MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 1 of 140
Midwest Independent System Operator (MISO)
Project G256
Queue-37519-01
Interconnection Evaluation Study
For 50 MW Generator #2 at Glendive, MT
Prepared by Wayne Haidle
Montana-Dakota Utilities Co. (MDU)
For
Midwest ISO
May 20, 2003
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 2 of 140
1. Executive Summary
A 50 MW peaking gas turbine generator is being installed near Glendive, MT on the
same site of the existing Glendive #1 peaking gas turbine generator. The Visual
Overview on page 3 and Glendive Turbine Jct Sub Switching Diagram on page 4,
identify the site of installation, configuration, and service territory of Montana-Dakota
Utilities Co. (MDU), all of which reside within the ND exporting interface (NDEX).
The primary purpose of the Glendive #2 peaking gas turbine generator is to meet summer
peak demand obligations for MDU network service customers.
A phase 1 system impact study separate from this interconnection evaluation study has
demonstrated no significant thermal or steady state voltage impacts to the system with
current system loads and approved transactions.
Similarly, this interconnection evaluation study demonstrates there are no significant
system impacts to local stability, given the implementation of generator tripping for all
but fast clearing line-to-ground faults on the Glendive CT – Dawson 115 kV line. Till
such time line protection is installed to discriminate adequately between single-phase and
multi-phase faults, both Glendive generators will be issued an unqualified trip for loss of
the Glendive CT – Dawson 115 kV line. The Glendive CT – Dawson 115 kV line is less
than 8 miles in length, so exposure to generator tripping is not significant even with the
existing protection.
With the addition of the Glendive #2 generator, there are no impacts (actually a slight
improvement) to regional stability for the worst system intact ND disturbance. For
incremental impact of scheduling 50 MW from Glendive #2 to MDU load, see Groton &
Wahpeton Voltage Sensitivity for CU Bipolar Block with Plant Trip – Full Scale and
Expanded Scale on pages 139 and 140 respectively.
MDU personnel have evaluated short circuit duty of equipment in the vicinity of the
Glendive #2 generator installation, and all existing equipment was found adequate.
A preexisting condition for Ft. Peck instability was discovered for a close-in 3-phase fault
on the Glendive CT – Dawson 115 kV line; given the modeling assumptions for 2nd zone
protective relaying at Dawson. The installation of Glendive #2 generator does not
exacerbate this preexisting condition or increase the probability that such an event would
occur. Investigation is under way to see if existing system protection adequately covers
this condition or if additional remedies such as pilot relaying will have to be
implemented. Until such time this condition has been evaluated and/or remedied, the
exposure for this event is limited to a 3-phase (perhaps also phase-to-phase) fault within 2
or 3 miles of the Glendive CT sub on the Dawson 115 kV line. The minimal exposure is
accentuated by the fact that this event has not occurred in all the years of the existing
system configuration.
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 3 of 140
2. Visual Overview
MDU Eastern
Interconnection
Service Territory
Existing Phase Shifter
Bilateral Transaction
165
165
To
Ft. Peck
New Glendive
Peaking Turbine
Existing Back-To-Back DC
Bilateral Transaction
200
150
Lines
Resagged
Miles
City
Existing Miles City
and Glendive
Peaking Turbines
MDU Load Center
2x(2x15) MVAR
Capacitors
Added @ Baker
and Hettinger
Little Missouri
Oil Load
Added
New Back-To-Back DC Bilateral Transaction
200
200
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 4 of 140
3. Glendive Turbine Jct Sub Switching Diagram
To Dawson
115 kV
Addition
57 kV Bus
To Baker
115 kV
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 5 of 140
4. Table of Contents
1.
EXECUTIVE SUMMARY ......................................................................................................................... 2
2.
VISUAL OVERVIEW ................................................................................................................................ 3
3.
GLENDIVE TURBINE JCT SUB SWITCHING DIAGRAM ............................................................... 4
4.
TABLE OF CONTENTS............................................................................................................................ 5
5.
STUDY NARRATIVE ................................................................................................................................ 8
6.
APPENDICES ............................................................................................................................................. 9
6.1
POWERFLOW BASE CASE INFORMATION ................................................................................................ 9
6.1.1
Powerflow Base Case Summary and Their Application to Dynamic Analysis ............................. 9
6.1.2
Glendive PSSE EXAM of Generators in “gag” Case ................................................................. 10
6.1.3
Ft. Peck PSSE EXAM of Generators in “gag” Case .................................................................. 11
6.2
MANUFACTURER INFORMATION SUPPLIED FOR GENERATOR SET ........................................................ 13
6.2.1
Round Rotor Generator Model (Quadratic Saturation) for LM6000 ......................................... 13
6.2.2
IEEE Type 2 Excitation System Model for LM6000.................................................................... 14
6.2.3
IEESGO Governor Model for LM6000 ....................................................................................... 15
6.2.4
LM6000 Generator Set “H” Constant Typical Derivation......................................................... 16
6.2.5
Generator Design Data ............................................................................................................... 17
6.2.6
Generator Voltage And Frequency Limits .................................................................................. 22
6.2.7
Generator Capability Curves ...................................................................................................... 23
6.2.8
Exciter No Load Saturation And Short Circuit Curves............................................................... 25
6.2.9
Generator V Curves..................................................................................................................... 27
6.2.10
Exciter Voltage & Short Circuit Current Vs. Field Current ....................................................... 29
6.2.11
Exciter Data Sheets ..................................................................................................................... 30
6.3
PSSE DOCU OF GLENDIVE GENERATOR DYNAMIC DATA .................................................................. 32
6.3.1
PSSE DOCU of Glendive 1 Generator........................................................................................ 32
6.3.2
PSSE DOCU of Glendive 2 Generator........................................................................................ 33
6.4
SNAPSHOT DERIVATION TO USE IN DYNAMIC SIMULATIONS................................................................ 34
6.4.1
makeSnapshot.sc.......................................................................................................................... 34
6.4.2
Glendive2.dyd.............................................................................................................................. 38
6.5
ASSUMPTIONS FOR BREAKER CLEARING SEQUENCE, TIMING, AND ZONE 1 REACH............................. 39
6.5.1
Normal Interrupting Sequence for Either 3-P or L-G Faults ..................................................... 39
6.5.2
Breaker Sequence With Breaker Stuck Near To L-G Fault......................................................... 39
6.5.3
Breaker Sequence With Breaker Stuck at Remote End From L-G Fault .................................... 40
6.6
FAULT DATA DERIVATION ................................................................................................................... 41
6.6.1
Influence of Glendive Generator Status on Fault Derivation ..................................................... 41
6.6.2
Influence of Zone 1 Reach ........................................................................................................... 41
6.6.3
3 Phase Fault Derivation of Open-End Line (Inverse of Positive Sequence Line Impedance) . 41
6.6.4
L-G Fault Derivation................................................................................................................... 42
6.7
SUMMARY OF STABILITY RESULTS ....................................................................................................... 43
6.7.1
Stability Results Legend .............................................................................................................. 43
6.7.2
Close-In Faults on Glendive CT – Dawson 115 kV Line ............................................................ 44
6.7.2.1 Simulations Without Mitigations – Both Glendive Generators On Line ................................ 44
6.7.2.1.1 Test For Preexisting Condition With Both Glendive Turbines Off Line .......................... 44
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 6 of 140
6.7.2.1.2 Test For Alternative Mitigations ....................................................................................... 44
6.7.3
Close-In Faults on Dawson – Glendive CT 115 kV Line ............................................................ 45
6.7.3.1 Simulations Without Mitigations – Both Glendive Generators On Line ................................ 45
6.7.3.2 Mitigation Confirmation and/or Alternatives.......................................................................... 45
6.7.3.2.1 Test for Preexisting Conditions – Both Glendive Generators Off Line ............................ 45
6.7.3.2.2 Test for Alternate Mitigations ........................................................................................... 45
6.7.4
Close-In Faults on Glendive CT – Baker 115 kV Line – Both Glendive Generators On Line.... 47
6.7.5
Close-In Faults on Baker – Glendive CT 115 kV Line – Both Glendive Generators On Line.... 47
6.8
SPECIAL FAULT DEFINITION COMMAND FILES ..................................................................................... 48
6.8.1
yas................................................................................................................................................ 48
6.8.2
ybs................................................................................................................................................ 50
6.8.3
ycs................................................................................................................................................ 52
6.8.4
yds................................................................................................................................................ 54
6.8.5
yes................................................................................................................................................ 56
6.8.6
yfs................................................................................................................................................. 58
6.8.7
ygs................................................................................................................................................ 60
6.8.8
yhs................................................................................................................................................ 62
6.8.9
yis................................................................................................................................................. 64
6.8.10
yjs................................................................................................................................................. 66
6.8.11
yks................................................................................................................................................ 68
6.8.12
yls................................................................................................................................................. 70
6.8.13
yms............................................................................................................................................... 72
6.8.14
yns................................................................................................................................................ 74
6.8.15
yos................................................................................................................................................ 76
