Series CL - Eoff Electric Supply

advertisement
Series CL
Three and four pole contactors
9 to 105A (AC3)
25 to 140A (AC1)
Contactors
• Control circuit: Alternating current up to 690V
Direct current up to 440V
• Terminal numbering in accordance with EN 50005 and EN 50012
• Fixing by clipping onto 35mm DIN rail EN 50022-35 or by screws
• Screws protected against accidental contact in accordance with VDE 0106
T.100, VBG4
• Ring terminal version
• Three coil terminals
• Mounting possibilities of front/side instantaneous auxiliary contact blocks,
timed auxiliary contact blocks, mechanical latch, transient suppressor block
and interface modules
• Degree of protection: IP20 to CL00 ... CL02
IP10 to CL25 ... CL10
• Maximum number of auxiliary contacts: 4 for CL00 ... CL25
6 for CL04 ... CL45
8 for CL06 ... CL10
A
Standard voltages
Standards
C
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
EN 50005
UL 508
NEMA ICS 1
BS 5424 & 775
D
Approvals
B
E
CSA 22.2/14
NFC 63-110
ASE 1025
VDE 0660/102
CENELEC HD 419
To complete the catalogue number, replace the symbol ♦ by the code
corresponding to the voltage and frequency of the control circuit.
(other voltages on request)*
Alternating current (V). Dual-frequency coil
Alternating current (V).
AC 32 127 220 380415500660
50Hz 230 400 690
cULus
SETI
IMQ
(hasta Ith=32A)
AC 60Hz
For contactors type CL...D / Operating limits: 0.80 ... 1.10 x Us
Lloyd’s
Register
RINA
Bureau
Veritas
♦
BD E F GH I J KNP R T X
Voltage 12 24 36 42 48 60 72 110120220230240250440
125
Coil with electronic module for contactors CL...E (can also be used with alternating current)
H
♦
DFHJNY
Voltage 24 42 60 110220440
28 48 72 125250
Direct current (V). Coil with wide voltage range (0.70 ... 1.30 x Us)
CE
For contactors type CL...D
X
208277380480460600
Direct current (V)
I
1293456713815
♦ E K L N T UWY Z
F
G
♦
AC
24 42 48 110120220230240400440480
50/60Hz 115
♦
WBWD WE WF WGWH WI WJ WKWNWP WR WT WX Maximun number of add-on
DC 12 24 33 42 48 60 72 110125220230240250440
Order codes
Auxiliary contact blocks
Accessories
Dimensions
|
|
|
|
pg. C.11
pg. C.15
pg. C.15
pg. C.24
Coil with electronic module for contactors CL...E
♦
WDWE WFWHWJWN
Voltage 24 33 48 72 110220
* Please Consult GE for non standard Coil Voltages
C.10
auxiliary contact blocks:
CL00D...CL02D : 2NO or 1NC
CL03D...CL45D : 1NO and 1NC
CL05D...CL10D : 4NO or 2NC
CL05E...CL10E : 4 cont. aux.
Different auxiliary contact
configurations, contact us.
Series CL
Three pole contactors. Screw terminal
Control circuit:
Admissible power Electrical Aux.
Alternating
endurance contacts
AC3
current
220V380V415V500V
230V400V440V
••33
•1•1 Cat. no. (1)Pack
Cat.
