Industrial Control Panel Short Circuit Current Ratings Presented by Peter Walsh, PE Rev: PRW 3-19 Overview of SCCR Requirements Introduction Requirements of NEC UL 508a and the NEC Branch and Feeder Analysis Current-Limiting Affects Increasing Panel SCCR 2 Presenter Peter Walsh, PE Senior Field Engineer-Mersen •Member – National Electrical Code Making Panel 4 2008 Cycle •Registered Professional Engineer •Member of Arc Flash & PPE Research Testing Team in Newburyport Lab •Participant in Annual 4-Day IEEE Safety Workshops •Member of NFPA and IEEE IAS, Assoc Member of IAEI •NFPA Technical Committee Member for NFPA 110 and NFPA 111 •IEEE Technical Committee Member for IEEE 1584 and IEEE 1814 3 Codes and Standards are Changing NEC® 409 – National Electrical Code – New article beginning in the 2005 NEC that covers “Industrial Control Panels” and requires panels to be clearly Marked with a Short Circuit Current Rating (SCCR). 4 5 Why the New Requirements? Why the New Requirements? - Safety People were not understanding equipment Ratings, and People were not applying Panels safely. 6 National Electrical Code Requirements Overview of National Electrical Code NEC 90.3 Code Arrangement-Chapters 1-4 apply generally. 90.4 Enforcement-The Authority Having Jurisdiction (AHD) has responsibility for enforcement and interpretation. 90.7 Examination of Equipment for Safety- Listed equipment is only examined to detect field modifications or damage 7 National Electrical Code Requirements NEC 100 (Definitions) Listed-Equipment that has been investigated and found safe for specific conditions by a nationally recognized testing firm which performs periodic inspections of production products and labels the listed products. 8 National Electrical Code Requirements NEC 110.3(A)(1) Examination. Identification, Installation, and use of Equipment. – (A) Examination-In judging equipment, considerations such as the following shall be evaluated: • (1) Suitability for installation and use with conformity with the provisions of this code FPN-Suitability of equipment may be evidenced by listing or labeling 9 National Electrical Code Requirements NEC 110.10 (Paraphrased)-The overcurrent devices and downstream components shall be selected and coordinated to prevent extensive damage. Listed products applied in accordance with their rating shall be considered to meet the requirements of this section. 10 National Electrical Code Requirements NEC 100 (Definitions) Interrupting Rating- The highest current at rated voltage that a device is intended to interrupt under standard test conditions. This Definition was frequently incorrectly used as an panel rating instead of a device rating. 11 Short Circuit 100 A FUSE L SOURCE N Up to 1,000 times rated current! 14 LOAD 15 Definition of SCCR From UL-508A 2.40 SHORT CIRCUIT CURRENT RATING – The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding the defined acceptance criteria. 16 17 NEC and SCCR What are the key references of Short Circuit Current Rating (SCCR) in the National Electrical Code? 18 National Electrical Code Requirements New Section Beginning in 2005 409 Industrial Control Panels – 409.1 Scope- This article covers industrial control panels intended for general use and operating at 600 volts or less. 20 National Electrical Code Requirements 409.110 Marking-An industrial control panel shall be marked with the following information that is plainly visible after installation: – (3) Short circuit current rating (SCCR) of the industrial control panel based on one of the following: 21 National Electrical Code Requirements 409.110(3) Markings-Continued – a. Short-circuit current rating of a listed and labeled assembly – b. Short-circuit current rating established using an approved method – FPN: UL 508A-2001, Supplement SB, is an example of an approved method. 