6.8.16
yps................................................................................................................................................ 78
6.8.17
yqs................................................................................................................................................ 80
6.8.18
yrs ................................................................................................................................................ 81
6.8.19
yss ................................................................................................................................................ 83
6.8.20
yts................................................................................................................................................. 85
6.8.21
zas................................................................................................................................................ 86
6.8.22
zbs................................................................................................................................................ 88
6.8.23
zcs ................................................................................................................................................ 90
6.8.24
zds................................................................................................................................................ 92
6.8.25
zes ................................................................................................................................................ 94
6.8.26
zfs................................................................................................................................................. 96
6.8.27
zgs................................................................................................................................................ 98
6.8.28
zhs.............................................................................................................................................. 100
6.9
STABILITY PLOTS ............................................................................................................................... 102
6.9.1
Close-In Faults On Glendive CT – Dawson 115 kV Line ......................................................... 103
6.9.1.1 gag|yas ................................................................................................................................... 103
6.9.1.2 gag|ybs................................................................................................................................... 105
6.9.1.3 gag|ycs ................................................................................................................................... 106
6.9.1.4 gag|yds................................................................................................................................... 107
6.9.1.5 gaa|yas ................................................................................................................................... 108
6.9.1.6 gag|yqs................................................................................................................................... 109
6.9.1.7 gag|yrs.................................................................................................................................... 111
6.9.1.8 gag|yss ................................................................................................................................... 113
6.9.2
Close-In Faults on Dawson – Glendive CT 115 kV Line .......................................................... 115
6.9.2.1 gag|yes ................................................................................................................................... 115
6.9.2.2 gag|yfs.................................................................................................................................... 116
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 7 of 140
6.9.2.3 gag|ygs................................................................................................................................... 117
6.9.2.4 gag|yhs................................................................................................................................... 118
6.9.2.5 gaa|ygs ................................................................................................................................... 119
6.9.2.6 gae|yfs.................................................................................................................................... 120
6.9.2.7 gag|yjs.................................................................................................................................... 121
6.9.2.8 gag|yis.................................................................................................................................... 122
6.9.2.9 gag|yks................................................................................................................................... 123
6.9.2.10
gag|yls................................................................................................................................ 124
6.9.2.11
gag|yns............................................................................................................................... 125
6.9.2.12
gag|yms.............................................................................................................................. 126
6.9.2.13
gag|yos............................................................................................................................... 127
6.9.2.14
gag|yps............................................................................................................................... 128
6.9.2.15
gag|yts................................................................................................................................ 129
6.9.3
Close-In Faults on Glendive Ct – Baker 115 kV Line ............................................................... 130
6.9.3.1 gag|zas ................................................................................................................................... 130
6.9.3.2 gag|zbs ................................................................................................................................... 132
6.9.3.3 gag|zcs ................................................................................................................................... 133
6.9.3.4 gag|zds ................................................................................................................................... 134
6.9.4
Close-In Faults on Baker – Glendive CT 115 kV Line.............................................................. 135
6.9.4.1 gag|zes ................................................................................................................................... 135
6.9.4.2 gag|zfs.................................................................................................................................... 136
6.9.4.3 gag|zgs ................................................................................................................................... 137
6.9.4.4 gag|zhs ................................................................................................................................... 138
6.9.5
Groton & Wahpeton Voltage Sensitivity for CU Bipolar Block with Plant Trip ...................... 139
6.9.5.1 Full Scale............................................................................................................................... 139
6.9.5.2 Expanded Scale ..................................................................................................................... 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 8 of 140
5. Study Narrative
The study procedure and results are documented in the appropriate subsections of the appendices. The
following subsections are particularly useful as base references:
•
•
•
6.1 Powerflow Base Case Information starting on page 9
6.5 Assumptions for Breaker Clearing Sequence, Timing, and Zone 1 Reach starting page 39
6.7 Summary of Stability Results starting on page 43
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 9 of 140
6. Appendices
6.1
Powerflow Base Case Information
6.1.1 Powerflow Base Case Summary and Their Application to Dynamic Analysis
Three 2002 summer off-peak NMORWG-compliant powerflow cases (see highlighted/underlined cases prefixed in the table below) were utilized
in this interconnection study, all of which were derived from the companion system impact study for MISO Transmission Service Requests
#75008893 & #75176496 (MISO Ref. A045 SIS).
For purposes of local stability analysis, the “gaa” and “gae” cases were utilized in dynamic simulations of preexisting conditions for the
Glendive 1 generator being off line and on line respectively. The “gag” case was utilized in dynamic simulations of the Glendive 2 generator
being on line with the existing Glendive 1 generator.
For purposes of transient voltage sensitivity analysis to the ND exporting interface, comparisons or transient voltage at Groton and Wahpeton
were provide for the Glendive 2 generator being off line in the “gaa” case and on line in the “gae” case.
All three of these cases had the Miles City DC scheduled at 150 MW W-E, the Rapid City DC at 200 MW E-W, and the Boundary Dam – Tioga
phase shifter scheduled 165 MW N-S. The output of the Glendive generators was scheduled to MDU network load.
------------------------------------------------------------------------------------------------------------------------------NDEX|
MHEX|
MWSI|
Case Name
|Miles G1|Glndv G1|Glndv G2|MDU Load| ND Load|ND %Load|MCDC E-W|RCDC E-W|B10T N-S|
==================|========|========|========|========|========|========|========|========|========|========|========|========|
ga0-so02aa.uurV4U4|
0.0|
0.0|
0.0|
250|
1771|
68.8|
-150|
200|
166|
1946|
1972|
1287|
------------------|--------|--------|--------|--------|--------|--------|--------|--------|--------|--------|--------|--------|
gaa-so02aa.uurV4U4|
0.0|
0.0|
0.0|
250|
1771|
68.8|
-150|
200|
166|
1946|
1972|
1287|
gab-so02aa.uurV4U4|
26.5|
0.0|
0.0|
277|
1798|
69.9|
-150|
200|
166|
1946|
1972|
1286|
gac-so02aa.uurV4U4|
0.0|
37.0|
0.0|
287|
1808|
70.3|
-150|
200|
165|
1945|
1972|
1286|
gad-so02aa.uurV4U4|
26.5|
37.0|
0.0|
314|
1835|
71.3|
-150|
200|
165|
1944|
1972|
1286|
------------------|--------|--------|--------|--------|--------|--------|--------|--------|--------|--------|--------|--------|
gae-so02aa.uurV4U4|
0.0|
0.0|
50.0|
300|
1821|
70.8|
-150|
200|
165|
1945|
1972|
1286|
gaf-so02aa.uurV4U4|
26.5|
0.0|
50.0|
327|
1848|
71.8|
-150|
200|
165|
1944|
1973|
1285|
0.0|
37.0|
50.0|
337|
1858|
72.2|
-150|
199|
167|
1945|
1969|
1284|
gag-so02aa.uurV4U4|
gah-so02aa.uurV4U4|
26.5|
37.0|
50.0|
364|
1885|
73.3|
-150|
200|
167|
1944|
1968|
1283|
-------------------------------------------------------------------------------------------------------------------------------
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 10 of 140
6.1.2 Glendive PSSE EXAM of Generators in “gag” Case
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E
SUN, MAY 18 2003
GAG-SO02AA.UURV4U4.SAV;SUMMER;OP LD;SYSTEM INTACT
ND=1945,MH=1969,MW=1284,OHMH=-196,OHMP=150,EWTW=-251,BD=167
17:36
DATA FOR BUS
1:
832 [GLENDCT7 115] RESIDING IN AREA
CODE PLOAD
2
16.5
ID ST
M5 1
PSI
1.000
PLNT PGEN
87.0
ID ST
1 1
2 1
QLOAD
5.4
PGEN
37.0
50.0
I - L O A D
0.0
0.0
PLOAD
16.5
QGEN
-13.8
QGEN
-5.9
-8.0
QLOAD
5.4
QMAX
48.7
QMAX
16.0
32.7
X-------TO-------X CKT
404 DAWSONC7 115 1
805 BAKER 7 115 1
LINE R
0.01550
0.08930
90, OWNER
Y - L O A D G-SHUNT B-SHUNT VOLTAGE
0.0
0.0
0.0
0.0 1.03000
I - L O A D
0.0
0.0
QMIN VSCHED X-33.7 1.03000
QMIN
-10.0
-23.7
6, ZONE
Y - L O A D
0.0
0.0
REMOTE BUS
AREA
6
ANGLE
67.87
ZONE OWNER
90
99
VOLTAGE
Q PCT-X
0.00
MBASE Z S O R C E
X T R A N
GENTAP
45.3 0.0050 0.1740 0.0000 0.1518 1.0193
67.5 0.0000 0.1810 0.0000 0.1868 1.0200
PMAX
42.5
50.0
PMIN OW1 FRAC1 OW2 FRAC2 OW3 FRAC3 OW4 FRAC4
10.0
1 1.000
10.0
1 1.000
LINE X CHARGING ST MET RATE-A RATE-B RATE-C LENGTH ZI OWN1 FRAC1 OWN2 FRAC2 OWN3 FRAC3 OWN4 FRAC4
0.04140 0.00450 1 F
112.5 112.5 112.5
0.0
1 1.000
0.31350 0.03680 1 F
112.5 112.5 112.5
0.0
1 1.000
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 11 of 140
6.1.3 Ft. Peck PSSE EXAM of Generators in “gag” Case
Since some of the dynamic simulations demonstrate instability of Ft. Peck generation, the following PSSE exam is provided for reference of predisturbance loading of Ft. Peck generators 3, 4, and 5 which were generating 42.0, 45.0, and 45.0 MW respectively.
