TECHNICAL SPECIFICATION OF 48 VOLTS 300/120AH SMPS BASED BATTERY CHARGER SUITABLE FOR VRLA MAINTENANCE FREE BATTERY BANK 1. SCOPE: This specification provides for design, Engineering, manufacture, stage testing, inspection and testing before dispatch, packing, forwarding and delivery at site FOR destination of 48 Volts 300/120AH SMPS based battery charger suitable for indoor installation, complete with all fittings accessories and associated auxiliary equipment mandatory which are required for efficient and trouble free operation as per specified here under. It is not the intent to specify completely all the details of design and construction of equipment. However, the equipment shall conform in all respects to the high standard of engineering, design and workmanship and shall be capable of performing in continuous commercial operation up to the Bidder’s guarantee acceptable to the purchaser. The equipment offered shall be complete in all component necessary for its effective and trouble free operation along with associated equipment interlocks protection scheme etc. Such components shall be deemed to be within the scope of supply irrespective of whether those are specially brought out in this Specification and or the commercial order or not. All similar parts particularly movable ones shall be interchangeable. 1.02 1.03 1.04 CLIMATIC CONDITIONS : The equipment to be supplied against the specification shall be suitable for satisfactory continuous operation under the following tropical conditions: Max. ambient air temperature Max. daily average ambient temperature Max. yearly weighted ambient temperature 500 C 450 C 350 C Min. air temperature Max. humidity Min. relative humidity Average number of thunder storm days per annum Average annual rain fall Number of months during which tropical monsoon conditions prevail altitude above MSL (-) 50 C 100% 26 % 40 15 cm to 100 cm. 4 months (June to Sept). Varies from 61 meters to 815.00 mtrs. 120 days 0.3g. Heavy 1.0 KW/sq.m. 195 kg/sq.m. Average number of rainly days per annum. Seismic level (Horizontal acceleration) Degree of pollution Intensity of solar radiation Max. Wind load STANDARD: All material and equipment shall comply in all respect with requirement of the latest addition of the relevant IS/IEC/TEC/RDSO. A set of standards adopted, translated in English, if it is in language other than English, shall also be enclosed with the tender, to enable due comparison, wherever a standard is specially mentioned in these specification. It is understood that the corresponding standard amongst the sources mentioned above shall also apply. MANUFACTURE AND WORKMANSHIP: All the material used in the construction of the equipment shall be of the best quality obtainable of their respective kinds and whole of the work shall be of the highest class, well finished and of approved design and make. Casting shall be free from blow holes, flaws and of the true form and dimensions. -1- All machined surfaces shall be true and smooth and well finished. 1.05 DUTY AND GENERAL ARRANGEMENTS: The power for the charging apparatus shall be given through an independents 4-core cable connection from an A.C. 50 cycles 3 phase 415 ± 10% volts switchboard fed from a Station Transformer. 1.06 GENERAL TECHNICAL REQUIREMENT: The battery chargers of 48V/25Amp. in N+1 configuration with ultimate capacity 50Amp/75 Amp/100Amp shall be of SMPS type with positive earth. The system shall consist of a Distribution/Switching/Alarms arrangement (DSA) and Float Rectifier-cumChargers (FR/FCs) in a rack. It shall employ modular configuration for flexible provision of DC Power. It shall employ menu driven Micro Processor Controlled Techniques for DSA as well as module for control, monitoring and alarm to achieve better reliability of the system. The SMPS battery chargers shall be capable of continuous operation with float voltage 2.23 to 2.25 Volts per cell (at 27 Deg. C) and 2.3 Volt per cell (at 27 Deg C) for charge voltage while supplying the constant DC load 1.06.1 The SMPS battery chargers shall have constant voltage characteristics throughout the range (from zero to full load) at the floating value of the voltage so as to keep the maintenance free type VRLA batteries fully charged but without harmful overcharge. The system shall employ a modular configuration to provide flexibility in view the future load requirements of DC power. The modules shall be accommodated in a rack. Distribution/Switching/Alarm (DSA) shall be provided in first rack or in a separate rack as per manufacturer’s design for the ultimate system capacity. All factory wiring for the rack shall be for the ultimate capacity so that only plugging of FR/FC module shall enhance the DC power plant output. 1.06.2 Principal Parameters: Input Nominal Voltage i) 230 Volt +/-10% AC single phase for module of 25Amp.For ultimate capacity of 50Amp ii) System rack having ultimate capacity of 75 Amp and 125Amp will be provided AC Three phase input power supply and each module shall operate on individual phase of three-phase AC input power supply. Input Voltage Range 165V to 260 V AC Frequency 48Hz to 52Hz Power factor >0.98 at 50% and above load Efficiency >0.90 at 50% and above load Soft Start time 10 sec Min output current ramp up Output Voltage adj. 48V to 56V DC Current limit adjustable For 50Amps SMPS 5 to 50A Current limit adjustable For 25Amps SMPS 5 to 25A Regulation: 1) Output voltage +/-5% of DC output voltage for any load of 25% to 100% over shoot/under shoot when charger is switched on +/-5% of DC output voltage for any load of 25% to 100% 2) DC output voltage over shoot for a step change in AC voltage 165V to 260V single +/-5% of DC output voltage for any load of 25% to 100% phase -2- 1.07. 