Instructions For Installation Of
3671 UNIVERSAL CONTROLLER
A6976E
I
Mounting Instructions
1. Mount exit device per instruction sheet provided.
2. Provide a 3/8” dia. min. raceway to allow insertion of electrical
wires running between signal switch and electric hinge.
3. Wiring instructions: See wiring diagram on page 6.
USE CONNECTORS ALLOWED
BY LOCAL CODE. ALLOW
SUFFICIENT LEAD LENGTH
FOR REMOVAL OF INSERT.
WIRES
FROM
HINGE
RAIL*
55- INSERT
3/8” DIA. HOLES
FOR ROUTING WIRES.
* Exit Device must be ordered for specific door width. Cutting of rail
in field is not recommended.
1
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
II
Elevation Diagram
1.
2.
3.
4.
5.
6.
7.
Exit Device, 80 Series, 55 Prefix Signal Switch
Electric Hinge (4 Wire Minimum)
Electromagnetic Lock, 24VDC only. .125 mA (1584)
Fire Alarm Reset Switch, Momentary N.O. Contact (Optional)
Fire Alarm, N.C. Contact (by others - opens upon alarm)
Universal Controller - 3671
Power Supply, 24VDC, 1.8 AMP, Regulated (#3510) or 2.0 AMP,
Regulated (#3530)
8. Key Switch (4375LH)
9. Door status Switch (3287 - Optional)
10. Optional Remote Release Switch Key Switch 4371LT
If Fire Alarm N.C. Contact (item 5) is not used, a jumper must be field installed
between terminals IN5, IN7 and COM of Logic Controller 3671.
5
6
2 WIRES
2 WIRES
2 WIRES
2 WIRES
2 WIRES
9
7 WIRES
2 WIRES
10
3
optional
10 WIRES
2
7
4
optional
optional
1
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
8
2
III
WIRE UNIT
ACCORDING TO
WIRING DIAGRAM
ON PAGE 6.
GREEN
A. Apply power to the “System”:
1.
2.
3.
RED
RED
RED
1.
2.
Insert key into cylinder of 4375LH keyswitch. (2-SPDT momentary switches).
Rotate key clockwise. RED LED will illuminate, magnet will de-energize.
3.
Rotate key counter clockwise (momentary position) and bring key to center
position RED LED illuminates.
After 10 seconds (Time delay, factory preset) GREEN LED illuminates.
Unit is now armed in a “Delayed Egress Mode”. When rail is depressed,
GREEN LED illuminates, RED LED flashes and horn sounds. After 15 seconds,
RED LED illuminates solid. See F - Violation.
C. “Momentary Egress Mode”:
1.
2.
3.
4.
RED
Rotate key counter clockwise (full rotation on 4375LH) and return key to
center position.
RED LED illuminates on keyswitch for ten seconds, magnet de-energizes for
momentary authorized egress.
After 10 seconds, (time delay expires) the magnet re-energizes and GREEN LED
illuminates.
Unit is then rearmed in “Delayed Egress Mode”.
D. “Maintained Egress Mode”:
1.
2.
3.
4.
Rotate key clockwise, return key to center position. You can pull out the key,
if desired.
RED LED will illuminate.
Magnet de-energizes.
Unit is in maintained egress mode and operates as a push/pull unit.
E. Resetting the unit from “Maintained Egress Mode” to “Delayed
Egress Mode”:
1.
2.
3.
4.
3
GREEN LED on 4375LH keyswitch will illuminate.
Magnet will energize.(1584)
Unit NOT armed. See “Arming System in Delayed Egress Mode”.
See B - below.
B. Arming the system in “Delayed Egress Mode”:
4.
5.
GREEN
Universal Controller
OPERATING INSTRUCTIONS
Rotate key counter clockwise, in 4375LH keyswitch. RED LED illuminates.
After 10 seconds (time delay expires), the RED LED will shut off and
GREEN LED will illuminate.
Magnet energizes.
Unit is in “Delayed Egress Mode” (armed position).
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
OPERATING INSTRUCTIONS CONTINUED
F. Violation occurs while in “Delayed Egress Mode” and
resetting the unit back in”Delayed Egress Mode”
1.
