Contactors and Contactor Assemblies SIRIUS Contactors for Switching Motors 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) Technical data Contactor Size Type S3 3RT14 46 General data AC and DC operation Permissible mounting position The contactors are designed for operation on a vertical mounting surface. For DC operation and forward inclination up to 22.5°: coil voltage tolerance 0.85 ... 1.1 × Us Upright mounting position: AC operation Special design required. Positions 13 ... 16 of the Order No. must be changed to -1AA0. Additional charge. – DC operation Mechanical endurance Oper. 10 million cycles Electrical endurance AC-1 utilization category at Ie Oper. cycles Rated insulation voltage Ui (pollution degree 3) V Rated impulse withstand voltage Uimp kV Safe isolation between coil and main contacts (acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89]) V in operation when stored Permissible ambient temperature °C °C Degree of protection acc. to IEC 60 947-1 and DIN 40 050 0.5 million 1000 6 690 –25 ... +60 –55 ... +80 IP 20 (terminal compartment IP 00), coil system IP 40 Shock resistance Rectangular pulse AC and DC operation g/ms 6.8/5 and 4/10 Sine pulse AC and DC operation g/ms 10.6/5 and 6.2/10 See page 2/143 Conductor cross-sections Short-circuit protection of contactors without overload relays Main circuit Fuse links, utilization category gL/gG NH, Type 3NA Type of coord. "1" 2) A 250 Fuse links, utilization category gR SITOR, Type 3NE Type of coord. "2" 2) A 250 A 10 A 10 Auxiliary circuit Fuse links, utilization category gL/gG (weld-free protection at Ik DIAZED Type 5SB, NEOZED Type 5SE or miniature circuit-breaker with C-characteristic (Ik < 400 A) 1 kA) Control circuit 0.8 ... 1.1 × Us AC/DC Coil voltage tolerance Power consumption of the coils (with coil in cold state and 1.0 × Us) Standard design For USA and Canada Hz 50 50/60 50 60 closing p.f. closed p.f. VA 270 0.68 22 0.27 298 /274 0.7 / 0.62 27 / 20 0.29/ 0.31 270 0.68 22 0.27 300 0.52 21 0.29 closing = closed W 15 AC operation DC operation VA Operating times at 0.8 ... 1.1 × Us 1) Break-time = opening time + arcing time AC operation closing time opening time ms ms 17 ... 90 10 ... 25 DC operation closing time opening time ms ms 90 ... 230 14 ... 20 ms 10 ... 15 Arcing time Operating times at 1.0 × Us 1) AC operation closing time opening time ms ms 18 ... 30 11 ... 23 DC operation closing time opening time ms ms 100 ... 120 16 ... 20 1) The opening times of the NO contacts and the closing times of the NC contacts increase if the contactor coils are protected against voltage peaks: varistor +2 ms to 5 ms, diode assemblies 2 to 6 times. Siemens Industry, Inc. Industrial Controls Catalog 2) According to excerpt from IEC 60 947-4-1 (VDE 0660 Part 102): Type of coordination "1": Destruction of the contactor and the overload relay is permissible. The contactor and/or overload relay must be replaced if necessary. Type of coordination "2": No damage can be tolerated to the overload relay, but contact welding on the contactor is permitted if the contacts can be easily separated. 2/123 Contactors and Contactor Assemblies Contactors for Special Applications SIRIUS 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) Technical data Contactor Size Type S3 3RT14 46 Main circuit Load ratings with AC AC-1 utilization category, switching resistive load Rated operational currents Ie at 40 °C up to 690 V at 60 °C up to 690 V at 1000 V at 230 V 400 V 500 V 690 V 1000 V at 40 °C at 60 °C Ratings of three-phase loads p.f. = 0.95 (at 60 °C) Minimum conductor cross-section with Ie load AC-2 and AC-3 utilization categories With an electrical endurance of 1.3 million