(3)
AC3
kW kW kW kW
HPHPHPHP Operations ••44
• 2• 2 Ref. no. see bottom
5
2.2 4
4 5.5
2x106 00 CL00A300T♦
5
3 5.55.57.5 10 CL00A310T♦
5
0
1 CL00A301T♦
25
12
3 5.5 5.5 7.5
2x106 00 CL01A300T♦
4 7.57.5 10 10 CL01A310T♦
0
1 CL01A301T♦
32
18
45
Control circuit:
Direct current
Control circuit:
Coil with electronic
module (AC/DC)
Cat. no. (1)Pack Cat. no. (1)Pack
(3)
Ref. no. see bottom
(3)
Ref. no. see bottom
CL00D310T♦
CL00D301T♦
10
10
5
5
5
CL01D310T♦
CL01D301T♦
10
10
4 7.5 7.5 10 1.7x10600 CL02A300T♦
5.5 10 10 13.5 10 CL02A310T♦
0
1 CL02A301T♦
5
5
5
CL02D310T♦
CL02D301T♦
10
10
25
7.5 11 11 15 1.2x10600 CL25A300T♦
10151520 5
CL25D300T♦
10
45
25
7.5 12 12 15
2x106 00 CL03A300M♦ 10
10161620 10 CL03A310M♦ 10
0
1 CL03A301M♦10
CL03D310M♦
CL03D301M♦
10
10
60
32
9 16 16 18.5 2x106 00 CL04A300M♦
12222225 10 CL04A310M♦
0
1 CL04A301M♦
CL04D310M♦
CL04D301M♦
10
10
60
40
11 18.5 22 25
2x106 00
15253034 11
CL45A300M♦ 10
CL45A311M♦ (2) 10
CL45D300M♦
10
90
50
15 22 25 30 1.8x10600
20303440 11
CL06A300M♦ 1
CL06A311M♦ (2) 1
CL06D300M♦
1
CL06E300M♦
1
110
65
18.5 30 37 40 1.7x10600
25405055 11
CL07A300M♦ 1
CL07A311M♦ (2) 1
CL07D300M♦
1
CL07E300M♦
1
110
80
22 37 45 45 1.5x10 00
30506060 11
CL08A300M♦ 1
CL08A311M♦ (2) 1
CL08D300M♦
1
CL08E300M♦
1
140
95
25 45 50 55 1.7x10600
34606875 11
CL09A300M♦ 1
CL09A311M♦ (2) 1
CL09D300M♦
1
CL09E300M♦
1
140
105
30 55 55 65 1.5x10600
40757588 11
CL10A300M♦ 1
CL10A311M♦ (2) 1
CL10D300M♦
1
CL10E300M♦
1
LB1A ♦
LB3A ♦
LB4A ♦
LB1D ♦
LB3D ♦
LB4D ♦
6
CL00 - CL25
CL03 - CL45
CL06 - CL10
coil + electronic module CL06E - CL10E
10
10
10
5
5
5
3P and 4P contactors
Spare
coils
Max.oper.current
Motors
Noninductive <440V,
3~
load
50/60Hz
AC3
AC1
A
A
25
9
A
5
5
1
LB4E ♦
B
C
D
E
F
1
G
H
(1) To complete the catalogue number, replace the symbol ♦ by the code corresponding
to the voltage and frequency of the control circuit (see C.10).
(2) Equipped with two blocks BCLF
(3) Multipack, see C.9
I
X
C.11
3-Pole Contactors
5-10 HP (460V)
10-17.5 FLA
Contactor catalog numbers are shown in the shaded area in the Contactor Selection and Data table. To complete the
catalog number, replace the asterisk (*) with the appropriate digit from the shaded area in the Coil Selection table.
Additional coil information is shown in the Coil Data table.
Hp @ 460V AC-3 (kW @ 380/415V, 50 Hz)
Contactor Selection and Data
AC Contactors
Full Voltage Non-Reversing
Reversing
DC Contactors
Full Voltage Non-Reversing
7.5 hp (5.5 kW) 10 hp (7.5 kW)
CL00A310T* CL01A310T* CL02A310T*
LAR00A*
LAR01A*
LAR02A*
CL00D310T* CL01D310T* CL02D310T*
LDR00A*
LDR01A*
LDR02A*
Maximum Aux. Contacts
4
4
4
Maximum Contact Block
Configuration
4 Front-Mount or 1 Side-Mount
on each side
Reversing
Aux. Contacts
5 hp (4 kW)
1NO
1NO
1NO
Continuous Amp Rating (UL)
25
25
32
AC-1 Amperes (IEC)
25
25
32
Max. FLA
10
13.8
17.5
Max. Hp (1-Phase)
115 Volts
230 Volts
.5
1.5
.75
2
1
3
Max. Hp (3-Phase)
200 Volts
230 Volts
460 Volts
575 Volts
3
3
5
7.5
3
3
7.5
10
5
5
10
15
3
3
5
7.5
3
3
7.5
10
5
5
10
15
20
2
20
2
20
1.8
Aux. Contacts (A600, P600) (Built in)
AC-2/AC-3
AC-4 Max. Hp
200 Volts
230 Volts
460 Volts
575 Volts
Mechanical Life (millions of operations)
Elec. Endurance (AC-3) At Rated Current
(millions of operations)
Maximum
Operational
Current
460V and
below
Net Weight
AC-1
≤ 1200 ops./hour
3000 ops./hour
25
12.5
25
12.5
32
16
AC-3
≤ 1200 ops./hour
3000 ops./hour
10
3.5
13.8
4.8
17.5
6.1
AC-4
360 ops./hour max
10
13.8
17.5
10 oz.