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E
SUN, MAY 18 2003
GAG-SO02AA.UURV4U4.SAV;SUMMER;OP LD;SYSTEM INTACT
ND=1945,MH=1969,MW=1284,OHMH=-196,OHMP=150,EWTW=-251,BD=167
18:06
DATA FOR BUS
1:
410 [FTPECK3G13.8] RESIDING IN AREA
CODE PLOAD
2
0.0
QLOAD
0.0
I - L O A D
0.0
0.0
PLNT PGEN
42.0
QGEN
-4.6
QMAX
16.0
ID ST
3 1
PGEN
42.0
QGEN
-4.6
QMAX
16.0
6, ZONE 105, OWNER
Y - L O A D G-SHUNT B-SHUNT VOLTAGE
0.0
0.0
0.0
0.0 1.03968
ANGLE
77.05
QMIN VSCHED XREMOTE BUS
VOLTAGE Q PCT-X
-22.0 1.04500
406 [FTPECK 7 115] 1.04500 100.00
QMIN
-22.0
MBASE Z S O R C E
X T R A N
GENTAP
45.8 0.0149 0.3138 0.0000 0.0000 1.0000
W M
X-------TO-------X CKT X-NAME-X 1 T
FRAC4
406 FTPECK 7 115 1
T T
406 FTPECK 7 115 2
T T
S C C C
T Z W M
R 1-2
X 1-2
1 1 1 1
1 1 1 1
0.05330
0.00940
0.57330
0.21730
WBASE1
100.0
100.0
PMAX
42.0
MAG1
MAG2
0.0000
0.0000
0.0000
0.0000
PMIN OW1 FRAC1 OW2 FRAC2 OW3 FRAC3 OW4 FRAC4
0.0
1 1.000
RATE-A RATE-B RATE-C OWN1 FRAC1 OWN2 FRAC2 OWN3 FRAC3 OWN4
22.0
50.0
22.0
50.0
28.0
63.0
1 1.000
1 1.000
X-------TO-------X CKT WINDV1 NOMV1 ANGLE WINDV2 NOMV2 CN RMAX
RMIN
VMAX
VMIN NTPS X--CONTROLLED BUS-X
406 FTPECK 7 115 1 1.0000 0.000
0.0 1.0000 0.000 0 1.5000 0.5000 1.5000 0.5000 9999
406 FTPECK 7 115 2 1.0000 0.000
0.0 1.0000 0.000 0 1.5000 0.5000 1.5000 0.5000 9999
CR
CX
TBL
NOMINAL R,X
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 12 of 140
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E
SUN, MAY 18 2003
GAG-SO02AA.UURV4U4.SAV;SUMMER;OP LD;SYSTEM INTACT
ND=1945,MH=1969,MW=1284,OHMH=-196,OHMP=150,EWTW=-251,BD=167
18:06
DATA FOR BUS
1:
414 [FTPECK4G13.8] RESIDING IN AREA
CODE PLOAD
2
0.0
QLOAD
0.0
I - L O A D
0.0
0.0
PLNT PGEN
45.0
QGEN
-3.4
QMAX
16.0
ID ST
4 1
PGEN
45.0
QGEN
-3.4
QMAX
16.0
6, ZONE 105, OWNER
Y - L O A D G-SHUNT B-SHUNT VOLTAGE
0.0
0.0
0.0
0.0 1.03300
QMIN VSCHED XREMOTE BUS
VOLTAGE
-22.0 1.04500
405 [FTPECK 4 230] 1.04500
QMIN
-22.0
ANGLE
80.48
Q PCT-X
50.00
MBASE Z S O R C E
X T R A N
GENTAP
42.1 0.0167 0.2379 0.0000 0.0000 1.0000
W M S C C C
X-------TO-------X CKT X-NAME-X 1 T T Z W M
FRAC4
405 FTPECK 4 230 1
T T 1 1 1 1
R 1-2
X 1-2
0.00750
0.26560
WBASE1
100.0
PMAX
48.0
MAG1
MAG2
0.0000
0.0000
PMIN OW1 FRAC1 OW2 FRAC2 OW3 FRAC3 OW4 FRAC4
0.0
1 1.000
RATE-A RATE-B RATE-C OWN1 FRAC1 OWN2 FRAC2 OWN3 FRAC3 OWN4
48.0
48.0
60.0
1 1.000
X-------TO-------X CKT WINDV1 NOMV1 ANGLE WINDV2 NOMV2 CN RMAX
RMIN
VMAX
VMIN NTPS X--CONTROLLED BUS-X
405 FTPECK 4 230 1 1.0000 0.000
0.0 1.0000 0.000 0 1.5000 0.5000 1.5000 0.5000 9999
DATA FOR BUS
415 [FTPECK5G13.8] RESIDING IN AREA
CODE PLOAD
2
0.0
QLOAD
0.0
I - L O A D
0.0
0.0
PLNT PGEN
45.0
QGEN
-3.4
QMAX
16.0
ID ST
5 1
PGEN
45.0
QGEN
-3.4
QMAX
16.0
6, ZONE 105, OWNER
QMIN
-22.0
R 1-2
X 1-2
0.00750
0.26560
WBASE1
100.0
TBL
NOMINAL R,X
ANGLE
80.48
Q PCT-X
50.00
MBASE Z S O R C E
X T R A N
GENTAP
42.1 0.0167 0.2379 0.0000 0.0000 1.0000
W M S C C C
X-------TO-------X CKT X-NAME-X 1 T T Z W M
FRAC4
405 FTPECK 4 230 1
T T 1 1 1 1
CX
1:
Y - L O A D G-SHUNT B-SHUNT VOLTAGE
0.0
0.0
0.0
0.0 1.03300
QMIN VSCHED XREMOTE BUS
VOLTAGE
-22.0 1.04500
405 [FTPECK 4 230] 1.04500
CR
PMAX
49.0
MAG1
MAG2
0.0000
0.0000
PMIN OW1 FRAC1 OW2 FRAC2 OW3 FRAC3 OW4 FRAC4
0.0
1 1.000
RATE-A RATE-B RATE-C OWN1 FRAC1 OWN2 FRAC2 OWN3 FRAC3 OWN4
48.0
48.0
60.0
1 1.000
X-------TO-------X CKT WINDV1 NOMV1 ANGLE WINDV2 NOMV2 CN RMAX
RMIN
VMAX
VMIN NTPS X--CONTROLLED BUS-X
405 FTPECK 4 230 1 1.0000 0.000
0.0 1.0000 0.000 0 1.5000 0.5000 1.5000 0.5000 9999
CR
CX
TBL
NOMINAL R,X
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 13 of 140
6.2
Manufacturer Information Supplied for Generator Set
6.2.1 Round Rotor Generator Model (Quadratic Saturation) for LM6000
Generator, Compensator, Stabilizer, and Excitation Limiter Model Data Sheets
GENROU
GENROU, Meidensha 800LL, 60 Hz
ROUND ROTOR GENERATOR MODEL (QUADRATIC SATURATION)
This model is located at system bus
machine
This model used CONs starting with
67.5 for each of
The machine MVA is
units =
MBASE.
0
ZSOURCE for this machine is
the above MBASE.
CONs
J
J+1
J+2
J+3
J+4
J+5
J+6
J+7
J+8
J+9
J+10
J+11
J+12
J+13
#
Value
7
0.39
2.4
2.4
1.227
0.81
2.56
2.42
0.26
2.42
0.17
0.15
0.132
0.419
#
#
#
IBUS,
I.
J.
1
+j
Description
T’do (>0) (Seconds)
T’'do (>0) (Seconds)
T’qo (>0) (Seconds)
T’'qo (>0) (Seconds)
Inertia H
Speed Damping D
Xd
Xq
X'd
X'q
X"d = X"q
Xl
S(1.0)
S(1.2)
0.181
Pm
SPEED
Efd EFD
VT
on
PMECH
VOLT at
terminal
bus
ISOURCE
GENROU
ETERM
ANGLE
Speed
Source
Current
Terminal
Voltage
Angle
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 14 of 140
6.2.2 IEEE Type 2 Excitation System Model for LM6000
Exciter Model Data Sheets
IEEET2
IEEE Type 2 Excitation System, Meidensha 800LL, 60 Hz
This model is located at system bus
machine
This model used CONs starting with
#
#
#
ECOMP
IBUS,
I.
J.
VOTHSG
EFD
IEEET2
VUEL
VOEL
CONs
J
J+1
J+2
J+3
J+4
J+5
J+6
J+7
J+8
J+9
J+10
J+11
J+12
J+13
#
Value
0.022
989.76
0.1
11.72
0
1
1.16
0.017
0.6
1.2
3.21
1.73
7.54
4.42
Description
TR (Seconds)
KA
TA (Seconds)
VRMAX or Zero
VRMIN
KE
TE (>0) (Seconds)
KF
TF1 (>0) (Seconds)
TF2 (>0) (Seconds)
E1
SE(E1)
E2
SE(E2)
IBUS, 'IEEET2', I, TR, KA, TA, VRMAX, VRMIN, KE, TE, KF, TF1, TF2, E1, SE(E1), E2, SE(E2)
SE
ψ
X
VREF
EC
p.u.