operating cycles Rated operational current Ie Ratings of slipring or squirrel-cage motors at 50 Hz and 60 Hz (at 60 °C) Power loss per conducting path up to 690 V at 230 V 400 V 500 V 690 V at Ie/AC-1 A A A kW kW kW kW kW mm2 mm2 140 130 60 50 86 107 148 98 50 50 A kW kW kW kW 44 12.7 22 29.9 38.2 W 12.5 Load ratings with DC DC-1 utilization category, switching resistive load L/R 1 ms) Number of conducting paths when connected in series Rated operational currents Ie (at 60 °C) up to 24 V 60 V 110 V 220 V 440 V 600 V A A A A A A DC-3 and DC-5 utilization categories, shunt and series motors Number of conducting paths when connected in series Rated operational currents Ie (at 60 °C) up to 24 V 60 V 110 V 220 V 440 V 600 V A A A A A A 1 2 3 130 80 12 2.5 0.8 0.48 130 130 130 13 2.4 1.3 130 130 130 130 6 3.4 1 2 3 130 130 130 1.75 0.42 0.27 130 130 130 4 0.8 0.45 6 3 1.25 0.35 0.15 0.1 Operating frequency Operating frequency z in operating cycles per hour Contactors without overload relays Rated operation No-load operating frequency for AC-1 for AC-3 1/h AC operation 5000 DC operation 1000 1/h 1/h 650 1000 650 1000 Dependence of the operating frequency z’ on the operational current I’ and the operational voltage U’: Ie z’ = z ---I 2/124 400 V ---------U 1.5 1/h Siemens Industry, Inc. Industrial Controls Catalog SIRIUS Contactors and Contactor Assemblies Contactors for Special Applications 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) Siemens Industry, Inc. Industrial Controls Catalog 2/125 Contactors and Contactor Assemblies Contactors for Special Applications SIRIUS 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) Technical data Contactor Size Type S6 3RT14 56 General data Permissible mounting position The contactors are designed for operation on a vertical mounting surface. Electrical endurance AC-1 utilization category at Ie Oper. 10 million cycles Oper. 0.5 million cycles Rated insulation voltage Ui (pollution degree 3) V Rated impulse withstand voltage Uimp kV Safe isolation between coil, auxiliary contacts and main contacts (acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89]) V Mechanical endurance in operation when stored Permissible ambient temperature 8 690 °C °C –25 ... +60/+55 with AS-Interface –55 ... +80 IP 00/open type, coil system IP 20 g/ms g/ms 8.5/5 and 4.2/10 13.4/5 and 6.5/10 See page 2/132 Degree of protection acc. to IEC 60 947-1 and DIN 40 050 Shock resistance Rectangular pulse Sine pulse Conductor cross-sections 1000 See page 2/14 Electromagnetic compatibility (EMC) Short-circuit protection Main circuit Fuse links, utilization category gL/gG, Type of coordination "1" A NH, Type 3NA Fuse links, utilization category gR, SITOR, Type 3NE Type of coordination "2" A Auxiliary circuit A Fuse links, utilization category gL/gG (weld-free protection at Ik 1 kA) DIAZED Type 5SB, NEOZED Type 5SE or miniature circuit-breaker with C-characteristic (Ik < 400 A) 355 350 10 Control circuit 0.8 × Us min ... 1.1 × Us max AC/DC (UC) Coil voltage tolerance Power consumption of solenoid mechanism (with coil in cold state and rated range Us min ... Us max) AC operation DC operation closing p.f. closed p.f. VA closing closed W W VA Conventional op. mechanism Us min Us max Solid-state op. mechanism Us min Us max 250 0.9 4.8 0.8 300 0.9 5.8 0.8 190 0.8 3.5 0.5 280 0.8 4.4 0.4 300 4.3 360 5.2 250 2.3 320 2.8 PLC control input (EN 61 131-2/Type 2) DC 24 V/ 30 mA Operating times (Break-time = opening time + arcing time) Conventional op. mechanism – at 0.8 × Us min ... 1.1 × Us max closing time opening time ms ms 20 ... 95 40 ... 60 Solid-state op. mechanism Operation via A1/A2 PLC input 95 ... 135 35 ... 75 80 ... 90 80 ... 