GE Aware™ PIR High Bay Fixture Mounted Line

advertisement
GE
Lighting Controls
GE AwareTM
PIR High Bay Fixture Mounted Line Voltage
Occupancy Sensor
HB-12
Overview
Specifications
The HB series occupancy sensor is specifically designed for applications such as warehouses,
distribution centers and other high ceiling areas. This product can be easily installed directly on a
fluorescent fixture. With well-developed PIR sensor technology and circuit design, the sensor achieves
high sensitivity and low false-trip occurrence. It comes with 360° high bay and low bay lenses as well as
shields for end of aisle use. For indoor use only.
Technology:
Passive Infrared (PIR)
Operation
The HB series sensor is a fixture mount, line voltage, Passive Infrared (PIR) motion sensing
lighting control, used for energy savings and convenience.
PIR Technology
The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes
in temperature that are created when a person, or part of a person as small as a hand, passes
into or out of a sensor zone. The -SR model allows the control of one load with one occupancy
sensor switch and the -DR can control two loads.
Dual load operation (-DR models)
The HB-12-DR can control two loads but always maintains one load on. This is for applications
where minimum light levels must be maintained. When motion is detected both loads are
energized for full lighting output. When no motion is detected and the time delay has elapsed,
one load will shut off leaving the other load on. In the next on/off cycle the opposite load will
shut off minimizing impact to lamp life due to switching.
Daylight Feature
The daylight feature (-D models) can provide additional energy savings for facilities with
windows or skylights. For -SR-D models, the lights will remain off (or turn off if already on) if the
photocell measures sufficient at the floor. The lights will turn back on when the light level
reaches the minimum setpoint. For the -DR-D models, the daylight feature will prevent both
loads from turning on at the same time when sufficient light is detected, but will always
maintain one load energized. The daylight mode and occupancy sensing modes can be used
together to maximize savings. When sufficient light is detected, daylight control will turn off (SR) or minimize (-DR) light levels regardless of occupancy. When insufficient light is detected,
then the sensor will operate like a standard occupancy sensor.
Power Requirements:
Input (per load):
• 120 - 277VAC 60Hz
Max Load:
• 800VA @ 120VAC 60Hz
• 1200VA @ 277VAC 60Hz
Time Delays: Selectable 10 s to 30 min.
Mounting Height:
• Up to 40 ft.
• Optional low bay lens provided for heights 20 ft. and
below.
Operating Environment:
• Temperature:
14° F – 160° F (-10° C – 60° C)
• Relative Humidity:
20 to 90% non-condensing
Size: 4" x 4" x 2.16" (102.6mm x 102.6mm x 55mm)
Warranty: 5 years
Ordering
Product
Code
64131
64132
64135
64136
Description
Rating
Loads
HB-12-SR
HB-12-SR-D
HB-12-DR
HB-12-DR-D
120/277 VAC
120/277 VAC
120/277 VAC
120/277 VAC
Single
Single
Dual
Dual
Daylight
Option
no
yes
no
yes
Features:
• Front dip switch for time delay and sensitivity control.
• Phototcell option (-D) for daylight harvesting.
• Single or Dual relay option.
• 360° coverage pattern.
HB-12
Wiring Diagram (consult sensor instruction sheet for other wiring options)
HB-12-SR-XX
HB-12-DR-XX
White(Neutral)
White(Neutral)
Red(Load1)
Red(Load1)
Black (Hot)
Load 1
Load 1
Black (Hot)
Brown(Load2)
Blue (Hot)
Coverage
Load 2
High bay lens coverage*
0
20 ft
(6.1 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
40 ft
(12.2 m)
30 ft
(9.1 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
10 ft
(3.0 m)
0
20 ft
(6.1 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
Low bay lens coverage*
0
10 ft
(3.0 m)
15 ft
(4.6 m)
20 ft
(6.1 m)
20 ft
(6.1 m)
15 ft
(4.6 m)
10 ft
(3.0 m)
5 ft
(1.5 m)
0
5 ft
(1.5 m)
10 ft
(3.0 m)
15 ft
(4.6 m)
20 ft
(6.1 m)
* Coverage testing performed at nominal room temperature.
Settings
DIP switch settings ( Ļ : off, Ĺ :on)
Sensitivity
Delay Time
1
2
3
4
5
љ
љ 100%
љ
љ
љ
љ
ј 90%
љ
љ
ј
ј
љ 80%
љ
ј
љ
ј
ј 70%
љ
ј
ј
ј
љ
љ
ј
љ
ј
ј
ј
љ
ј
ј
ј
Sensor factory pre-sets:
10 seconds
30 seconds
1 minute
5 minute
10 minutes
15 minutes
20 minutes
30 minutes
Sensor Logic
6
7
8
љ
љ
љ
љ
љ
ј
љ
ј
ј
Occ. Only
Occ. + PC
PC only
1
2
3
4
5
6
7
8
Manufactured for GE Lighting • General Electric Company• Nela Park Cleveland, OH 44112 • 1-877-584-2685 • www.gelightingcontrols.com • © 2012 GE