CCH UX Series LED Exit Signs 10L - crouse

advertisement
10L
NEMA 4X, IP66
UL Listed
Available with Cl. I, Div. 2,
Groups A, B, C, D rating
CCH UX Series
LED Exit Signs
The Cooper Crouse-Hinds CCH UX Series LED Exit Sign combines
the strength and durability of die cast aluminum with architecturallypleasing aesthetics. The CCH UX Series is illuminated by LEDs,
providing the customer with a long-life, low maintenance,
dependable exit sign for use in conditions where reliability is crucial.
Designed for the most severe environments, the CCH UX Series will
provide maximum performance against rain, moisture, cold,
corrosion, and dust in applications such as manufacturing plants,
refineries, petrochemical and chemical plants, waste and sewage
treatment facilities, food processing, and other industrial facilities.
Applications:
• In locations deemed hazardous due to the presence of flammable
vapors or gases
• In areas where the presence of gases or vapors may become
present during an abnormal, unusual, or accidental conditions
• Outdoor and wet applications
• Where required by the National Electrical Code®, Life Safety
Code®, or other applicable codes
10L
Features and Benefits:
• Wet location, outdoor rated for use in the most demanding
environments
• Optional hazardous location rating available
• Dual voltage 120V/277V reduces wiring errors
• Heavy-duty nickel cadmium battery for long life
• 24-hour charge and recharge recovery time increases safety
• Heavy-duty injection molded polycarbonate lens protects against
impact and corrosion
• Brown-out protection protects battery and reduces labor
• Heavy-duty aluminum die cast housing protects against impact
and chemical resistance
• LEDs provide long life, even illumination, and energy savings
• Wide operating temperature range (-45°C to 45°C)
• Self-diagnostic testing reduces costs by eliminating scheduled
equipment verification tests
• Heavy duty nickel cadmium battery for long life meets 90 minute
requirements for battery operated emergency system
NEMA 4X, UL50
UL924 wet location
IP65, IP66
Available with NEC hazardous location rating
- UL844 Class I, Division 2, Groups A, B, C, D
In Inches:
Mounting: wall mount, ceiling mount, end mount
Conduit Entry: top, bottom, or either side of the unit
www.crouse-hinds.com
US: 1-866-764-5454
Temperature Performance Data:
CCH UX Series Exit Sign:
• -45ºC (-49ºF) to 45ºC (113ºF)
CCH UX-HAZ Hazardous Location Exit Sign:
• T6 rating at 45ºC (113ºF)
Electrical Ratings:
• Power Supply
120V/277V dual voltage
• LED Exits - Red
Input Power
120V = 2.7W
277V = 3.2W
• LED Exits - Green
Input Power
120V = 2.3W
277V = 3.0W
Input Current:
(Max.)
120V = .08A
277V = .03A
Ordering Information:
Dimensions
1162
• Provides safe and reliable exit marking both indoors and outdoors
during power failure or interruption of power to normal lighting
system
• Long life (>50K hours) for years of maintenance-free operation
• Energy-efficient for lower cost of operation
• Low temperature operation with no loss of illumination
• Rugged and durable light source for the harshest of environments
Input Current:
(Max.)
120V = .07A
277V = .04A
Certifications and Compliances:
•
•
•
•
Benefits of LED Technology:
CAN: 1-800-265-0502
Catalog Number
Housing Finish
Letter Color
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
CCH
Silver Housing
Silver Housing
Silver Housing
Silver Housing
Silver Housing
White Housing
Black Housing
Silver Housing
White Housing
Black Housing
Silver Housing
White Housing
Black Housing
Silver Housing
White Housing
Black Housing
Red LED
Red LED
Green LED
Green LED
Red LED
Red LED
Red LED
Red LED
Red LED
Red LED
Green LED
Green LED
Green LED
Green LED
Green LED
Green LED
UX70RSDHAZ
UX60RHAZ
UX70GSDHAZ
UX60GHAZ
UX70RSD
UX70RWHSD
UX70RBKSD
UX60R
UX60RWH
UX60RBK
UX70GSD
UX70GWHSD
UX70GBKSD
UX60G
UX60GWH
UX60GBK
Copyright© 2012 Cooper Crouse-Hinds
1154-1155.qxp
5/30/2011
11:16 AM
Page 1155
CPMVFB Emergency
Compact Fluorescent
Cl. I, Div. 2, Groups A, B, C, D
Restricted Breathing Cl. I, Div. 2
& Zone 2 (Suffix S826)
Certified for IEC Zone 2
(Suffix S826TB)
Continuous Operation
Champ-Pak™ Luminaires
Cl. II, Groups E, F, G; Cl. III &
Simultaneous Presence*
Marine & Wet Locations
3, 3R, 4, 4X; IP66
Emergency Lighting
Applications:
Standard Materials:
• Where emergency lighting is required to
permit workers in industrial areas to
safely encounter their surroundings
during power failures
• Where emergency egress lighting is
required, such as: catwalks, walkways,
tunnels, doorways, stairs, stairwells,
ramps and aisles
• Indoor and outdoor wall mounting or
vertical surface mounting where minimal
luminaire depth is required in:
– Manufacturing plants and heavy
industrial facilities
– Industrial process facilities such as
refineries, chemical, petrochemical,
pharmaceutical, and platforms
– Waste or sewage treatment plants
– Offshore, dockside, and harbor
installations
• For security and safety lighting in
industrial facilites for lighting of loading
docks, tunnels, and stairways
• For marine, wet location, hose down,
and corrosive environments
• Luminaire housing and door frame
assembly – copper-free aluminum
• External hardware – stainless steel
• Lens – heat- and impact-resistant
refractor style glass
• Gaskets – silicon rubber
• Reflector – aluminum light sheet
• Wire guard – stainless steel
Features and Benefits:
Certifications and
Compliances:
• NEC/CEC:
Class I, Division 2, Groups A, B, C, D
Class II, Class III & Simultaneous
Presence
(Class I, Division 2 and Class II)
Class I, Zone 2
• IEC:
Zone 2 Ex nR IIC
• UL Standards:
844, 2279 Hazardous (Classified)
Locations
1598 Luminaires
1598A Marine Locations
• CSA Standards:
C22.2 No. 137
• IEC Standards:
60079-15
Standard Finishes:
• Aluminum – Corro-free™ epoxy powder coat
• Stainless steel – natural
Options:
Description
Suffix
Restricted breathing construction.................................................................................
S826
Class I, Division 2 & Zone 2 suitability
Cooler operating temperatures (T-numbers)
Certified for IEC Zone 2 (Suffix S826TB)....................................................................... S826TB
Furnished with:
Terminal Block
Crimp Terminals
Dedicated voltage ballasts (no MT, DT or TT)
Factory assembled with lamp installed.........................................................................