22 National Electrical Code Requirements 670 Industrial Machinery 670.3 Machine Nameplate Data 670.3 (A) Permanent Nameplate 25 National Electrical Code Requirements 670.3(A)(4) Short-circuit current rating (SCCR) of the machine industrial control panel based upon one of the following: – a. Short-circuit current rating of a listed and labeled machine control enclosure or assembly – b. Short-circuit current rating established using an approved method – FPN: UL 508A-2001, Supplement SB, is an example of an approved method. 26 National Electrical Code Revision-2011 409.22 Short-Circuit Current Rating. An industrial panel shall not be installed where the available fault current exceeds its short-circuit current rating as marked in accordance with 670.3(A)(4). 670.5 Short-Circuit Current Rating. Industrial machinery shall not be installed where the available fault current exceeds its short-circuit current rating as marked in accordance with 670.3(A)(4). 27 SCCR Determination? How are Short-Circuit Current Ratings Determined? 28 What Drove The Change UL508A – Industrial Control Panels – Listed panels required the SCCR to be clearly MARKED on the panel effective April 25, 2006. 29 Determining Panel SCCR Let’s look at an example of a panel to determine its SCCR. We’ll consider strategies for increasing panel SCCR. 30 Key Definitions From UL508A Short Circuit Current Rating (SCCR) The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding the defined acceptance criteria. Branch Circuit: – The conductors and components following the last overcurrent protective device protecting a load. Feeder Circuit: – The conductors and circuitry on the supply side of the branch circuit overcurrent protective device. Interrupting Rating (NEC definition) The highest current at rated voltage that a device is intended to interrupt under standard test conditions. 31 Determining Panel SCCR Step 1: Assign a SCCR to each branch circuit. Step 2: Assign a SCCR to the feeder circuit. Step 3: Consider the current-limiting effects of the Feeder OCPD (IF current-limiting). 32 Step 1: Consider Each Branch Step 1: Make a pass of each branch circuit to determine the SCCR value of each branch circuit in the panel. – A) Check each component for SCCR markings: • • If marked - use that value If not marked - check instruction sheets provided with component to determine if there is a value assigned and under what conditions. – B) If no SCCR value is marked on the component or on instruction / installation sheets: • Refer to Table SB4.1 to determine the default SCCR for the component. – C) Check if “type testing” was done for a motor controller per UL 508 for high fault currents. • The tested value may be used as the SCCR. 33 UL 508A Supplement SB4.1 34 60A Class J-TD What is the SCCR of this panel? 15A Fuse FSPDB Size 2A 175A 20A MCCB 15A Contactor Overload Relay 35 Integral Motor Controller 15A Fuse 15A Contactor Overload Relay Step 1: consider each branch circuit. First Pass – Branch 1 15A Fuse 60A Class J-TD FSPDB Size 2A 175A 20A MCCB 15A Fuse 200KA SCCR Marked on Product 15A Contactor 10KA Overload Relay 10KA 36 Integral Motor Controller 15A Contactor Overload Relay Step 1: consider each branch circuit. First Pass – Branch 1 60A Class J-TD FSPDB Size 2A 175A Branch 1 SCCR 10KA 15A Fuse 20A MCCB 15A Fuse 200KA SCCR Marked on Product 15A Contactor 10KA Overload Relay 10KA 37 Integral Motor Controller 15A Contactor Overload Relay Step 1: consider each branch circuit. Branch 1 SCCR 10KA First Pass – Branch 2 15A Fuse 60A Class J-TD FSPDB Size 2A 175A 20A MCCB 200KA 15A Fuse 65KA SCCR Marked on Product 15A Contactor 10KA Overload Relay 10KA 38 Integral Motor Controller 15A Contactor 10KA Overload Relay 60A Class J-TD Step 1: consider each branch circuit. Branch 1 SCCR 10KA First Pass – Branch 2 Branch 2 SCCR 10KA 15A Fuse 200KA FSPDB Size 2A 175A 20A MCCB 15A Fuse 65KA SCCR Marked on Product 15A Contactor 10KA Overload Relay 10KA 39 Integral Motor Controller 15A Contactor 10KA Overload Relay 60A Class J-TD Step 1: consider each branch circuit. FSPDB Size 2A 175A Branch 1 SCCR 10KA Branch 2 SCCR 10KA 15A Fuse 200KA First Pass – Branch 3 20A MCCB 15A Fuse 65KA 200KA SCCR Not Marked on Product 15A Contactor 10KA Overload Relay 10KA 40 Integral Motor Controller 15A Contactor ? 