1
1+sTR
VRMAX
+
Σ
+
KA
1+sTA
Σ
+
VS
-
+
VRMIN
1
1+sTF2
SKF
(1+sTF1)
Σ
1
(KE+sTE
EFD
p.u.
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 15 of 140
6.2.3 IEESGO Governor Model for LM6000
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 16 of 140
6.2.4 LM6000 Generator Set “H” Constant Typical Derivation
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 17 of 140
6.2.5 Generator Design Data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 18 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 19 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 20 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 21 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 22 of 140
6.2.6 Generator Voltage And Frequency Limits
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 23 of 140
6.2.7 Generator Capability Curves
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 24 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 25 of 140
6.2.8 Exciter No Load Saturation And Short Circuit Curves
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 26 of 140
Generator Open Circuit Voltage & Short Circuit Current Vs. Rotor Amps
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 27 of 140
6.2.9 Generator V Curves
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 28 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 29 of 140
6.2.10
Exciter Voltage & Short Circuit Current Vs. Field Current
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 30 of 140
6.2.11
Exciter Data Sheets
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 31 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 32 of 140
6.3
PSSE DOCU of Glendive Generator Dynamic Data
Although this interconnection study is for the Glendive 2 generator, dynamic modeling
data for the Glendive 1 generator is documented below as well for comparison.
Particularly noteworthy is the disparity in the “H” constant between the units, i.e. 5.91 for
Glendive 1 and 1.23 for Glendive 2. The Glendive 2 turbine is an aero-derivative engine
and as such has a much lower inertia than Glendive 1. These differences in inertia are
readily apparent in the different modes of oscillation during dynamic simulations.
6.3.1 PSSE DOCU of Glendive 1 Generator
1
PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS/E
TUE, MAY 13 2003
SO02AA.UVVV4U4.SAV;SUMMER;OP LD;SYSTEM INTACT
:
ND=1951,MH=1975,MW=1479,OHMH=-197,OHMP=149,EWTW=-254,BD=165
12:10
PLANT MODELS
REPORT FOR PLANT MODELS
BUS
** GENROU ** BUS
NAME
BSKV MACH
832 GLENDCT7 115 1
MBASE
45.3
T'D0 T''D0
5.82 0.024
Z S O R C E
0.00500+J 0.17400
T'Q0 T''Q0
0.46 0.057
H
5.91
X T R A N
0.00000+J 0.15180
GENTAP
1.01930
S(1.2)
0.4218
BUS
NAME
BSKV MACH
832 GLENDCT7 115 1
TR
KA
TA VRMAX VRMIN
0.000 120.00 0.150 1.200 -1.200
S T A T E S
388-393
DAMP
XD
XQ
X'D
X'Q
X''D
XL
0.00 2.0760 1.9660 0.2680 0.4370 0.1740 0.1430
S(1.0)
0.1057
** IEEET3 **
C O N S
1650-1663
832 [GLENDCT7 115]
C O N S
18791-18802
S T A T E S
8911-8914
TE
KF
TF
KP
KI
0.500 0.020 0.582 1.190 0.000
VBMAX
4.152
KI VAR
0.0000
** GAST **
R
0.040
BUS
NAME BSKV MACH
832 GLENDCT7 115 1
T1
0.100
T2
0.100
T3
21.400
C O N S
28270-28278
LOAD LIM
KT
0.820
2.000
S T A T E S
11768-11770
VMAX
1.000
VMIN
0.200
VAR
1822
DT
0.000
VAR
1266
KE
1.000
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 33 of 140
6.3.2 PSSE DOCU of Glendive 2 Generator
** GENROU ** BUS
NAME
BSKV MACH
832 GLENDCT7 115 2
MBASE
67.5
T'D0 T''D0
7.00 0.390
Z S O R C E
0.00000+J 0.18100
T'Q0 T''Q0
2.40 2.400
H
1.23
TR
0.022
KA
989.76
E1
3.2100
** IEESGO **
T1
T2
7.890 0.010
VRMIN
0.000
S(E1)
1.7300
S(1.2)
0.4190
KE
1.000
E2
7.5400
T5
0.01
T6
0.01
C O N S
39517-39530
TE
1.160
TF1
0.600
VAR
5296
TF2
1.200
KE VAR
0.0000
C O N S
39531-39541
K1
20.2
S T A T E S
14725-14729
KF
0.017
S(E2)
4.4200
BUS
NAME
BSKV MACH
832 GLENDCT7 115 2
T3
T4
0.010 0.010
GENTAP
1.02000
DAMP
XD
XQ
X'D
X'Q
X''D
XL
0.81 2.5600 2.4200 0.2560 2.4200 0.1700 0.1500
BUS
NAME
BSKV MACH
832 GLENDCT7 115 2
TA
VRMAX
0.100 11.720
S T A T E S
14719-14724
X T R A N
0.00000+J 0.18680
S(1.0)
0.1320
** IEEET2 **
C O N S
39503-39516
K2
0.00
S T A T E S
14730-14734
K3
0.00
PMAX
1.20
PMIN
0.10
VAR
5297
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 34 of 140
6.4
Snapshot Derivation to Use in Dynamic Simulations
6.4.1 makeSnapshot.sc
#! /bin/ksh
../../mdl/mapp99.pssds -gnikool -w off -buses 50000 << endpsse | tee mapp99-060402_G256_Glendive2.tsc
TEXT
TEXT Get compatable load flow case and convert generators
TEXT
lofl /* Enter load flow
TEXT
TEXT Get a load flow case with all the topology changes including new Glendive Turbine #2
TEXT
case ../../lf/g10-so02aa.uuvV4U4.sav
cong /* Convert generators
TEXT
TEXT Enter dynamics to develop a new snapshot.
TEXT
rtrn /* Return to dynamics
TEXT
TEXT Get snapshot prior to Glendive #2 and other topology additions
TEXT
rstr ../../mdl/mapp99-060402.snp
TEXT
TEXT Read in dynamic data for new Glendive 2 generator
TEXT
dyre /* Read dynamic data
1 /* Add models
Glendive2.dyd /* From this file
Glendive2.conec /* Output conec data here
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 35 of 140
Glendive2.conet /* Output conet data here
Glendive2.relay /* Output relay data here
/* Take next available addresses
TEXT
TEXT Add channels to monitor dynamic voltage on GlendiveCT,
TEXT Dawson, and Baker 115 kV buses
TEXT and flows on the GlendiveCT - Dawson 115 kV line
TEXT and flows on the GlendiveCT - Baker 115 kV line
TEXT
chan
/* Take next available channel address
13 /* Voltage category
832 /* Glendive CT 115 kV bus
404 /* Dawson 115 kV bus
805 /* Baker 115 kv bus
/* No more Voltage channels
16 /* P&Q category
832 404 1 'MW Glendive CT To Dawson' /* POWR for GlendiveCT - Dawson 115 kV line
'MVAR Glendive CT To Dawson' /* MVAR for GlendiveCT - Dawson 115 kV line
832 805 1 'MW Glendive CT to Baker' /* MW for GlendiveCT - Baker 115 kV line
'MVAR Glendive CT to Baker' /* MVAR for GlendiveCT - Baker 115 kV line
/* No more P&Q channels
1 /* Select ANGLE
832 1 /* Glendive 1 ANGLE
832 2 /* Glendive 2 ANGLE
412 1 /* Miles City ANGLE
/* No more ANGLE
2 /* Select PELEC
832 1 /* Glendive 1 PELEC
832 2 /* Glendive 2 PELEC
412 1 /* Miles City PELEC
/* No more PELEC
3 /* Select QELEC
832 1 /* Glendive 1 QELEC
832 2 /* Glendive 2 QELEC
412 1 /* Miles City QELEC
/* No more QELEC
4 /* Select EFD
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 36 of 140
832 1 /* Glendive 1 EFD
832 2 /* Glendive 2 EFD
412 1 /* Miles City EFD
/* No more EFD
6 /* Select PMECH
832 1 /* Glendive 1 PMECH
832 2 /* Glendive 2 PMECH
412 1 /* Miles City PMECH
/* No more PMECH
7 /* Select SPEED
832 1 /* Glendive 1 SPEED
832 2 /* Glendive 2 SPEED
412 1 /* Miles City SPEED
/* No more SPEED
18 /* Select RELAY2 (R&X)
832 404 1 'puR Glendive CT To Dawson' /* puR for GlendiveCT - Dawson 115 kV line
'puX Glendive CT To Dawson' /* puX for GlendiveCT - Dawson 115 kV line
832 805 1 'puR Glendive CT to Baker' /* MW for GlendiveCT - Baker 115 kV line
'puX Glendive CT to Baker' /* MVAR for GlendiveCT - Baker 115 kV line
/* No more RELAY2 (R&X)
0/* Exit channel category selector
TEXT
TEXT Update governor load limit on Miles City and Glendive #1
TEXT GAST governor model such that steady state load output will
TEXT be within range, i.e. not intitialize with a DSTATE
TEXT
altr
2 /* CONS
27787
1 /* Yes change it.
1.01 /* 26.5 MW / 26.4 MBASE = 1.004 -- Miles City governor load limit
28274
1 /* Yes change it.
