm hex crank (3/16" Allen), supplied
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54, Enclosure Type2
cULus according. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according. to
2004/108/EC & 2006/95/EC
<50dB(A) motor @ 75 seconds
<62dB(A) spring return
ISO 9001
Dimensions
9.77”
[248.2]
4.04”
[102.7]
C
D
E
B
F
A
Valve Nominal Size
Valve Body Inches DN [mm]
B312-B316
½”
15
B317-B321
¾”
20
B322-B325
1”
25
B329-B331 1¼”
32
B338-B341 1½”
40
B347-B352
2”
50
Dimensions (Inches [mm])
A
B
C
2.38” [60.4] 1.72” [43.7] 1.26” [32.1]
2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
AFRBUP-S, AFRXUP-S
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
96
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Transformer sizing
D1370
Power consumption
24 to 240 VAC -20% / +10%, 50/60 Hz
24 to 125 VDC +10%
running 7 W
holding 3.5 W
7 VA @ 24 VAC (class 2 power source)
8.5 VA @ 120 VAC
18 VA @ 240 VAC
Dimensions (Inches [mm])
A
B
2.38” [60.4]
1.72” [43.7]
2.73” [69.3]
1.81” [45.9]
3.09” [78.4]
1.81” [45.9]
3.72” [94.6]
1.81” [45.9]
3.72” [94.6]
1.98” [50.4]
3.88” [98.5]
1.98” [50.4]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
2.50”
[63.5]
Technical Data
Power supply
Valve Nominal Size
Inches DN [mm]
½”
15
¾”
20
1”
25
1¼”
32
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B212-B216
B217-B221
B222-B225
B229-B230
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
3.93”
[99.9]
AFRBUP
AFRBUP-S
AFRXUP
AFRXUP-S
2
3
4
Provide overload protection and disconnect as required.
CAUTION Equipment Damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
No ground connection is required.
For end position indication, interlock control, fan startup, etc.,
AFRBUP-S and AFRXUP-S incorporates two built-in auxiliary switches:
2 x SPDT, 3A (0.5A) @250 VAC, UL Approved, one switch is fixed at
+10°, one is adjustable 10° to 90°.
AFBUP, AFBUP-S
AFXUP, AFBUP-S
On/Off wiring for AFRBUP, AFRXUP
Meets cULus requirements without the need of an electrical ground
connection.
W067_AFB(X)UP-S
1
W066_AFB(X)UP
Wiring Diagrams
Wht
Blk
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
AFBUP-S
AFXUP-S
Auxiliary Switches for AFRBUP-S, AFRXUP-S
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
97
AFRB24-SR, AFRX24-SR
Proportional, Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA Control Signal
D1369
Dimensions
9.77”
[248.2]
4.04”
[102.7]
3.93”
[99.9]
2.50”
[63.5]
Dimensio
C
D
E
B
F
A
AFX...
Overload protection
Operating range Y
Input impedance
Feedback output U
Direction of rotation
spring
motor
Mechanical angle of rotation
spring
Running time
motor
Position indication
Manual override
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
Noise level
Servicing
Quality standard
Weight
3 ft, 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft, 18 gauge appliance cables
with 1/2” conduit connectors
3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA
appliance or plenum cables, with or without 1/2”
conduit connector
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables, with or without 1/2"
conduit connectors
electronic throughout 0 to 95° rotation
2 to 10 VDC, 4 to 20mA
100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
2 to 10 VDC (max. 0.5 mA)
reversible with CW/CCW mounting
reversible with built-in switch
95° (adjustable with mechanical end stop, 35° to
95°)
< 20 seconds @ -4°F to 122°F [-20°C to 50°C];
< 60 seconds @ -22°F [-30°C]
95 seconds
visual indicator, 0° to 95°
(0° is full spring return position)
5 mm hex crank (³⁄₁₆" Allen), supplied
max. 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
Nema 2, IP54, Enclosure Type2
zinc coated metal and plastic casing
cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC &
2006/95/EC
≤40dB(A) motor @ 95 seconds
≤62dB(A) spring return
maintenance free
ISO 9001
4.6 lbs (2.1 kg); 4.9 lbs (2.25 kg) with switches
Dimensions
9.77”
[248.2]
4.04”
[102.7]
C
D
E
B
F
A
Valve Nominal Size
Valve Body Inches DN [mm]
B312-B316
½”
15
B317-B321
¾”
20
B322-B325
1”
25
B329-B331 1¼”
32
B338-B341 1½”
40
B347-B352
2”
50
Dimensions (Inches [mm])
A
B
C
2.38” [60.4] 1.72” [43.7] 1.26” [32.1]
2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
800-543-9038 USA
98
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Transformer sizing
Electrical connection
AFRB...
D1370
Power consumption
24 VAC ±20%, 50/60 Hz
24 VDC +20% / -10%
running 5.5 W
holding 3 W
8.5 VA (class 2 power source)
Dimensions (Inches [mm])
A
B
2.38” [60.4]
1.72” [43.7]
2.73” [69.3]
1.81” [45.9]
3.09” [78.4]
1.81” [45.9]
3.72” [94.6]
1.81” [45.9]
3.72” [94.6]
1.98” [50.4]
3.88” [98.5]
1.98” [50.4]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
2.50”
[63.5]
Power supply
Valve Nominal Size
Inches DN [mm]
½”
15
¾”
20
1”
25
1¼”
32
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B212-B216
B217-B221
B222-B225
B229-B230
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
3.93”
[99.9]
Technical Data
AFRB24-SR, AFRX24-SR
Proportional, Spring Return, 24 V, for 2 to 10 VDC to 4 to 20 mA Control Signal
Accessories
WARNING
G Live Electrical Components!
ZG-AFB
ZG-AFB118
ZS-100
ZS-150
ZS-260
ZS-300
NOTE: When using AFRB24-SR, AFRB24-SR-S, AFRX24-SR and AFRX24-SR-S actuators, only use
accessories listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
1
W068_AFB(X)24-SR
Shaft extension
Damper position indicator
Crank arm
Universal clamp for up to 1.05” dia jackshafts
Conduit fitting
8mm and 10 mm wrench
Universal mounting bracket
Universal mounting bracket
Mounting bracket for Barber Colman® MA 3../4.., Honeywell®
Mod III or IV or Johnson® Series 100 replacement or new crank
arm type installations
Crank arm adaptor kit
Crank arm adaptor kit
Weather shield (metal)
Weather shield (polycarbonate)
Explosion-proof housing
NEMA 4X housing
24 VAC Transformer
1 Common
Line
Volts
3
2 + Hot
Control Signal (–)
2 to 10 VDC (+)
3 Y1 Input, 2 to 10V
5 U Output 2 to 10V
AFB24-SR, AFB24-SR-S
AFX24-SR, AFX24-SR-S
2
2 to 10 VDC control of AFRB24-SR and AFRX24-SR
W069_AFB(X)24-SR
AV 8-25
IND-AFB
KH-AFB
K7-2
TF-CC US
Tool-06
ZG-100
ZG-101
ZG-118
Typical Specification
Spring return control damper actuators shall be direct coupled type which require no
crank arm and linkage and be capable of direct mounting to a jackshaft up to a 1.05”
diameter. The actuator must provide proportional damper control in response to a 2 to
10 VDC or, with the addition of a 500Ω resistor, a 4 to 20 mA control input from an
electronic controller or positioner. The actuators must be designed so that they may be
used for either clockwise or counterclockwise fail-safe operation. Actuators shall use
a brushless DC motor controlled by a microprocessor and be protected from overload
at all angles of rotation. Run time shall be constant, and independent of torque. A 2 to
10 VDC feedback signal shall be provided for position feedback. Actuators shall be
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001
International Quality Control Standards. Actuators shall be as manufactured by Belimo.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2
2
3
4
5
W064_AFB(X)24_SR_-S
4 to 20 mA control of AFRB24-SR and AFRX24-SR with
2 to 10 VDC feedback output
Wiring Diagrams
1
AFB24-SR, AFB24-SR-S
AFX24-SR, AFX24-SR-S
Provide overload protection and disconnect as required.
CAUTION Equipment Damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
Up to 4 actuators may be connected in parallel if not mechanically mounted
to the same shaft. With 4 actuators wired to one 500 Ω resistor.
Power consumption must be observed.
Actuator may also be powered by 24 VDC.
For end position indication, interlock control, fan startup, etc., AFB24-SR-S
and AFX24-SR-S incorporates two built-in auxiliary switches: 2 x SPDT, 3A
(0.5A) @250 VAC, UL Approved, one switch is fixed at +10°, one is adjustable 10° to 90°.
