Ferrule Fuse Catalog

advertisement
High Speed Fuses
Ferrule Fuses
Table of Contents
Basic Catalog
Number
FWA
FWX
FWH
FWC
FWP
FWK
FWJ
FWL/FWS
Volts
150
250
500
600
690V/700
750
1000
1250/1500/2000
Amp
Range
5-60
1-50
0.25-30
6-32
1-100
5-60
20-30
2-30
Accessories
Fuse Holders
Page
224-225
226-227
228-231
232-233
234-237
238-239
240-241
242
241
Ferrule Fuse Ranges
Amps
5-60
1-50
0.25-30
6-32
20-100
1-50
5-60
20-30
20-30
8-15
2-6
AC
X
X
X
X
X
X
X
X
X
X
X
DC
X
X
X
X
—
X
X
X (800Vdc)
X (1000Vdc)
X (1000Vdc)
X (1000Vdc)
Bussmann offers a full line of ferrule style (cylindrical
clip-mounted) fuses, designed and tested to meet standards
and requirements in various locations around the world.
Their unique design and construction provide:
• Superior cycling capability
• Low energy let-through (I2t)
Ferrule fuses provide an excellent solution for small UPS,
small ac drives and other low power applications where
space is at a premium.
Voltage Rating
All Bussmann ferrule fuses — except 690V — have been
tested at their rated voltage. The 690V ferrule fuse has been
tested to the IEC 60269 standard, which requires clearing at
the rated voltage +5%.
Accessories
Ferrule fuses may be mounted in fuseclips, fuse holders,
fuse blocks or fused switches. A variety of products are
available. Please consult Bussmann Application Engineering
to discuss your requirement.
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
223
High Speed
Fuses
Volts
150
250
500
600
700 (22 x 58mm)
700 (14 x 51mm)
750
1000
1250
1500
2000
General Information
High Speed Fuses
Ferrule — FWA 150V: 5-60A
FWA 5-30A (10 x 38mm)
35-60A (21 X 51mm)
Arc Voltage
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of theapplied
working voltage, Eg, (rms)
at a power factor of 15%.
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 150Vac/dc
Amps: — 5-60A
IR: — 100kA Sym.
Agency Information: CE, UL Recognition JFHR2.E91958
Electrical
Characteristics
Total Clearing I t
2
The total clearing I t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
2
1.5
1.0
0.3
0.2
0.15
2)
22
Dimensions
A
B
1.5 (38.1)
0.375 (9.5)
2.0 (50.8)
0.625 (15.9)
A
70
102
1) 5-30A Range
2) 35-60A Range
Eg
150
C
0.406 (10.3)
0.811 (20.6)
C
B
100
1.0
Kp
0.8
100
150
0.6
0.5
0.4
0.3
0.2
0.1
30 40 50
60
70
Ib
80 90 100%
Electrical Characteristics
I2t (A2 Sec)
Catalog
Numbers
FWA-5A10F
FWA-10A10F
FWA-15A10F
FWA-20A10F
FWA-25A10F
FWA-30A10F
FWA-35A21F
FWA-40A21F
FWA-45A21F
FWA-50A21F
FWA-60A21F
Size
10 x 38mm
(13⁄32” x 11⁄2”)
21 x 51mm
(13⁄16” x 2”)
Rated
Current
RMS-Amps
5
10
15
20
25
30
35
40
45
50
60
• Watts loss provided at rated current.
• See accessories on page 243.