2.
Unit is in “Delayed Egress Mode” (Armed position).
Depressing the push bar for more than 2 seconds, starts an irreversible
alarm sequence.
3.
4.
RED LED flashes on the key switch and GREEN LED illuminates solid.
During this process, the magnet remains energized and the alarm on
the key switch sounds.
5.
After 15 seconds (factory preset delay) the RED LED illuminates solid.
GREEN does not illuminate.
Magnet de-energizes, allowing egress.
Alarm continues to sound until unit is reset by a key at the door.
PUSH BAR
GREEN
RED
RED
6.
7.
GREEN
8.
9.
GREEN
10.
11.
12.
RED
Insert and rotate key clockwise and return it to center position.
Alarm stops sounding, GREEN LED flashes and magnet is still
de-energized.
Rotate key counter clockwise and return to center position.
After 10 seconds (time delay expires) RED LED shuts off and GREEN
LED illuminates.
Unit is in “Delayed Egress Mode” (armed position).
G. Unit tied to a fire alarm:
1.
2.
3.
In case of a fire/emergency, the magnet will de-energize instantaneously
(voiding the 15 second delay) allowing immediate egress.
RED LED illuminates.
Resetting the fire alarm automatically sets the unit in a “Delayed Egress
Mode” (Armed position). GREEN LED illuminates when a jumper is
installed from IN7 to COM.
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
4
OPERATING INSTRUCTIONS CONTINUED
H.
“Door propped” alarm (Requires door status switch-3287):
An alarm condition to signal the console and remote location that a door has been
held open beyond a factory adjustable time period (0-60 adjustable seconds). Units
are preset at the factory for approximately 15 seconds. When a momentary legal
release is used, the door is opened, the timer will monitor the “door open” state. If
the door remains open beyond the time set:
a. The local console alarm and remote alarm will sound
b. The station RED LED will remain lit
c. The alarm circuitry will not be latched
When the door is closed, the alarms will silence. The RED LED will extinguish, and the
GREEN LED will illuminate. If the legal release is used during the alarm state, the
alarm will silence, the timer will be reset, and the circuitry will resume with the
functions of a normal legal release. If Door Status Switch is not used, a jumper from
IN6 to COM, must be added.
OPTIONAL REMOTE RELEASE
•
Used to disable system from the exterior of the opening or from
security area
•
Momentary switch 4371LT, located at Terminals IN1 and COM
SPECIFICATIONS
Input Voltage:
Power Consumption:
Output Relays:
Operating Temp:
Enclosure Size:
Power Supply:
24 VDC regulated/filtered
300 mA unloaded, 1.5A maximum
Form C, 1AMP, 24 VDC
-18°C to + 55°C ( 0°F to + 131°F)
Steel enclosure with hinged lid, 12"x 12"x 4"
Sargent 3510, 24VDC, 1.8A, UL Listed, Class 2
FIRE ALARM APPLICATIONS
1. Fire Alarm with (Normally Open) Momentary Reset Switch (as shown on page 6)
Fire alarm contact opens on alarm (Maintained Egress Mode). After alarm condition
ceases and Fire Alarm Contact is reset to closed position a momentary switch closure
at IN7 to COM is required to reset system back to Delayed Egress mode.
2. Fire Alarm without Momentary Reset Switch
Jumper wire must be connected from IN7 to COM. Fire alarm contact opens on alarm
(Maintained Egress Mode). After alarm condition ceases and Fire Alarm Contact is
reset to closed position the system resets back to Delayed Egress mode automatically.
3. Fire Alarm NOT used
Jumper wire must be connected from IN5 to COM and IN7 to COM.