FA
Fused - projects ballast and capacitors against abnormal line conditions..................
S658
(Not for use in Canada)
(Not for Marine use)
Electrical Rating Ranges:
•
•
•
•
52 watts
120–277V, 50–60 Hz
120V, 60 Hz
347V, 60 Hz
About the Battery:
•
•
•
•
•
•
•
•
•
10L
• Unique compact shallow profile design
mounts virtually anywhere
• Side hinged cover with two screw
closing for easy installation and
maintenance
• Gray Corro-free™ epoxy powder coat
two-piece housing provides superior
corrosion resistance
• Unique stainless steel wire guard
accessory attaches without any
additional hardware for easy installation
and maintenance
• Glass refractor provides uniform light
distribution to eliminate glare
• Silicon gaskets make luminaire suitable
for NEMA 4X, marine enviroments
• High power factor ballasts (+90%) are
standard, which allow more luminaires
per circuit
10L
Bodine fluorescent battery pack ballasts are UL component recognized
Sealed, maintenance-free, high temperature nickel cadmium
Solid state chargers are sealed inside the ballast case
90 minute illumination time
10-year life expectancy
2-year full warranty
During auxiliary use 1 lamp has continuous operation
A red indicator light indicates the battery is charging
Wiring instructions for a "Push-to-Test" button is supplied with the fixture
Accessories:
Description
Stainless steel wire guard.............................................................................................
Cat. #
P55
*Consult Cooper Crouse-Hinds.
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1155
1156-1157.qxp
5/30/2011
11:16 AM
Page 1156
CPMVFB Emergency
Compact Fluorescent
10L
Ordering Information
Dimensions & Weights
Continuous Operation
Champ-Pak™ Luminaires
Ordering Information:
Hub Size
Lamp
Watts
Cat. # for use
with ANSI Lamps
/4 NPT
26
CPMVFB2W026
3
Standard Voltage Ballasts
Voltage
Suffix
NEC/UL
120–277V 50–60 Hz
/UNV
CEC/CSA (cUL)
120V/60 Hz
347V 60 Hz
/120CAN
/347
Dimensions
10L
In Inches:
Net Weights:
Luminaire Less Guard
P55 Guard
1156
www.crouse-hinds.com
18.6 lbs.
0.5 lbs.
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1148-1149.qxp
5/30/2011
11:14 AM
Page 1149
Cl. I, Div. 2; Groups A, B, C, D
Restricted Breathing Cl. I,
Div. 2 & Zone 2 (Suffix S826)
Certified for IEC Zone 2
(Suffix S826TB)
DMVF(B) – Exit Sign
Fluorescent Luminaire
Applications:
DMVF(B) Exit Signs are used:
• In any building or enclosed area where
people work
• Where illuminated exit signs are required
• To provide distinct, highly visible exit
markings
• To indicate the direction of travel to exits
• In locations deemed hazardous due to
the presence of flammable vapors or
gases, or combustible dusts
Features:
• Six inch letters on white glass sign panel
make the word "exit" stand out boldly
and clearly
• Housings made of die-cast copper-free
aluminum (less than 0.4 of 1% copper)
for strength and resistance to corrosion
• Mounting module equipped with integral
hub set-screws for vibration resistance
(ceiling and pendant mounts)
• Hubs are provided with an integral
conduit stop and bushing to help prevent
damage to field wiring during installation
• Epoxy powder finish and stainless steel
external hardware for resistance to
corrosion
• Long life gaskets which provide seals
between mounting module, housing, and
globe assembly
• Grounding wire for safety
• Cool operating design
• Optional emergency battery back-up
operation during power outage
About the Battery:
Energy Savings:
• Less wattage used with compact
fluorescent lamps compared to
equivalent incandescent lamps providing
the same light output
10L
Certifications and
Compliances:
• NEC and CEC:
Class I, Division 2, Groups A, B, C, D
Class II, Class III & Simultaneous
Presence
(Class I, Division 2 and Class II)
Class I, Zone 2
• IEC:
Zone 2 Ex nR IIC
• UL Standards:
844, 2279 Hazardous (Classified)
Locations
1598 Luminaires
1598A Marine Luminaires
• CSA Standards:
C22.2 No. 137
• IEC Standards:
60079-15
Standard Materials:
• Ballast housings and mountings – copperfree aluminum (less than 0.4 of 1%)
• Exterior hardware – stainless steel
• Globe – heat- and impact-resistant
internally fluted glass
Standard Finishes:
• Aluminum – gray epoxy powder coat
• Krydon material – high reflectance white
• Stainless steel – natural
Options:
Description
Suffix
Lamps supplied with exit sign...............................................
S714
Top hat with stainless steel threaded insert..........................
S806
Restricted breathing construction..........................................
S826
Class I, Division 2 & Zone 2 suitability
Cooler operating temperatures (T-Numbers)
Certified for IEC Zone 2......................................................... S826TB
Furnished with:
Terminal Block
Crimp Terminals
Dedicated voltage ballasts (no MT, DT or TT)
10L
• Bodine fluorescent battery pack ballasts
are UL component recognized
• Sealed, maintenance-free, high
temperature nickel cadmium
• Solid state chargers are sealed inside the
ballast case
• 90 minute illumination time
• 10-year life expectancy
• 2-year full warranty
• During emergency use 1 lamp has
continuous operation
• A red indicator light indicates the battery
is charging
• Wiring instructions for a "Push-to-Test"
button is supplied with the fixture
Cl. II, Groups E, F, G,
Cl. III & Simultaneous Presence
Marine & Wet Locations
3, 3R, 4X; IP66
Electrical Rating Ranges:
•
•
•
•
52 Watt
120–277V, 50–60 Hz
120V, 60 Hz
347V, 60 Hz
Ordering Information:
Mounting
Type
Supply
Voltage
Volts/Hertz
Fluorescent Cat. #
Pendant
120–277V / 50–60 Hz
120V / 60 Hz (Canada)
347V / 60 Hz
DMVF2C052G/UNV EXD
Ceiling
120–277V / 50–60 Hz
120V / 60 Hz (Canada)
347V / 60 Hz
Wall
120–277V / 50–60 Hz
120V / 60 Hz (Canada)
347V / 60 Hz
DMVF2TW052G/UNV EXD DMVFB2TW052G/UNV EXD
DMVFB2TW052G/120CAN EXD
DMVF2TW052G/347 EXD DMVFB2TW052G/347 EXD
www.crouse-hinds.com
US: 1-866-764-5454
DMVF2A052G/UNV EXD
Fluorescent with
Battery Back-up Cat. #
DMVF2A052G/347 EXD
DMVF2C052G/347 EXD
CAN: 1-800-265-0502
DMVFB2A052G/UNV EXD
DMVFB2A052G/120CAN EXD
DMVFB2A052G/347 EXD
DMVFB2C052G/UNV EXD
DMVFB2C052G/120CAN EXD
DMVFB2C052G/347 EXD
Copyright© 2011 Cooper Crouse-Hinds