•
•
•
•
•
•
•
•
Pre-arc
1.6
3.6
14
33
58
100
75
100
130
170
250
Clearing
at 150V
8
16
55
130
220
400
800
1000
1300
1600
2400
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
Data Sheet: 720003
224
50
Eg
Catalog Numbers
Dimensions - in (mm)
Amp
Range
5-30
35-60
200
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
1)
0.5
300
Power Losses
K
UL
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts
Loss
1
2.7
3.3
3.8
4.9
4.9
4.5
5.1
6
7.3
8.0
High Speed Fuses
Ferrule — FWA 150V: 5-60A
FWA 5-30A: 150V (10 x 38mm)
FWA 35-60A: 150V (21 x 51mm)
Time-Current Curve
103
Virtual Pre-Arcing Time In Seconds
102
Time-Current Curve
104
6
4
6
4
2
2
6
4
103
6
4
2
2
6
4
102
6
4
Virtual Pre-Arcing Time In Seconds
104
2
101
FWA-5A10F
FWA-10A10F
FWA-15A10F
FWA-20A10F
FWA-25A10F
FWA-30A10F
6
4
2
100
6
4
2
10–1
10–2
10–3
2
100
6
4
2
2
2
6
4
10–2
6
4
2
2
6
4
10–3
6
4
2
2
2
4
6
8
101
2
4
6
8
102
2
4
6
8
Prospective Current In Amps RMS
10–4
103
2
101
4
6
8
2
102
104
4
4
2
Peak Let-Through Current
FWA-30A10F
FWA-25A10F
FWA-20A10F
FWA-15A10F
6
4
2
FWA-12A10F
FWA-10A10F
FWA-5A10F
102
4
10
3
6
4
2
102
4
2
101
103
6
6
101
8
FWA-60A21F
FWA-50A21F
FWA-45A21F
FWA-40A21F
FWA-35A21F
6
6
2
6
Peak Let-Through Curve
104
103
4
Prospective Current In Amps RMS
High Speed
Fuses
Peak Let-Through Curve
Peak Let-Through Current
2
101
6
4
10–1
6
4
6
4
10–4
FWA-35A21F
FWA-40A21F
FWA-45A21F
FWA-50A21F
FWA-60A21F
2
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
Data Sheet: 35785317
2
4
6
105
2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785305
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
225
High Speed Fuses
Ferrule — FWX 250V (UL): 1-50A
FWX (14 x 51mm)
This curve gives the
peak arc voltage, UL,
which may appear
across the fuse during
its operation as a
function of the applied
working voltage, Eg,
(rms) at a power factor
of 15%.
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 250Vac/dc
Amps: — 1-50A
IR: — 200kA RMS Sym.
— 50kA @ 250Vdc
Agency Information: CE, UL Recognition JFHR2.E91958
1-50A & CSA Component Acceptance file Class 1422-30,
1422-90 (53787) 5-30A
Electrical
Characteristics
Total Clearing I2t
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
1.4
1.2
Arc Voltage
1.5
1.0
0.5
0.3
0.2
0.15
2)
125
200
250
14.3
(0.563")
15.5
(0.610")
400
1)
300
200
50
1.0
Kp
0.8
Eg
300
Catalog
Number
FWX-1A14F
FWX-2A14F
FWX-3A14F
FWX-4A14F
FWX-5A14F
FWX-10A14F
FWX-15A14F
FWX-20A14F
FWX-25A14F
FWX-30A14F
FWX-50A14F
150
200
Eg
250
0.6
0.5
0.4
0.3
0.2
0.1
30 40 50
60
70
Ib
80 90 100%
Size
14 x 51mm
(9⁄16” x 2”)
Electrical Characteristics
Rated
I2t (A2Sec)
Current
Clearing
RMS-Amps
Pre-arc
at 250V
1
—
—
2
—
—
3
—
—
4
—
—
5
1.6
13
10
3.6
24
15
14
83
20
33
200
25
58
300
30
100
500
50
200
1800
Watts
Loss
—
—
—
—
1.3
3.4
3.8
4.6
5.3
5.9
5.7
• Watts loss provided at rated current.
• (250Vdc/Interrupting rating 50kA) UL Recognition & CSA Component Acceptance on 5
through 30A only. Consult Bussmann for additional ratings.
• See accessories on page 243.
•
•
•
•
•
•
•
•
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
Data Sheet: 720006
226
100
2)
Catalog Numbers
Dimensions - mm (in)
50.8
(2.000")
600
500
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
1)
75
800
Power Losses
K
UL
103
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
High Speed Fuses
Ferrule — FWX 250V (UL): 1-50A
FWX 1-30A: 250V (14 x 51mm)
Time-Current Curve
Prospective Current In Amps RMS
Peak Let-Through Curve
High Speed
Fuses
Prospective Current In Amps RMS
Data Sheet: 35785302
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
227
High Speed Fuses
Ferrule — FWH 500V: 0.25-30A
FWH (6 x 32mm)
Catalog Numbers
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustrations.
