Product Description Jockey Pump Controllers • FTA500 Options—The following are available as options to the controllers: Circuit Breaker Option -A Standard Short Circuit Current Rating 200-240V - 65,000 Amps, RMS Sym. 380-480V - 25,000 Amps, RMS Sym. 550-600V - 14,000 Amps, RMS Sym. NOTE—Consult factory for high interrupting capacity circuit breakers. Omit Minimum Run Timer -B Controller without minimum run timer Floor Mounting Legs FTA -N2 Specify when ordering Modifications—The following are available as modifications to the controllers: ® Description—Firetrol FTA500 Jockey Pump Controllers are intended for use with fire pump systems. They are used for pressure maintenance in fire pump installations to prevent unnecessary cycling of the main fire pump. Approvals—Firetrol jockey pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL508, Standard for Industrial Controls, and CSA, Standard for Industrial Control Equipment. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest edition NFPA 70, National Electrical Code. Standard Features—The following are included as standard with each controller: NEMA Type 2 drip-proof enclosure Horsepower rated fusible disconnect switch with fuseblock and fuses Horsepower rated motor contactor and overload relay HAND-OFF-AUTO selector switch Minimum run timer 120V Secondary - Control circuit transformer 15-290 psi (1-20 bars) Pressure switch, diaphragm style, snap action type contact and 15-120 psi (1-8.3 bars) adjustable differential, suitable for fresh water applications. Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (painted steel) (IEC IP56) -F NEMA Type 4X (#304 stainless steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) *Note: Only the standard NEMA type 2 enclosures are supplied with a red finish - all other painted finishes are supplied Gray as standard. Consult factory for special paint color or finish. Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Pressure Switches and Recorders -B 20-675 psi (1.4-46.5 bars) Pressure Switch for freshwater service (Diaphragm Type, Snap Action Switch) -C 5-250 psi (.35-17.2 bars) Pressure Switch for seawater/foam service (Diaphragm Type, Snap Action Switch) -D 20-675 psi (1.4-46-5 bars) Pressure Switch for seawater/foam service (Diaphragm Type, Snap Action Switch) -SL 0-300 psi (0-20.7 bars) pressure recorder for fresh water service -SM 0-500 psi (0-34.5 bars) pressure recorder for fresh water service -SN 0-1,000 psi (0-69 bars) pressure recorder for fresh water service NOTE: Firetrol Brand Jockey Pump controllers DO NOT CONTAIN MERCURY filled pressure switches. -SP 0-300 psi (0-20.7 bars) pressure recorder for sea water/foam service -SR 0-500 psi (0-34.5 bars) pressure recorder for sea water/foam service -SS 0-1,000 psi (0-69 bars) pressure recorder for sea water/foam service Alarms -AC Extra contacts (1 normally open & 1 normally closed) for remote indication, pump operating -AM Contacts for remote indication, pump fail to start -BY Contacts for remote indication, pump overload -BW Contacts for remote indication, pump power failure -BX Contacts for remote indication, phase reversal/ phase failure Miscellaneous -BJ Power ON pilot light -BZ Elapsed time meter -S Tropicalization -R Pump operating pilot light -GZ 50 Hertz operation Dimensions and Shipping Weight (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27518 USA PD500-01 (10-22-08) ©ASCO 2008 Specifications Jockey Pump Controllers The auxiliary jockey pump controller, if required and specified on the plans and specifications, shall be factory assembled, wired, and tested and specifically designed for this type of service. This controller shall be UL listed, and shall be of the same manufacturer as the main fire pump controller. The controller shall incorporate a magnetic starter, control circuit transformer, main disconnect switch, motor fuse block with fuses, HAND-OFFAUTOMATIC selector switch and a pressure switch. The pressure switch shall have a range of 15-290 psi (1-20 bars) and have an adjustable differential range of 15-120 psi (1-8.3 bars). The pressure switch shall be of the diaphragm type utilizing snapaction type contacts. The pressure switch shall be mounted inside the controller to prevent any unauthorized adjustment and/or accidental damage. The pressure switch shall be directly pipe mounted to a bulkhead pipe coupling without any other supporting members. Field connections shall be made externally at the controller coupling to prevent distortion of the pressure switch element and mechanism. The controller shall have a running period timer to prevent too frequent automatic starting of the jockey pump motor. The timer shall be set to keep the motor in operation for at least one minute and interwired with the pressure switch. The disconnect switch shall be mechanically interlocked so that the enclosure door cannot be opened with the handle in the ON position except by • FTA500 a hidden tool operated defeater mechanism. The disconnect switch shall be capable of being padlocked in the OFF position with up to three padlocks for installation and maintenance safety. The minimum enclosure rating shall be NEMA Type 2 (IEC IP11), drip-proof. All pushbuttons, selector switches, pilot lights shall be NEMA Type 12, oiltight. Pilot lights (when specified) shall be transformer type. No pushbuttons or pilot lights shall be mounted on the enclosure door. The control circuit transformer shall be of the molded winding construction type with built-in molded terminals and shall be fuse protected. The fuse shall be built into the transformer. The controller manufacturer, prior to shipment, shall hook up and test the jockey pump controller as a completed assembly. This test shall include, but not be restricted to, each function the controller may be required to perform including manual startstop, automatic start-stop and minimum run timing. The manufacturer shall perform a high potential test of the controller power circuits at not less than two times the rated voltage plus 1000 Volts. The controller shall be a Firetrol brand. (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27512 USA SP500-01 (04-30-07)