1149
1156-1157.qxp
5/30/2011
11:16 AM
Page 1157
Cl. I, Div. 2, Groups A, B, C, D
Restricted Breathing Cl. I,
Div. 2 & Zone 2 (Suffix S826)
Certified for IEC Zone 2
(Suffix S826TB)
DMVFB Emergency
Compact Fluorescent
Continuous Operation
Champ® Luminaires
Applications:
DMVF Series Champ Lighting Luminaires
are used:
• Where emergency lighting is required to
permit workers in industrial areas to
safely encounter their surroundings
during power failures
• Where emergency egress lighting is
required, such as: catwalks, walkways,
tunnels, doorways, stairs, stairwells,
ramps, and aisles
• In areas made hazardous by abnormal
conditions resulting in the presence of
flammable vapors or gases
• In areas made hazardous by the
presence of combustible dusts
• Where combustible dusts and flammable
vapors are present simultaneously
• In marine applications where water spray
and corrosive atmospheres are
considerations
• On installations where vibration and
rough usage are problematic
• Where a cool, efficient light source
is required
• In areas that require lamps to reach full
illumination immediately
• In refineries, chemical and petrochemical
facilities, grain processing, handling or
storage facilities, manufacturing plants,
wastewater treatment plants, sewage
treatment plants, oil terminals, food
processing facilities, breweries, and
any other manufacturing or processing
facility where safe, reliable hazardous
area fluorescent or auxiliary lighting
is needed
• Housings made of die-cast copper-free
aluminum (less than 0.4 of 1% copper)
for strength and resistance to corrosion
• Mounting modules equipped with
integral hub set-screws for vibration
resistance (ceiling, pendant, and quad
mounts)
• Hubs are provided with an integral
conduit stop and bushing to help prevent
damage to field wiring during installation
• Epoxy powder finish and stainless steel
external hardware for resistance to
corrosion
• Long-life gaskets which provide seals
between mounting module, housing,
and optical assembly
• Grounding wire for safety
• Cool operating design
• Optional stainless steel open bottom
guard permits direct access to the globe
for easy relamping
• Battery pack ballast for emergency
lighting
10L
Certifications and
Compliances:
• NEC/CEC:
Class I, Division 2, Groups A, B, C, D
Class II, Class III &
Simultaneous Presence (Class I,
Division 2 and Class II)
Class I, Zone 2
Emergency Lighting
• IEC:
Zone 2 Ex nR IIC
• UL Standards:
844, 2279 Hazardous (Classified)
Locations
1598 Luminaires
1598A Marine Locations
924 Emergency Lighting
• CSA Standards:
C22.2 No. 137
• IEC Standards:
60079-15
Standard Materials:
• Ballast housings and mountings – copperfree aluminum (less than 0.4 of 1%)
• External hardware guards – stainless steel
• Reflectors – Krydon® fiberglassreinforced polyester material
• Globe – heat- and impact-resistant
internally fluted glass
Standard Finishes:
• Aluminum – gray epoxy powder coat
• Krydon material – high reflectance white
• Stainless steel – natural
Options:
Description
Suffix
• Restricted breathing
construction................................
S826
-Class I, Division 2 &
Zone 2 suitability
-Cooler operating temperatures
(T-numbers)
• Certified for IEC Zone 2............. S826TB
-Furnished with:
Terminal Block
Crimp Terminals
• Emergency operation only –
Consult Cooper-Hinds
• Factory assembled with lamp
installed.......................................
FA
• Fused – to protect ballast
against abnormal line conditions
(not for use in Canada) (not for
marine use).................................. S658
• Lamps supplied with luminaire...
S714
• Top hat with stainless steel
threaded insert to attach ballast
housing........................................ S806
• TEFLON® coating on globe for
increased shatter protection.......
S808
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Electrical Rating Ranges:
• 52, 64, and 84 watts
• 120–277V, 50–60 Hz
• 347V, 60 Hz
Accessories:
(Order separately)
Description
Cat. #
Dome
30° Angle
RD739
RA739
10L
Standard Features:
Cl. II, Groups E, F, G; Cl. III &
Simultaneous Presence
Marine & Wet Locations
3, 3R, 4, 4X; IP66
Emergency Lighting
Energy Savings
• Less wattage used with compact
fluorescent lamps compared to
equivalent incandescent lamps
providing the same light output
About the Battery
(DMVFB Units):
• Bodine fluorescent battery pack ballasts
are UL component recognized
• Sealed, maintenance-free, high
temperature nickel cadmium
• Solid state chargers are sealed inside
the ballast case
• 90 minute illumination time
• 10-year life expectancy
• 2-year full warranty
• During auxiliary use 1 lamp has
continuous operation
• A red indicator light indicates the battery
is charging
• Wiring instructions for a "Push-to-Test"
button is supplied with the fixture
Copyright© 2011 Cooper Crouse-Hinds
1157
1158-1159.qxp
10L
5/30/2011
11:17 AM
Page 1158
DMVFB Emergency
Compact Fluorescent
Cl. I, Div. 2, Groups A, B, C, D
Restricted Breathing Cl. I,
Div. 2 & Zone 2 (Suffix S826)
Certified for IEC Zone 2
(Suffix S826TB)
Continuous Operation
Champ® Luminaires
Mounting
Style
Pendant Mount
DMVFB Series
Fluorescent with Battery
Back-Up with G303 Globe
and P33 Guard
Cat. #
DMVFB2A052GP
DMVFB3A052GP
DMVFB2A064GP
DMVFB3A064GP
DMVFB2A084GP
DMVFB3A084GP
/4
1
3
/4
1
3
/4
1
52
/4
/4
3
/4
52
64
84
DMVFB2HA052GP
DMVFB2HA064GP
DMVFB2HA084GP
/4
1
3
/4
1
3
/4
1
52
DMVFB2C052GP
DMVFB3C052GP
DMVFB2C064GP
DMVFB3C064GP
DMVFB2C084GP
DMVFB3C084GP
/4
1
3
/4
1
3
/4
1
52
Quad-Mount
Pendant, Adjustable
Thru-Feed, 25° Angle,
121/ 2° Angle
3
/4
/4
3
/4
52
64
84
DMVFB25Q052GP
DMVFB25Q064GP
DMVFB25Q084GP
Stanchion Mount
25° Angle
11/2
11/2
11/2
52
64
84
DMVFBJ052GP
DMVFBJ064GP
DMVFBJ084GP
Stanchion Mount
Straight
11/ 2
11/ 2
11/ 2
52
64
84
DMVFBP052GP
DMVFBP064GP
DMVFBP084GP
3
Flexible Pendant
Mount
3
Ceiling Mount
Thru-Feed
3
Wall Mount
Thru-Feed
10L
Hub
Lamp
Size (In.) Watts
64
84
3
64
84
3
64
84
3
DMVFB2TW052GP
DMVFB3TW052GP
DMVFB2TW064GP
DMVFB3TW064GP
DMVFB2TW084GP
DMVFB3TW084GP
Note: For technical information on family
trees, temperature performance data,
dimensions, weights, and photometrics,
refer to Series in Section 6L.