Ratings:
Volts: — 500Vac (0.25-6.3A)
500Vdc (2-5A)
Amps: — 0.25-30A
IR: — 50kA at ≥ 20% pf (0.25-20A)
— 20kA at ≥ 20% pf (25-30A)
Agency Information: CE, UL Recognition JFHR2.E91958
0.25-30A, CSA Component Acceptance file Class 1422-30,
1422-90 (53787) 0.25-7A
Opening Times
Amp Ratings
0.25-7
10-30
150%
> 30 min
< 30 min
200%
< 30 min
< 30 min
Dimensions - mm (inches)
31.8
(1.25")
300%
≤ 10 sec
≤ 10 sec
6.4
(0.25")
Catalog
Size
Numbers
FWH-.250A6F
FWH-.500A6F
FWH-001A6F
FWH-002A6F
FWH-3.15A6F
FWH-005A6F
FWH-6.30A6F 6 x 32mm
FWH-007A6F (1⁄4” x 11⁄4”)
FWH-010A6F
FWH-12.5A6F
FWH-015A6F
FWH-016A6F
FWH-020A6F
FWH-025A6F
FWH-030A6F
Rated
Current
RMS-Amps
0.25*
0.5*
1*
2*
3.15*
5*
6.3*
7*
10**
12.5**
15**
16**
20**
25**
30**
*300% minimum opening current at rated voltage.
**200% minimum opening current at rated voltage.
• Consult Bussmann for DC ratings.
• See accessories on page 243.
•
•
•
•
•
•
•
•
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
3.2
(0.125")
Data Sheet: 720038
228
Electrical Characteristics
I2t (A2 Sec)
Clearing
Pre-arc
at 500V
0.01
0.05
0.05
0.25
0.4
2
1.3
3.5
3.1
7.7
15
40
36
90
50
125
9.9
139
20
60
44
146
48
177
75
259
126
345
145
430
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts
Loss
2.7
1.2
1.7
3.2
2.9
2.1
2.3
2.5
2.86
3.53
3.08
4.48
4.26
—
—
High Speed Fuses
Ferrule — FWH 500V: 0.25-30A
FWH 10-30A: 500V (6 x 32mm)
FWH 0.25-7A: 500V (6 x 32mm)
Time-Current Curve
Time-Current Curve
104
6
4
FWH-002A6F
FWH-3.15A6F
2
10
FWH-005A6F
3
FWH-6.30A6F
FWH-007A6F
6
4
2
102
Virtual Pre-Arcing Time In Seconds
6
4
2
101
6
4
2
100
6
4
2
10–1
6 FWH-.250A6F
4 FWH-.500A6F
FWH-001A6F
2
10–2
4x10–3
.2
.4
.6
.8
100
2
4
6
8
101
2
4
6
8
102
2
Prospective Current In Amps RMS
High Speed
Fuses
Data Sheet: 35785256
Data Sheet: 50955
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
229
High Speed Fuses
Ferrule — FWH 500V: 1-30A
FWH (14 x 51mm)
Arc Voltage
This curve gives the peak
arc voltage, UL, which may
appear across the fuse
during its operation as a
function of the applied
working voltage, Eg, (rms)
at a power factor of 15%.
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See Dimensions
illustration.
Ratings:
Volts: — 500Vac
Amps: — 1-30A
IR: — 200kA RMS Sym.
— 50kA @500Vdc
Agency Information: CE, UL Recognition 1- 30A & CSA
Component Acceptance file Class 1422-30, (53787) on:
5 - 30A.
Power Losses
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of the
power losses at load
currents lower than the
rated current. The correction
factor, Kp, is given as a
function of the RMS load
current, Ib, in % of the rated
current.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated
voltage and at power factor
of 15% are given in the
electrical characteristics. For
other voltages, the clearing
I2t is found by multiplying by
correction factor, K, given as
a function of applied working
voltage, Eg, (rms).
1.5
1.0
K
Catalog Numbers
0.5
0.3
0.2
0.15
100
Dimensions - mm (inches)
50.8
(2.000")
15.5
(0.610")
250
400
14.3
(0.563")
Eg
500
Catalog
Numbers
Size
FWH-1A14F
14 x 51mm
9
FWH-2A14F
( ⁄16” x 2”)
FWH-3A14F
FWH-4A14F
FWH-5A14F
FWH-6A14F
FWH-10A14F
FWH-12A14F
FWH-15A14F
FWH-20A14F
FWH-25A14F
FWH-30A14F
2.0
1.2
103
800
600
500
400
300
100
1.0
Kp
0.8
200
300
•
•
•
•
500
0.4
0.3
0.2
0.1
30 40 50
60
70
Features and Benefits
Excellent cycling capability and dc performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC common bus
DC drives
Power converters/rectifiers
Reduced voltage starters
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Ib
80 90 100%
Electrical Characteristics
Rated
I2t (A2 Sec)
Current
Clearing
RMS-Amps
Pre-arc
at 500V
1
—
—
2
—
—
3
—
—
4
—
—
5
1.6
6.4
6
1.6
6.4
10
3.6
13
12
—
—
15
10
40
20
26
96
25
49
191
30
58
232
• Watts loss provided at rated current.
