White paper Determining short circuit current ratings in industrial control panels Steve Zbytowski Technology Manager-Control Products, ABB Standards documents can be quite intimidating. Often lengthy and written in detailed, technical language, they do not make for particularly enjoyable reading. Little wonder people are seldom eager to dig into a detailed review of standards. Of course these standards aren’t intended to entertain. They contain critical information related to crucial safety practices. Such is the case with UL 508A, the UL Standard for safety for industrial control panels. It includes instructions for calculating a panel’s short circuit current rating (SCCR), but many people clearly have trouble working through that process. Steve Zbytowski, Technology Manager-Control Products, ABB, says he frequently makes presentations on the topic, and they are always packed with people eager to better understand it. “It’s a critical figure to determine,” Zbytowski says. “That number is essential to adequately protecting the people who work on or around power equipment. A panel with an incorrectly calculated SCCR could actually explode or cause an arc flash, with the potential to cause series injury or death, as well as significant damage to the facility.” While people refer to “calculating” the SCCR of a panel, that’s really not accurate because there aren’t any true calculations. It requires only that you investigate the fault capacity of the relevant components and then identify the component with the lowest capacity ... the weakest link in the circuit. The SCCR of that component is the SCCR of the entire panel assembly. This white paper provides a brief background on SCCR, then goes on to detail the process for determining the SCCR of an industrial control panel. What is SCCR? Before 2005, the NEC required industrial machinery electrical panels to be marked only with the interrupting rating of the main overcurrent-protective device. This, however, did not ensure the electrical panel was adequately protected against short circuits. The new standard includes the entire combined power circuit in determining the SCCR requirements. Many people confuse SCCRs with interrupting ratings, but there is big a difference. The interrupting rating pertains only to an overcurrent protective device like a fuse or circuit breaker. It is the maximum current a protective device can safely interrupt. Components and equipment whose function isn’t to interrupt fault currents are rated with SCCRs, when used with a specified current protective device. It is critical that the overcurrent-protective devices and the combination have an adequate interrupting rating for the available short circuit current. In fact, that rating is required by NEC 110.9 which says that the interrupting rating must be equal to or greater than the maximum available fault current. But this alone doesn’t provide adequate protection from damage or injury due to short circuits. Determining a panel’s SCCR Following is more detailed information about each step. Step 1: Determine the short circuit current rating of each component in the power circuit. Circuit protection falls in three categories: − No circuit protection (referred to as non-combination). − Feeder circuit: Similar to power distribution, it the main power entering or within the enclosure. − Branch circuit: A internal starter panel circuit that is protected by a fuse or circuit breaker within the panel. How is the SCCR calculated? There are four steps in the process: Step 1: Determine the short circuit current rating (SCCR) of each component or combination in the power circuit. (SB4.2 in UL 508A) Step 2: Determine whether feeder circuit components limit fault current (SB4.3 in UL 508A) circuit-protective devices, like the fuse. Step 3: Determine overall short circuit current rating for industrial control panel (SB4.4 in UL 508A). Step 4: List the SCCR marking on the control panel nameplate (SB5.1 in UL 508A). The first step is to determine the SCCR of each component or combination, which is usually on the component label or its instruction manual. You don’t need to include the SCCR for power transformers. Another source of SCCR information is the Assumed Maximum Short Circuit Current Rating For Unmarked Components, Table SB4.1 in the UL 508A Standard. This is also referred to as the standard fault. All components must have a standard fault current rating, and it is typically very low. Finally, you can refer to information in manufacturers’ procedures based on ratings from recognized component reports or determined from product testing. The application data for a recognized component can be found on the UL website, in the component’s UL file, or manufacturer’s installation instructions. These components typically must be used with another component to get the desired rating. Feeder-circuit components that modify fault current include: − Power transformers − Current-limiting circuit breakers − Current-limiting fuses You need to locate these parts and include them in your consideration of the SCCR. On the branch circuit, you need to consider transformer ratings. For transformers rated 10kVA or less, the transformer secondary is assigned an available current of 5kA, and all secondary side components in the power circuit must have a SCCR of 5kA or greater. On the primary side, only the primary overcurrent protection is relative to the overall panel SCCR. An example is Class CC fuses used on the primary side of the transformer, which have a SCCR of 100kA. The branch circuits must have a SCCR equal to or higher than the let-through current of the feeder circuit. If they don’t, the overall rating for the panel is the lower rating of the panel or the branch circuit. Step 2: Determine whether feeder circuit components limit fault current. Once you’ve identified the SCCR for the components, the next step is to determine whether feeder-circuit components, specifically circuit-protective devices like fuses, limit the fault current. Circuit breakers must be marked “Current Limiting” to use SB4.3.2. The breaker let-through current will not exceed a defined value. One of two conditions apply: − If the devices on the load side of this breaker have a higher SCCR than the interrupt capacity of the breaker, then you can use the interrupt capacity. These may also be a combination that was tested by the manufacturer or panel shop. − If the devices have a lower SCCR than the interrupt capacity of the circuit breaker, the SCCR for this circuit is the lower value. 2 Determining short circuit current ratings in industrial control panels | ABB white paper The maximum let-through for a circuit breaker is determined by the manufacturer. For fuses it is determined by a standard, allowing you to use a Table SB4, “Peak let through currents, IP and clearing I2T for fuses”. In determining the panel SCCR, the SCCR on the line side of any current-limiting circuit breaker can’t exceed the SCCR of any branch-circuit protection or the interrupt capacity of the circuit breaker. The peak current let-through cannot exceed the SCCR for any branch circuit on the load side. This basically states that the device on the load side of this breaker can withstand the let-through breaker energy and current. Know your panel Most people fear the unknown. When it comes to working with power-control equipment, that’s a prudent approach. The people who buy, operate, and maintain industrial powercontrol panels need to understand their capability to provide protection for their employees and facility from short circuit current. The short circuit current rating provides that key piece of information. Panel makers rely on the steps laid out in the UL 508A standard to calculate/determine the SCCR of their products and provide this information. For fuses, use the values in Table SB4.2 “Peak let-through currents, IP and clearing, I2T for fuses” to get the I2T and IP for the fuse used in the combination circuit. Any fuse with a lower value for both the I2T and IP can be used. If your fuse size is not shown, use the next larger value in the table. Step 3: Determine overall short circuit current rating. With the component research complete, you have the information needed to determine the panel’s SCCR. You do this by determining three different SCCRs. The lowest of the three is the panel SCCR. The three values to determine are: − For each protected branch circuit in the panel, determine the smallest SCCR for the power circuit components on the load side of a branch circuit protective device. (SB4.4.1) − Determine the lowest SCCR of all feeder components. − If current-limiting components are supplied in the feeder circuit, determine the modified SCCR for the feeder component and all branch circuit(s) [from A) above] connected to load side. (SB4.3), see step 2 above. Compare these values from this panel. The SCCR is the lowest of the three. Step 4: List the SCCR marking on the control panel nameplate (SB5.1). The value from step 3 above must be listed on the panel rating or name plate label. The name plate marking must include the SCCR in kAmps rms symmetrical, at the rated voltage. ABB white paper | Determining short circuit current ratings in industrial control panels 3