100-1,200 amp, +24 VDC Vortex® Power System with 100 or 130 amp PCUs Key Features Description • Single Point Adjustment Adjustment—no tools required to make settings and adjustments; one intelligence shelf controls up to 56 PCUs The Vortex power platform with 100 or 130 amp power conversion units (PCUs) is a modular power system providing up to 1,200 amps of power for +24 volt systems. The basic components of a Vortex power system include an intelligence shelf, which houses the meter–control–alarm microprocessor (MCA) and PCUs; expansion shelves for additional PCUs; and a modular distribution cabinet. • Remote Access Access—options allow users to view, control and interact with all power systems in a network from a remote location • Plug’n’Play Plug’n’Play—add PCUs without adjustments and settings; no system shutdown • Front Accessible Accessible—allows for easy installation, additions and maintenance • Modular Design Design—simple to install and operate; allows users to grow system in costeffective increments • High Density Density—compact design takes up less floor space; houses four PCUs per 10.5" (26.67cm) H x 23” (58.42cm) W shelf • Optional Temperature Compensation Compensation—provides automatic adjustment of PCU output voltage when battery temperature increases or decreases The intelligence shelf can accommodate up to four PCUs, and the expansion shelves, also housing up to four PCUs each, can be added for larger load requirements. The intelligence and expansion shelves are 23" (58.42cm) wide x 10.5" (26.67cm) high. In addition to housing the PCUs, the intelligence shelf provides a powerful, microprocessorbased meter–control–alarm system which is capable of monitoring and controlling up to 56 PCUs. The front of the intelligence shelf provides a 16-character alphanumeric display which can be activated at the touch of a keypad. Vortex distribution is modular by row and position. The cabinet allows for up to four rows with a maximum of 96 positions. Users can combine any number of 1-150 amp circuit breakers and 1-50 amp TPA-style fuses to customize power plants. GJ-style circuit breakers and TPL-style fuses are also available. Application The Vortex system, powered with 100 or 130 amp PCUs, is ideal for wireless applications such as MTSO, cell sites and base stations, cellular, PCS and GSM technologies. Additional Information For additional specification, engineering and installation information, specify spec. number 582120000 (power system), 588701101 (400 amp power shelf and 100 amp PCUs) or 588703800 (520 amp power shelf and 130 amp PCUs). For ordering information, request drawing SAG582120000, PD588701101 or PD588703800. • Saf ety Compliance Safety Compliance—UL listed to UL subject 1801 LLP 2-51 100-1,200 amp, +24 VDC Vortex Power System with 100 or 130 amp PCUs The System Distribution The Vortex platform includes a modular distribution product line that can be designed with one to four panels. Each modular panel can be configured with any combination of distribution positions, low voltage disconnect, battery disconnect and dual voltage bus panels. Distribution cabinets are front accessible, modular in design and are initially configured in the factory. The cabinets are 24.375" (61.91cm) wide, 17.5” (44.45cm) deep and vary in height depending on the capacity. Circuit breakers and/or fuse modules snap into the multi-position distribution blocks to provide for easy installation. For larger device requirements, TPL-style fuses and GJ-style breakers are available up to 600 amp rating. One Row Distribution Intelligence Shelf A front access intelligence shelf houses up to four PCUs. Available shelf ratings are 400 amps (with 100 amp PCUs) or 520 amps (with 130 amp PCUs). The intelligence shelf includes the MCA, which provides a single point of adjustment for such features as float voltage, test/ equalize voltage, high voltage shutdown and current limit adjustments for all PCUs in the entire power system. The intelligence shelf display allows users to view specific alarm conditions, system measurements and system settings. All adjustments can be performed locally via the alphanumeric display panel on the front of the intelligence shelf or remotely via optional software and hardware. The MCA provides local indicators and the ability to transmit various alarm conditions such as PCU failure, high voltage shutdown and AC failure. Four Row Distribution Intelligence Shelf LLP 2-52 100-1,200 amp, +24 VDC Vortex Power System with 100 or 130 amp PCUs Expansion Shelf A standard 7’ high power system can contain one to