• See accessories on page 243.
•
•
•
•
400
Eg
0.6
0.5
Data Sheet: 720008
230
UL
1.6
Watts
Loss
—
—
2.3
—
1.5
1.5
4
—
5.5
6
7
9
High Speed Fuses
Ferrule — FWH 500V: 1-30A
FWH 1-30A: 500V (14 x 51mm)
Time-Current Curve
104
6
4
2
103
6
4
2
Virtual Pre-Arcing Time In Seconds
102
6
4
FWH-5A14F
FWH-10A14F
FWH-15A14F
FWH-20A14F
FWH-25A14F
FWH-30A14F
2
101
6
4
2
100
6
4
2
10–1
6
4
2
10–2
6
4
2
10–3
6
4
2
2
4
6
8
101
2
4
6
8
2
102
4
6
8
High Speed
Fuses
10–4
103
Prospective Current In Amps RMS
Peak Let-Through Curve
104
6
4
2
Peak Let-Through Current
10
FWH-30A14F
FWH-25A14F
3
6
4
2
FWH-20A14F
FWH-15A14F
FWH-10A14F
FWH-5A14F
102
6
4
2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785298
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
231
High Speed Fuses
Ferrule — FWC 600V: 6-32A
voltage, Eg, (rms).
FWC (10 x 38mm)
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 600Vac/700Vdc (6-25A)
600Vac (30-32A)
Amps: — 6-32A
IR: — 200kA RMS Sym.
— 50kA @ 700Vdc (6-25A)
Agency Information: CE, UL Recognition JFHR8.E91958
6-32A. & CSA Component Acceptance file Class 1422-30,
(53787) on (6-32A)
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated
voltage and at power factor
of 15% are given in the
electrical characteristics. For
other voltages, the clearing
I2t is found by multiplying by
correction factor, K, given as
a function of applied working
1.5
1.0
Arc Voltage
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of theapplied
working voltage, Eg, (rms)
at a power
factor of 15%.
Power Losses
Watts loss at rated
current is given in the
electrical characteristics.
The curve allows the
calculation of the power
losses at load currents
lower than the rated
current. The correction
factor, Kp, is given as a
function of the RMS load
current, Ib, in % of the
rated current.
K
0.5
0.3
0.2
0.15
100
Dimensions - mm (in)
38.1
(1.500")
1.6
250
400
Eg
500
600
Catalog
Numbers
Size
FWC-6A10F
FWC-8A10F
FWC-10A10F
FWC-12A10F 10 x 38mm
FWC-16A10F (13⁄32” x 11⁄2”)
FWC-20A10F
FWC-25A10F
FWC-30A10F
FWC-32A10F
1.2
103
800
600
500
400
300
200
1.0
Kp
0.8
Eg
300
500
400
600
0.6
0.5
0.4
0.3
0.2
0.1
30 40 50
60
70
Ib
80 90 100%
Electrical Characteristics
Rated
I2t (A2 Sec)
Current
Clearing
RMS-Amps
Pre-arc
at 600V
6
4
30
8
6
50
10
9
70
12
15
120
16
25
150
20
34
260
25
60
390
30
95
600
32
95
600
• Watts loss provided at rated current.
• See accessories on page 243.
•
•
•
•
•
•
•
•
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
Data Sheet: 720011
232
UL
Catalog Numbers
10.3
(0.406")
9.5
(0.375")
2.0
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts
Loss
1.5
2.0
2.5
3.0
3.5
4.8
6.0
7.5
7.5
High Speed Fuses
Ferrule — FWC 600V: 6-32A
FWC 6-32A: 600V (10 x 38mm)
Time-Current Curve
104
6
4
2
103
FWC-6A10F
FWC-8A10F
FWC-10A10F
FWC-12A10F
FWC-16A10F
FWC-20A10F
FWC-25A10F
FWC-30A10F & FWC-32A10F
6
4
2
102
6
4
Virtual Pre-Arcing Time In Seconds
2
10
1
6
4
2
100
6
4
2
10–1
6
4
2
10–2
6
4
2
10–3
6
4
2
2
101
4
6
8 102
2
4
6
Prospective Current In Amps RMS
High Speed
Fuses
10–4
8 103
Peak Let-Through Curve
104
6
FWC-30A10F & FWC-32A10F
FWC-25A10F
FWC-20A10F
FWC-16A10F
4
2
Peak Let-Through Current
10
3
6
4
2
FWC-12A10F
FWC-10A10F
FWC-8A10F
FWC-6A10F
102
6
4
2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
4
6
105
2
Data Sheet: 35785306
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
233
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 1-50A,
Striker Optional
FWP (14 x 51mm)
Arc Voltage
Specifications
Description: Ferrule style high
speed fuses with and without
indicating striker.