1. Catalog numbers are basic numbers. Voltage must be specified.
Standard Voltage Ballasts
NEC/UL
1. Voltage
Suffix
1158
CEC/CSA (cUL)
120–277V 50–60 Hz
/UNV
www.crouse-hinds.com
US: 1-866-764-5454
Cl. II, Groups E, F, G; Cl. III &
Simultaneous Presence
Marine & Wet Locations
3, 3R, 4, 4X; IP66
Emergency Lighting
120V/60 Hz
/120CAN
CAN: 1-800-265-0502
347V 60 Hz
/347
Copyright© 2011 Cooper Crouse-Hinds
1148-1149.qxp
10L
5/30/2011
11:14 AM
Page 1148
EVLPF(B) – Exit Sign
Fluorescent Luminaire
Applications:
EVLPF(B)-EXD Exit Signs are used:
• In any building or enclosed area where
people work – where illuminated exit
signs are required
• To provide distinct, highly visible exit
marking
• To indicate the direction of travel to exits
• In locations deemed hazardous due to
the presence of flammable vapors,
gases, or combustible dusts
Features and Benefits:
• Six inch red letters on white glass sign
panel make the word "EXIT" stand out
boldly and clearly
• Lightweight copper-free aluminum
housing with powdered epoxy finish
• All exterior hardware is corrosionresistant stainless steel
• Three mounting arrangements: pendant,
ceiling, and wall bracket
• Integral ballast
• High power factor (90%+) ballasts
• Easier assembly, installation, and
maintenance
• Outdoor, hose down, marine and
corrosive environments suitable
• Ideal for adverse environments typical of
industrial facilities
• Ground wire for safety
• Optional battery back-up for operation
during power outage
Cl. I, Div. 1, Groups B (suffix GB), C, D
Cl. I, Zone 1, Groups IIB + H2
(GB suffix), IIB
Cl. II, Div. 1, Groups E, F, G; Class III,
Simultaneous Presence
Marine & Wet
Locations
3, 3R, 4, 4X;
IP66
Certifications and
Compliances:
• NEC and CEC:
Class I, Division 1, Groups B (GB
suffix), C, D
Class I, Zone 1, Groups IIB + H2 (GB
Suffix), IIB, IIA
Class II, Class III & Simultaneous
Presence (Class I and Class II)
• UL Standards:
844 Hazardous (Classified) Locations
1598 Luminaires
1598A Marine Locations
• CSA Standards:
C22.2 No. 137
Standard Materials:
• Mounting modules, cover, ballast
housing, globe holder – copper-free
aluminum
• Globe – heat- and impact-resistant glass
• Exterior hardware – stainless steel
Ratings (Electrical/Size):
Sources/wattage:
• 52W (2-26W lamps)
• 120-277V, 50-60 Hz
• 120V, 60 Hz
• 347V, 60 Hz
Conduit entries:
• 3/4", 1" NPT – pendant, wall bracket,
ceiling
Standard Finishes:
• Copper-free aluminum – Corro-free™
powdered epoxy
Options:
Description
Group B suitability
Factory assembled with lamps
Suffix
GB
FA
10L
About the Battery:
• Bodine fluorescent battery pack ballasts
are UL component recognized
• Sealed, maintenance-free, high
temperature nickel cadmium
• Solid state chargers are sealed inside
the ballast case
• 90 minute illumination time
• 10-year life expectancy
• 2-year full warranty
• During emergency use 1 lamp has
continuous operation
• Red indicator light indicates the battery
is charging
• Wiring instructions for a "Push-to-Test"
button is supplied with the luminaire
Ordering Information:
Supply
Mounting Voltage
Type
Volts/Hertz
Fluorescent Cat. #
Pendant
120–277V / 50–60 Hz EVLPFA02520/UNV EXD EVLPFBA02520/UNV EXD
120V / 60 Hz (Canada)
EVLPFBA02520/120CAN EXD
347V / 60 Hz
EVLPFA02520/347 EXD EVLPFBA02520/347 EXD
Ceiling
120–277V / 50–60 Hz EVLPFCX02520/UNV EXD EVLPFBCX02520/UNV EXD
120V / 60 Hz (Canada)
EVLPFBCX02520/120CAN EXD
347V / 60 Hz
EVLPFCX02520/347 EXD EVLPFBCX02520/347 EXD
Wall
120–277V / 50–60 Hz EVLPFBX02520/UNV EXD EVLPFBBX02520/UNV EXD
120V / 60 Hz (Canada)
EVLPFBBX02520/120CAN EXD
347V / 60 Hz
EVLPFBX02520/347 EXD EVLPFBBX02520/347 EXD
Energy Savings:
• Less wattage used with compact
fluorescent lamps compared to
equivalent incandescent lamps providing
the same light output
1148
www.crouse-hinds.com
Fluorescent with
Battery Back-up Cat. #
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1158-1159.qxp
5/30/2011
11:17 AM
Page 1159
Cl. I, Div. 1, Groups B
(GB Suffix), C, D
Cl. I, Zone 1, Groups IIB + H2
(GB suffix), IIB, IIA
Cl. II, Div. 1, Groups E, F, G; Class III,
Simultaneous Presence
EVLPFB Emergency
Compact Fluorescent
Continuous Operation
Low Profile Luminaires
Marine & Wet
Locations
3, 3R, 4, 4X; IP66
Emergency Lighting
10L
Applications:
Cooper Crouse-Hinds Low Profile
Hazard•Gard® Luminaires are used in:
• Areas that require lamps to reach full
lumination immediately
• Where emergency lighting is required to
permit workers in industrial areas to
safely encounter their surroundings
during power failures
• Where emergency lighting is required
such as: catwalks, walkways, tunnels,
doorways, stairs, stairwells, ramps, and
aisles
• Areas where flammable or explosive
vapors or gases are present
• Hazardous areas, both indoors and
outdoors, where long life and low
maintenance costs are desired
• Petroleum refineries, chemical,
petrochemical and pharmaceutical
plants, oil terminals, gas plants and
other heavy process industry facilities
• Waste treatment facilities
• Drilling platforms and other coastal and
offshore hazardous areas
Features and Benefits:
Certifications and
Compliances:
• NEC/CEC:
Class I, Division 1, Groups B
(with GB suffix), C, D
Class I, Zone 1, Groups IIB + H2
(GB Suffix), IIB, IIA
Class II, Class III & Simultaneous
Presence
(Class I and Class II)
Emergency Lighting
• UL Standards:
844 Hazardous (Classified) Locations
1598 Luminaires
1598A Marine Locations
924 Emergency Lighting
• CSA Standards:
C22.2 No. 137
Ratings (Electrical/Size):
• Mounting modules, cover, ballast
housing, globe holder – copper-free
aluminum
• Globe – heat- and impact-resistant glass
• Exterior hardware – stainless steel
• Reflectors (dome & angle) – Krydon®
fiberglass-reinforced polyester
Sources/Wattage:
• Fluorescent continuous operation
emergency lighting 52W (2-26W lamps)
and 64W (2-32W lamps) compact
fluorescent voltages
• Fluorescent emergency lighting
120–277V, 50–60 Hz
120V, 60 Hz
347V 60Hz
Conduit entries:
• 3/4", 1" NPT – pendant, wall bracket,
ceiling
• 11/4" NPT – stanchion
Standard Finishes:
• Copper-free aluminum – Corro-free™
powdered epoxy
• Krydon – white
• Stainless steel guard
Energy Savings
• Less wattage used with compact
fluorescent lamps compared to
equivalent incandescent lamps providing
the same light output
Options:
Description
Group B suitability
Fused (not for use in Canada) (not for marine use)
Factory assembled with lamps
Emergency operation only – Consult Cooper Crouse-Hinds
Suffix
GB
S658*
FA
10L
• Small, compact size
• Two start Acme threaded construction
• Easier assembly, installation, and
maintenance
• Lightweight copper-free aluminum
housing with powdered epoxy finish
• All exterior hardware is corrosionresistant stainless steel
• Four mounting arrangements: pendant,
ceiling, wall bracket, and stanchion
• Integral ballast
• High power factor (90%+) ballasts
• Uses same mounting modules as the
standard Hazard•Gard®
• Internally fluted glass globes
• Krydon® construction dome and angle
reflectors – won't rust, corrode, dent,
chip, or peel
• Now available in components – luminaire
body, mounting module, guard,
reflectors
• Three wire construction
• For energy conservation, luminaires can
be switched off without affecting the
emergency operation feature
Standard Materials:
*When ordering fuses for luminaires, option S658, you must specify the operating voltage. S658 cannot be
ordered with /MT in the catalog number.
Accessories:
Description
Cat. #
Dome reflector
Angle reflector
RD739
RA739
About the Battery:
• Bodine fluorescent battery pack ballasts are UL component recognized
• Sealed, maintenance-free, high temperature nickel cadmium
• Solid state chargers are sealed inside the ballast case; 90 minute illumination time; 10-year
life expectancy
• 2-year warranty
• During emergency use, 1 lamp has continuous operation
• A red indicator light indicates the battery is charging
• Wiring instructions for a "Push-to-Test" button is supplied with the fixture
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1159
1160-1161.qxp
10L
5/30/2011
11:17 AM
Page 1160
EVLPFB Emergency
Compact Fluorescent
Continuous Operation
Low Profile Luminaires
Cl. I, Div. 1, Groups B (GB Suffix), C, D
Cl. I, Zone 1, Groups IIB + H2
(GB suffix), IIB, IIA
Cl. II, Div. 1, Groups E, F, G; Class III,
Simultaneous Presence
Marine & Wet
Locations
3, 3R, 4, 4X; IP66
Emergency Lighting
Ordering Information:
Pendant Mount
Pendant
Wall Bracket†
Hub
Size With Guard
With Guard
Watt (In.) Cat. #
Cat. #
Fluorescent with Emergency Ballast – High Power
3
/4
EVLPFBA02521 EVLPFBBX02521
EVLPFBA03521 EVLPFBBX03521
52W 1
11/4
3
/4
1
11/4
64W
EVLPFBA02641
EVLPFBA03641
EVLPFBBX02641
EVLPFBBX03641
Ceiling†
Stanchion
With Guard
With Guard
Cat. #
Cat. #
Factor Ballast (Min. P.F. 90%)
EVLPFBCX02521
EVLPFBCX03521
EVLPFBJ04521
EVLPFBCX02641
EVLPFBCX03641
Luminaire
Body
Less
Mounting
Module &
Guard
Cat. #
EVLPFB0520
EVLPFB0640
EVLPFBJ04641
Complete Catalog Numbers as follows:
Standard Voltage Ballasts
NEC/UL
1.
Voltage
Suffix
2.
Wall Bracket Mount†
120–277V 50–60 Hz
/UNV
CEC/CSA (cUL)
120V/60 Hz
/120CAN
347V 60 Hz
/347
Example: EVLPFB02521/UNV
Other Voltages – Consult Cooper Crouse-Hinds
Note: For technical information on family trees, temperature performance data, dimensions,
weights, and photometrics, refer to DMVF Series in Section 6L.
EVFPFB Fluorescent Emergency Lighting
10L
• Three wire construction, for switching purposes, is standard on fluorescent emergency lighting.
• For energy conservation, luminaires can be switched off without affecting the emergency operation
feature.
Ceiling Mount†
*Test switch is remote mounted.
Use Cooper Crouse-Hinds EDSC218 (Not furnished).
Stanchion Mount
†Ceiling and bracket mounts have 4 hubs: 3 are plugged.
1160
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1146-1147.qxp
5/30/2011
10L
11:14 AM
Page 1146
EXL Explosionproof Exit Sign
Cl. I, Div. 1 & 2, Groups C, D
Cl. I, Zone 1 IIB
Cl. II, Div. 1, Groups E, F, G
Factory-sealed
Applications:
Ordering Information:
EXL Exit Signs are used:
• In locations deemed hazardous due to
the presence of flammable vapors or
gases, or combustible dusts
• In any building or enclosed area where
people work – where illuminated exit
signs are required
• To provide distinct, highly visible exit
marking
• To indicate the direction of travel to exits
When ordering an EXL Series Exit Sign,
you will need to specify:
(A) Voltage (120VAC or 120VDC)
(B) Mounting (Wall, End Bracket, or
Pendant)
(C) Exit Sign Designation
All units come standard with 3/4" hubs and
exit signs with red lettering and white
background. Complete catalog numbering
is as follows:
Lamp Wattage:
EXL (A) 2 (B) (C)
(A) Voltage: 120VAC ............ leave blank
120VDC .......................... D
(B) Mounting: Wall................................. 1
End Bracket.................... 2
Pendant .......................... 3
(C) Exit Sign Designation:
A
Single Face (Wall Mount)
AA
Double Face (End Bracket
& Pendant)
AB
Double Face, one side
arrowhead right, the other
no arrowhead (End Bracket
& Pendant)
AC
Double Face, one side
arrowhead left, the other no
arrowheads (End Bracket &
Pendant)
AD
Double Face, one side
arrowhead both ends, the
other no arrowheads (End
Bracket & Pendant)
B
Single Face, arrowhead
right (Wall Mount)
BC
Double Face, one side
arrowhead right, the other
arrowhead left (End Bracket
& Pendant)
BD
Double Face, one side
arrowhead both ends, the
other arrowhead right (End
Bracket & Pendant)
C
Single Face, arrowhead left
(Wall Mount)
CD
Double Face, one side
arrowhead both ends, the
other arrowhead left (End
Bracket & Pendant)
D
Single Face, arrowhead
both ends (Wall Mount)
DD
Double Face, both sides
arrowhead both ends (End
Bracket & Pendant)
• Two 60 watt, 60T10 clear lamps for AC units
• Two 25 watt, 25T10 clear lamps for DC units
• Lamps not included with luminaire
Mounting
Type
Sign Panel
Description
Hub
Size (In.)