four front-access expansion shelves, each of which houses up to four PCUs. Available shelf ratings are 400 amps (with 100 amp PCUs) or 520 amps (with 130 amp PCUs). The expansion shelves are 23" (58.42cm) wide, 10.5" (26.67cm) high and 14.88" (37.78cm) deep. Easy System Expansion Power Conversion Units The modular, high frequency, switch-mode Vortex PCUs are the foundation of the Vortex platform. Plug’n’play technology allows for easy system configuration. System capacity can be increased by simply plugging an additional PCU into an existing intelligence or expansion shelf – no adjustments or setup are required. The Vortex power system can house up to 20 PCUs which provide load power, battery float current and battery recharge current. The PCUs are monitored and controlled by the intelligence shelf. The PCUs allow the user to appropriately size a power plant (100 to 1,200 amps) to meet specific applications. Power Conversion Unit Specifications Input Voltage: Nominal 208/240 volts AC, single phase, 50/60 Hz, with a range of 176 to 264 volts. Extended range is 150 volt AC to 290 volt AC (100 amp unit only). Inrush Current: Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage within the rated input voltage range. Frequency: 45 -70 Hz Protection: Each PCU is individually wired and connections for individual AC input branch circuits are provided. If the AC input voltage decreases or increases beyond a nonadjustable predetermined value, the PCU power conversion circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC input voltage is reestablished within specifications limits. Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to 50% of rated full load at nominal line. Meets IEC 1000–3–2. Typical Operating Efficiency: 88% at full load. Output Voltage: Nominal +24 volts DC, Negative Ground. Current: 100 amps per PCU, up to a total of 400 amps per shelf with four PCUs installed. 130 amps per PCU, up to a total of 520 amps per shelf with four PCUs. Regulation: Steady state output voltage remains within ±0.5% of any voltage within the range of 23.0 to 29.0 volts DC (23.0 to 28.0 volts DC for 130 amp PCUs) for any combination of frequency, normal input voltage, and load from no load to full load over the temperature range of -20° C to +65° C (-4° F to +149° F) for 100 amp PCUs, -20° C to +50° C (-4° F to +122° F) for 130 amp PCUs. Filtering: On or off battery Voice Band Noise — Less than 32 dBrndC Wide Band Noise — Does not exceed 250 mv peak-to-peak, or 25 mv rms Psophometric Noise — Does not exceed 1 mv LLP 2-53 100-1,200 amp, +24 VDC Vortex Power System with 100 or 130 amp PCUs Power Conversion Unit Specifications (continued) Protection Current Limiting — Maximum output current of each PCU can be set from 10% to 110% (105% maximum for 130 amp PCUs) of full load current. High Voltage Shutdown — If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three seconds, the PCU automatically restarts. Status/Alarm Indicators and Metering Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed on the 16character numerical display of the intelligence shelf and on the PCUs within the shelf. Environmental Operating Temperature: -40° C to +65° C (-40° F to +149° F) for 100 amp PCUs, -20° C to +50° C (-4° F to +122° F) for 130 amp PCUs Storage Temperature: -40° C to +85° C (-40° F to +185° F) Humidity: 0% to 95% relative humidity, non-condensing Altitude: The maximum operating ambient temperature should be derated by +10° C (+50° F) at an elevation of 10,000' (3,048m) above sea level. For elevations between 3,000' (914m) and 10,000' (3,048m), derate the maximum operating ambient temperature linearly. Ventilation: Fan-cooled front to rear EMI/RFI Suppression: Conforms to FCC rules Part 15, Subpart B, Class A with an option for FCC and CISPR22 Class B emission ratings. Audible Noise: 3' from any vertical surface does not exceed 65dBA; 55dBA with low fan speed selected. Physical Characteristics Mounting: Plug-in installation Dimensions: Width: 5.13" (13.02cm) Height: 9.88" (25.08cm) Depth: 14.5" (36.83cm) Weight: 18 lbs. (8.16kgs) Safety Compliance UL recognized (UL 1950) CSA 22.2, No. 950 CE 100 or 130 amp, +24 Volt Power Conversion Unit www er w.. m a r c o n i . c o m /pow /power Marconi Communications 1122 F Street Lorain, OH 44052 800-800-1280 Fax: 440-246-4876 Vortex® and Lorain® are trademarks of Marconi Communications Inc. © 2000 Marconi Communications Inc. Printed in the USA. All rights reserved. Any unauthorized reproduction or transmission without the prior consent of Marconi Communications Inc. is prohibited. LLP 2-54