AFB24-SR-S
AFX24-SR-S
Auxiliary switches for AFRB24-SR-S, AFX24-SR-S
Only connect common to neg. (–) leg of control circuits
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC.
ATTENTION:
ATTENTION
AFRB24-SR(-S)
AFRB24
SR( S) andd AFRX24-SR(-S)
AFRX24 SR( S) cannott bbe ttandem
d mounted
t d
on the same damper or valve shaft. Only On/Off and MFT AF models can be used
for tandem mount applications.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
99
AFRX Actuators, Multi-Function Technology
D1369
Dimensions
9.77”
[248.2]
3.93”
[99.9]
2.50”
[63.5]
4.04”
[102.7]
C
D
E
B
F
A
Models
Overload protection
Feedback output*
Input impedance
Angle of rotation
Direction of rotation*
spring
motor
Position indication
Manual override
Running time
motor*
spring
Ambient temperature
Housing
Agency listings
Noise level
Quality standard
† Programmed for 70 sec motor runtime. At 150 sec motor run time, transformer sizing
Dimensions
9.77”
[248.2]
4.04”
[102.7]
C
D
E
B
F
A
Valve Nominal Size
Valve Body Inches DN [mm]
B312-B316
½”
15
B317-B321
¾”
20
B322-B325
1”
25
B329-B331 1¼”
32
B338-B341 1½”
40
B347-B352
2”
50
Dimensions (Inches [mm])
A
B
C
2.38” [60.4] 1.72” [43.7] 1.26” [32.1]
2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
is 8.5 VA and power consumption is 6 W running/3 W holding.
* Variable when configured with MFT options
‡ Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control
Pollution Degree 3.
AFRX24-MFT-S
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10° to 90°
800-543-9038 USA
100
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Power consumption† running
holding
Transformer sizing†
Electrical connection
D1370
Power supply
MFT
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
24 VAC, +/- 20%, 50/60 Hz
24 VDC, +20% / -10%
7.5 W
3W
10 VA (Class 2 power source)
3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
1/2" conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or 16
ft. [5m] appliance cables with or without 1/2”
conduit connectors
electronic throughout 0 to 90° rotation
2 to 10 VDC, 0.5 mA max (variable)
100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for on/off and floating point
95°
reversible with CW/CCW mounting
reversible with built-in
visual indicator 0° to 95°(0° is spring return
position)
5 mm hex crank (3/16” Allen), supplied
150 seconds (default),
variable (70 to 220 seconds)
<20 sec @ -4°F to 122°F [-20°C to 50°C]
-22° F to 122° F [-30° C to 50° C]
NEMA 2, IP54, Enclosure Type 2
cULus according. To UL60730-1A/-2-14,
CAN/CSA E60730- 1:02, CE according. To
2004/108/EC & 2006/95/EC
<40dB(A) motor @ 150 seconds, run time
dependent
<62dB(A) spring return
ISO 9001
Dimensions (Inches [mm])
A
B
2.38” [60.4]
1.72” [43.7]
2.73” [69.3]
1.81” [45.9]
3.09” [78.4]
1.81” [45.9]
3.72” [94.6]
1.81” [45.9]
3.72” [94.6]
1.98” [50.4]
3.88” [98.5]
1.98” [50.4]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
2.50”
[63.5]
Technical Data
Control
Control signal
Valve Nominal Size
Inches DN [mm]
½”
15
¾”
20
1”
25
1¼”
32
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B212-B216
B217-B221
B222-B225
B229-B230
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
3.93”
[99.9]
AFRX24-MFT
AFRX24-MFT-S
AFRX Actuators, Multi-Function Technology
AFR_LGCCV
9.77”
[248.2]
W600_AFB_AFX
Dimensions
3.93”
[99.9]
2.50”
[63.5]
4.04”
[102.7]
D
I
C
AFB24-MFT-S
AFX24-MFT-S
G
B
E
F
Auxiliary Switches for AFRX24-MFT
W399_08
A
Valve
Body
Nominal
Pipe
Size
B6250
2½" [65]
B6300
3" [80]
B6400
4" [100]
Top
Flange
Design
F05
Flange
Diameter
Face-to-Face
Length
A
B
Height
C
7.50" [190.5] 5.50" [139.7]
8.10" [205.4]
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
VDC/4-20 mA
W399_08
Wiring Diagrams
3
4
5
8
9
CAUTION Equipment Damage!
Actuators may be connected in parallel if not mechanically mounted
to the same shaft. Power consumption and input impedance must be
observed.
Actuators may also be powered by 24 VDC.
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection of the controller.
PWM
M
W399_08
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2
Provide overload protection and disconnect as required.
Meets UL requirements without the need of an electrical ground
connection.
The ZG-R01 500 Ω resistor may be used.
On/Off
Off controll
W399_08
1
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
Floating Point control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
101
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
D1369
Dimensions
9.77”
[248.2]
3.93”
[99.9]
2.50”
[63.5]
4.04”
[102.7]
C
D
E
B
F
A
Models
AFRX24-MFT95
spring
motor
Position indication
Manual override
Running time
motor*
spring
Ambient temperature
Housing
Agency listings
Noise level
Quality standard
† Programmed for 70 sec motor runtime. At 150 sec motor run time, transformer sizing
is 8.5 VA and power consumption is 6 W running/3 W holding.
* Variable when configured with MFT options
‡ Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control
Pollution Degree 3.
800-543-9038 USA
102
Dimensions
9.77”
[248.2]
4.04”
[102.7]
C
D
E
B
F
A
Valve Nominal Size
Valve Body Inches DN [mm]
B312-B315
½”
15
B317-B321
¾”
20
B322-B325
1”
25
B329-B331 1¼”
32
B338-B341 1½”
40
B347-B352
2”
50
866-805-7089 CANADA
Dimensions (Inches [mm])
A
B
C
2.38” [60.4] 1.72” [43.7] 1.26” [32.1]
2.73” [69.3] 1.81” [45.9] 1.45” [36.8]
3.09” [78.4] 1.81” [45.9] 1.56” [39.8]
3.96” [100.6] 2.21” [56.2] 2.14” [54.3]
4.39” [111.6] 2.45” [62.2] 2.33” [59.1]
4.90” [124.5] 2.68” [68.0] 2.60” [66.0]
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Overload protection
Feedback output*
Angle of rotation
Direction of rotation*
D1370
Power consumption† running
holding
Transformer sizing†
Electrical connection
Dimensions (Inches [mm])
A
B
2.38” [60.4]
1.72” [43.7]
2.73” [69.3]
1.81” [45.9]
3.09” [78.4]
1.81” [45.9]
3.72” [94.6]
1.81” [45.9]
3.72” [94.6]
1.98” [50.4]
3.88” [98.5]
1.98” [50.4]
4.21” [107.0]
2.21” [56.2]
4.93” [125.2]
2.68” [68.0]
5.55” [140.9]
2.68” [68.0]
5.82” [147.9]
2.68” [68.0]
2.50”
[63.5]
Power supply
MFT
0 to 135 Ω Honeywell Electronic Series 90,
0 to 135 Ω input
24 VAC, +/- 20%, 50/60 Hz
24 VDC, +20% / -10%
7.5 W
3W
10 VA (Class 2 power source)
3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
plenum cables, with or without 1/2" conduit
connector
electronic throughout 0 to 90° rotation
2 to 10 VDC, 0.5 mA max (variable)
95°
reversible with CW/CCW mounting
reversible with built-in
visual indicator 0° to 95°(0° is spring return
position)
5 mm hex crank (3/16” Allen), supplied
150 seconds (default),
variable (70 to 220 seconds)
<20 sec @ -4°F to 122°F [-20°C to 50°C]
-22° F to 122° F [-30° C to 50° C]
NEMA 2, IP54, Enclosure Type 2
cULus according. To UL60730-1A/-2-14,
CAN/CSA E60730- 1:02, CE according. To
2004/108/EC & 2006/95/EC
<40dB(A) motor @ 150 seconds, run time
dependent
<62dB(A) spring return
ISO 9001
3.93”
[99.9]
Technical Data
Control
Control signal
Valve Nominal Size
Inches DN [mm]
½”
15
¾”
20
1”
25
1¼”
32
1¼”
32
40
1½”
2”
50
2”
50
2½”
65
3”
80
Valve Body
B212-B215
B217-B221
B222-B225
B229-B230
B231-B232
B238-B240
B248-B250
B251-B254
B261-B265
B277-B280
9.77”
[248.2]
D1378
Dimensions
4.04”
[102.7]
Switch A
Switch B
Damper Open
Damper Closed
2.50”
[63.5]
3.93”
[99.9]
Damper Position
W015_AFRX
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
The direction of rotation switch is set so that the fail safe position and the
position of the damper is closed with no signal at wire R.