AC
Cat. #
DC
Cat. #
Wall
End Bracket
Pendant
Single face
Double face
Double face
3
Electrical Ratings:
/4
/4
3
/4
EXL21A
EXL22AA
EXL23AA
EXLD21A
EXLD22AA
EXLD23AA
Features:
• Two incandescent lamps (not included)
wired in parallel – to provide extra
margin of light source reliability
• Solid state circuit for extended lamp life
in AC units
• Six inch red letters on white acrylic sign
panel make word "exit" stand out boldly
and clearly
• Edge lighting characteristic of sign panel
makes visibility excellent at all lighting
levels
• Factory-sealed explosionproof housing
• Pendant, wall, and end bracket mounts
provide universal installation options
• Impact-resistant acrylic sign panel needs
no guard – makes cleaning easy
• Internal rectifier extends lamp life
beyond 1,000-hour rated life – reduces
relamping cost
• Relamping tool provided
10L
Certifications and
Compliances:
• NEC:
Class I, Groups C, D
Class II, Groups E, F, G
• UL Standard: 844
• NFPA Life Safety Code No. 101-1991
Standard Materials:
• Body – copper-free aluminum
• Sign panel – acrylic
Conduit Entrance:
• 3/4" hubs
• 120VDC or 120VAC operation
Temperature Performance
Data:
(for both AC & DC operation):
Ambient
Temp. (°C)
25
40
1146
Class I (C, D)
Class II (E, F, G)
Supply
Wire °C
T3C
T3C
150°C
www.crouse-hinds.com
Pendant Style
End Bracket Style
Wall Style
3
Options:
Description
Suffix
Exit signs with green lettering on white background........................................................
GN
Unit provided with epoxy powder coat............................................................................. S752
277VAC – (Order ECT413 Transformer Separately)
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1146-1147.qxp
5/30/2011
11:14 AM
Page 1147
EXL Explosionproof Exit Sign
10L
Factory-sealed
Dimensions
Dimensions
In Inches:
Wall Style
Pendant Style
10L
End Bracket Style
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1147
Ex-Lite LED Exit Signs
Cl. I, Div. 2, Groups A, B, C, D
Cl. I, Zone 1, AEx em ib IIC (NEC)
Cl. I, Zone 1, Ex em ib IIC (CEC)
Cl. II, Div. 2, Groups F, G (NEC)
Cl. II, Div. 2, Groups E, F, G (CEC)
10L
UL Listed
IP66
The Ex-Lite Series of LED exit signs are
designed for hazardous locations and are
ideally suited for marking escape routes
and exits in potentially explosive
atmospheres.
The Ex-Lite Z is available as an AC only
version, while the Ex-Lite ZE is available
with self-contained battery. As an
emergency lighting luminaire with selfcontained battery system, the Ex-Lite ZE
features a nickel cadmium battery with
automatic test and monitoring feature.
Applications:
• In harsh and hazardous environments
where illuminated exit signs are required
Features and Benefits:
Ordering Information:
Catalog Number
Material Number
Description
Ex Lite Z
12191001005
AC/DC Exit Sign
Ex Lite ZE
12191130005
with Battery
Light Source
Life of LED
Rated Voltage, VAC
Frequency, Hz
Rated Voltage, DC
Power Consumption
Battery
LED
50K hours
120V-277V
50/60
110V-250V
6VA
N/A
-4ºF to 122ºF
(-20ºC to 50ºC)
Wall
Ex-e
3
/4"
IP66
LED
50K hours
120V-277V
50/60
110V-250V
6VA
NiCad
41ºF to 95ºF
(5ºC to 35ºC)*
Wall
Ex-e
3
/4"
IP66
Allowable Temperature Range
Mounting
Cable Entry
Conduit Entry
Protection
10L
LED Technology:
• Long life (>50K hours) for years of
maintenance-free operation
• Energy-efficient for lower cost of
operation
• Low temperature operation with no loss
of illumination
• Rugged and durable light source for the
harshest of environments
Exit Sign System:
• Can be used in a hazardous location
• Conduit or cable entry
• Can be installed in moist, humid, rain,
and wet environments
• Universal input voltage 110VAC-277VAC
and 110VDC-250VDC reduces inventory
• Ex-Lite ZE with self-monitoring, selfdiagnostic, and test capability
• Premium heavy-duty nickel cadmium
battery
• 24-hour charge and recharge time
increases safety by recovering quickly
from outage
• "EXIT" legend with alternative wings left, right, or left and right; simple field
modification
• Emergency lighting cycle three hours
• The housing of the luminaire is
constructed with a corrosion resistant,
robust, lightweight aluminum alloy
material and illumination of the sign is
provided with red, high-efficient LEDs
*Due to battery chemistry, the charging capacity will be limited at temperatures below 5ºC and above 35ºC.