10KA Overload Relay ? UL 508A Supplement SB4.1 41 60A Class J-TD Step 1: consider each branch circuit. FSPDB Size 2A 175A Branch 1 SCCR 10KA Branch 2 SCCR 10KA 15A Fuse 200KA First Pass – Branch 3 20A MCCB 15A Fuse 65KA 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 42 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA 60A Class J-TD Step 1: consider each branch circuit. FSPDB Size 2A 175A Branch 1 SCCR 10KA Branch 2 SCCR 10KA 15A Fuse 200KA First Pass – Branch 3 20A MCCB 65KA Branch 3 SCCR 5KA 15A Fuse 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 43 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA Step 2: Consider Feeder Circuit Step 2: Make a pass of the feeder circuit and determine the SCCR of the feeder circuit. 44 Step 2: what’s the SCCR of the feeder circuit ? Second Pass – Feeder 15A Fuse 60A Class J-TD FSPDB Size 2A 175A 200KA ? 20A MCCB 200KA 15A Contactor 10KA Overload Relay 10KA 45 SCCR Not Marked on Product 15A Fuse 65KA Integral Motor Controller 200KA 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA Step 2: what’s the SCCR of the feeder circuit ? Second Pass – Feeder 15A Fuse 60A Class J-TD FSPDB Size 2A 175A 200KA 100KA 20A MCCB 200KA 15A Contactor 10KA Overload Relay 10KA 46 65KA Integral Motor Controller From Table SB4.1 the default SCCR is 10KA unless Tested 15A Fuse 200KA 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA FSPDB Ratings FSPDB Ratings 47 FSPDB Ratings 48 Step 2: what’s the SCCR of the feeder circuit ? Second Pass – Feeder 15A Fuse 60A Class J-TD FSPDB Size 2A 175A 200KA 100KA 20A MCCB 200KA 15A Contactor 10KA Overload Relay 10KA 49 Feeder SCCR 100KA 15A Fuse 65KA Integral Motor Controller 200KA 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA Feeder & Branch SCCRs after Step 2. Branch 1 SCCR 10KA Branch 2 SCCR 10KA 15A Fuse 200KA 60A Class J-TD FSPDB Size 2A 175A 200KA Feeder SCCR 100KA 100KA Branch 3 SCCR 5KA 20A MCCB 65KA 15A Fuse 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 50 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA Step 3: Effects of Feeder OCPD Step 3: Consider the current-limiting effects of the feeder OCPD. – If a FUSE, refer to Table SB4.2 to determine the Ip for the fuse and compare the Ip to the SCCR for each branch component. • If the Ip is equal to or lower than each downstream component, then you are allowed to mark the panel with the SCCR value for the appropriate Ip column (50kA, 100kA or 200kA). But the Ip is not allowed to increase the SCCR value of the downstream fuse or circuit breaker, just the SCCR value of other components. – If a circuit breaker, and if labeled “Current-limiting” , the CB manufacturer’s published Ip curves may be used to determine CB Ip. 51 Fuse Basics - Ip FAULT CURRENT WITHOUT FUSE IN CIRCUIT NORMAL LOAD CURRENT 52 FUSE OPERATION Fuse Basics - Ip (IRMS )2 t ~ Thermal Energy Ip MELTING TIME ARCING TIME CLEARING TIME 53 Step 3: If current-limiting, consider feeder OCPD effects From Table SB4.2 (100KA): Ip = 10KA Branch 1 SCCR 10KA Branch 2 SCCR 10KA 15A Fuse 200KA 60A Class J-TD FSPDB Size 2A 175A 200KA Feeder SCCR 100KA 100KA Branch 3 SCCR 5KA 20A MCCB 15A Fuse 65KA 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 54 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA UL 508A Supplement SB Updates 55 60A Class J-TD Step 3: Feeder OCPD effects on branch #1 From Table SB4.2 (100KA): Ip = 10KA Branch Branch11SCCR increases from 10KA to SCCR 100KA 100KA Branch 2 SCCR 10KA 15A Fuse 200KA FSPDB Size 2A 175A 200KA 100KA Branch 3 SCCR 5KA 20A MCCB 65KA 15A Fuse 