5
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
Wiring Diagram For Delayed Egress Applications
SARGENT EXIT DEVICE 55-80 SERIES, 3510 POWER SUPPLY, 3671 LOGIC CONTROLLER, 1584
ELECTROMAGNETIC LOCK, AND 4375LH KEY SWITCH
+24VDC
3510
1.8 Amp
24VDC
Power Supply
-24VDC
120VAC
IN1* Optional Remote Release
COM
IN2
COM
3671
Universal Controller
IN3
COM
IN4
COM
IN5*
COM
Fire Alarm
Contact
IN8
COM
K1
NC
C
NO
NC
K8 C
NO
Return
+24
Fire Alarm
Reset
Earth
IN6*
COM
IN7*
COM
NC
C
NO
NC
1584 K2
C
NO
Maglock
NC
Red LED K3 C
NO
4375
NC
Green LED K4 C
NO
4375
NC
K5 C
NO
NC
K6 C
NO
Horn
K7
White (Green LED)
(+) Horn
Red
Black
C
3287
Door Status
Switch
N.C.
White (Red LED)
(-) Horn
Red (Red LED)
1584
Maglock
Red (Green LED)
SARGENT
4375LH
Key Switch
EMERGENCY EXIT ONLY
Push until alarm sounds. Door
can be opened in fifteen seconds
Momentary Release
Yellow
IN3
COM
Green
IN4
COM
Gray
Black
Red
White
Maintained Release
Electric Hinge
55-80 Series Exit Device
NOTES:
1. WIRES MUST BE PROTECTED AGAINST ABRASION.
IN4
2. COLORS OF WIRES SHOWN ARE LEADS FROM EXIT DEVICE,
COM
NOT ELECTRIC HINGE.
3. DOOR STATUS IS (NORMALLY OPEN) HELD CLOSED WHEN DOOR IS CLOSED.
IF NOT USED A JUMPER WIRE MUST BE INSTALLED FROM IN6 TO COM.
4. IN3, IN4 ARE NORMALLY OPEN
5. ALL INTERCONNECTING EQUIPMENT MUST BE LOCATED WITHIN THE SAME AREA.
6. CONSULT 3287 INSTRUCTION SHEET FOR PROPER WIRE COLORS.
*
M
SEE NOTES ON PAGE 5
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
6
Wiring From Universal Controller to Optional 4371LT
Key Switch Used For Outside Operation
SARGENT EXIT DEVICE 55-80 SERIES, 3510 POWER SUPPLY, 3671 LOGIC CONTROLLER,
1584 ELECTROMAGNETIC LOCK, AND 4375LH KEY SWITCH
Both Red Wires of the Green and Red
LED’s to +24VDC
White Wire of Green LED to K4 N.O. of 3671
GRN
LED
Red
Red
White Wire of Red LED to K3 N.O. of 3671
RED
LED
SARGENT
Black Wire from
Key Switch
to +24VDC
7
White Wire from
Top of Timer
to IN1 of 3671
factory
wire from
switch
to timer
Black Wire from
Top of Timer
to IN1 Com of 3671
Black Wire from
Bottom of Timer
to -24VDC
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
TROUBLE SHOOTING
1. Unit does not arm
• Check all wire connections
• Check position of keyswitch. If GREEN LED is illuminated, magnet
should be energized
2. Magnet does not release
• Check all wire connections
• Fire alarm must be jumped if not using (IN5 and COM)
• Disconnect two magnet leads. With OHM meter, measure
contacts K2NO and K2 C for continuity
For installation assistance, contact SARGENT at 800-810-WIRE (9473)
8
SARGENT Manufacturing Company • 100 Sargent Drive • P.O. Box 9725 • New Haven • CT 06536-0915
Phone: 800-727-5477 • Fax: 888-863-5054 • Website: www.sargentlock.com
SARGENT of Canada • Phone: 905-940-2040 • Fax: 905-940-3242 • Website: www.sargentcanada.ca
SARGENT® Manufacturing Company is an ASSA ABLOY Group company. Founded in 1864, SARGENT® is a market leader in locksets, cylinders, door closers, exit devices,
electro-mechanical products, and access control systems for new construction, renovation, and replacement applications. The company’s customer base includes
commercial construction, institutional and industrial markets.
The ASSA ABLOY Group is the world’s leading manufacturer and supplier of locks and associated products,
dedicated to satisfying end-user needs for security, safety and convenience.
An ASSA ABLOY Group company
Download