Conducting Effective Visual Inspections: Mechanical Integrity for Refrigeration Systems Daniel Dettmers Associate Researcher, IRC What is an Effective Visual Inspection? • Thorough inspection of the exterior of the refrigeration system – Insulated and uninsulated components – Easily accessible and less than accessible components – No drive-by’s • What’s included? – – – – – Piping & valves Vessels Heat exchangers Ammonia pumps Etc. Origin of the Requirement 29 CFR 1910.119 (j)(4) – (j)(4)(i) Inspections and tests shall be performed on process equipment – (j)(4)(ii) Inspection and testing procedures shall follow recognized and generally accepted good engineering practices – (j)(4)(iii) The frequency of inspections & tests of process equipment shall be consistent with applicable manufacturers‘ recommendations and good engineering practices, practices and more frequently if determined to be necessary by prior operating experience Good Engineering Practice? • Manufacturers’ recommendations • Industry standards – ASME B31.5 or B31.3 • Pre-startup inspection – NB-23 (National Board Inspection Code) • Refers to ASME Boiler & Pressure Vessel Code • Guidelines – IIAR Bulletin 109 – IIAR Bulletin 110 – IRC Mechanical Integrity Guidebook • Currently in trial use IIAR 109 & 110 109:4.7.3 – “Ammonia piping should be inspected…” 109:4.7.4 – “Uninsulated refrigerant piping should be inspected… 110:6.4.2.1 - While the system is operational, the external appearance of the surface of vessels or heat exchangers … should be visually inspected weekly by the system operating staff for any departures from normal.” 110:6.4.3 – “The external surface or the insulation and associated vapor barrier applied to…vessels and heat exchangers should be inspected no less than once every 12 months.” IIAR 109 & 110 110:6.7.1 – “All uninsulated piping and associated components…shall be inspected annually for any damage or deterioration…” 110:6.7.2 – “At least as part of the annual piping inspection, but preferably more frequently, the external condition of the insulation and supports shall be inspected.” • Additional components for yearly inspection in 110 – Ammonia pumps – Shut-off valves • 6 months for exposed stems – Relief valves Conducting the Inspection • Establish a plan – Identify and categorize equipment within scope of 1910.119 §(j) – Establish prioritized list of appropriate inspections & tests – Conduct necessary tests and inspections within prescribed frequencies – Train all personnel –- consistent inspections – Establish “go, no-go” criteria for continued service – Document inspection and tests Conducting the Inspection • Assign inspection duties & timeframe – Undesirable: • All inspection duties fall on 1 person • All inspections are planned for the day they are due – Desirable: • Diversify inspection duties – Be certain inspection criteria is consistent – Incorporate with other inspection/maintenance of valves, valve tags, vessels, evaporators, etc. – Involve new hires in process as part of OTJ training • Plan inspection at least 1 month before due • Train all involved and document their training Potential Failure Mechanics • • • • Which can we catch in a visual inspection? No Weld Failure No Stress Corrosion Cracking (SCC) No Internal Erosion External Corrosion Yes! – Corrosion Under Insulation (CUI) Almost Corrosion • “The deterioration of a material, usually a metal, by reaction with its environment.” - National Association of Corrosion Engineers (NACE) • An anodic-cathodic reaction – Positive ions travel through an electrolyte (i.e. water, ice, etc.) – Material is sacrificed • General (Uniform) Corrosion • Pitting Corrosion Corrosion • Positive ions detach at the anode and travel through a electrolyte (i.e. water, ice, etc.) which acts as a carrier connecting to the cathode the anode and cathodes need to be joined to complete the circuit – Anode => metal of the refrigeration system – Cathode => metal of the refrigeration system – Electrolyte => water Controlling water is essential!! Corrosion “Low Risk” Areas • Uninsulated, painted pipe – Easy to see any corrosion forming • High temperature pipe – If pipe is on the high side of the system and insulated (i.e. HPL) there aren’t large driving forces pulling moisture into the insulation system Frozen Insulation • “Always Frozen” – Ice is a poor electrolyte slowing the corrosion process – Be careful of what is defined as “always frozen” Wet Insulation Frozen Pipe Solid Ice Corrosion Under Insulation (CUI) • CUI is general corrosion that occurs undetected under piping insulation – Water infiltrates the insulation system through a break in the jacket/vapor barrier – Insulation then becomes an enabler which aids in corrosion by holding the water tight to the pipe – Pipe must also be without or have a failure in the surface protection (i.e. pipe paint) Corrosion Under Insulation (CUI) “Vapor Barrier” Soaked Insulation Pipe Rust/Insulation Inside Insulation Outside Insulation How Does Moisture Enter? • Insulation system failures – Breaches in jacket, vapor retarder and insulation – Travel under/through the insulation from a breach elsewhere in the system • Water trapped at time of installation • Diffusion of water vapor in the air into insulation – Driving forces pull moisture laden air through cracks, holes and unsealed joints – Vapor retarder not barrier Corrosion “High Risk” Areas • Piping that is near to or above the freezing point • Piping that cycles temp (defrost condensate) • Piping that has circumferential temp distribution (wet suction) • Low points in the piping system – Dips in line or end/corner of horizontal run – Bottom of vertical run – Bottom edge of a horizontal pip run • Piping that is hard to inspect – under supports – Behind walls/piping chases Other Tell-Tale Signs Biological Growth External Frost Especially in Summer Corrosion of the Jacket Wet Suction Returns • Vapor sits in bottom of pipe – Bottom always frozen – Top can freeze-thaw • CUI at mid-pipe or higher • Look for bottom frost/water Cross-section Vapor NH3 Ammonia Condensate Defrost Lines 80 • Large swings in temperature 60 40 – Above and below freezing (32oF) 20 – Large driving 0 force for moisture – Multiple freeze/thaw cycles that tear apart the insulation 2 4 6 8 10 12 14 16 18 20 22 24 Physical Impact • Physical damage to insulation, pipe or vessel is usually easy to spot • Equipment susceptible to damage is often located in areas of heavy traffic, outside (exposed to the elements) or in an area subject to frequent clean-up wash downs • Look anywhere fork trucks can reach (and areas they can’t) – – – – Behind guards Ceiling hung evaps Piping running up or along walls Vessels in spaces Documentation 1910.119 (j)(4)(iv) The employer shall document each inspection and test that has been performed on process equipment. The documentation shall identify the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test. Questions? • Innovation – Knowledge – Progress www.irc.wisc.edu