0.82 /* 37.0 MW / 45.3 MBASE = 0.817 -- Glendive #1 governor load limit
28276
1 /* Yes change it.
1.00 /* Increase maximum allowable fuel flow -- Glendive #1 governor fuel flow limit
-1 /* Exit
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 37 of 140
0 /* No network changes
TEXT
TEXT With dynamics data updates, save new snapshot
TEXT
snap ../../mdl/mapp99-060402_G256_Glendive2.snp
/* Take all addresses
TEXT
TEXT Output documentation for all Glendive and Miles City Plant dynamic data
TEXT
docu
2 /* To output file
Glendive.docu
0/* Reporting mode
832 /* Glendive 115 kV bus
2 /* All Plant Models
/* No more buses
TEXT
TEXT Output documentation for all Glendive and Miles City Plant dynamic data
TEXT
docu
2 /* To output file
MilesCity.docu
0/* Reporting mode
412 /* Miles City 115 kV bus
2 /* All Plant Models
/* No more buses
stop,delete
endpsse
# No alterations to conet and conec or relays, so delete void files.
\rm -f Glendive2.conet Glendive2.conec Glendive2.relay
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 38 of 140
6.4.2 Glendive2.dyd
832 'GENROU' 2
1.2270
2.4200
832 'IEEET2' 2
832 'IEESGO' 2
7.0000
0.8100
0.1700
0.0220
0.0000
0.6000
7.5400
7.8900
0.0100
0.0000
0.39000
2.56000
0.15000
989.76000
1.00000
1.20000
4.42000
0.01000
0.01000
1.20000
2.40000
2.42000
0.13200
0.10000
1.16000
3.21000
/
0.01000
20.21600
0.10000
2.40000
0.25600
0.41900
11.72000
0.01700
1.73000
0.01000
0.00000
/
/
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 39 of 140
6.5
Assumptions for Breaker Clearing Sequence, Timing, and Zone 1 Reach
The following sequence and timings were applied uniformly for the step-distance relay and breaker failure simulations on the
Glendive CT – Dawson 115 kV line and the Glendive – Baker 115 kV line. In conformance with NERC standards, only L-G
faults were simulated simultaneous with a stuck breaker condition. To be conservative, zone 1 was assumed to reach only to
70% of the line during intermediate clearing.
6.5.1 Normal Interrupting Sequence for Either 3-P or L-G Faults
|
For Intermediate Clearing, Assume Zone 1 Reach @ 70% of Line|
|
+----------<----------<----------<----------<----------<----|
|
**2**
**1**
|
**3**
|
|
_
_
v
_
_
|
|---|_|---|_|------x------------------------------------------------------|_|---|_|---|
|
7.5~
Fault
^
26.0~
|
|
Reach of Zone 1
|
|
|---------->---------->---------->---------->---------->----+
|
|
6.5.2 Breaker Sequence With Breaker Stuck Near To L-G Fault
|
For Intermediate Clearing, Assume Zone 1 Reach @ 70% of Line|
|
+----------<----------<----------<----------<----------<----|
|
**2**
**1**
|
**3**
|
|
_
_
v
_
_
|
|---|_|---|_|------x------------------------------------------------------|_|---|_|---|
| 18.5~ Stuck
Fault
^
26.0~
|
|
Breaker
|
|
|
Reach of Zone 1
|
|
|---------->---------->---------->---------->---------->----+
|
|
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 40 of 140
6.5.3 Breaker Sequence With Breaker Stuck at Remote End From L-G Fault
|
For Intermediate Clearing, Assume Zone 1 Reach @ 70% of Line|
|
+----------<----------<----------<----------<----------<----|
|
**2**
**1**
|
**3**
|
|
_
_
v
_
_
|
|---|_|---|_|------x------------------------------------------------------|_|---|_|---|
|
7.5~
Fault
^
Stuck 37.0~ |
|
|
Breaker
|
|
Reach of Zone 1
|
|
|---------->---------->---------->---------->---------->----+
|
|
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 41 of 140
6.6
Fault Data Derivation
6.6.1 Influence of Glendive Generator Status on Fault Derivation
All fault data was calculated with both Glendive generators on line. Since (1) positive sequence data is inherently updated with
powerflow topology changes, and (2) zero sequence data is insensitive to Glendive generator status while the generator step-up
transformers (grounded wye on 115 kV) remain in service for generator breaker tripping; the overall results for L-G fault calculations
are not substantially compromised by the uncorrected negative sequence impedance for a Glendive generator status change.
Although the modeling compromise is small when one or more of the generators are off line, the simulated deviation from actual
conditions errors on the safe side. 3-P faults are not compromised at all.
6.6.2 Influence of Zone 1 Reach
To preclude optimistic deterministic results for impedances associated with end-of-line faults, the fault impedances for open-ended
lines were assumed to be at 70% of the line length during intermediate clearing. This allows for the possibility that zone 1 (or
ground instantaneous) high-speed clearing does not actually reach the aspired 90% of line length.
6.6.3 3 Phase Fault Derivation of Open-End Line (Inverse of Positive Sequence Line Impedance)
=======================================================================================================================
Line impedances and 3-P shunt contribution for open ended line @ 100% and 70% of line.
=======================================================================================================================
X------FROM------X X-------TO-------X CKT
puR1&2
puX1&2
puR0
puX0
100% Z1 MVA G & B
70% Z1 MVA G & B
11243 GLENDCT5 115 11238 DAWSON 5 115 1
0.01086 0.03822 0.03686 0.11978
687.9 -2421.0
982.7 -3458.5
11243 GLENDCT5 115 11267 BAKER 5 115 1
0.08930 0.31350 0.30370 0.95200
84.0
-295.0
120.1
-421.5
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 42 of 140
6.6.4 L-G Fault Derivation
=======================================================================================================================
The following are applied to specified buses with system intact.
=======================================================================================================================
BUS
NAME BSKV
11243 GLENDCT5 115
ZERO
0.01317 0.07665
POSITIVE
0.01299 0.09341
NEGATIVE
0.01427 0.09246
ZERO+NEGATIVE
0.02744 0.16911
MVA SHUNT G B
93.5
-576.2
BUS
NAME BSKV
11238 DAWSON 5 115
ZERO
0.00197 0.02468
POSITIVE
0.01065 0.08039
NEGATIVE
0.01145 0.07986
ZERO+NEGATIVE
0.01342 0.10454
MVA SHUNT G B
120.8
-941.1
BUS
NAME BSKV
11267 BAKER 5 115
ZERO
0.00790 0.10964
POSITIVE
0.02669 0.19192
NEGATIVE
0.02732 0.19155
ZERO+NEGATIVE
0.03522 0.30119
MVA SHUNT G B
38.3
-327.5
=======================================================================================================================
Buses with 9999 are 70% of the distance on from the "From" terminal.
Each pair inludes results for system intact and remote end (30% section) open.
=======================================================================================================================
BUS
NAME BSKV
9999 GDV-DAW
9999 GDV-DAW
ZERO
0.00978 0.05000
0.03837 0.24119
POSITIVE
0.01177 0.08525
0.02654 0.23521
NEGATIVE
0.01271 0.08461
0.03270 0.23127
ZERO+NEGATIVE
0.02249 0.13461
0.07107 0.47246
MVA SHUNT G B
120.7
-722.7
31.1
-207.0
BUS
NAME BSKV
9999 DAW-GDV
9999 DAW-GDV
ZERO
0.01426 0.07079
0.02772 0.11088
POSITIVE
0.01271 0.09047
0.02269 0.13010
NEGATIVE
0.01384 0.08966
0.02292 0.12995
ZERO+NEGATIVE
0.02810 0.16045
0.05064 0.24083
MVA SHUNT G B
105.9
-604.7
83.6
-397.6
=======================================================================================================================
BUS
NAME BSKV
9999 GDV-BAK
9999 GDV-BAK
ZERO
0.06854 0.26431
0.22610 0.74877
POSITIVE
0.03517 0.19465
0.07627 0.31888
NEGATIVE
0.03597 0.19413
0.07772 0.31780
ZERO+NEGATIVE
0.10451 0.45844
0.30382 1.06657
MVA SHUNT G B
47.3
-207.4
24.7
-86.7
BUS
NAME BSKV
9999 BAK-GDV
9999 BAK-GDV
ZERO
0.07065 0.25112
0.21837 0.78811
POSITIVE
0.02969 0.15524
0.08487 0.51519
NEGATIVE
0.03075 0.15449
0.08511 0.51502
ZERO+NEGATIVE
0.10140 0.40561
0.30348 1.30313
MVA SHUNT G B
58.0
-232.0
17.0
-72.8
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 43 of 140
6.7
Summary of Stability Results
6.7.1 Stability Results Legend
G
Grade
F = (Upper
f = (Lower
P = (Upper
p = (Lower
Case)
Case)
Case)
Case)
Fail without an immediate mitigation available
Failed, however a mitigation in subsequent simulation has been implemented
Pass directly and/or with mitigation already implemented
Passes if the mitigation so identified were implemented
bas
Base conditions
gaa = No MDU peaking turbines on line
gae = Glendive 2 peaking turbine on line
gag = Glendive 1 & 2 peaking turbines on line
flt
lnk
Fault code
Link back to an original "flt" of similar origin which failed to meet criteria
fbs
tbs
From bus terminal (Initial fault initiated here)
To bus (Intermediate fault impedance moved here including 70% of line impedance towards "From" bus with "From" terminal open)
gdv = Glendive CT 115 kV bus
daw = Dawson 115 kV bus
bak = Baker 115 kV bus
typ
Type of fault where in all cases initial fault
3-P
L-G
LBF
RBF
=
=
=
=
3 phase fault
L-G fault
Local breaker failure (i.e. at "From" bus terminal)
Remote breaker fault (i.e. at "To" bus terminal)
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 44 of 140
6.7.2 Close-In Faults on Glendive CT – Dawson 115 kV Line
6.7.2.1 Simulations Without Mitigations – Both Glendive Generators On Line
3-P fault drives Ft. Peck unstable due to 2nd zone clearing at Dawson…
All normal and breaker failure L-G faults stable…
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------F|gag|yas|
|gdv|daw|3-P|
0.0
-1e6 | 7.5| 982.7 -3458.5|26.0|
|??? Dawson-Ft. Peck out-of-step tripping
P|gag|ybs|
|gdv|daw|L-G| 93.5
-576.2| 7.5| 31.1
-207.0|26.0|
|
P|gag|ycs|
|gdv|daw|LBF| 93.5
-576.2|18.5| 31.1
-207.0|26.0|Trip Glendive Load
|
P|gag|yds|
|gdv|daw|RBF| 93.5
-576.2| 7.5| 31.1
-207.0|37.0|Clear Dawson 115 kV bus|
Mitigation
Confirmation
and/or Alternatives
6.7.2.1.1 Test For Preexisting Condition With Both Glendive Turbines Off Line
Ft. Peck unstable even with both Glendive generators off line...