D
I
1
C
24 VAC Transformer
1 Common, Blk
Line
Volts
2 + Hot, Red
A
G
E
4
3 W, Wht
135
B
3
4 R, Wht
B
F
5 B, Wht
A
6 ‘U5’ Output 2-10 VDC
1
Valve
Body
B6250
Nominal
Pipe
Size
Top
Flange
Design
2½" [65]
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
AFRX24-MFT95
24 VAC Transformer
1 Common, Blk
Line
Volts
2 + Hot, Red
7.50" [190.5] 5.50" [139.7]
Line
Volts
8.10" [205.4]
3 W, Wht
4 R, Wht
R
B
B
B6300
3" [80]
B6400
4" [100]
F05
4
A
W
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
2
3
5 B, Wht
6 ‘U5’ Output 2-10 VDC
Controller
AFRX24-MFT95
Override of AFRX24-MFT95
1
Provide overload protection and disconnect as required.
2
Actuators and controller must have separate transformers.
3
Consult controller instruction data for more detailed installation
information.
24 VAC Transformer
1 Common, Blk
Line
Volts
2 + Hot, Red
4
2
W
Series 90
Controller
W
B
R
To reverse control rotation, use the reversing switch.
5
Resistor value depends on the type of controller and the number of
actuators. No resistor is used for one actuator. Honeywell resistor
kits may also be used.
1
4 R, Wht
B
5 B, Wht
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
6 ‘U5’ Output 2-10 VDC
AFRX24-MFT95
24 VAC Transformer
1 Common, Blk
Line
Volts
WARNING Live Electrical Components!
3 W, Wht
R
Series 90 low limit control
135 for 0 to 50% control
280 for 0 to 100% control
4
3
W017
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
1
W016
Wiring Diagrams
2 + Hot, Red
4
2
3 W, Wht
W
Series 90
Controller
3
4 R, Wht
R
B
R
W
B
5 B, Wht
6 ‘U5’ Output 2-10 VDC
Series 90 high limit control - 280
AFRX24-MFT95
AFRX24-MFT95 used with a Series 90 controller
and a Series 90 low limit control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
103
W018_AFRX
W020_AFRX
AFRX24-MFT95 Actuator, Proportional Potentiometric Control
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
W019_AFRX
Wiring multiple actuators to a Series 90 controller.
AFRX24-MFT95
AFRX24-MFT95
AFRX24-MFT95
Wiring multiple actuators to a Series 90 controller
using a minimum position potentiometer.
AFRX24-MFT95
Typical wiring diagrams for multiple actuators used
with the W973, W7100 and T775 controllers.
800-543-9038 USA
104
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
AFRX24-MFT95
AFRB24 N4, AFRB24 N4H, AFRB24-S N4, AFRB24-S N4H,
AFRX24 N4, AFRX24 N4H, AFRX24-S N4, AFRX24-S N4H
NEMA 4, On/Off, Spring Return, 24 V
D1363
Dimensions with 2-Way Valve
12.98
[330]
6.77
[172]
10.29
[261]
6.02
[153]
D
E
Models
Valve Body
B231-B232
B238-B240
B248-B254
B277-B280
Technical Data
Power consumption
Transformer sizing
Electrical connection
AFR... N4
B
A
Basic Version
Basic Version w/built in heater
Basic Version w/built-in aux. switch
Basic Version w/built-in aux. switch & heater
Flexible Version
Flexible Version w/built-in aux. switch
Flexible Version w/built in heater
Flexible Version aux. switch & heater
Power supply
F
24 VAC ± 20% 50/60 Hz
24 VDC +20% / -10%
running 5 W / heater 25 W
holding 2.5 W
7.5 VA (class 2 power source) / heater 25 VA
3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance
cable, with or without 1/2” conduit connector
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables with or without 1/2” conduit
connectors
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
3”
80
Dimensions (Inches [mm])
A
B
3.72” [94.6]
1.84” [47.4]
3.88” [98.5]
2.04” [51.9]
4.93” [125.2]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
Dimensions with 3-Way Valve1363
D1364
AFRB24 N4
AFRB24 N4H
AFRB24-S N4
AFRB24-S N4H
AFRX24 N4
AFRX24-S N4
AFRX24 N4H
AFRX24-S N4H
C
6.77
[172]
12.98
[330]
10.29
[261]
6.02
[153]
C
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
D
heater (N4H)
Overload protection
Control
Torque
Direction of rotation
spring
Mechanical angle of rotation
Running time
motor
terminal block, 26-16 GA
electronic throughout 0 to 95° rotation
on/off
180 in-lb [20 Nm] minimum
reversible with CW/CCW mounting in housing
95° (adjustable with mechanical end stop, 35° to 95°)
< 75 seconds
spring 20 seconds @ -4°F to 122°F [-20°C to 50°C];
< 60 seconds @ -22°F [-30°C]
spring (with heater) 20 seconds @ -4°F to 122°F [-20°C to 50°C], <60
seconds @ -49°F [-45°C]
Position indication
visual indicator, 0° to 95°
(0° is full spring return position)
Manual override
5 mm hex crank (³⁄₁₆" Allen), supplied
Humidity
max. 95% RH non-condensing
Ambient temperature
-22°F to 122°F [-30°C to 50°C]
with heater -49°F to 122°F [-45°C to 50°C]
Storage temperature
-40°F to 176°F [-40°C to 80°C]
Housing
UL Type 4, NEMA 4, IP66
Housing material
polycarbonate
Agency listings †
cULus acc. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE acc. to
2004/108/EC & 2006/95/EC
Noise level
<50dB(A) motor @ 75 seconds
≤62dB(A) spring return
Servicing
maintenance free
Quality standard
ISO 9001
Weight
9.7 lbs (4.4 kg); 10 lbs (4.5 kg) with switches;
10.5 lbs (4.8 kg) with heater
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B332 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 4.
AFRB24-S N4, AFRB24-S N4H, AFRX24-S N4, AFRX24-S N4H
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
105
AFRB24 N4, AFRB24 N4H, AFRB24-S N4, AFRB24-S N4H,
AFRX24 N4, AFRX24 N4H, AFRX24-S N4, AFRX24-S N4H
NEMA 4, On/Off, Spring Return, 24 V
Accessories
Wiring Diagrams
Tool-06
8mm and 10 mm wrench
43442-00001
Gland (needed for additional wires)
11097-00001
Gasket for Gland (needed for additional wires)
NOTE: When using AFRB24 N4, AFRB24 N4H, AFRB24-S N4, AFRB24-S N4H, AFRX24 N4,
AFRX24 N4H, AFRX24-S N4, AFRX24-S N4H actuators, only use accessories listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
Provide overload protection and disconnect as required.
1
CAUTION Equipment Damage!
2
Actuators may be connected in parallel.
Power consumption and input impedance must be
observed.
Typical Specification
The actuators must be designed so that they may be used for either clockwise or
counterclockwise fail-safe operation. Actuators shall be protected from overload at all
angles of rotation. If required, two SPDT auxiliary switch shall be provided having the
capability of one being adjustable. Actuators with auxiliary switches must be
constructed to meet the requirements for Double Insulation so an electrical ground is
not required to meet agency listings. Actuators shall be cULus Approved and have a 5
year warranty, and be manufactured under ISO 9001 International Quality Control
Standards. Actuators shall be as manufactured by Belimo.
Actuators may also be powered by 24 VDC.
3
For end position indication, interlock control, fan startup, etc., AFRB24-S
N4, AFRB24-S N4H, AFRX24-S N4, AFRX24-S N4H incorporates two built-in
auxiliary switches: 2 x SPDT, 3A (0.5A) @250 VAC, UL Approved, one
switch is fixed at +10°, one is adjustable 10° to 90°.
4
Meets cULus requirements without the need of an electrical ground
connection.
WARNING
G Live Electrical Components!