3) DC output voltage for a step load change of 25% to 100% Ripple <200mV RMS Load Sharing Better than +/-5% active current sharing at full load Cooling Convection Main Features of SMPS Charger 1.07.1 CONSTRUCTIONAL FEATURES: The rack structure shall be made up of rigid frame work of steel profiles and rear door may be of hinged or removable type. The rear door shall be provided with ventilation arrangement. Alternate design of aluminum and other rigid structure meeting the requirements are also permitted. The rack shall be free of sharp edges or sharp corners. The rack shall be designed for easy maintenance & installation. The rack mounting arrangement shall be such as to provide easy access from rear and top for installation and maintenance. The individual FR/FC module shall be easily mounted to/removed from the front side of the rack. The FR/FC module shall be designed to slide in to the rack on a suitable mechanical arrangement. The associated AC input, DC output connections, control/systems & interface cable connecting the modules shall be connected /disconnected easily without causing any interruption in the supply and damage to load or other working module. Proper thermal engineering of hardware design shall be done by the manufacturer so as to ensure the uninterrupted use of the equipment. The rack complete with all panels fitted shall be designed to allow cooling by natural convection. With the doors in position, all the common visual alarms and meters shall be clearly visible. However the fixtures on the door shall not restrict the movement of door in any way. The FR/FC modules shall be cooled by natural convection. AC input to FR/FC shall be through locking type arrangement. DC output shall be through hot plug in connector on the FR/FC side and through lugged termination on the bus bar/termination end. Control alarm and mentoring connection shall be through connectors. The FR/FC module shall be removable from the rack only. All AC input, DC output & alarm/control/monitoring cables interconnecting the modules and rack shall be easily disconnected by plugs or connectors. AC Terminations The input terminal should be single phase or three phases as the case may be cleared marked as R Y B and N and for AC three phase, L and N for AC single phase. AC input termination shall be suitably protected against the accidental touch/contact with the working staff for their protection and shall also have clear and prominent be “Danger” marking. Screening shall be provided between AC and DC components to prevent accidents. The AC input connection to the rectifier module shall be by means of locking type plug and socket arrangement. All the connection between distribution and FR/FC shall be through proper rated cables only. Fuses and circuit breakers for each FR/FC shall be easily accessible and properly rated. Proper termination for the AC input of the circuit breakers and its output to the FR/FC. The system racks having ultimate capacity of 100 Amp. will be provided AC three phase input power supply and each module shall operate on individual phase of three phase AC input power supply. DC Terminations The output of each rectifier in the negative load shall be taken through full rated ISI -3- marked MCBs. All the AC, DC control & alarm cabling shall be supplied with the rack. All DC +ve and - ve leads shall be clearly marked. Wiring All insulated conductors except those within the confines of a printed circuit board assembly shall be of the rating enough to withstand the maximum current and voltage during fault and overload. All the wires and cables used shall be fire retardant as per IS 1554 with amendment I (June 94). All wiring shall be neatly secured in position and accurately supported. Where wires pass through any part of metal or cover the holes through which they pass shall be suitably bushed. Earthing: Two power earth terminals shall be provided in the frame of the system. Mounting off component & layout: Components mounting and fixing methods shall be secured. Suitable mechanical structure/ arrangement for holding modules in position shall be provided so that the module is held firmly by sliding through it. The FR/FC modules shall be cooled convection. AC input to FR/FC shall be through locking type arrangement. DC out put shall be through hot plug in connector on the FR/FC side and through lugged termination on the bus-bar termination end. Control, alarm and monitoring connections shall be through connectors. The FR/FC module shall be removable from the front of the rack only. All AC input, DC output and alarm/control/monitoring cables interconnecting the modules and racks shall be easily disconnected by plugs or connectors. 