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------F|gaa|yas|
|gdv|daw|3-P|
0.0
-1e6 | 7.5| 982.7 -3458.5|26.0|
|??? Dawson-Ft. Peck out-of-step tripping
6.7.2.1.2 Test For Alternative Mitigations
Ft. Peck stable with pilot tripping...
Unconditional trip of both Glendive CT generators required for Glendive CT stability even with pilot tripping…
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------f|gag|yqs|yas|gdv|daw|3-P|
0.0
-1e6 | 7.5|
| 7.5|
|Assume future pilot relaying
0.0
-1e6 | 7.5|
| 7.5|
|Pilot trip + Gdv unit 1 @ 7.5~
f|gag|yrs|yas|gdv|daw|3-P|
p|gag|yss|yas|gdv|daw|3-P|
0.0
-1e6 | 7.5|
| 7.5|
|Pilot trip + Gdv unit 1&2 @ 7.5~
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 45 of 140
6.7.3 Close-In Faults on Dawson – Glendive CT 115 kV Line
6.7.3.1 Simulations Without Mitigations – Both Glendive Generators On Line
All fault types fail on Glendive CT instability for close-in faults on Dawson – Glendive CT line due to 2nd zone clearing at Glendive CT…
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------f|gag|yes|
|daw|gdv|3-P|
0.0
-1e6 | 7.5| 982.7 -3458.5|26.0|
|
f|gag|yfs|
|daw|gdv|L-G| 120.8
-941.1| 7.5| 83.6
-397.6|26.0|
|
f|gag|ygs|
|daw|gdv|LBF| 120.8
-941.1|18.5| 83.6
-397.6|26.0|Clear Dawson 115 kV bus|
f|gag|yhs|
|daw|gdv|RBF| 120.8
-941.1| 7.5| 83.6
-397.6|37.0|Trip Glendive Load
|
6.7.3.2 Mitigation Confirmation and/or Alternatives
6.7.3.2.1 Test for Preexisting Conditions – Both Glendive Generators Off Line
With both Glendive generators off line, system confirmed stable for local breaker failure…
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------P|gag|ygs|
|daw|gdv|LBF| 120.8
-941.1|18.5| 83.6
-397.6|26.0|Clear Dawson 115 kV bus|
6.7.3.2.2 Test for Alternate Mitigations
6.7.3.2.2.1 Glendive 2 Unstable with Glendive 1 Off Line for 2nd Zone Clearing L-G Clearing At Glendive CT
With Glendive 1 off line, Glendive 2 still unstable for Glendive CT 2nd zone L-G fault clearing on Dawson line…
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl| Interm G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------f|gae|yfs|
|daw|gdv|L-G| 120.8
-941.1| 7.5| 83.6
-397.6|26.0|
|
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 46 of 140
6.7.3.2.2.2 Unqualified Trip Of Both Glendive Generators Mitigates All Stability Issues For Close-In Dawson – Glendive CT Faults
Installed
mitigation initiates unqualified
trip of both Glendive generators for loss of Dawson – Glendive CT line…
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------f|gag|yjs|ygs|daw|gdv|LBF| 120.8
-941.1|18.5| 83.6
-397.6|26.0|Clear Dawson 115 kV bus|Trip Gdv units 1 @ 26~
P|gag|yis|ygs|daw|gdv|LBF| 120.8
-941.1|18.5| 83.6
-397.6|26.0|Clear Dawson 115 kV bus|Trip Gdv units 1&2 @ 26~
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------f|gag|yks|yfs|daw|gdv|L-G| 120.8
-941.1| 7.5| 83.6
-397.6|26.0|
|Trip Gdv units 1 @ 26~
-941.1| 7.5| 83.6
-397.6|26.0|
|Trip Gdv units 1&2 @ 26~
P|gag|yls|yfs|daw|gdv|L-G| 120.8
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------f|gag|yns|yes|daw|gdv|3-P|
0.0
-1e6 | 7.5| 982.7 -3458.5|26.0|
|Trip Gdv units 1 @ 26~
P|gag|yms|yes|daw|gdv|3-P|
0.0
-1e6 | 7.5| 982.7 -3458.5|26.0|
|Trip Gdv units 1&2 @ 26~
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------f|gag|yos|yhs|daw|gdv|RBF| 120.8
-941.1| 7.5| 83.6
-397.6|37.0|Trip Glendive Load
|Trip Gdv units 1 @ 37~
P|gag|yps|yhs|daw|gdv|RBF| 120.8
-941.1| 7.5| 83.6
-397.6|37.0|Trip Glendive Load
|Trip Gdv units 1&2 @ 37~
6.7.3.2.2.3 Glendive CT – Dawson Pilot Relaying Mitigates Tripping of Glendive CT’s for 2nd Zone Clearing L-G Faults
Test pilot relaying to see if generator tripping for 2nd Zone L-G faults can be mitigated for both turbines on line...
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl| Interm G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------p|gag|yts|yfs|daw|gdv|L-G| 120.8
-941.1| 7.5|
| 7.5|
|Assume future pilot relaying
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 47 of 140
6.7.4 Close-In Faults on Glendive CT – Baker 115 kV Line – Both Glendive Generators On Line
Both Turbines On Line...
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------P|gag|zas|
|gdv|bak|3-P|
0.0
-1e6 | 7.5| 120.1
-421.5|26.0|
|
P|gag|zbs|
|gdv|bak|L-G| 93.5
-576.2| 7.5| 24.7
-86.7|26.0|
|
P|gag|zcs|
|gdv|bak|LBF| 93.5
-576.2|18.5| 24.7
-86.7|26.0|Trips Generator # 2
|
P|gag|zds|
|gdv|bak|RBF| 93.5
-576.2| 7.5| 24.7
-86.7|37.0|Clear Baker 115 kV bus |
6.7.5 Close-In Faults on Baker – Glendive CT 115 kV Line – Both Glendive Generators On Line
G|bas|flt|lnk|fbs|tbs|typ| Initial G & B |Cycl|Interim G & B |Cycl|Additional BF Tripping |Additional Mitigations
-|---|---|---|---|---|---|---------------|----|---------------|----|-----------------------|---------------------------------------------P|gag|zes|
|bak|gdv|3-P|
0.0
-1e6 | 7.5| 120.1
-421.5|26.0|
|
P|gag|zfs|
|bak|gdv|L-G| 38.3
-327.5| 7.5| 17.0
-72.8|26.0|
|
P|gag|zgs|
|bak|gdv|LBF| 38.3
-327.5|18.5| 17.0
-72.8|26.0|Clear Baker 115 kV bus |
P|gag|zhs|
|bak|gdv|RBF| 38.3
-327.5| 7.5| 17.0
-72.8|37.0|Trips Generator # 2
|
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 48 of 140
6.8
Special Fault Definition Command Files
6.8.1 yas
fault:yas: Tue May 13 20:41:48 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Close-In 3-P on Glendive CT - Dawson
distit2:Open Gdv End @ 7.5~; Open Daw End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in 3-P fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 49 of 140
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,982.7 -3458.5 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 50 of 140
6.8.2 ybs
fault:ybs: Wed May 14 13:00:07 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Glendive CT - Dawson
distit2:Open Gdv End @ 7.5~; Open Daw End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in L-G fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,93.5 -576.2 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,31.1 -207.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 51 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 52 of 140
6.8.3 ycs
fault:ycs: Wed May 14 15:45:01 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Glendive CT - Dawson w Stk Brkr @ Glendive CT
distit2:Open Gdv End @ 18.5~ + Gdv Load; Open Daw End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in L-G fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,93.5 -576.2 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.4083 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove all load served from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:/* No dynamic changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Using working case
spcarg:1 /* Select bus data
spcarg:832 /* Glendive CT bus number
spcarg:/* Bypass alterations to code and shunts
spcarg:/* Bypass other bus data alterations
spcarg:/* Take next load ID
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 53 of 140
spcarg:1 /* Yes, change it
spcarg:, 0.0 0.0 0.0 0.0 0.0 0.0 /* New P, Q, IP, IQ, YP, YQ in MVA
spcarg:/* Next load
spcarg:q /* No more buses, so quit
spcarg:/* Exit activity
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,31.1 -207.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 54 of 140
6.8.4 yds
fault:yds: Tue May 13 16:58:41 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Glendive CT - Dawson w Stk Brkr @ Dawson
distit2:Open Gdv End @ 7.5~; Open Daw End @ 37~ + Clr Daw 115kV Bus
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply near fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,93.5 -576.2 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance at Glendive
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Dawson
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,31.1 -207.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 55 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.7167 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Dawson
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Disconnect Dawson 115 kV bus ...