Dimensions: See dimensions
illustrations.
Ratings:
Volts: — 690Vac (IEC)
— 700Vac (UL)
FWP with
— 800Vdc (5-50A)
striker option.
Amps: — 1-50A
IR: — 200kA RMS Sym.
— 50kA @800Vdc
Agency Information: CE, UL Recognition JFHR2.E91958,
CSA Component Acceptance file Class 1422-30, 1422-90
(53787) for versions without indicator only. Designed and
tested to IEC 60269: Part 4.
Electrical
Characteristics
Total Clearing I2t
1.4
1.2
1.0
0.9
0.8
0.7
0.6
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
0.5
the electrical
1)
characteristics. For other 0.4
2)
voltages, the clearing I2t is
0.3
found by multiplying by
200
correction factor, K, given
as a function of applied working
voltage, Eg, (rms).
1.4
1.2
103
9
8
7
6
Power Losses
3
Catalog Numbers
300
400
500
1) 5-30A Range
2) 32-50A Range
600
Eg
700
Without Striker
50.8
(2.000")
14.3
(0.563")
15.5
(0.610")
With Striker
5 (0.197")
Size
51 (2.00")
13 (0.511")
•
•
•
•
4
200
1.0
Kp
0.8
300
400
500
600
Eg
700
0.6
0.5
0.4
0.3
0.2
Ib
0.1
30 40 50 60 70 80 90 100%
Electrical Characteristics
Rated
I2t (A2 Sec)
Current
Minimum
Clearing At
Watts
RMS-Amps
Melting
Rated Voltage Loss
14 x 51mm
(9⁄16" x 2")
14 x 51mm
(9⁄16” x 2”)
*Striker range is 600Vdc only
• Watts loss provided at rated current.
• See accessories on page 243.
59 (2.323")
14.3
(0.563")
Catalog
Numbers
Without Striker
FWP-1A14F
FWP-2A14F
FWP-2.5A14F
FWP-3A14F
FWP-4A14F
FWP-5A14F
FWP-10A14F
FWP-15A14F
FWP-20A14F
FWP-25A14F
FWP-30A14F
FWP-32A14F
FWP-40A14F
FWP-50A14F
With Striker*
FWP-10A14FI
FWP-15A14FI
FWP-20A14FI
FWP-25A14FI
FWP-30A14FI
FWP-32A14FI
FWP-40A14FI
FWP-50A14FI
UL
5
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
K
Dimensions - mm (in)
234
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of theapplied
working voltage, Eg, (rms)
at a power factor of 15%.
1
2
2.5
3
4
5
10
15
20
25
30
32
40
50
10
15
20
25
30
32
40
50
—
—
—
—
—
1.6
3.6
8.6
26.0
46.5
58
68
84
200
3.6
8.6
26.0
46.5
58
68
84
200
—
—
—
—
—
11.0
38.5
70
230
375
485
600
750
1800
38.5
70
230
375
485
600
750
1800
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Data Sheet: 720025
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
—
—
—
—
—
1.5
4
5.5
6
7
9
7.6
8
9
4
5.5
6
7
9
7.6
8
9
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 1-50A,
Striker Optional
Without Striker
FWP 5-50A: 660V/700V (14 x 51mm)
Time-Current Curve
104
6
4
2
103
6
4
2
Virtual Pre-Arcing Time In Seconds
102
FWP-25A14F
FWP-30A14F
FWP-32A14F
FWP-40A14F
FWP-50A14F
6
4
2
101
6
4
2
100
10–1
6
4
FWP-5A14F
FWP-10A14F
FWP-15A14F
FWP-20A14F
2
6
4
2
10–2
6
4
2
10–3
6
4
2
10–4
2
4
6
8
2
101
4
6
8
2
102
4
6
8
103
High Speed
Fuses
Prospective Current In Amps RMS
Peak Let-Through Curve
104
FWP-50A14F
FWP-40A14F
FWP-32A14F
FWP-30A14F
FWP-25A14F
6
4
2
Peak Let-Through Current
103
6
4
2
FWP-20A14F
FWP-15A14F
FWP-10A14F
FWP-5A14F
102
6
4
2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785307
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
235
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL):
20-100A, Striker Optional
FWP (22 x 58mm)
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of theapplied
working voltage, Eg, (rms)
at a power factor of 15%.