1.07.02 Distribution, Switching, Control, alarm & Monitoring (DSA) The Distribution Switching sub - system of DSA shall preferably be in the modular from whereas control, alarm &, monitoring sub-system shall only be modular. The Controller must be Microprocessor based. The distribution switching sub-system 'may be accommodated in a rack with other FR/FCs or in separate rack. These sub systems shall be rack mountable. DSA shall preferably be housed in the upper portion of the rack above the FR/FC modules. The unit shall be equipped to meet the ultimate system capacity. 1.07.03. Battery Temperature Compensation. The charger shall be provided with the appropriate circuitry to interface with the temperature probe assembly. With the probe, the charger shall automatically compensate gassing and constant voltage setting inversely proportional to the probe’s temp/ battery ambient temp., so that over charging at high temperature and under charging at low temperature can be prevented. 1.07.04 Current Limiting (Voltage Drop) Current Limiting (Voltage" Drop) shall be provided for float/ charge operation. The float/charge limiting shall be continuously adjustable between 50% to 100% of rated out put current for out put voltages range of 44.4 to 56 volt. For test purposes upper limit of 100% +5% and lower limit of 50% - 5% shall be acceptable. The float and charge current limit adjustment shall be provided on the front panel of the rectifier module. The FR/FC modules shall be fully protected against short circuit. It shall be ensured that short circuit does not lead to any fire hazard. 1.07.5 Fuses All fuses shall be HRC Link type. Fuses shall be mounted on fuse carriers which are in turn mounted on fuse bases. Wherever it is not possible to mount fuses on carriers, fuses shall be directly mounted on plug-in type base. In such case one insulated fuse pulling handle shall be supplied for each charger. Fuse rating shall be chosen by the -4- Bidder depending on the circuit requirement. All fuses in the chargers shall be monitored. Fuse failure annunciation shall be provided on the failure of any fuse. 1.07.6 Blocking Arrangements Blocking arrangement shall be provided in the positive pole of the out put circuit of the charger to prevent current flow fr9m the DC battery into the charger. 1.07.7 Monitoring, Alarm and Indicating Lamps. The visual indications/ display such as LEDs, LCDs or a combination of both shall be provided on each FR/FC module to indicate: (A) Functional indications: The following functional indications shall be provided on FR/FC and DSA: a) Mains available. b) FR/FC on Auto Float. c) FR/FC on Auto charge. Note: The functional indication (a) shall be provided on both DSA & FR/FC module. While b and c may be provided either on DSA or both FR/FC & DSA. (B) Alarm indications (i) On FR/FC (a) FR/FC over voltage, under voltage or output fail. (b) FR/FC over load (voltage drop) Functional indications shall be extended as status and alarm. FR/FC fail to distribution / switching / control & alarm unit. (ii) On DSA a) Load voltage high (above 56v /low (below 45.6 v) b) FR/FC fail c) Mains out of range d) System Over Load e) Mains ON/Battery Discharge f) Temp. Compensation fail g) Battery Fail or No Battery h) Battery Isolated from the load All alarm circuits shall be provided with suitable delay to ensure that they do not operate to transient. All the protection /alarm shall be within tolerance of O.25v in case of DC voltage and 10/0 in case of current. For AC voltage it shall be +/- 5V. Every alarm, condition shall be accompanied with an audio alarm with audio cut off facility. Potential free contacts two (one for alarm and one redundant) shall be provided for extension of alarms to centralized display. . 1.07.8 Radio Interference The equipment shall be efficiently screened against interference to radio and also other communication equipment, which may be installed in the same building. All sources of noise shall be filtered if necessary with suppressors generally in accordant with relevant standards. 1.07.9 Name plates and marking The name plates shall be while with Black engraved letters. On top of each charger, on front as well as rear sides, larger and bold name plates shall be provided to identify the charger. Name plates with full and clear inscriptions shall also be provided on and inside of the -5- panels for identification of the various equipments and ease of operation and maintenance. An etched, engraved or anodizer name plate shall be fitted on each $MPS battery charger unit having following details inscribed. Manufacture's name. P.O . No. & date. S.No. of SMPS unit Rating of SMPS charger Input voltage of SMPS charger Output voltage of SMPS charger Year of Manufacture 8.0 RESPONSIBILITY FOR DESIGNS: The contractor shall assume full responsibility for co-ordinate and adequate design and shall conform to the best engineering practice for the operating conditions specified. In case the equipment covered by this specification is to be co-ordinate with other equipment, the contractor shall furnish complete information and data as may be desired by the purchaser. 