7 oz.
10 oz.
7 oz.
10 oz.
7 oz.
14-10
15
14-10
15
14-10
15
25
25
25
Contactor
Class 10 Overload Relay
Wire Size - Power Terminals 75°C (Cu) AWG
Torque (Main) in.-lb.
Noise (dba)
2
Coil Selection
AC Voltage
60 Hz
50 Hz
DC
Voltage
Coil *
Suffix
24
—
—
48
—
120
—
208
277
240
—
480
—
600
24
—
—
42
—
110
—
—
220/230
—
—
380/400
415
500
—
12
24
—
48
—
125
—
—
—
250
—
—
—
1
B
D
F
G
J
K
L
N
S
T
U
W
Y
AC
Voltage
DC
Voltage
Burden
Inrush
Holding
45 VA
6 VA
5.5 W
5.5 W
Pick-up Voltage (% Of Coil Volts)
85-110
80-110
Drop-Out Voltage (% Of Coil Volts)
40-55
20-40
6-25
8-20
35-65
40-50
6-13
6-13
30-60
30-60
9000
1200
360
3600
1200
360
Coil Data
Switching Delay (ms)
Switching Delay On
Coil Voltage at +10% to -20%
Coil Voltage At Rated Value
Switching Delay Off
Coil Voltage at +10% to -20%
Coil Voltage At Rated Value
Maximum Operations per Hour
No Load
Rated Load — AC1, AC3
Rated Load — AC4
REFERENCES
Standards and Listings . . . . . . . . . . . . . . . . . . . . . . . . . Page 41
Overload Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 26-29
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 30-37
Life Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 42-44
Additional Coil Information . . . . . . . . . . . . . . . . . . Page 37
Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GEH-6223
UL File Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E76233
CSA File Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LR30821
C-2000™ Contactors & Starters
3-Pole Contactors
5-10 HP (460V)
10-17.5 FLA
Legend and Notes for Illustration
A Extra Auxiliary Contacts, Side Mounted
(if used)
B Extra Auxiliary Contacts, Front
Mounted (if used)
C Pneumatic Timer (if used)
D Mechanical Latch (if used)
E Transient Voltage Suppressor
Add 1⁄2 inch for electrical clearance to
enclosure.
4 mounting
holes for #8
or M4 Screws
Contactor - Front View
Starter - Front View
Reversing Contactor - Front View
Reversing Starter - Front View
AC Contactor - Side View
AC Starter - Side View
Engineering Outline Drawings
AC
Contactor . . . . . . . . . . . . . . . . . . . . . . 55-215782
Starter . . . . . . . . . . . . . . . . . . . . . . . . . . 55-215824
Reversing Contactor . . . . . . . . . . 55-215790
Reversing Starter . . . . . . . . . . . . . . 55-215791
DC
Contactor . . . . . . . . . . . . . . . . . . . . . . 55-215835
Starter . . . . . . . . . . . . . . . . . . . . . . . . . . 55-215765
Reversing Contactor . . . . . . . . . . 55-215779
Reversing Starter . . . . . . . . . . . . . . 55-215803
DC Contactor - Side View
3
C-2000™ Contactors & Starters
General Specifications
Standards And Listings
IEC 947-1
IEC 947-4
IEC 158-1
GENELEC HD419
NFC.63-110
Pending Standards
And Listings
SEMKO, NEMKO, DEMKO, Lloyds Register
Ambient Temperature
Operating
Storage
Altitude Derating
Up to 10,000 ft.
(3,000 m)
BS 5424
BS 775
CEI 17-3/252
ASE 1025
UL 508
CSA C.22.2/14
EN 50005
UNE 20109
VDE 0660/102
CE Mark
-13˚ to +131˚F/-25˚ to +55˚C
-58˚ to +176˚F/-50˚ to +80˚C
Nominal Values
10,000 to 13,200 ft.
(3,000 to 4,000 m)
90% rated current
13,200 to 16,000 ft.
(4,000 to 5,000 m)
80% rated current
Rated Insulation Voltage
600 VAC, UI = 1000V (IEC 947-1)
Mounting Position
3-Pole and 4-Pole
CL Contactors (5-75 hp)
To maintain operating integrity, the contactor must be mounted in one of the positions
shown below:
3-Pole and 4-Pole
CK Contactors
(100-500 hp)
The contactor must be installed vertically or tilted a maximum of 30˚ from vertical,
as shown below:
41