spcarg:TEXT
spcarg:lofl
spcarg:dscn
spcarg:404 /* Disconnect this bus
spcarg: /* No more
spcarg:rtrn
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 56 of 140
6.8.5 yes
fault:yes: Wed May 14 20:51:22 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near 3-P Dawson - Glendive CT Fault
distit2:Open Daw End @ 7.5~; Open Gdv End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply remote-end 3-P fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,982.7 -3458.5 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 57 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 58 of 140
6.8.6 yfs
fault:yfs: Wed May 14 10:39:52 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Dawson - Glendive CT line
distit2:Open Daw End @ 7.5~; Open Gdv End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 59 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 60 of 140
6.8.7 ygs
fault:ygs: Tue May 13 16:58:41 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Dawson - Glendive CT Line w Stk Brkr @ Dawson
distit2:Open Daw @ 18.5~ Clearing 115 kV Bus; Open Gdv End @ 26~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.4083 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Disconnect Dawson 115 kV bus -- this opens lines and loads to bus ...
spcarg:TEXT
spcarg:lofl
spcarg:dscn
spcarg:404 /* Disconnect this bus
spcarg: /* No more
spcarg:rtrn
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 61 of 140
spcarg:0.5333 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 62 of 140
6.8.8 yhs
fault:yhs: Wed May 14 21:10:53 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Dawson - Glendive CT Line w Stk Brkr @ Gdv CT
distit2:Open Daw @ 7.5~; Open Gdv End @ 37.0~ + Trip Load at Gdv
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 63 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.7167 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Remove all load served from Glendive CT bus
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No dynamic changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Using working case
spcarg:1 /* Select bus data
spcarg:832 /* Glendive CT bus number
spcarg:/* Bypass alterations to code and shunts
spcarg:/* Bypass other bus data alterations
spcarg:/* Take next load ID
spcarg:1 /* Yes, change it
spcarg:, 0.0 0.0 0.0 0.0 0.0 0.0 /* New P, Q, IP, IQ, YP, YQ in MVA
spcarg:/* Next load
spcarg:q /* No more buses, so quit
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 64 of 140
6.8.9 yis
fault:yis: Wed May 14 08:48:32 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Daw - Gdv CT Line w Stk Brkr @ Dawson; Open Daw
distit2:18.5~ Clearing 115 kV Bus; Open Gdv End @ 26~ + Trip Gdv 1&2
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.4083 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Disconnect Dawson 115 kV bus -- this opens lines and loads to bus ...
spcarg:TEXT
spcarg:lofl
spcarg:dscn
spcarg:404 /* Disconnect this bus
spcarg: /* No more
spcarg:rtrn
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 65 of 140
spcarg:0.5333 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip both Glendive generating units with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:2 /* Machine #2
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 66 of 140
6.8.10
yjs
fault:yjs: Wed May 14 11:05:27 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Daw - Gdv CT Line w Stk Brkr @ Dawson; Open Daw
distit2:18.5~ Clearing 115 kV Bus; Open Gdv End @ 26~ + Trip Gdv 1
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.4083 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Disconnect Dawson 115 kV bus -- this opens lines and loads to bus ...
spcarg:TEXT
spcarg:lofl
spcarg:dscn
spcarg:404 /* Disconnect this bus
spcarg: /* No more
spcarg:rtrn
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 67 of 140
spcarg:0.5333 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip Glendive 1 generating unit with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 68 of 140
6.8.11
yks
fault:yks: Wed May 14 13:00:08 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Dawson - Glendive CT line
distit2:Open Daw End @ 7.5~; Open Gdv End @ 26.0~ + Trip Gdv 1
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 69 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip Glendive 1 generating unit with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 70 of 140
6.8.12
yls
fault:yls: Wed May 14 13:00:09 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Dawson - Glendive CT line
distit2:Open Daw End @ 7.5~; Open Gdv End @ 26.0~ + Trip Gdv 1&2
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 71 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip both Glendive generating units with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:2 /* Machine #2
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 72 of 140
6.8.13
yms
fault:yms: Wed May 14 22:12:55 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near 3-P Dawson - Glendive CT Fault
distit2:Open Daw End @ 7.5~; Open Gdv End @ 26.0~ + Trip Gdv 1&2
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply remote-end 3-P fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,982.7 -3458.5 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 73 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip both Glendive generating units with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:2 /* Machine #2
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 74 of 140
6.8.14
yns
fault:yns: Thu May 15 08:34:00 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near 3-P Dawson - Glendive CT Fault
distit2:Open Daw End @ 7.5~; Open Gdv End @ 26.0~ + Trip Gdv 1
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply remote-end 3-P fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,982.7 -3458.5 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 75 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip Glendive 1 generating unit with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 76 of 140
6.8.15
yos
fault:yos: Thu May 15 09:18:14 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Daw - Gdv CT Line w Stk Brkr @ Gdv CT; Open Daw
distit2:@ 7.5~; Open Gdv End @ 37.0~ + Trp Gdv Load + Gdv Unit 1
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 77 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.7167 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Remove all load served from Glendive CT bus
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No dynamic changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Using working case
spcarg:1 /* Select bus data
spcarg:832 /* Glendive CT bus number
spcarg:/* Bypass alterations to code and shunts
spcarg:/* Bypass other bus data alterations
spcarg:/* Take next load ID
spcarg:1 /* Yes, change it
spcarg:, 0.0 0.0 0.0 0.0 0.0 0.0 /* New P, Q, IP, IQ, YP, YQ in MVA
spcarg:/* Next load
spcarg:q /* No more buses, so quit
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip Glendive 1 generating unit with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 78 of 140
6.8.16
yps
fault:yps: Thu May 15 09:18:15 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Daw - Gdv CT Line w Stk Brkr @ Gdv CT; Open Daw
distit2:@ 7.5~; Open Gdv End @ 37.0~ + Trp Gdv Load + Gdv Unit 1&2
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 79 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.7167 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Remove all load served from Glendive CT bus
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No dynamic changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Using working case
spcarg:1 /* Select bus data
spcarg:832 /* Glendive CT bus number
spcarg:/* Bypass alterations to code and shunts
spcarg:/* Bypass other bus data alterations
spcarg:/* Take next load ID
spcarg:1 /* Yes, change it
spcarg:, 0.0 0.0 0.0 0.0 0.0 0.0 /* New P, Q, IP, IQ, YP, YQ in MVA
spcarg:/* Next load
spcarg:q /* No more buses, so quit
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip both Glendive generating units with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:2 /* Machine #2
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 80 of 140
6.8.17
yqs
fault:yqs: Thu May 15 11:15:07 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Close-In 3-P on Glendive CT - Dawson
distit2:Open both terminals @ 7.5~ -- Assume Pilot Relaying
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in 3-P fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 81 of 140
6.8.18
yrs
fault:yrs: Thu May 15 12:04:03 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Close-In 3-P on Glendive CT - Dawson
distit2:Open both terminals @ 7.5~ via Pilot + Trip Gdv Gen 1
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in 3-P fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip Glendive 1 generating unit with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 82 of 140
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 83 of 140
6.8.19
yss
fault:yss: Thu May 15 12:04:03 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Close-In 3-P on Glendive CT - Dawson
distit2:Open both terminals @ 7.5~ via Pilot + Trip Gdv Gen 1&2
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in 3-P fault on Glendive CT - Dawson 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip both Glendive generating units with the line relay action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:1 /* Machine #1
spcarg:1 /* Yes, change it
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 84 of 140
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:2 /* Machine #2
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 85 of 140
6.8.20
yts
fault:yts: Thu May 15 13:23:38 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Dawson - Glendive CT line
distit2:Open Both Terminals @ 7.5~ -- Assume Pilot Relaying
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply near L-G fault on Dawson - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Dawson ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Dawson 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 404 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Dawson bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:404 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 86 of 140
6.8.21
zas
fault:zas: Thu May 15 19:25:59 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Close-In 3-P on Glendive CT - Baker
distit2:Open Gdv End @ 7.5~; Open Bak End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in 3-P fault on Glendive CT - Baker 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Baker bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.1 -421.5 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 87 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Baker CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 88 of 140
6.8.22
zbs
fault:zbs: Thu May 15 20:34:12 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Glendive CT - Baker
distit2:Open Gdv End @ 7.5~; Open Bak End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in L-G fault on Glendive CT - Baker 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,93.5 -576.2 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Baker bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,24.7 -86.7 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 89 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Baker bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 90 of 140
6.8.23
zcs
fault:zcs: Thu May 15 21:35:22 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Glendive CT - Baker w Stk Brkr @ Glendive CT
distit2:Open Gdv End @ 18.5~ + Trip Gdv Gen 2; Open Bak End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply close-in L-G fault on Glendive CT - Baker 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,93.5 -576.2 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.4083 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Baker bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,31.1 -207.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 91 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip Glendive 2 generating unit with the breaker failure action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:2 /* Machine #2
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Baker bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 92 of 140
6.8.24
zds
fault:zds: Thu May 15 21:05:24 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Glendive CT - Baker w Stk Brkr @ Baker
distit2:Open Gdv End @ 7.5~; Open Bak End @ 37~ + Clr Bak 115kV Bus
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply near fault on Glendive CT - Baker 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,93.5 -576.2 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Glendive CT ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance at Glendive
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Baker
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,24.7 -86.7 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 93 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.7167 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Baker
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Disconnect Baker 115 kV bus ...
