Spec Sheet: ZFV32EL (type: ZFVPFLH4A40) Features: - Compact enclosed 4P non polarized isolator 32A rated up to 1500V DC. - Fault-make load-break switch operation, ideal for DC systems. - Padlockable handle and external mounting position. - Oxidation proof contacts with up to 16mm2 cable capacity. - IP65 protection and UV stabilised. Application: PV array isolators. Certification: EN 60947.3, UL 508, File E332938. Ratings Free air thermal current (Ith)32A Rated insulation pollution degree III (Ui)1000V Rated insulation pollution degree II (Ui)1500V Rated impulse withstand voltage (Uimp)8kV Ambient temperature enclosed -40 to +45 Maximum fuse (A)80 Rated conditional short-cct current5kA Rated Short-cct making capacity1.7kA Short time withstand (1sec)1kA Power loss / pole4.0W Mechanical endurance10,000 Weight0.2kg Operating torque1.7Nm Connection torque 1.2 - 1.8Nm Cable size mm2 4 -16 The contact ratings need to be read in conjunction with AS5033-2012 Appendix B5 for floating PV systems with transformerless inverters. See over. ZFVPFLH4A40 Dimensions Nov 15 IPD GROUP LIMITED Phone: 1300 556 601 www.ipdgroup.com.au Ref.0915M ZFV32 - Technical Data AS5033 2014 Appendix B5 Main Contacts Type ZFV32 Rated thermal current Ithe A 32 Making & Rated insulation voltage Ui1) V 1000Breaking Rated insulation voltage Ui2) V15005x Distance of contacts (per pole) mm 8 operations Rated operational current Ie 300V A 2740.5 DC21A 1 pole 400VA 1624 and A1 500V A 1319.5 DC21B 600V A 10 15 1 800V A 5 7.5 L/R = 1ms 1000V A 2.5 3.75 2 poles in series500V A 32 48 DC21BA2 600V A 32 48 700V A 27 40.5 800V A 23 34.5 900V A 20 30 1000V A 13 19.5 1 2 1200V A 10 15 1500V A 5 7.5 2 poles in series500V A 58 87 + 2 poles parallel600V A 50 75 A2+2 700V A 27 40.5 Type: ZFV32SMAH1A40 800V A 23 34.5 1 2 900V A 20 30 1000V A 13 19.5 3 4 1200V A 10 15 1500V A 5 7.5 3 poles in series500V A 32 48 A3 600V A 32 48 700V A 32 48 800V A 32 48 900V A 32 48 1000V A 32 48 1 2 3 1200V A 16 24 1500V A 13 19.5 3 poles in series500V A 58 87 + 2 poles parallel600V A 50 75 A3 + 2 700V A 45 67.5 800V A 45 67.5 1 2 3 900V A 45 67.5 1000V A 45 67.5 4 5 6 1200V A 16 24 1500V A 13 19.5 4 poles in series500V A 32 48 Type: ZFVPFLH4A40 A4 600V A 32 48 700V A 32 48 800V A 32 48 900V A 32 48 1 2 3 4 1000V A 32 48 1200V A 32 48 1500V A 23 34.5 4 poles in series500V A 58 87 + 2 poles parallel600V A 58 87 A4 + 2 700V A 58 87 1) Suitable at overvoltage category I to III, pollution degree 3 800V A 58 87 (standard-industry): Uimp = 8kV. 900V A 58 87 1 2 3 4 5 6 7 8 1000V A 58 87 2) Suitable at overvoltage category I to III, pollution degree 2 1200V A 50 75 (min. IP55): Uimp = 8kV. 1500V A 23 34.5 Data according to IEC 60947-3, VDE 0660, GB1448.3 (CCC China) Nov 15 IPD GROUP LIMITED Phone: 1300 556 601 www.ipdgroup.com.au Ref.0614E Temperature - ZFV32 In Australia, operating temperature can create onerous conditions for switchgear to operate in. Often overlooked but of extreme importance is the thermal stresses placed on switchgear due to cyclic loading, i.e. thermal current with varying loads over a 24 hour period. Switchgear should be de-rated according to the “Fluid Environment” it is subjected to. The definition of “Fluid Environment” is the area immediately surrounding the switchgear. This environment is subject to change as equipment and installations vary but the derating in each case must be considered to ensure a reliable network design. Ratings ZFV32 4P[°C] 20253035404550556065707580 500V / 6mm² [A] 32323232323230282725232119 600V / 6mm² [A] 32323232323230282725232119 700V / 6mm² [A] 32323232323230282725232119 800V / 6mm² [A] 32323232323230282725232119 900V / 6mm² [A] 32323232323230282725232119 1.000V / 6mm² [A] 32323232323230282725232119 1.000V / 10mm²[A] 32323232323232302827252321 1.000V / 16mm²[A] 32323232323232323028272523 4 mm2[°C] 20253035404550556065707580 500V / 4mm² [A] 25252525252524222119181615 600V / 4mm² [A] 25252525252524222119181615 700V / 4mm² [A] 25252525252524222119181615 800V / 4mm² [A] 25252525252524222119181615 900V / 4mm² [A] 25252525252524222119181615 1.000V / 4mm² [A] 25252525252524222119181615 ZFV32 Type: ZFV32SMAH1A40 Note: Enclosed rating, enclosure size is 180mm x 98mm x 76mm. Fluid Environment Nov 15 IPD GROUP LIMITED Phone: 1300 556 601 www.ipdgroup.com.au Ref.0915K