Specifications
Description: Ferrule style high
speed fuses with and without
indicating striker.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 690Vac (IEC)
— 700Vac (UL)
FWP with
— 500Vac
striker
option.
— 500Vdc (20-100A)
Amps: — 20-100A
IR: — 200kA RMS Sym.
— 50kA @ 500Vdc
Agency Information: CE, UL Recognition JFHR2.E91958,
CSA Component Acceptance file Class 1422-30, 1422-90
(53787)
Electrical
Characteristics
Total Clearing I2t
The total clearing I t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
2
1.4
1.2
1.0
0.9
0.8
0.7
0.6
Power Losses
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
K
0.5
0.4
0.3
200
300
58.0
(2.283")
400
500
22.2
(0.875")
600
Eg
700
Catalog
Numbers
Without Striker
FWP-20A22F
FWP-25A22F
FWP-32A22F
FWP-40A22F
FWP-50A22F
FWP-63A22F
FWP-80A22F
FWP-100A22F
With Striker
FWP-20A22FI
FWP-25A22FI
FWP-32A22FI
FWP-40A22FI
FWP-50A22FI
FWP-63A22FI
FWP-80A22FI
FWP-100A22FI
Size
22 x 58mm
(7⁄8" x 29⁄32")
22 x 58mm
(7⁄8" x 29⁄32")
*IEC/UL Voltage rating 690/700
15.0
(0.591")
With Striker
66 (2.598")
58 (2.283")
5
(0.197")
22.2 (0.874")
UL
5
4
3
200
1.0
Kp
0.8
400
500
600
700
0.6
0.5
0.4
0.3
0.2
0.1
30 40 50
16 (0.630"
•
•
•
•
•
•
•
•
Rated
Current
RMS-Amps
20
25
32
40
50
63
80
100*
20
25
32
40
50
63
80
100*
60
70
Ib
80 90 100%
Electrical Characteristics
I2t (A2 Sec)
Minimum
Clearing At
Melting
Rated Voltage
Watts
Loss
19.0
34.0
53.5
68
135
280
600
1100
5
6
8
9
9.5
11
13.5
16
19.0
34.0
53.5
68
135
280
600
1100
260
410
605
750
1600
3080
6600
12500
260
410
605
750
1600
3080
6600
12500
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
Data Sheet: 720026
236
300
Eg
Catalog Numbers
Dimensions - mm (in)
Without Striker
1.4
1.2
103
9
8
7
6
Arc Voltage
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
5
6
8
9
9.5
11
13.5
16
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 20-100A,
Striker Optional
Without Striker
FWP 20-100A: 660V/700V (22 x 58mm)
Time-Current Curve
104
6
4
2
103
6
4
2
102
FWP-50A22F
FWP-63A22F
FWP-80A22F
FWP-100A22F
6
4
2
Virtual Pre-Arcing Time In Seconds
101
6
4
2
10
0
6
4
FWP-20A22F
FWP-25A22F
FWP-32A22F
FWP-40A22F
2
10–1
6
4
2
10–2
6
4
2
10–3
6
4
2
2
101
4
6
8
2
102
4
6
8
High Speed
Fuses
10–4
103
Prospective Current In Amps RMS
Peak Let-Through Curve
104
FWP-100A22F
FWP-80A22F
6
FWP-63A22F
Peak Let-Through Current
4
FWP-50A22F
2
103
6
FWP-40A22F
FWP-32A22F
4
FWP-25A22F
FWP-20A22F
2
102
102
2
4
6
103
2
4
6
104
2
Prospective Short-Circuit Current Symmetrical RMS
4
6
105
2
Data Sheet: 35785291
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
237
High Speed Fuses
Ferrule — FWK 750V: 5-60A
•
•
•
•
FWK 5-30A (20 x 127mm
35-60A (25 x 146mm)
Specifications
Description: Ferrule style high speed fuses.
Dimensions: See Dimensions illustrations.
Ratings:
Volts: — 750Vac
— 750Vdc (Time constant = 10-15mS)
Amps: — 5-60A
IR: — 45kA RMS Sym.