24 VAC Transformer
Line
Volts
1 Common
2 + Hot
AFRB24 N4
AFRB24 N4H
AFRB24-S N4
AFRB24-S N4H
AFRX24 N4
AFRX24-S N4
3
2
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
1
W063_AFRBX24_N4
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
On/Off wiring
AFRB24-S N4
AFRB24-S N4H
AFRX24-S N4
AFRX24-S N4H
GK-AF-NF N4H 24V heater
Auxiliary Switches
NEMA 4 Heater
800-543-9038 USA
106
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H,
AFRXUP N4, AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H
NEMA 4, On/Off, Spring Return, 24 to 240 VAC
D1363
Dimensions with 2-Way Valve
12.98
[330]
6.77
[172]
10.29
[261]
6.02
[153]
D
Models
E
Basic Version
Basic Version w/built-in aux. switch
Basic Version w/built in heater
Basic Version w/built-in aux. switch & heater
Flexible Version
Flexible Version w/built-in aux. switch
Flexible Version w/built in heater
Flexible Version w/built-in aux. switch & heater
Valve Body
B231-B232
B238-B240
B248-B254
B261-B265
B277-B280
24...240 VAC -20% / +10%, 50/60 Hz
24...125 VDC ±10%
running 7 W / heater 25 W
holding 3.5 W
7 VA @ 24 VAC (class 2 power source)
8.5 VA @ 120 VAC / heater 25 VA @120 VAC
18 VA @ 240 VAC
Power consumption
Transformer sizing
Electrical connection
AFRBUP... N4
AFRXUP... N4
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
heater (N4H)
Overload protection
Control
Torque
Direction of rotation
Mechanical angle of rotation
Running time
spring
motor
spring
spring (with heater)
Position indication
Manual override
Humidity
Ambient temperature
with heater
Storage temperature
Housing
Housing material
Agency listings †
Noise level
Servicing
Quality standard
Weight
B
A
Technical Data
Power supply
F
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2½”
65
3”
80
Dimensions (Inches [mm])
A
B
3.72” [94.6]
1.84” [47.4]
3.88” [98.5]
2.04” [51.9]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
Dimensions with 3-Way Valve1363
D1364
AFRBUP N4
AFRBUP-S N4
AFRBUP N4H
AFRBUP-S N4H
AFRXUP N4
AFRXUP-S N4
AFRXUP N4H
AFRXUP-S N4H
C
6.77
[172]
3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance
cable, with or without 1/2” conduit connector
-S models: Two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables with or without 1/2” conduit
connectors
terminal block, 18-16 GA
electronic throughout 0 to 95° rotation
on/off
180 in-lb [20 Nm] minimum
reversible with CW/CCW mounting inside housing
95° (adjustable with mechanical end stop,
35° to 95°)
< 75 sec
20 sec @ -4°F to 122°F [-20°C to 50°C];
< 60 sec @ -22°F [-30°C]
20 sec @ -4°F to 122°F [-20°C to 50°C];
< 60 sec @ -49°F [-45°C]
visual indicator, 0° to 95°
(0° is full spring return position)
5 mm hex crank (³⁄₁₆" Allen), supplied
max. 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-49°F to 122°F [-45°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
UL Type 4, NEMA 4, IP66
polycarbonate
cULus acc. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE acc. to
2004/108/EC & 2006/95/EC
<50dB(A) motor @ 75 seconds
≤62dB(A) spring return
maintenance free
ISO 9001
9.7 lbs (4.4 kg), 10 lbs (4.5 kg) with switches
10.5 lbs (4.8 kg) with heater
12.98
[330]
10.29
[261]
6.02
[153]
C
D
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
† Rated Impulse Voltage 4kV, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 4.
AFRBUP-S N4, AFRBUP-S N4H, AFRXUP-S N4, AFRXUP-S N4H
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL Approved
one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
107
AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H,
AFRXUP N4, AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H
NEMA 4, On/Off, Spring Return, 24 to 240 VAC
W066_AFRBUP_N4
Accessories
Tool-06
8mm and 10 mm wrench
43442-00001
Gland (needed for additional wires)
11097-00001
Gasket for Gland (needed for additional wires)
NOTE: When using AFRBUP N4, AFRBUP-S N4, AFRBUP N4H, AFRBUP-S N4H, AFRXUP N4,
AFRXUP-S N4, AFRXUP N4H, AFRXUP-S N4H actuators, only use accessories listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
Typical Specification
AFRBUP N4
AFRBUP N4H
AFRBUP-S N4
AFRBUP-S N4H
AFRXUP N4
AFRXUP N4H
AFRXUP-S N4
AFRXUP-S N4H
On/Off Wiring
W067_AFRBUP-S_N4
On/Off spring return damper actuators shall be direct coupled type which require
no crank arm and linkage and be capable of direct mounting to a jackshaft up to a
1.05” diameter. The actuators must be designed so that they may be used for either
clockwise or counterclockwise fail-safe operation. Actuators shall be protected
from overload at all angles of rotation. If required, two SPDT auxiliary switch shall
be provided having the capability of one being adjustable. Actuators with auxiliary
switches must be constructed to meet the requirements for Double Insulation so
an electrical ground is not required to meet agency listings. Actuators shall be
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001
International Quality Control Standards. Actuators shall be as manufactured by Belimo.
Wiring Diagrams
Wht
1
2
Blk
Provide overload protection and disconnect as required.
CAUTION Equipment Damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be
observed.
4
Actuators may also be powered by 24 VDC.
For end position indication, interlock control, fan startup, etc., AFRB24-S
N4, AFRB24-S N4H, AFRX24-S N4, AFRX24-S N4H incorporates two built-in
auxiliary switches: 2 x SPDT, 3A (0.5A) @250 VAC, UL Approved, one
switch is fixed at +10°, one is adjustable 10° to 90°.
Meets cULus requirements without the need of an electrical ground
connection.
WARNING
G Live Electrical Components!
AFRBUP-S N4
AFRBUP-S N4H
AFRXUP-S N4
AFRXUP-S N4H
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
AF-NF N4H 120V heater
Auxiliary Switches
NEMA 4 Heater
800-543-9038 USA
108
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
3
AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H
NEMA 4, Proportional, Spring Return, Direct Coupled, 24V, Multi-Function Technology®
D1363
Dimensions with 2-Way Valve
12.98
[330]
6.77
[172]
Models
AFRB24-MFT N4
AFRB24-MFT-S N4
AFRB24-MFT N4H
AFRB24-MFT-S N4H
AFRX24-MFT N4
AFRX24-MFT-S N4
AFRX24-MFT N4H
AFRX24-MFT-S N4H
10.29
[261]
Basic Version
Basic Version w/built-in aux. switch
Basic Version w/built in heater
Basic Version w/built-in aux. switch & heater
Flexible Version
Flexible Version w/built-in aux. switch
Flexible Version w/built in heater
Flexible Version w/built in aux. switch & heater
6.02
[153]
D
E
C
F
B
A
Technical Data
Power
running
holding
consumption
Transformer sizing
Electrical connection
AFRB... N4
AFRX... N4
heater (N4H)
Overload protection
Operating range Y*
Input impedance
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Feedback output U*
Torque
Direction of
rotation*
Mechanical
angle of rotation*
Running time
spring
motor
24 VAC, +/- 20%, 50/60 Hz
24 VDC, +20% / -10%
7.5 W / heater 25 W
3W
10 VA (Class 2 power source) / heater 25 VA
3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA appliance cables, with
1/2” conduit connector
-S models: two 3 ft [1m], 10 ft [3m] or
16 ft [5m] appliance cables with 1/2” conduit connectors
terminal block, 26-16 GA
electronic throughout 0 to 95° rotation
2 to 10 VDC, 4 to 20 mA (default)
variable (VDC, PWM, floating point, on/off)
100 kΩ for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20 mA
1500 Ω for PWM, floating point and on/off control
2 to 10 VDC, 0.5 mA max
minimum 180 in-lb (20 Nm)
reversible with cw/ccw mounting inside housing
reversible with built-in switch
95° (adjustable with mechanical end stop, 35° to 95°)
Valve Body
B231-B232
B238-B240
B248-B254
B261-B265
B277-B280
Valve Nominal Size
Inches DN [mm]
1¼”
32
40
1½”
2”
50
2½”
65
3”
80
Dimensions (Inches [mm])
A
B
3.72” [94.6]
1.84” [47.4]
3.88” [98.5]
2.04” [51.9]
4.93” [125.2]
2.73” [69.5]
5.55” [140.9]
2.73” [69.5]
5.82” [147.9]
2.73” [69.5]
Dimensions with 3-Way Valve1363
D1364
Power supply
6.77
[172]
12.98
[330]
10.29
[261]
6.02
[153]
C
D
motor* 150 seconds (default), variable (70 to 220 seconds)
spring <20 sec @ -4°F to 122°F [-20°C to 50°C];
<60 sec @ -22°F [-30°C]
spring (with heater) <20 sec @ -4°F to 122°F [-20°C to 50°C];
<60 sec @ -49°F [-45°C]
Angle of Rotation
off (default)
adaptation
Override control*
min position = 0%
mid. position = 50%
max. position = 100%
Position indication
visual indicator, 0° to 95°
(0° is spring return position)
Manual override
5 mm hex crank (³⁄₁₆" Allen), supplied
Humidity
max. 95% RH non-condensing
Ambient temperature
-22°F to 122°F (-30°C to 50°C)
with heater -49°F to 122°F (-45°C to 50°C)
Storage temperature
-40°F to 176°F (-40°C to 80°C)
Housing
UL Type 4, NEMA 4, IP66
Housing material
polycarbonate
Noise level
≤40dB(A) motor @ 150 seconds, run time dependent
≤62dB(A) spring return
Agency listings †
cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-
E
F
B
A
Valve Nominal Size
Dimensions (Inches [mm])
Valve Body Inches DN [mm]
A
B
C
B329-B331 1¼”
32
3.96” [100.6] 2.27” [57.7] 2.14” [54.3]
B338-B341 1½”
40
4.39” [111.6] 2.51” [63.7] 2.40” [61.1]
B347-B352
2”
50
4.90” [124.5] 2.73” [69.5] 2.74” [69.7]
1:02, CE acc. to 2004/108/EC & 2006/95/EC
Quality standard
Servicing
Weight
ISO 9001
maintenance free
9.7 lbs. (4.4 kg), 10 lbs. (4.5 kg) with switches
10.5 lbs (4.8 kg) with heater
* Variable when configured with MFT options
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 4.