spcarg:TEXT
spcarg:lofl
spcarg:dscn
spcarg:805 /* Disconnect this bus
spcarg: /* No more
spcarg:rtrn
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 94 of 140
6.8.25
zes
fault:zes: Thu May 15 19:44:21 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near 3-P Baker - Glendive CT Fault
distit2:Open Bak End @ 7.5~; Open Gdv End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply remote-end 3-P fault on Glendive CT - Baker 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 -1e6 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Baker bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.1 -421.5 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 95 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 96 of 140
6.8.26
zfs
fault:zfs: Thu May 15 20:22:36 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Baker - Glendive CT line
distit2:Open Bak End @ 7.5~; Open Gdv End @ 26.0~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply near L-G fault on Baker - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,38.3 -327.5 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till Zone 1 clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Baker bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still observed at Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,17.0 -72.8 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 97 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.533 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Remove fault admittance from Glendive CT bus
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 98 of 140
6.8.27
zgs
fault:zgs: Thu May 15 20:01:07 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Baker - Glendive CT Line w Stk Brkr @ Baker
distit2:Open Bak @ 18.5~ Clearing 115 kV Bus; Open Gdv End @ 26~
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Baker - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,38.3 -327.5# /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.4083 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process breaker failure clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Disconnect Baker 115 kV bus -- this opens lines and loads to bus ...
spcarg:TEXT
spcarg:lofl
spcarg:dscn
spcarg:805 /* Disconnect this bus
spcarg: /* No more
spcarg:rtrn
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,17.0 -72.8 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till 2nd zone clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 99 of 140
spcarg:0.5333 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 100 of 140
6.8.28
zhs
fault:zhs: Thu May 15 21:35:26 CDT 2003 Last Rev. by: Wayne Haidle
distit1:Near L-G on Baker - Glendive CT Line w Stk Brkr @ Gdv CT
distit2:Open Bak @ 7.5~; Open Gdv End @ 37.0~ + Trip Gdv Gen 2
spcarg:TEXT
spcarg:TEXT Run predisturbance for 100 milliseconds
spcarg:TEXT
spcarg:run
spcarg:0.100 0 3 0 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Apply Near L-G fault on Baker - Glendive CT 115 kV line
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,120.8 -941.1 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.225 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Process Zone 1 clearing at Baker ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT
spcarg:TEXT Open Glendive CT - Baker 115 kV line
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:3 /* Select branch data
spcarg:832 805 1 /* From bus, To bus, Circuit No.
spcarg:1 /* Yes, change the data
spcarg:0 /* New branch status; 0 = Open; 1 = Closed
spcarg:q /* No more branch data changes
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Remove fault admittance from Baker
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:805 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT
spcarg:TEXT Apply fault admittance still seen from Glendive CT
spcarg:TEXT
spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,83.6 -397.6 /* Fault G & B in MVA
spcarg:q /* No more bus data
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 101 of 140
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Run simulation till breaker failure clearing at Glendive ...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:run
spcarg:0.7167 0 1 5 /* TPAUSE, NPRT, NPLT, CRTPLT respectively
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Clear fault at Glendive
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:0 /* No dynamic data changes
spcarg:1 /* Yes, network changes forthcoming
spcarg:0 /* Do not pick up new saved case
spcarg:1 /* Select bus data
spcarg:832 /* Bus number
spcarg:1 /* Yes, prepare to change bus shunt
spcarg:,0.0 0.0 /* Fault G & B in MVA
spcarg:q /* No more bus data
spcarg:0 /* No more changes now
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT Trip Glendive 2 generating unit with the breaker failure action...
spcarg:TEXT -------------------------------------------------------------------------------spcarg:altr
spcarg:/* No changes to dynamics
spcarg:1 /* Yes, make changes to network
spcarg:0 /* Use working case
spcarg:2 /* Select generator data
spcarg:832 /* Glendive 115 kV bus
spcarg:/* No change
spcarg:2 /* Machine #2
spcarg:1 /* Yes, change it
spcarg:0 /* To off line status
spcarg:q /* No more changes
spcarg:/* Exit activity
spcarg:TEXT -------------------------------------------------------------------------------spcarg:TEXT All faults now cleared. Resuming dynamic simulation...
spcarg:TEXT -------------------------------------------------------------------------------poexls:
porqls:
fltcom:
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 102 of 140
6.9
Stability Plots
The following subsections have disturbances identified by a unique 3-character
power flow case prefix and a 3-character fault identifier.
To get a description of the 3-character powerflow case prefix, see section 6.1.1
Powerflow Base Case Summary and Their Application to Dynamic Analysis
starting on page 9.
To get a description of the 3-character fault prefix, see the section by the same
3-character name starting in section 6.8 Special Fault Definition Command
Files starting on page 48.
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 103 of 140
6.9.1 Close-In Faults On Glendive CT – Dawson 115 kV Line
6.9.1.1 gag|yas
Ft. Peck unstable for
close-in 3 Phase fault on
Glendive CT – Dawson
115 kV line with 26cycle 2nd zone clearing
at Dawson terminal.
Glendive 1 & 2 also
unstable for same
fault even though high
speed clearing at
Glendive CT
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 104 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 105 of 140
6.9.1.2 gag|ybs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 106 of 140
6.9.1.3 gag|ycs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 107 of 140
6.9.1.4 gag|yds
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 108 of 140
6.9.1.5 gaa|yas
… Ft. Peck is still
unstable
If both Glendive
generators taken off line
before the fact …
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 109 of 140
6.9.1.6 gag|yqs
If pilot relaying reduces
Dawson clearing to 7.5
cycles, then Ft. Peck is
stable even with both
Glendive generators on
line.
Glendive 1 & 2 are still
unstable -- clearing
time for them cannot be
reduced since already
high speed.
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 110 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 111 of 140
6.9.1.7 gag|yrs
… Ft. Peck is stable as
before
If Glendive 1 is
tripped, Glendive 2
is still unstable …
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 112 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 113 of 140
6.9.1.8 gag|yss
… Ft. Peck is stable as
before
Both Glendive
generators require
tripping for multiphase faults on
Dawson line …
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 114 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 115 of 140
6.9.2 Close-In Faults on Dawson – Glendive CT 115 kV Line
6.9.2.1 gag|yes
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 116 of 140
6.9.2.2 gag|yfs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 117 of 140
6.9.2.3 gag|ygs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 118 of 140
6.9.2.4 gag|yhs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 119 of 140
6.9.2.5 gaa|ygs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 120 of 140
6.9.2.6 gae|yfs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 121 of 140
6.9.2.7 gag|yjs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 122 of 140
6.9.2.8 gag|yis
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 123 of 140
6.9.2.9 gag|yks
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 124 of 140
6.9.2.10
gag|yls
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 125 of 140
6.9.2.11
gag|yns
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 126 of 140
6.9.2.12
gag|yms
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 127 of 140
6.9.2.13
gag|yos
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 128 of 140
6.9.2.14
gag|yps
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 129 of 140
6.9.2.15
gag|yts
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 130 of 140
6.9.3 Close-In Faults on Glendive Ct – Baker 115 kV Line
6.9.3.1 gag|zas
… Ft. Peck
remains
stable
Close-in 3-Phase
fault on the
Glendive CT-Baker
115 kV line …
Both Glendive
generators
remain stable
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 131 of 140
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 132 of 140
6.9.3.2 gag|zbs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 133 of 140
6.9.3.3 gag|zcs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 134 of 140
6.9.3.4 gag|zds
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 135 of 140
6.9.4 Close-In Faults on Baker – Glendive CT 115 kV Line
6.9.4.1 gag|zes
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 136 of 140
6.9.4.2 gag|zfs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 137 of 140
6.9.4.3 gag|zgs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 138 of 140
6.9.4.4 gag|zhs
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 139 of 140
6.9.5 Groton & Wahpeton Voltage Sensitivity for CU Bipolar Block with Plant Trip
6.9.5.1 Full Scale
MISO Generator Interconnection G256 Queue-37519-01 – DFAFT #1 Page 140 of 140
6.9.5.2 Expanded Scale
Download