9.0 TESTS & INSPECTION: The tenderer must furnish test reports carried out on one of the SMPS battery charge unit which shall pass all the prescribed type tests for conformity of relevant standards. These type test reports must be issued by a Govt. approved / Govt. recognized/ a Govt. accredited laboratory and must not be older than 7 years from the date of opening of tender. Routine/ acceptance tests shall also be carried out on each SMPS Battery Charger as per specification. Following type tests shall be carried out for compliance of specification requirements: TYPE TESTS: (I) (II) (III) (IV) (V) (VI) (VII) (VIII) 9.1 Visual Inspection Insulation Resistance Test Applied high Voltage test. Performance test. Test for protection device. Burn in test. Climatic test. Vibration test. ROUTINE & ACCEPTANCE TESTS: On each of the SMPS battery chargers following routine and acceptance tests shall be carried out at manufacturer's works before dispatch. (I) (II) (III) (IV) (V) Visual Inspection Insulation Resistance Test Applied high Voltage test. Performance test. Test for protection device & other tests shall be carried out as per requirement of GTP in the presence of inspecting officer. -6- 9.2 a) b) c) d) INSPECTION: The inspection of the equipments shall be carried out by the purchaser's representatives in accordance to the relevant standards. The purchaser shall have access at all times to the works and all other places of manufacture, where the equipments are being manufactured and; the supplier shall provide all facilities for unrestricted inspection of the Supplier's works, raw materials, manufacture of the material and for conducting necessary tests at any stage. The supplier shall keep the purchaser informed in advance about the manufacturing program so, that arrangements could be made for inspection. No equipments shall be dispatched from its point of manufacture unless the material has been satisfactorily inspected, tested and cleared. Inspection and acceptance of any quantity of equipment shall in no way relieve the Supplier from his responsibility for meeting all the requirements of this specification and shall not prevent subsequent rejection if such equipment is later found to be defective. 9.3 TESTS AT SITE: The purchaser reserves the right to conduct all the tests on the equipment after arrival at site and the supplier shall guarantee test certificate figures under actual service conditions. 10. DRAWINGS, LITERATURE AND MANUALS: In addition to any other drawings which the tenderer may like to submit lo show the arrangement and merits of the offered equipments. The following drawings shall be supplied with the tender. General installation layout of SMPS equipments showing position of all associated equipments. Detailed dimensional drawings and descriptive literatures of all the associated equipments separately. Circuit wiring diagram and schematic diagram. Literature/ pamphlets / manuals of SMPS and its associated equipments. i. ii. iii. iv. The successful tenderer shall within four weeks of placement of order, submit four sets of final version of all the drawings of the SMPS Battery Charger for purchaser’s approval. The purchaser shall communicate his comments/approval on drawings to the supplier within a period of four weeks. The supplier shall if necessary modify the drawings and resubmit three copies of modified drawings for purchaser’s approval within two weeks from the purchaser’s comment, which will be approved within 15 days. After receipt of purchaser’s approval the supplier shall submit four sets of drawings and literature containing erection, operating and maintenance instructions per equipment. A set of reproducibles of the approved drawing too will be supplied for the purchaser use. 11. i. ii. iii. iv. PACKING & MARKING All SMPS equipments shall be packed in strong seasoned wooden crates to avoid handling problem. The packing shall be of sufficient strength to withstand rough handling during transit, strong at site and subsequent handling in the field. Suitable cushioning, protective padding, or dunnage or spacers shall be provided to prevent damage or deformation during transit and handling. All packing cases shall be marked legibly with the appropriate caution symbol and correctly so as to ensure safe arrival at their destination and avoid dispatched on account of faulty packing and faulty or illegible markings stenciled on it-in indelible ink. -7- v. Whenever necessary, proper arrangement for lifting, such as lifting hooks etc. shall be provided. Any material found short inside the packing cases shall be supplied by supplier without any extra cost. Each consignment shall be accompanied by a detailed packing list containing the following information: a) Name of the consignee. b) Details of consignment. c) Destination. d) Total weight of consignment. e) Sign showing upper/lower side of the crate. f) Handling and unpacking instruction. All gauges, meters, instruments etc. shall have dials or scales calibrated in metric system of units. All name plates, instruction plate, warning signs and any marking what-so-ever on the equipment and its parts and accessories shall be in Hindi-English Language, using idioms, words and meaning as in current use in India. In order to facilitate sorting and erection at site every part of the plant and equipment shall be suitably marked. 12. PLACE OF MANUFACTURE AND INSPECTION: The tenderer shall state in his tender the place(s) of manufacture, testing and inspection of the various portions of the work included in the tender. The purchaser or his duly authorised agent shall have access to the contractor's or sub contractor's work at any time during working hours for the purpose of inspecting the manufacture and testing of materials, equipment and completed plant and the contractor shall provide the necessary facilities for inspection. 