Programmed for 70 sec motor run time. At 150 sec motor run time, transformer sizing
iis 8.5 VA and power consumption is 6 W running / 3 W holding.
AFRB24-MFT-S N4, AFRB24-MFT-S N4H, AFRX24-MFT-S N4,
AFRX24-MFT-S N4H
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
109
AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H
NEMA 4, Proportional, Spring Return, Direct Coupled, 24V, Multi-Function Technology®
W399_08
Accessories
Tool-06
8mm and 10 mm wrench
43442-00001
Gland (needed for additional wires)
11097-00001
Gasket for Gland (needed for additional wires)
NOTE: When using AFRB24-MFT N4, AFRB24-MFT-S N4, AFRB24-MFT N4H, AFRB24-MFT-S N4H
AFRX24-MFT N4, AFRX24-MFT-S N4, AFRX24-MFT N4H, AFRX24-MFT-S N4H actuators, only use
accessories listed on this page. For actuator wiring information and diagrams, refer to Belimo
Wiring Guide.
Typical Specification
VDC/4-20 mA
W399_08
The actuator must provide proportional damper control in response to a 2 to 10 VDC or, with the
addition of a 500Ω resistor, a 4 to 20 mA control input from an electronic controller or positioner.
The actuators must be designed so that they may be used for either clockwise or counterclockwise
fail-safe operation. Actuators shall use a brushless DC motor controlled by a microprocessor and
be protected from overload at all angles of rotation. Run time shall be constant, and independent of
torque. A 2 to 10 VDC feedback signal shall be provided for position feedback. Actuators shall be
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001 International
Quality Control Standards. Actuators shall be as manufactured by Belimo.
Wiring Diagrams
3
4
5
8
9
CAUTION Equipment Damage!
Actuators may be connected in parallel if not mechanically linked. Power
consumption and input impedance must be observed.
Actuators may also be powered by 24 VDC.
PWM
M
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source) or the Common
(sink) 24 VAC line.
Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator must be connected
to the hot connection of the controller.
Meets UL requirements without the need of an electrical ground
connection.
W399_08
On/Off
Off C
Controll
The ZG-R01 500 Ω resistor may be used.
WARNING Live Electrical Components!
Floating Point Control
GK-AF-NF N4H 24V heater
W600_AFRB_AFRX_N4
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
NEMA 4 Heater
AFB24-MFT-S N4
AFRB24-MFT-S N4H
AFR$X24-MFT-S N4
AFRX24-MFT-S N4H
Auxiliary Switches
800-543-9038 USA
110
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2
Provide overload protection and disconnect as required.
W399_08
1
AFRB24-5-14, AFRB24-S-5-14 Actuators, On/Off
9.77”
[248.2]
D1378
Dimensions
3.93”
[99.9]
2.50”
[63.5]
4.04”
[102.7]
D
I
C
G
B
E
F
A
Models
AFRB24-5-14
AFRB24-S-5-14
Valve
Body
Technical Data
Power supply
Power consumption
Transformer sizing
Electrical connection
AFRB24...
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
AFRX24...
Overload protection
Control
Direction of rotation
Angle of rotation
Running time
Position indication
Manual override
Ambient temperature
Storage temperature
Housing
Agency listings †
Noise level
Quality standard
24 VAC ± 20% 50/60 Hz
24 VDC +20% / -10%
running 5 W
holding 2.5 W
7.5 VA (class 2 power source)
Nominal
Pipe
Size
B6250
2½" [65]
B6300
3" [80]
B6400
4" [100]
Top
Flange
Design
F05
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
7.50" [190.5] 5.50" [139.7]
8.10" [205.4]
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance
cables with 1/2” conduit connectors
3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
1/2” conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or
16 ft. [5m] appliance cables, with or without
1/2" conduit connectors
electronic throughout 0 to 95° rotation
on/off
spring reversible with CW/CCW mounting
95°
motor < 75 seconds
spring 20 seconds @ -4°F to 122°F [-20°C to 50°C];
< 60 seconds @ -22°F [-30°C]
visual indicator, 0° to 95°
(0° is full spring return position)
5 mm hex crank (3/16" Allen), supplied
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2, IP54, Enclosure Type2
cULus according. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according. to
2004/108/EC & 2006/95/EC
<50dB(A) motor @ 75 seconds
<62dB(A) spring return
ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
AFRB24-S, AFRX24-S
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
111
AFRB24-5-14, AFRB24-S-5-14 Actuators, On/Off
1
2
3
4
24 VAC Transformer
1 Common
Line
Volts
Provide overload protection and disconnect as required.
CAUTION Equipment Damage!
2 + Hot
3
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
AFB24, AFB24-S
AFX24, AFX24-S
Actuators may also be powered by 24 VDC.
For end position indication, interlock control, fan startup, etc.,
AFRB24-S and AFRX24-S incorporates two built-in auxiliary switches:
2 x SPDT, 3A (0.5A) @250 VAC, UL Approved, one switch is fixed at
+10°, one is adjustable 10° to 90°.
2
On/Off wiring for AFRB24, AFRX24
W064_AFB(X)_-S
1
W063_AFB(X)
Wiring Diagrams
Meets cULus requirements without the need of an electrical ground
connection.
WARNING
G Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
AFB24-S
AFX24-S
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary Switches for AFRB24-S, AFRX24-S
800-543-9038 USA
112
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
AFRBUP-5-14, AFRBUP-S-5-14 Actuators, On/Off
9.77”
[248.2]
D1378
Dimensions
3.93”
[99.9]
2.50”
[63.5]
4.04”
[102.7]
D
I
C
G
B
E
F
A
Models
AFRBUP-5-14
AFRBUP-S-5-14
Technical Data
Power supply
Power consumption
Transformer sizing
Electrical connection
AFRBUP...
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
AFRXUP...
Overload protection
Control
Direction of rotation
Angle of rotation
Running time
Position indication
Manual override
Ambient temperature
Storage temperature
Housing
Agency listings †
Noise level
Quality standard
24 to 240 VAC -20% / +10%, 50/60 Hz
24 to 125 VDC +10%
running 7 W
holding 3.5 W
7 VA @ 24 VAC (class 2 power source)
8.5 VA @ 120 VAC
18 VA @ 240 VAC
Valve
Body
Nominal
Pipe
Size
B6250
2½" [65]
B6300
3" [80]
B6400
4" [100]
Top
Flange
Design
F05
Flange
Diameter
Face-to-Face
Length
A
B
Height
C
7.50" [190.5] 5.50" [139.7]
8.10" [205.4]
8.00" [203.2] 6.60" [167.6]
8.40" [213.1]
9.00" [228.6] 8.30" [210.8]
9.30" [235.9]
3 ft., 18 GA appliance cable, 1/2" conduit
connector
-S models: two 3 ft., 18 gauge appliance
cables with 1/2” conduit connectors
3 ft. [1m], 10 ft. [3m] or 16 ft. [5m] 18 GA
appliance or plenum cables, with or without
1/2” conduit connector
-S models: two 3 ft. [1m], 10 ft. [3m] or
16 ft. [5m] appliance cables, with or without
1/2" conduit connectors
electronic throughout 0 to 95° rotation
on/off
spring reversible with CW/CCW mounting
95° (adjustable with mechanical end stop, 35°
to 95°)
motor < 75 seconds
spring 20 seconds @ -4°F to 122°F [-20°C to 50°C];
< 60 seconds @ -22°F [-30°C]
visual indicator, 0° to 95°
(0° is full spring return position)
5 mm hex crank (3/16" Allen), supplied
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54, Enclosure Type2
cULus according. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according. to
2004/108/EC & 2006/95/EC
<50dB(A) motor @ 75 seconds
<62dB(A) spring return
ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
AFRBUP-S, AFRXUP-S
Auxiliary switches
2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
113
AFRBUP-5-14, AFRBUP-S-5-14 Actuators, On/Off
2
3
4
Provide overload protection and disconnect as required.