Dimensions
In (mm):
Certifications and
Compliances:
•
•
•
•
•
•
•
•
•
•
Class I, Division 2, Groups A, B, C, D
Class I, Zone 1, AEx em ib IIC (NEC)
Class I, Zone 1, Ex em ib IIC (CEC)
Class II, Division 2, Groups F, G (NEC)
Class II, Division 2, Groups E, F, G
(CEC)
IP66
UL844
UL924/CSA22.2 No. 141-02
UL60079/CSA22.2 E60079
UL1203/CSA22.2 E6124-1-1-02
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2012 Cooper Crouse-Hinds
1161
1150-1151.qxp
5/30/2011
10L
11:15 AM
Page 1150
ELPS Light-Pak™
Emergency Lighting
System
Applications:
ELPS Series Emergency Lighting Systems
are used:
• To provide safe, reliable illumination
indoors or outdoors to designated areas
during failure or interruption of power to
the normal lighting system
• In areas made hazardous by the
presence of flammable gases and
vapors, combustible dusts, or easily
ignitible fibers and flyings
• In areas where corrosion, vibration,
moisture, dirt, and rough usage may be
encountered
• Where required by the National Electrical
Code®, the Life Safety Code, or other
codes
• In refineries, chemical and petrochemical
facilities, grain processing, handling or
storage facilities, manufacturing plants,
wastewater treatment facilities, and
other areas where safe, reliable,
hazardous area emergency lighting is
needed
10L
Features:
• Compact factory-sealed luminaire
assemblies are each furnished with a 12
watt tungsten-halogen lamp and inner
reflector for appropriate photometrics in
hazardous areas
• Luminaire assemblies are fully adjustable
and lockable on two axes to provide
flexible and consistent light aiming
capabilities
• Luminaire lens ring is threaded for easy
relamping and locks in place with hex
head set-screw; will not loosen due to
vibration
• Ground joint cover with external flange
design permits large opening and easy
access to internal components; stud
bolts in diagonally opposite corners of
body ease cover removal and installation
• Neoprene cover gasket seals out
moisture for superior protection of
internal components against wetness
and corrosion
• Lightweight, compact size, and
mounting feet ease installation and allow
placement in confined areas
• Two 1" NPT drilled and tapped conduit
openings, with plugs, are standard, for
choice of top or bottom feed
• Factory-installed PUSH-TO-TEST
pushbutton enables easy testing of
system
• MAIN POWER ON pilot light indicates
AC power is being supplied to the
battery charger; pilot light jewel is
threaded for easy lamp replacement
• Stainless steel drain minimizes moisture
collection; stainless steel breather with
aluminum cap provides ventilation,
minimizes moisture collection
Cl. I, Div. 1 & 2, Groups C, D
Cl. I, Div. 1 & 2, Groups B, C, D
(with suffix GB)
Cl. II, Div. 1, Groups E, F, G
Cl. III
• CID 101 corrosion inhibitor device is
provided with each ELPS system to help
protect electrical components and
connections
• Rugged, long-life, maintenance-free,
nickel cadmium battery provides 30
watts of power for the required 11/2 hours
• Solid state battery charger for long life
and reliable service prevents deep
discharge by automatically
disconnecting luminaires from battery
• Terminal block facilitates field wiring
connections
• Instruction sheet and maintenance
record card provided with unit in a
protective plastic envelope
• A time delay is standard; time delay is
preset at factory for 5 minute delay but
can be field set for 5 seconds or 15
minutes, thus allowing HID type lamps
time to restrike and reach desired
illumination levels
• Solid state battery charger will accept
120, 220/240 or 277 VAC, 50/60 Hz
Certifications and
Compliances:
• NEC:
Class I, Groups B, C, D
Class II, Groups E, F, G
Class III
Simultaneous Presence
• NEMA: 3R, 12 (ELPS power supply)
• Suitable for wet locations (EVLA fixtures)
• Marine (EVLA fixtures)
• UL Standard:
844 – Electric Luminaire – Hazardous
Locations
924 – Emergency Lighting and Power
Equipment
1203 – Explosionproof and DustIgnitionproof Electrical Equipment
• Life Safety Code:
Section 5-9 (Emergency Lighting)
• Suitable for Wet Locations
• NEMA 3, 3R, 12
• Marine
Standard Materials:
• Power supply enclosure and luminaire
assembly – copper-free aluminum (less
than 0.4 of 1% copper)
Standard Finishes:
• Power supply enclosure and fixture
assemblies – powder coat epoxy paint
finish
Electrical Ratings:
• Power Supply:
Input:
120, 220/240, 277 VAC, 50 or 60 Hz
0.5 Amps Maximum
Output:
12 VDC
UL listed for 28 watts for 11/2 hours at 0° –
40°C
• Luminaires:
Voltage: 12 VDC
Lamp Type: #789, miniature
Tungsten halogen, G4, 2-pin, 14 watt
Options:
Description
Suffix
• Remote mounted lamp head and arm .... EVLA12
• Key operated disconnect switch
as part of the ELPS502
emergency light system .......................... S794
• Keyless operated designated
disconnect switch as part of the
ELPS502 emergency light system .......... S854
Ordering Information:
Description
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Cat. #
• Standard unit with
ELPS502†
adjustable heads............
• Replacement power
interior, includes circuit
ELPS K50
board and battery pack
• Power supply .................
ELPS50†
• Lamphead and arm .......
EVLA12†
• Exit sign, double sided
ELPS502 EXD
with EVI, red letters........
• Exit sign, double sided
ELPS502 EXD GN
with EVI, green letters....
• Exit sign, single or
double sided with
Group B EVA,
ELPS502 EXD GB
red letters.......................
• Exit sign, single or
double sided with
Group B EVA, green
letters ............................. ELPS502 EXD GB GN
• Exit sign, single sided
with EVI, red letters........
ELPS502 EXS
• Exit sign, single
sided with EVI,
green letters ...................
ELPS502 EXS GN
†Base unit comes standard with Class I, Division 1, Group B.
1150
Cl. I, Zone 1
Simultaneous Presence
Wet Locations
NEMA 3, 3R, 12
Copyright© 2011 Cooper Crouse-Hinds
1150-1151.qxp
5/30/2011
11:15 AM
Page 1151
ELPS Light-Pak™
Emergency Lighting System
Temperature Performance Data
Photometric Data
Dimensions and Weights
Temperature Performance Data:
Cat. #
Class
Maximum Ambient Temperature 55°C
I
II*
EVLA12
III*
10L
Photometric Data:
T-number
T4A
T3B
T3B
Maximum Ambient Temperature 40°C
ELPS EVI
ELPS EVA
T3C
T4
T3C
T4
*For Class II and Class III applications, fixtures must not be aimed more than 30° above
horizontal (see diagram below).
Dimensions
In Inches:
10L
Unit Net Weights:
• ELPS502 complete emergency lighting system – 50 lbs.
• ELPS50 power supply – 40 lbs.
• EVLA12 luminaire assembly – 5 lbs.