Agency Information: CE
•
•
•
•
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
Catalog Numbers
Catalog
Numbers
FWK-5A20F
FWK-8A20F
FWK-10A20F
FWK-15A20F
FWK-20A20F
FWK-25A20F
FWK-30A20F
FWK-35A25F
FWK-40A25F
FWK-50A25F
FWK-60A25F
Size
20 x 127mm
(13⁄16” x 5”)
25 x 146mm
(1” x 53⁄4”)
Electrical Characteristics
Rated
I2t (A2 Sec)
Current
Clearing
RMS-Amps
Pre-arc
at 750Vdc
5
8.5
16
8
50
100
10
95
200
15
100
240
20
125
315
25
400
1100
30
800
2600
35
1300
4300
40
1600
5300
50
3100
12000
60
5900
24000
Recommended fuseholders for 20x127, -2, -3
Recommended fuseclips for 20x127, 1A1837
Recommended fuseclips for 25x146, A3354705
Dimensions - mm (in)
Fig. 1: 5-30A
127.0
(5.000")
20.5
(0.807")
16.0
(0.630")
Fig. 2: 35-60A
146.05
(5.75")
25.4
(1")
20.64
(0.813")
Data Sheet: 720039
238
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
High Speed Fuses
Ferrule — FWK 750V: 5-60A
FWK 750V: 5-30A (20 x 127mm)
35-60A (25 x 146mm)
Time-Current Curve
104
6
4
FWK-15A20F
2
FWK-20A20F
103
FWK-25A20F
6
FWK-30A20F
4
FWK-40A25F
FWK-50A25F
2
FWK-60A25F
102
Virtual Pre-Arcing Time In Seconds
6
4
2
101
6
4
2
100
6
4
FWK-5A20F
FWK-8A20F
2
10
FWK-10A20F
±1
6
4
2
10
±2
4x10
±3
2
4
6
8
101
2
4
6
8
102
2
4
6
8
103
Prospective Current In Amps RMS
High Speed
Fuses
Data Sheet: 720028
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
239
High Speed Fuses
Ferrule — FWJ 1000V: 20-30A
FWJ (14 x 67mm)
Arc Voltage
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of theapplied
working voltage, Eg, (rms)
at a power factor of 15%.
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 1000Vac/800Vdc
Amps: — 20-30A
IR: — 25kA RMS Sym.
— 20kA @ 800Vdc
Agency Information: CE, UL Recognized JFHR2.E91958
Electrical
Characteristics
Total Clearing I2t
1.5
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
1.0
0.15
200
500
800
Dimensions - mm (in)
66.7
(2.626")
14.5
(0.571")
15.9
(0.625")
Fuseclips:
• Catalog Number: 5591 (see data sheet 2132)
800
400
200
1.0
Kp
0.8
1000 1400 1800
0.6
0.5
0.4
0.3
0.2
0.1
30 40 50
60
70
Ib
80 90 100%
Catalog
Numbers
FWJ-20A14F
FWJ-25A14F
FWJ-30A14F
Size
14 x 67mm
9
( ⁄16” x 25⁄8”)
• Watts loss provided at rated current.
• See accessories on page 243.
•
•
•
•
•
•
•
•
Electrical Characteristics
I2t (A2 Sec)
Clearing
Pre-arc
at 1000V
25
220
33
350
52
450
Rated
Current
RMS-Amps
20
25
30
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
Data Sheet: 35785031
240
600
Eg
Catalog Numbers
Eg
1000
1200
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
0.5
UL
1600
Power Losses
K
0.3
0.2
2000
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
Watts
Loss
9
11
14
High Speed Fuses
Ferrule — FWJ 1000V: 20-30A
FWJ 20-30A: 1000V (14 x 67mm)
Time-Current Curve
104
6
4
2
103
6
4
2
102
6
4
Virtual Pre-Arcing Time In Seconds
2
101
6
4
FWJ-20A14F
FWJ-25A14F
FWJ-30A14F
2
100
6
4
2
10–1
6
4
2
10–2
6
4
2
10–3
6
4
101
2
4
6
8 102
2
4
6
High Speed
Fuses
2
10–4
8 103
Prospective Current In Amps RMS
Peak Let-Through Curve
104
6
4
FWJ-30A14F
FWJ-25A14F
FWJ-20A14F
2
Peak Let-Through Current
103
6
4
2
102
6
4
2
101
101
2
4
6
102
2
4
6
103
2
4
6
104
Prospective Short-Circuit Current Symmetrical RMS
2
4
6
105
2
Data Sheet: 35785315
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
241
High Speed Fuses
Ferrule — FWS/FWL 1000Vdc: 2-30A
•
•
•
•
FWS 2-15A (20 x 127mm)
FWL 20-30A (20 x 127mm)
Specifications
Description: Ferrule style full range
fuses.