CAUTION Equipment Damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
No ground connection is required.
For end position indication, interlock control, fan startup, etc.,
AFRBUP-S and AFRXUP-S incorporates two built-in auxiliary switches:
2 x SPDT, 3A (0.5A) @250 VAC, UL Approved, one switch is fixed at
+10°, one is adjustable 10° to 90°.
AFBUP, AFBUP-S
AFXUP, AFBUP-S
On/Off wiring for AFRBUP, AFRXUP
Meets cULus requirements without the need of an electrical ground
connection.
W067_AFB(X)UP-S
1
W066_AFB(X)UP
Wiring Diagrams
Wht
Blk
WARNING
G Live Electrical Components!
AFBUP-S
AFXUP-S
Auxiliary Switches for AFRBUP-S, AFRXUP-S
800-543-9038 USA
114
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
GKRB24-3-5-14 Actuators, On/Off, Floating Point, Fail-Safe
2.36” [60]
3.43” [87]
D1379
Dimensions
7.05” [179]
D
C
I
G
B
E
A
Models
Valve
Body
Nominal
Pipe
Size
B6400
4” [100]
B6500
5" [125]
B6600
6" [150]
GKRB24-3-5-14
Technical Data
Control
Power supply
Power consumption
Transformer sizing
Electrical connection
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Overload protection
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
Manual override
Ambient temperature
Housing
Agency listings †
Noise level
Quality standard
on/off, floating point
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 12 W
holding 3 W
18 VA (Class 2 power source)
3 ft,18 GA plenum rated cable
½” conduit connector
electronic throughout 0° to 95° rotation
100 kΩ (0.1mA), 500 Ω, 1500 Ω (floating
point, on/off)
max. 95°, adjustable with mechanical stop
Top
Flange
Design
F
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
9.00" [228.6] 8.30” [210.8] 9.30” [235.9]
F05
10.00" [254] 10.30" [261.6] 10.50" [266.4]
11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
reversible with
visual indicator
running 150 seconds
fail-safe 35 seconds
external push button
-22°F to 122°F [-30°C to 50°C]
NEMA 2/IP54, Enclosure Type 2
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EEC and 2006/95/EC
<45 dB(A)
ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
115
GKRB24-3-5-14 Actuators, On/Off, Floating Point, Fail-Safe
Electrical Installation
Wiring Diagrams
T
–
~
Wiring diagram
+
Note
!
• Connect via safety isolation transformer.
• Parallel connection of other actuators possible.
Note performance data for supply.
DC 0 ... 10 V
Y
U
1
2
3
DC 2 ... 10 V
1
Provide overload protection and disconnect as required.
2
CAUTION
N Equipment Damage!
3
Actuators may also be powered by 24 VDC.
5
Cable lengths
C
Y
U
~
T
L2
4
Ltot
Note
When several actuators are connected in parallel,
the maximum cable length must be divided by the
number of actuators.
Actuators may be connected in parallel if not mechanically mounted
to the same shaft. Power consumption and input impedance must be
observed.
5
L1
1
2
3
5
8
A
N
L
9
AC
C 230 V
Position feedback cannot be used with Triac sink controller.
ntroller.
The actuator internal common reference is not comppatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection of the controller.
C
T
AC 24 V
Y
U
Meets UL requirements without the need of an electrical ground
connection.
WARNING
G Live Electrical Components!
L1
=
=
=
=
=
Cross section
L2
/
0.75 mm2
1.00 mm2
1.50 mm2
2.50 mm2
T
A
C
L1
L2
Ltot
Actuator
Control unit
Belimo connecting cable, 1 m (4 x 0.75 mm2)
Customer cable
Maximum cable length
During installation, testing, servicing and troubleshooting of this product, it
may be necessary to work with live electrical components. Have a qualified
licensed electrician or other individual who has been properly trained in
handling live electrical components perform these tasks. Failure
ailure to follow all
electrical safety precautions when exposed to live electrical
al components could
result in death or serious injury.
A
Max. cable length
Ltott = L1 + L2
AC
DC
<30 m
<5 m
<40 m
<8 m
<70 m
<12 m
<100 m
<20 m
Example for DC
1 m (L 1) + 4 m (L 2)
1 m (L 1) + 7 m (L 2)
1 m (L 1) + 11 m (L 2)
1 m (L 1) + 19 m (L 2)
A = Actuator
C = Control unit
L1 = Belimo connecting cable, 1 m (4 x 0.75 mm
m2)
W399_10
On/Off
Off controll
Floating Point control
800-543-9038 USA
116
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Cable colors:
1 = black
2 = red
3 = white
5 = orange
3
5
W399_10
1
2
~
Note
There are no special restrictions on installation if
the supply and data cable are routed separately.
GKRX24-MFT-5-14 Actuators, Multi-Function Technology, Fail-Safe
2.36” [60]
3.43” [87]
D1379
Dimensions
7.05” [179]
D
C
I
G
B
E
A
Valve
Body
Nominal
Pipe
Size
B6400
4” [100]
B6500
5" [125]
B6600
6" [150]
Top
Flange
Design
Models
GKRX24-MFT-5-14
Technical Data
Control
Power supply
Power consumption
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Transformer sizing
Electrical connection
Overload protection
Feedback output
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
Manual override
Ambient temperature
Housing
Housing material
Agency listings †
Noise level
Quality standard
2 to 10 VDC, 4 to 40 mA (default)
variable (VDC, PWM, floating point, on/off)
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 12 W
holding 3 W
21 VA (Class 2 power source)
3 ft,18 GA plenum rated cable
½” conduit connector
10 ft. [3m], 16 ft. [5m]
electronic throughout 0° to 95° rotation
2 to 10 VDC, 0.5 mA max, VDC variable
100 kΩ (0.1 mA, 500 Ω)
1500 Ω (PWM, floating point , on/off)
max. 95°, adjustable with mechanical stop
electronically variable
F
Flange
Diameter
Face-to-Face
Length
Height
A
B
C
9.00” [228.6] 8.30” [210.8] 9.30” [235.9]
F05
10.00" [254] 10.30" [261.6] 10.50" [266.4]
11.00" [279.4] 12.50" [317.5] 11.70" [296.9]
reversible with
visual indicator
150 seconds (default)
variable (90 to 150 seconds)
fail-safe 35 seconds
external push button
-22°F to 122°F [-30°C to 50°C]
NEMA 2/IP54, Enclosure Type 2
UL94-5V (flammability rating)
cULus according to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02, CE according to
2004/108/EEC and 2006/95/EC.
<45 dB(A)
ISO 9001
† Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
117
GKRX24-MFT-5-14 Actuators, Multi-Function Technology, Fail-Safe
1
Provide overload protection and disconnect as required.
2
CAUTION
N Equipment Damage!
3
Actuators may also be powered by 24 VDC.
5
8
9
Actuators may be connected in parallel if not mechanically mounted
to the same shaft. Power consumption and input impedance must be
observed.
Position feedback cannot be used with Triac sink controller.
The actuator internal common reference is not compatible.
Control signal may be pulsed from either the Hot (source)
or the Common (sink) 24 VAC line.
Contact closures A & B also can be triacs.
A & B should both be closed for triac source and open for triac sink.
For triac sink the common connection from the actuator
must be connected to the hot connection of the controller.
VDC/4-20 mA
W399_08
4
W399_08
Wiring Diagrams
Meets UL requirements without the need of an electrical ground
connection.
The ZG-R01 500 Ω resistor may be used.
PWM
M
During installation, testing, servicing and troubleshooting of this product, it
may be necessary to work with live electrical components. Have a qualified
licensed electrician or other individual who has been properly trained in
handling live electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical components could
result in death or serious injury.
W399_08
On/Off
Off controll
Floating Point control
800-543-9038 USA
118
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
W399_08
WARNING
G Live Electrical Components!
Accessories
Application
The CCV-EXT-KIT can be used with most CCV’s* and PICCV in order
to achieve a large clearance over the pipe. The Extension Kit will
provide an additional 2” of space between the top of the valve and the
base of the actuator. bracket is made from aluminum and is not
intended as a thermal block.
– Extension kit will be automatically assembled with any
Flanged CCV assembly.