13. DEPARTURE FROM SPECIFICATION: Should the tendered wish to depart from provision of this specification either on account of a manufacturing practice or for any other reasons, he will draw special attention to the proposed points of departure in his tender and submit such full information, drawings & specifications as will enable the merit of his proposal to be appreciated. -8- APPENDIX ‘A’ SCHEDULE OF REQUIREMENT Battery Charger: The Battery Charging equipment shall be housed in a sheet steel cabin finished in stove enameled light grey color conforming to shade of 631 of IS-5 specification. The charger cabin shall have thickness of 18 gauge or better with adequate ventilation. The minimum size of cubical should be 585mm Width, 500mm depth and 560mm Height. The rack shall be free of sharp edges or sharp corners. The rack shall be designed for easy maintenance & installation. The rack mounting arrangement shall be such as to provide easy access from rear and top for installation and maintenance. Two power earth terminals shall be provided in the frame of the system to provide effective earthing to the system. The individual Rectifier module shall be easily mounted to/removed from the front side of the rack. The Rectifier module shall be designed to slide in to the rack on a suitable mechanical arrangement. The associated AC input, DC output connections, control/systems & interface cable connecting the modules shall be connected /disconnected easily without causing any interruption in the supply and damage to load or other working module. There should be auto/manual change over between float and boost charger. Charger Section: The charger should be suitable for operation from single (230 ± 30% volts, 50Hz) or 3 phase (415 ± 30% volts, 50Hz) AC supply as per the system ultimate capacity and suitable for charging 24 cell at 2.16 to 2.40 per cell while simultaneously supplying a continuous load as per requirement at an ambient temp. of 45⁰C. The output of charger should be stabilized within 1% of the charging voltage. There should be individual MCB for each module and complete system. The charger section shall comprise of the following items: S No. Item Description Qty 1. Cabinet 1 2. Hot Swap Rectifiers Modules 25A/48V N+1 ( N = Load Current + Battery Charging Current) The rectifier Modules shall be hot swappable with Individual Alarm Indications for Over Voltage/ Under Voltage or Output Fail. 3 Dropping Diode During the Boost charging the full battery voltage should not be reflected on the bus bars, that is, it should be ensured that the constant voltage is available on DC bus bars irrespective of the fact whether the battery is on float or on boost charge and at same time all battery cell should be equally charged. There should be auto/manual change over between float and boost charger. 4 Voltage monitoring Card 1 5 AC Contactor 1 6 DC Contactor 1 7 Low Voltage Detection Card 1 8 MCB 10A 4 9 MCB 64A 2 10 Lightening Protection Device Class C 1 11 Battery temperature Compensation Probe 2m 12 Microprocessor based Controller 1 No The controller should be mounted so that it is front accessible , front monitored and Front Controlled. It shall be installed in such a manner that the LCD panel is visible without opening and Lock / Door of the unit. The controller should have the following facilities: -9- A. Metering : a) Load Voltage. b) Load Current. c) Battery Voltage. d) Battery Current. e) Battery Temp. f) Voltage and current of Individual module. B. Alarms and Indications : a) Load voltage high. b) Single Rectifier alarm c) Multiple Rectifier alarm d) Mains out of range e) System Over Load f) Mains ON/Battery Discharge g) Temp. Compensation fail h) Battery Fail or No Battery i) Battery Isolated from the load All alarm circuits shall be provided with suitable delay to ensure that they do not operate to transient. All the protection /alarm shall be within tolerance of O.25v in case of DC voltage and 10/0 in case of current. For AC voltage it shall be +/- 5V. Every alarm, condition shall be accompanied with an audio alarm with audio cut off facility. C. Functional Indications: a) Mains available. b) Rectifier on Auto Float. c) Rectifier on Auto Charge. d) Alarm to indicate general alarm condition 13. Potential free contacts: Potential free contacts should be provided for extension of alarms to centralized display. a) Mains out of range. b) Single Rectifier alarm c) Multiple Rectifier alarm d) Communication Error. e) System Over Load. f) System voltage high. g) System voltage low. All the components should be of best quality and from reputed manufacturers. The layout of components, wiring workmanship reliability etc. shall be of best quality. Adequate space should be provided within the charger section and Distribution, Switching, Control, alarm & Monitoring section for easy accessibility of MCB, Fuses, Alarms, protection devices etc. The charging equipment should be complete with the various component listed above but necessarily limited to the same. The charger shall also be complete with wiring, glands and fixing bolts. - 10 -