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 56 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA Step 3: Feeder OCPD effects on branch #2 Ip = 10KA allows increase in SCCR of Branch 2 Branch 1 SCCR 100KA Branch 2 SCCR increases from 10KA to 65KA 15A Fuse 200KA 60A Class J-TD FSPDB Size 2A 175A 200KA Feeder SCCR 100KA 100KA Branch 3 SCCR 5KA 20A MCCB 65KA 15A Fuse 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 57 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA 60A Class J-TD Step 3: Feeder OCPD effects on branch 3 From Table SB4.2 (100KA): Ip = 10KA Branch 1 SCCR 100KA Branch 2 SCCR 65KA 15A Fuse 200KA FSPDB Size 2A 175A 200KA Feeder SCCR 100KA 100KA Branch 3 SCCR remains 5KA 20A MCCB 65KA 15A Fuse 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 58 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA Question: What’s the panel SCCR? Answer: 5KA due to branch 3 Branch 1 SCCR 100KA Branch 2 SCCR 65KA 15A Fuse 200KA 60A Class J-TD FSPDB Size 2A 175A 200KA Feeder SCCR 100KA 100KA Branch 3 SCCR remains 5KA 20A MCCB 65KA 15A Fuse 200KA Table SB 4.1 15A Contactor 10KA Overload Relay 10KA 59 Integral Motor Controller 15A Contactor SB4.1 5KA 10KA Overload Relay SB4.1 5KA SB4.3 and SB4.4 Require Panel SCCR cannot be higher than the feeder circuit SCCR and cannot be higher than the lowest branch circuit SCCR. This results in this panel being limited to installations with available fault current of less than 5,000A! Most industrial facilities have 20,000 to 65,000 of available fault current. 60 Increasing Panel SCCR Use current-limiting feeder fuses to protect weak components. Upgrade to components with higher SCCR. Add sub-feeder fuses. Consider type tested components, i.e., components that have been tested by the manufacturer under specific conditions and witnessed by UL. 61 How can we increase this panel SCCR ? 1) Upgrade your components in Branch 3 15A CC Fuse 200KA 15A Contactor Originally 5KA Upgraded Overload Relay 62 Upgrade to component with 10KA SCCR How can we increase this panel SCCR ? Option 1) Upgrade your components in Branch 3 FEEDER FUSE: 60A J – TD 10KA Ip @ at 100KA from Table SB4.2 15A CC Fuse 200KA Ip of 60A J fuse at 100KA is equal to or lower than branch rating. Component upgrade allows the branch 3 SCCR to be increased to 100KA after considering effects of 60A feeder fuse. SCCR is now marked on Product 15A Contactor New - 10KA Upgraded Overload Relay New - 10KA 63 How can we increase this panel SCCR ? Option 2) Add a sub feeder fuse in Branch 3 20A CC 200KA Fuse By adding a 20A Class CC fuse as a sub feeder, you are now allowed to use this fuse as your current limiting feeder fuse. 15A CC Fuse 200KA Table SB 4.1 15A Contactor Sub Feeder Fuse 20A Class CC 4KA Ip @ 100KA from Table SB4.2 64 SB4.1 5KA Overload Relay SB4.1 5KA SCCR Not Marked on Product 65 How can we increase this panel SCCR ? Option 2) Add a sub feeder fuse in Branch 3 20A CC 200KA Fuse By adding a 20A Class CC fuse as a sub feeder, you are now allowed to use this fuse as a current limiting feeder fuse. 15A CC Fuse Adding a sub feeder fuse allows the branch 3 SCCR to be increased to - 100KA - 200KA Table SB 4.1 15A Contactor Sub Feeder Fuse 20A Class CC 4KA Ip @ 100KA from Table SB4.2 66 SB4.1 5KA Overload Relay SB4.1 5KA SCCR Not Marked on Product How can we increase this panel SCCR ? Option 3) Use type tested combination components Components that have been tested by the manufacturer under specific conditions and witnessed by UL. 15A CC Fuse 200KA 15A Contactor 5KA Overload Relay 5KA 67 SB4.2.2 c) SB4.2.3 How can we increase this panel SCCR ? 