Available for Spring
g
and Non-Spring
Actuators
Technical Data
Extension Height
Total Weight
2"
0.7 lb
Material
Extension Housing
Shaft
Threaded Hardware
Bearing
Retaining Clip
Aluminum - Anodized
Stainless Steel
Stainless Steel
Oilite® Bearing
Stainless Steel
TR
Extension Bracket
CCV-EXT-Kit
●
LRB (X) ARB (X)
●
●
TF
LF
AF
●
●
●
* Cannot be used with N4 actuators.
* Available for previous NF assemblies.
* CCV-EXT-KIT cannot be used with any valve smaller than the
B212(B) and B312(B).
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
* For use with B2 and B3 series only. Cannot be used with B6 series.
2"
1.65"
1.65"
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
119
Accessories
ZS-CCV... New Characterized Control Valve Weather Shield
Application
The ZS-CCV... weather shield provides moderate protection for valves
which are mounted outdoors. This product is designed as a water tight
enclosure. The housing allows easy mounting over the actuator, while
allowing easy viewing of the actuator in operation. Weather shield for
PICCV/CCV to provide protection for actuators in outdoor applications.
Specifications
Cover
Perimeter Gasket
Rubber Gasket
Spring Clips
Temperature limitations:
Plate (ZS-CCV-100)
(
)
Plate
L
16.25” [413]
[ ]
Actuator
LF, AF
LRB(X),
( ) ARX
AFRB(X)
W
8.75” [222]
[ ]
H
4.5” [114]
[ ]
Parts List
Cover including Rubber Perimeter Gasket, Rubber Gasket
Back Plate
Anti-Rotation Post with screw and lock washer
Valve Gasket
Assorted Cap plugs for unused holes
Screws AF - 2 bolts with nylon insert locking nuts
LRB(X), ARX - 1 screw, 1 washer
No weather shield available at this time for the TF and TR actuators.
Designed for NEMA 4 specifications.
* Cannot be used with B6 series.
800-543-9038 USA
120
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Part Number
ZS - CCV - 90
ZS - CCV - 100
ZS - CCV - 110
PETG with UV resistant smoke tint
Silicon Rubber
Silicon Rubber
Stainless Steel
-22˚F to 122˚F ((-30˚C to 50˚C))
Aluminum
Galvaneal w/black powder coat
Accessories
Auxiliary Switches S1A, S2A
For non-spring return direct-coupled actuators
Application
The S1A and S2A auxiliary switches are used to indicate when a
desired position of a valve is reached or to interface additional
controls for a specific control sequence.
Operation
The S1A and S2A auxiliary switches are mounted onto the direct coupled
actuator. The switches are modular units that mount directly onto LR and
AR type actuators and are locked into place by guiding grooves on the
sides of the actuator.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
A driver disk is attached to the actuator handle and offers direct
transmission of the actuator position to the micro switch cams. The
switching points can be set over the full scale of 0 to 1 simply by
adjusting the slotted discs.
Types
S1A
S1A/300
S1A/500
1 SPDT
1 SPDT
1 SPDT
3 ft, 18 GA Appliance Cable
6 ft, 18 GA Appliance Cable
10 ft, 18 GA Appliance Cable
S2A
S2A/300
S2A/500
2 SPDT
2 SPDT
2 SPDT
3 ft, 18 GA Appliance Cable
6 ft, 18 GA Appliance Cable
10 ft, 18 GA Appliance Cable
Technical Data
Number of switches
Weight
Switching capacity
Switching point
Pre-setting
Humidity
Ambient temperature
Storage temperature
Housing
Housing rating
Servicing
Agency listings
S1A
S2A
1 SPDT
2 SPDT
4.6 oz [130 g]
6.0 oz [170 g]
3A (0.5A), 250 VAC
adjustable over full rotation (0° to 95°)
with scale possible
5 to 95% RH non-condensing
-22°F to 122°F [-30°C to +50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2 / IP54
UL94-5VA
maintenance free
cULus acc. to UL60730-1
CE according to 73/23/EEC
ISO 9001
Quality standard
Wiring Diagram
Mounting Instructions
1. Press down the manual override button and rotate the actuator
fully counter clockwise.
2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.
3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.
4. Check for correct mating of the adaptor to the switch.
5. Adjust switch dials as necessary.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
121
Accessories
Feedback Potentiometer P...A
For the non-spring return direct-coupled actuators
Application
The P…A feedback potentiometers are used with LR and AR actuators
to provide a resistive signal which varies with valve position.
The P…A units are applied with commercial proportional temperature
controllers to provide feedback of the valve position, or with electric or
electronic meters to provide position indication. The signal can also be
used as a positioner for parallel operation of multiple actuators.
Operation
The P…A feedback potentiometers are mounted onto the direct coupled
actuator. The switches are modular units that mount directly onto LR and
AR type actuators and are locked into place by guiding grooves on the
sides of the actuator.
A driver disk is attached to the actuator handle and offers direct
transmission of the actuator position to the micro switch cams.
Types
Technical Data
P...A
Resistance values
Output
Tolerance
Linearity
Resolution
Residual resistance
Electrical connection
as above
1W
± 5%
± 2%
min. 1%
max. 5% on both sides
3 ft, 18 GA appliance cable
½" conduit connector
5 to 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2 / IP54
UL94-5VA
maintenance free
cULus acc. to UL60730-1
CE according to 73/23/EEC
ISO 9001
4.6 oz [130 g]
Humidity
Ambient temperature
Storage temperature
Housing
Housing rating
Servicing
Agency listings
Quality standard
Weight
Mounting Instructions
1. Press down the manual override button and rotate the
actuator fully counter clockwise.
2. Place the switch/potentiometer adaptor onto the hex shaft of the
handle which is in the center of the valve/actuator coupling.
3. Slide switch onto the actuator using the actuator guiding grooves
on the sides of the actuator.
4. Check for correct mating of the adaptor to the switch.
5. Adjust switch dials as necessary.
800-543-9038 USA
122
Feedback Potentiometer
Feedback Potentiometer
Feedback Potentiometer
Feedback Potentiometer
Feedback Potentiometer
Feedback Potentiometer
Feedback Potentiometer
140 Ω
200 Ω
500 Ω
1000 Ω
2800 Ω
5000 Ω
10000 Ω
Wiring Diagram
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
P140A
P200A
P500A
P1000A
P2800A
P5000A
P10000A
Wiring Accessories
Protective Terminal Cover
For the non-spring return direct-coupled actuators
Application
Belimo non-spring return actuators with terminal strips are can be
converted from NEMA 1/IP20 to NEMA 2/IP54 using the protective
terminal cover ZS-T.
The ZS-T terminal cover accessory consists of:
• Terminal Cover
• Conduit Fitting
• Rubber Seal for Wire Diameter 4-6
• Rubber Seal for Wire Diameter 6-8
Terminal
Cover
Conduit
Fitting
Rubber
Seals
Mounting the Terminal Cover
1. Attach terminal cover to actuator, if not done already.
2. Slide the conduit fitting and correct size rubber seal onto wire.
3. Wire up actuator using the terminal strips.
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
4. Fit rubber seal into slot of terminal cover.
5. Shut terminal top and screw on conduit connector.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
123
MFT Standard Configuration
Code
P-10001
P-10002
P-10003
P-10004
P-10005
P-10006
P-10007
P-10009
P-10010
P-10013
P-10015
P-10016
P-10017
P-10018
P-10020
P-10028
P-10031
P-10063
P-10064
P-20001
P-20002
P-20003
P-20004
P-20005
P-30001
P-30002
P-30003
P-30004
P-30005
P-30006
P-40001
P-40002
P-40003
P-40004
P-40005
A01
A02
A03
A04
A05
A06
A07
A09
A10
A13
A15
A16
A17
A18
A20
A28
A31
A63
A64
W01
W02
W03
W04
W05
F01
F02
F03
F04
F05
F06
J01
J02
J03
J04
J05
Control
Motion
Input Range
Position Feedback
Running Time†
Torque %
Adaptation
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
4.0 to 7.0 VDC
6.0 to 9.0 VDC
10.5 to 13.5 VDC
0.0 to 5.0 VDC
5.0 to 10.0 VDC
5.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 5.0 VDC
2.0 to 6.0 VDC
6.0 to 10.0 VDC
14.0 to 17.0 VDC
9.0 to 12.0 VDC
0.0 to 10.0 VDC
0.0 to 4.0 VDC
0.5 to 4.5 VDC
5.5 to 10.0 VDC
0.59 to 2.93 sec.
0.02 to 5.00 sec.
0.10 to 25.50 sec.
0.10 to 25.60 sec.
0.10 to 5.20 sec.