Dimensions: See dimensions
illustrations.
Ratings:
Volts: — 1200Vac (FWL 20-30A)
— 1400Vac (FWS 8-15A)
— 2100Vac (FWS 2-6A)
— 1000Vdc (FWL/FWS 2-30)
Amps: — 2-30A
IR: — 45kA RMS Sym.
— 30kA @ 1000Vdc
Agency Information: CE, IEC 60077
•
•
•
•
•
•
Features and Benefits
Excellent cycling capability and DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss in a compact size
Used with finger-safe holders/blocks
Typical Applications
DC Common bus
DC Drives
Power converters/rectifiers
Reduced voltage starters
Traction aux circuits
Capacitor protection
FWL/FWS 2-30A: 1000Vdc 2-30A
(20 x 127mm)
Time-Current Curve
Catalog Numbers
Catalog
Numbers
FWS-2A20F
FWS-6A20F
FWS-8A20F
FWS-10A20F
FWS-12A20F
FWS-15A20F
FWL-20A20F
FWL-25A20F
FWL-30A20F
Size
20 x 127mm
(13⁄16” x 5”)
20 x 127mm
(13⁄16” x 5”)
Electrical Characteristics
Rated
I2t (A2 Sec)
Current
Clearing
RMS-Amps
Pre-arc
at 1000Vdc
2
0.8
2.4
6
27
81
8
64
192
10
118
277
12
170
380
15
209
500
20
675
1550
25
1200
2760
30
1850
4300
• ADD “I” to catalog number for indicating version.
• Enclosed finger-safe fuse holder – CH127
• See accessories on page 243.
• Watts loss provided at rated current.
Dimensions - mm (in)
127.0
(5.000")
Watts
Loss
4.4
6.7
7.6
3.0
3.4
5.0
5.9
6.5
7.5
20.5
(0.807")
16.0
(0.630")
Indicating Version – Dimensions - mm (in)
8.0
(0.315")
127.0
(5.000")
20.5
(0.807")
2.0
16.0
(0.630")
Data Sheet: 720040
242
2.0
(0.079")
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
High Speed Fuses
Ferrule Fuse Accessories
Fuse Blocks
Fuse Holders
Specifications
Catalog Symbol: CH Series
Description: DIN-Rail mount
fuse holders
Agency Information:
UL File E14853, Guide IZLT
Listed, IZLT2 Recognized
CSA: File 47235, CHPV and
CHM - Class 6225-30,
CHCC - Class 6225-01
Ratings: 600V/30A (UL)
690V/32A (IEC)
Features and Benefits
• Finger-safe design - No exposed contacts
• DIN-Rail mount (35mm) - Fits standard mounting rails
• Optional open fuse indication lights tells fuse status at a
glance
• Handle/fusepuller easily installs and removes fuses
• Available in single and multi-pole configurations
• Wire ready lugs and spade terminal connections save
installation time
• CE marking
• Available up to 1000Vdc
• PLC device available for remote monitoring
Specifications
Catalog Symbol: J70100,
J70032
Description: Fuse blocks
for 22x58mm & 14x51mm
fuses.
Ratings:
Volts: — 700Vac/dc
Amps: — 32-100A
Withstand: — 200kA RMS Sym.
Agency Information: CE, UL Recognized, Guide IZLT2,
File E14853
Flammability Rating: UL 94V0
Catalog Numbers
Catalog
Numbers
Fuse
Size
J70032-2CR
14x51
J70100-2CR
22x58
22x58
J70032-1CR
J70032-3CR
J70100-1CR
J70100-3CR
32
Poles
100
1
Amps
32
32
100
100
1
2
3
2
3
Max Wire
Size
#2
#2
#2
#2
#2
Terminations
Box Lug w/
Box Clip
Lug w/
Retaining
Retaining Clip
#2
Typical Applications
• Switchboard panel, control consoles, small motors,
transformers, and similar applications
High Speed
Fuses
Recommended Cooper Bussmann Fuse Types
Class CC North American Class CC Fuses - LP-CC,
FNQ-R, KTK-R
10 x 38
North American Midget Fuses - FNQ, KTK, AGU,
BAF, BAN, FNM, FWA, FWC, & PV
14 x 51
FWX, FWH, FWP & NON
22 x 58
FWP
See pages 274-280 for CH Series fuse holder information.
Data Sheet: 2053
Data Sheet: 1211
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
243
High speed fuses
Faster lead-time.
Better protection.
More energy efficient.
244