90 – at Us min ... Us max closing time opening time ms ms 25 ... 50 40 ... 60 100 ... 120 80 ... 90 40 ... 60 80 ... 90 ms 10 ... 15 10 ... 15 10 ... 15 A A A kW kW kW kW kW mm2 mm2 275 250 100 95 165 205 285 165 2 × 70 120 W 20 Arcing time Main circuit Load ratings with AC AC-1 utilization category, switching resistive load Rated operational currents Ie Ratings of three-phase loads p.f. = 0.95 (at 60 °C) Minimum conductor cross-section with Ie load Power loss per conducting path 2/126 at 40 °C up to 690 V at 60 °C up to 690 V at 1000 V at 230 V 400 V 500 V 690 V 1000 V at 40 °C at 60 °C at Ie/AC-1 Siemens Industry, Inc. Industrial Controls Catalog SIRIUS Contactors and Contactor Assemblies Contactors for Special Applications 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) Siemens Industry, Inc. Industrial Controls Catalog 2/127 Contactors and Contactor Assemblies Contactors for Special Applications SIRIUS 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) Technical data Contactor Size Type S10 3RT14 66 S12 3RT14 76 General data Permissible mounting position The contactors are designed for operation on a vertical mounting surface. Mechanical endurance Oper. 10 million cycles Electrical endurance AC-1 utilization category at Ie Oper. cycles Rated insulation voltage Ui (pollution degree 3) V Rated impulse withstand voltage Uimp kV Safe isolation between coil, auxiliary contacts and main contacts (acc. to DIN VDE 0106 Part 101 and A1 [draft 2/89]) V in operation when stored Permissible ambient temperature 1000 8 690 °C °C –25 ... +60/+55 with AS-Interface –55 ... +80 IP 00/open type, coil system IP 20 g/ms g/ms 8.5/5 and 4.2/10 13.4/5 and 6.5/10 See page 2/135 Degree of protection acc. to IEC 60 947-1 and DIN 40 050 Shock resistance Rectangular pulse Sine pulse Conductor cross-sections 0.5 million See page 2/14 Electromagnetic compatibility (EMC) Short-circuit protection Main circuit Fuse links, utilization category gL/gG, NH, Type 3NA Fuse links, utilization category gR, SITOR, Type 3NE Type of coordination "1" A 500 800 Type of coordination "2" A 500 710 A 10 Auxiliary circuit Fuse links, utilization category gL/gG (weld-free protection at Ik 1 kA) DIAZED Type 5SB, NEOZED Type 5SE or miniature circuit-breaker with C-characteristic (Ik < 400 A) Contactor Size Type S10 3RT14 66 Control circuit 0.8 × Us min ... 1.1 × Us max AC/DC (UC) Coil voltage tolerance Power consumption of solenoid mechanism (with coil in cold state and rated range Us min ... Us max) AC operation DC operation closing p.f. closed p.f. VA closing closed W W VA Conventional op. mechanism Us min Us max Solid-state op. mechanism Us min Us max 490 0.9 5.6 0.9 590 0.9 6.7 0.9 400 0.8 4 0.5 530 0.8 5 0.4 540 6.1 650 7.4 440 3.2 580 3.8 PLC control input (EN 61 131-2/Type 2) DC 24 V/ 30 mA Operating times (Break-time = opening time + arcing time) Conventional op. mechanism – at 0.8 × Us min ... 1.1 × Us max closing time opening time ms ms 30 ... 95 40 ... 80 Solid-state op. mechanism Operation via A1/A2 PLC input 105 ... 145 45 ... 80 80 ... 200 80 ... 100 – at Us min ... Us max closing time opening time ms ms 35 ... 50 50 ... 80 110 ... 130 80 ... 100 50 ... 65 80 ... 100 ms 10 ... 15 10 ... 15 10 ... 15 Arcing time 2/128 Siemens Industry, Inc. Industrial Controls Catalog SIRIUS Contactors and Contactor Assemblies Contactors for Special Applications 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) Siemens Industry, Inc. Industrial Controls Catalog 2/129 Contactors and Contactor Assemblies Contactors for Special Applications SIRIUS 3RT14 contactors, 3-pole, for switching resistive loads (AC-1) 2/130 Siemens Industry, Inc. Industrial Controls Catalog