Floating point
Floating point
Floating point
Floating point
Floating point
Floating point
On/Off
On/Off
On/Off
On/Off
On/Off
2.0 to 10.0 VDC
0.0 to 10.0 VDC
0.0 to 5.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
0.5 to 4.5 VDC
5.5 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 5.0 VDC
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 5.0 VDC
0.0 to 10.0 VDC
0.0 to 5.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 5.0 VDC
0.0 to 10.0 VDC
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
100
150
150
150
150
150
150
150
150
150
150
100
100
100
150
75
150
75
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
*P-10001 is the default configuration.
Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.
Note: V-codes used for NV…Series actuator. All other MFT actuators use P-codes.
Note: Most popular configurations available at no additional cost.
Note: If the configuration needed is not listed, please fill in pg. 112 or call Belimo Customer Service at 800-543-9038.
Note: For Non-Spring Return Actuators the 3-digit code can be used in place of the P… pre-set MFT configuration number.
800-543-9038 USA
124
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
On/Off
Floating Point
PWM
Voltage
Configuration
(Substitute ‘V’ for ‘P’ for
NV[F] actuators)
MFT Programming Codes, Flexible Products
PRODUCTS
Base Actuator
Codes
LRX24-3
LR000
LR030
LRX24-SR
LRX24-PC
LRXX0†
LR100
LRX24-MFT
LRX24-MFT95
LRXX0†
LRX120-3
LR060
LRX120-SR
LR450
Control Input
Feedback
Running Time
On/Off, Floating Point
2-10 VDC (4-20mA*)
0-20 V Phasecut
2-10 VDC (Default)
0 to 135 Ohm
On/Off, Floating Point
2-10 VDC (4-20mA*)
—
—
2-10 VDC
2-10 VDC
2-10 VDC
—
—
95 (Default)
95 (Default)
95 (Default)
150 (Default)
150 (Default)
95 (Default)
95 (Default)
Angle of
Rotation/Stroke
95 deg
95 deg
95 deg
95 deg
95 deg
95 deg
95 deg
ARX24-3
ARX24-SR
ARX24-PC
ARX24-MFT
ARX24-MFT95
ARX120-3
ARX120-SR
On/Off, Floating Point
2-10 VDC (4-20mA*)
0-20 V Phasecut
2-10 VDC (Default)
0 to 135 Ohm
On/Off, Floating Point
2-10 VDC (4-20mA*)
—
—
2-10 VDC
2-10 VDC
2-10 VDC
—
—
95 (Default)
95 (Default)
95 (Default)
150 (Default)
150 (Default)
95 (Default)
95 (Default)
95 deg
95 deg
95 deg
95 deg
95 deg
95 deg
95 deg
180 in-lb [20 Nm]
45 in-lb [5 Nm]
MODEL
AR000
AR030
ARXX0†
AR100
ARXX0†
AR060
AR450
Power Supply
VA Rating
Weight (lb)
24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
120-240 VAC
120-240 VAC
3
3
3
3
3
3
3
1.08
1.08
1.08
1.08
1.08
1.08
1.08
24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
24 VAC/DC
120-240 VAC
120-240 VAC
5
5
5
5
5
5
5
1.08
1.08
1.08
1.08
1.08
1.08
1.08
† For correct code please call Belimo Customer service 800-543-9038
PWM
Floating Point
On/Off
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
Voltage
Configuration
(Substitute ‘V’ for ‘P’ for
NV[F] actuators)
Code
P-10001
P-10002
P-10003
P-10004
P-10005
P-10006
P-10007
P-10009
P-10010
P-10013
P-10015
P-10016
P-10017
P-10018
P-10020
P-10028
P-10031
P-10063
P-10064
P-20001
P-20002
P-20003
P-20004
P-20005
P-30001
P-30002
P-30003
P-30004
P-30005
P-30006
P-40001
P-40002
P-40003
P-40004
P-40005
A01
A02
A03
A04
A05
A06
A07
A09
A10
A13
A15
A16
A17
A18
A20
A28
A31
A63
A64
W01
W02
W03
W04
W05
F01
F02
F03
F04
F05
F06
J01
J02
J03
J04
J05
Control
Motion
Input Range
Position Feedback
Running Time†
Torque %
Adaptation
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
4.0 to 7.0 VDC
6.0 to 9.0 VDC
10.5 to 13.5 VDC
0.0 to 5.0 VDC
5.0 to 10.0 VDC
5.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 5.0 VDC
2.0 to 6.0 VDC
6.0 to 10.0 VDC
14.0 to 17.0 VDC
9.0 to 12.0 VDC
0.0 to 10.0 VDC
0.0 to 4.0 VDC
0.5 to 4.5 VDC
5.5 to 10.0 VDC
0.59 to 2.93 sec.
0.02 to 5.00 sec.
0.10 to 25.50 sec.
0.10 to 25.60 sec.
0.10 to 5.20 sec.
Floating point
Floating point
Floating point
Floating point
Floating point
Floating point
On/Off
On/Off
On/Off
On/Off
On/Off
2.0 to 10.0 VDC
0.0 to 10.0 VDC
0.0 to 5.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
0.5 to 4.5 VDC
5.5 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 5.0 VDC
2.0 to 10.0 VDC
0.0 to 10.0 VDC
2.0 to 10.0 VDC
0.0 to 5.0 VDC
0.0 to 10.0 VDC
0.0 to 5.0 VDC
None
2.0 to 10.0 VDC
None
0.0 to 5.0 VDC
0.0 to 10.0 VDC
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
100
150
150
150
150
150
150
150
150
150
150
100
100
100
150
75
150
75
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
*P-10001 is the default configuration.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
125
Custom MFT Configuration Order Form
FAX: USA Toll Free 1-800-228-8283
#1 Select an Actuator
(use one sheet for each unique actuator/configuration)
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
AF24-MFT US
AF24-MFT-S US
NF24-MFT US
LF24-MFT US
LF24-MFT-S US
AF24-MFT95 US
NV24-MFT US
NVF24-MFT US
NVF24-MFT-E US
NVFD24-MFT US
NVFD24-MFT-E US
GMX24-MFT
GMX24-MFTX1
Quantity
______
______
______
______
______
______
______
______
______
______
______
______
______
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
AMX24-MFT
AMX24-MFTX1
NMX24-MFT
NMX24-MFTX1
LMX24-MFT
LMX24-MFTX1
LRX24-MFT
GMX24-MFT95
AMX24-MFT95
NMX24-MFT95
LMX24-MFT95
LHX24-MFT
LUX24-MFT
Name _______________________________________________________________________________
Quantity
______
______
______
______
______
______
______
______
______
______
______
______
______
Company ____________________________________________________________________________
Address _____________________________________________________________________________
City_______________________________________ State _____________Zip _____________________
Phone_____________________________________ Fax_______________________________________
Email _____________________________________
FIELD LABELING: LBL-MFT
❑
(-S=Auxiliary Switch)
Custom configuration labels required
1-3/8” X 1-¼” orange labels preprinted to your specifications 12 label sets per sheet.
Includes configuration code and wiring labels.
#2 Create a Custom Configuration
g
1 Angle of rotation setting
Deactivated (Default)
The following settings
Activated
The following settings
mechanical angle of rotation.
-
refer to the full angle of rotation of 95º.
are automatically adapted to the effective
Manual triggering by pressing the push button twice.
Automatic triggering each time the unit is powered up
or by pressing the push button twice.
VDC
3 Feedback Signals U5
Floating Point
2 – 10
0.2 to 5.0 seconds
0 – 10
0.1 to 25.5 seconds
Variable
On/Off
0.59 to 2.93 seconds
Start
.
Variable
Stop
.
Start
.
Stop
.
Position Feedback U
DC 2...10 V (Default)
Position Feedback U
DC 0...10 V
Position Feedback U
Start
DC
.
V (0...8 V)
Finish DC
.
V (2...10 V)
The finish must
be at least 2 V
above the start!
150 seconds (Default)
Running time
seconds (75...300 seconds) (in 5 second increments)
4 Running Time
Note:
5 Override control and
Min. (min. position)
=
%
(0...100%)
(beginning of working range) default 0
ZS
=
%
(0...100%)
(0% = Min.; 100% = Max.) default 50
=
%
(0...100%)
(end of working range) default 100
electronic angle of
rotation limiting
800-543-9038 USA
126
The sound power level [dB(A)]
increases when the running time
is below 150 seconds.
(intermediate position)
Max. (max. position)
866-805-7089 CANADA
LM
NM
AM
GM
Others
35…150 seconds
45…170 seconds
90…300 seconds
90…300 seconds
75…300 seconds
203-791-8396 LATIN AMERICA
P10419 - 09/13 - Subject to change. © Belimo Aircontrols (USA), Inc.
2 Control Types
PWM
Download