3) Use “type tested” combination components Components that have been tested by the manufacturer under specific conditions and witnessed by UL. 15A CC Fuse 200KA SB4.2.2 c) SB4.2.3 This particular Controller SCCR is 100kA when protected by branch 15A Class CC fuses due UL “type testing” 68 How can we increase this panel SCCR ? Option 3) Use type tested combination components Components that have been tested by the manufacturer under specific conditions and witnessed by UL. It’s a little work to get the information and many combinations have not been tested but it can save some time and money. 15A CC Fuse 200KA Using type tested components allows branch 3 SCCR to be increased to - 100KA - Combination “type test” increased SCCR rating. 100KA 69 Example Supplier Data Sheet Data for A-B 100C09D10 Motor Controller (A) Signifies amp rating of OCPD Data Courtesy Rockwell Automation 70 What’s the short circuit rating of the panel ? Answer: 65KA Branch 1 SCCR 100KA PDB 175A Branch 2 SCCR 65KA 15A Fuse 200KA 60A Class J-TD 200KA Feeder SCCR 100KA 100KA Branch 3 SCCR 100KA 20A MCCB 65KA 15A Fuse 200KA Table SB 4.1 15A Contactor Marked 10KA Overload Relay Marked 10KA 72 Integral Motor Controller Marked 10KA 15A Contactor 100KA type tested Overload Relay 100KA type tested The Control Circuit - SCCR See SB3.2 and SB4.4 For control circuits tapped from the feeder, just provide a branch circuit protective device with an I.R. that is not less than the panel SCCR. The control circuit components are considered protected with the above procedure. Similarly using a control transformer the primary protection I.R. is used for SCCR calculations. Control components are never exposed to the fault current as result of the shorting out of the load current of the panel, therefore they have no SCCR. 73 The Control Circuit - SCCR 74 Power Transformers Power Transformers 5kVA Max – Secondary components must have 2kA SCCR Min – 120 V secondary Max – Must have the primary OCPD with rating at least the same as the panel Power Transformers 10kVA Max – Secondary components must have 5kA SCCR Min – Must have the primary OCPD with rating at least the same as the panel Other Power Transformer circuits must use the lowest rated SCCR component rating of the secondary 75 In summary: How can we increase the panel SCCR ? Select components with high SCCR. 1. – Select components with higher SCCRs marked on them. No markings means using the default values. Use current-limiting fuses to protect weak components. 2. – Feeder or sub-feeder fuse allows you to take advantage of the lower Ip a smaller fuse provides. Consider use of type tested combination components. 3. – Components that have been tested by the manufacturer under specific conditions and witnessed by UL. 76 How Can We Help? Provide COMPONENTS with high SCCR values marked on them. – – – – – USFM - 200kA UltraSafe – 200kA Open style fuse blocks – up to 200kA SurgeTrap – 200kA FS UL-98 disconnects – 50 to 200kA – FSPDBs – 100kA – Open style PDBs – 100kA 77 Instructions allow high SCCR of 100k. Can be directly marked on product. How Can We Help? Provide COMPONENTS with high SCCR values as a result of Special Testing Mersen MPDB protected by a specific Circuit Breaker – Mersen will test popular MPDBs with specific CBs to obtain UL certification – Customer will provide 3 circuit breakers for the testing – Timing is dependent on available lab schedule but is estimated to be about 2 months 78 80 Example 100k SCCR 81 FuserBloc Switch and FSPDB 82 Surge Trap and UltraSafes 83 Summary Significant changes to the 2005 NEC and UL508A require SCCR values to be MARKED on Industrial Control Panels to ensure their safe use in end user installations. – In many industrial facilities 5KA and 10KA SCCRs will not be enough based on the fault levels available. The higher the safer. Methods to achieve higher SCCR values is eased by the use of FUSES. – 50KA is pretty easy to obtain – With a little review 100KA is attainable – 200KA is achievable with properly selected current limiting fuses when using higher rated components. Literature is available at the Mersen Booth and from the EP.Mersen.com website 85 Presented by Peter Walsh, PE 86