Status Indication:
LED Status
Condition
No light
Meaning of the Indication
AC power is removed from the circuit
•
Steady light (no blinking)
Fully charged
•
Light blinks once
Charging
••
Light blinks twice
Battery failure
Light blinks three times
Light blinks four times
Circuit failure
Lamp failure
•••
••••
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1151
10L
LED N2LPS LIGHT-PAK™
Emergency Lighting System
Applications:
LED N2LPS Light-Pak™ emergency lighting
systems are used:
• To provide reliable illumination for
egress areas during failure or
interruption of power to the normal
lighting system
• In areas where flammable gases or
vapors may become present due to
abnormal, unusual, or accidental
conditions
• In manufacturing plants, refineries,
petrochemical and chemical plants,
waste and sewage treatment facilities,
oil terminals, food processing facilities,
breweries, and other industrial
manufacturing or process industry
facilities subject to wet or corrosive
conditions
• To illuminate machinery or panels during
a loss of AC power
• Where moisture, dirt, dust, or corrosion
will limit the life and reliability of ordinary
emergency lighting systems
• Where required by the National
Electrical Code®, the Life Safety Code®
or other applicable codes
• Outdoor applications
10L
Features:
• Compact, factory-assembled luminaire
featuring LED lamps for improved lumen
performance, on-time, and lamp life
• Nonmetallic, enclosed, and gasketed
housing provides corrosion protection in
the most extreme environments
• Durable and marine rated LED lamp
head assemblies provide protection
against water ingress, corrosion, and
impact
• High temperature rated nickel cadmium
battery for reliable operation up to 55ºC
ambient
• Solid state battery charger for long life
and reliable battery operation prevents
deep discharge by automatically
disconnecting the battery from the
luminaire
• Factory-installed "push-to-test" button
• Self-test, monitoring, and diagnostics
reduce costly maintenance checks
• Remote luminaire head assemblies (one
or two) are available for mounting of
luminaire heads away from main power
system
• Stainless steel drain minimizes moisture
collection
• Standard battery disconnect switch
(Krydon® unit)
1152
www.crouse-hinds.com
Cl. I, Div. 2, Groups B, C, D
Cl. I, Zone 2
Wet Locations, Marine
NEMA 3, 3R, 4X
Ambient 0ºC to 55ºC
Certifications and
Compliances:
NEC/CEC:
• Class I, Division 2, Groups B, C, D,
Zone 2
UL Standards:
• 1598A (Supplemental Requirements for
Luminaires for Installation on Marine
Vessels)
• 924 (Emergency Lighting and Power
Equipment)
• 844 (Electric Luminaires Hazardous
Locations)
CSA Standards:
• C22.2 No. 141-M1985 unit equipment
for emergency lighting
• C22.2 No. 137-M1981 non-incendive
electrical equipment for use in Class I,
Division 2 hazardous locations
• Life Safety Code NFPA101® –
Section 5-9 (Emergency Lighting)
• Marine wet locations suitability, Type 4X
Standard Materials:
• Power supply and remote luminaire
enclosures – Krydon® fiberglassreinforced polyester
• LED lamp head assembly – epoxy
powder coated stainless steel
• Exterior hardware – nylon, plastic
coated, and stainless steel
• Cover gasket – Hypalon® synthetic rubber
Electrical Ratings:
• Power supply –
Input: 120, 220, 230, 240, or 277 VAC,
50 or 60 Hz; 28 watts max.
Output: 12 VDC
• Luminaire heads –
Voltage: 12 VDC; Lamp: 3 watt LED
Total lumen output: 80
Unit Net Weights:
•
•
•
•
Temperature Performance
Data:
Based on 55°C ambient
Cat. #
Class I, Division 2
N2LPS (all)
N2RF (all)
Note:
Note:
40ºC - T5; 55ºC - T4A
T5
Ambient temperature at which the Light-Pak
system is rated is 0°C to 55°C. Operation at
temperatures outside this range will affect the
battery life and/or charging performance.
Battery time in emergency mode is 90 minutes.
National Electrical Code and Life Safety Code are
registered trademarks of the National Fire Protection
Association, Inc.
Noryl is a registered trademark of General Electric
Company.
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2012 Cooper Crouse-Hinds
N2LPS12222 – 16 lbs.
N2LPS12220 – 12 lbs.
N2RF1221 – 8 lbs.
N2RF1222 – 9 lbs.
1152-1153.qxp
5/30/2011
11:15 AM
Page 1153
LED N2LPS LIGHT-PAK™
Emergency Lighting System
10L
Cl. I, Div. 2, Groups B, C, D
Cl. I, Zone 2
Wet Locations, Marine
NEMA 3, 3R, 4X
Ambient 0ºC to 55ºC
Ordering Information:
Description
Cat. #
28 watt, 12 volt power supply assembly with two 3 watt LED lamp heads
28 watt, 12 volt stainless steel power supply assembly with two 3 watt LED lamp heads
28 watt, 12 volt power supply assembly less luminaire heads
Remote luminaire assembly with one 3 watt LED lamp head
Remote luminaire assembly with two 3 watt LED lamp heads
28 watt, 120V LED Light-Pak with single sided exit sign**
28 watt, 277V LED Light-Pak with single sided exit sign**
28 watt, 120V LED Light-Pak with double sided exit sign**
28 watt, 277V LED Light-Pak with double sided exit sign**
N2LPS12222
N2LPS12222 SS
N2LPS12220*
N2RF1221*
N2RF1222*
N2LPS12222/120
N2LPS12222/277
N2LPS12222/120
N2LPS12222/277
EXS DR0391734
EXS DR0391734
EXD DR0391734
EXD DR0391734
*Not cUL approved. UL Listed only.
**Exit sign operates in both normal and emergency mode.
Note: Up to four (4) remote LED lamp assemblies can be connected to the N2LPS12222. Up to six (6) remote LED lamp assemblies can be
connected to the N2LPS12220.
Wire Sizing for Remote Installation:
For Copper Wire –
Running Distance† (ft.) Between Power Supply and Remote Luminaire
Load In Watts
Load In Watts
Wire Size
8
16
24
32
Wire Size
8
16
24
32
16 AWG
14 AWG
12 AWG
26
42
66
13
21
33
6
10
16
3
5
8
10 AWG
8 AWG
6 AWG
106
168
270
53
84
135
26
42
67
13
21
33
†Maximum distance to limit line voltage drop to 5%.
Dimensions (N2LPS):
1.1
13.5
10L
16.0
7.5
5.0
13.8
14.5
7.4
18.0
Standard – N2LPS LED Light-Pak™
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds
1153
1154-1155.qxp
5/30/2011
11:16 AM
Page 1154
LED N2LPS LIGHT-PAK™
Emergency Lighting System
10L
Cl. I, Div. 2, Groups B, C, D
Cl. I, Zone 2
Wet Locations, Marine
NEMA 3, 3R, 4X
Ambient 0ºC to 55ºC
Dimensions (N2LPS):
EXS, EXD Option – N2LPS LED Light-Pak™ with Optional Emergency Exit Luminaire
Dimensions (N2RF):
9.50
10L
9.50
3.83
3.83
7.27
4.38
11.77
Detail Indication Logic:
Status Indication
Status Description
Status Definition
*
*-*
**-**
***-***
No Light
Steady Light (No Blinks)
Light Blinks Once
Light Blinks Twice
Light Blinks Three Times
AC Power Removed from Circuit
Fully Charged
Battery Charging
Battery Failure
Circuit Failure
1154
www.crouse-hinds.com
US: 1-866-764-5454
CAN: 1-800-265-0502
Copyright© 2011 Cooper Crouse-Hinds