10L NEMA 4X, IP66 UL Listed Available with Cl. I, Div. 2, Groups A, B, C, D rating CCH UX Series LED Exit Signs The Cooper Crouse-Hinds CCH UX Series LED Exit Sign combines the strength and durability of die cast aluminum with architecturallypleasing aesthetics. The CCH UX Series is illuminated by LEDs, providing the customer with a long-life, low maintenance, dependable exit sign for use in conditions where reliability is crucial. Designed for the most severe environments, the CCH UX Series will provide maximum performance against rain, moisture, cold, corrosion, and dust in applications such as manufacturing plants, refineries, petrochemical and chemical plants, waste and sewage treatment facilities, food processing, and other industrial facilities. Applications: • In locations deemed hazardous due to the presence of flammable vapors or gases • In areas where the presence of gases or vapors may become present during an abnormal, unusual, or accidental conditions • Outdoor and wet applications • Where required by the National Electrical Code®, Life Safety Code®, or other applicable codes 10L Features and Benefits: • Wet location, outdoor rated for use in the most demanding environments • Optional hazardous location rating available • Dual voltage 120V/277V reduces wiring errors • Heavy-duty nickel cadmium battery for long life • 24-hour charge and recharge recovery time increases safety • Heavy-duty injection molded polycarbonate lens protects against impact and corrosion • Brown-out protection protects battery and reduces labor • Heavy-duty aluminum die cast housing protects against impact and chemical resistance • LEDs provide long life, even illumination, and energy savings • Wide operating temperature range (-45°C to 45°C) • Self-diagnostic testing reduces costs by eliminating scheduled equipment verification tests • Heavy duty nickel cadmium battery for long life meets 90 minute requirements for battery operated emergency system NEMA 4X, UL50 UL924 wet location IP65, IP66 Available with NEC hazardous location rating - UL844 Class I, Division 2, Groups A, B, C, D In Inches: Mounting: wall mount, ceiling mount, end mount Conduit Entry: top, bottom, or either side of the unit www.crouse-hinds.com US: 1-866-764-5454 Temperature Performance Data: CCH UX Series Exit Sign: • -45ºC (-49ºF) to 45ºC (113ºF) CCH UX-HAZ Hazardous Location Exit Sign: • T6 rating at 45ºC (113ºF) Electrical Ratings: • Power Supply 120V/277V dual voltage • LED Exits - Red Input Power 120V = 2.7W 277V = 3.2W • LED Exits - Green Input Power 120V = 2.3W 277V = 3.0W Input Current: (Max.) 120V = .08A 277V = .03A Ordering Information: Dimensions 1162 • Provides safe and reliable exit marking both indoors and outdoors during power failure or interruption of power to normal lighting system • Long life (>50K hours) for years of maintenance-free operation • Energy-efficient for lower cost of operation • Low temperature operation with no loss of illumination • Rugged and durable light source for the harshest of environments Input Current: (Max.) 120V = .07A 277V = .04A Certifications and Compliances: • • • • Benefits of LED Technology: CAN: 1-800-265-0502 Catalog Number Housing Finish Letter Color CCH CCH CCH CCH CCH CCH CCH CCH CCH CCH CCH CCH CCH CCH CCH CCH Silver Housing Silver Housing Silver Housing Silver Housing Silver Housing White Housing Black Housing Silver Housing White Housing Black Housing Silver Housing White Housing Black Housing Silver Housing White Housing Black Housing Red LED Red LED Green LED Green LED Red LED Red LED Red LED Red LED Red LED Red LED Green LED Green LED Green LED Green LED Green LED Green LED UX70RSDHAZ UX60RHAZ UX70GSDHAZ UX60GHAZ UX70RSD UX70RWHSD UX70RBKSD UX60R UX60RWH UX60RBK UX70GSD UX70GWHSD UX70GBKSD UX60G UX60GWH UX60GBK Copyright© 2012 Cooper Crouse-Hinds 1154-1155.qxp 5/30/2011 11:16 AM Page 1155 CPMVFB Emergency Compact Fluorescent Cl. I, Div. 2, Groups A, B, C, D Restricted Breathing Cl. I, Div. 2 & Zone 2 (Suffix S826) Certified for IEC Zone 2 (Suffix S826TB) Continuous Operation Champ-Pak™ Luminaires Cl. II, Groups E, F, G; Cl. III & Simultaneous Presence* Marine & Wet Locations 3, 3R, 4, 4X; IP66 Emergency Lighting Applications: Standard Materials: • Where emergency lighting is required to permit workers in industrial areas to safely encounter their surroundings during power failures • Where emergency egress lighting is required, such as: catwalks, walkways, tunnels, doorways, stairs, stairwells, ramps and aisles • Indoor and outdoor wall mounting or vertical surface mounting where minimal luminaire depth is required in: – Manufacturing plants and heavy industrial facilities – Industrial process facilities such as refineries, chemical, petrochemical, pharmaceutical, and platforms – Waste or sewage treatment plants – Offshore, dockside, and harbor installations • For security and safety lighting in industrial facilites for lighting of loading docks, tunnels, and stairways • For marine, wet location, hose down, and corrosive environments • Luminaire housing and door frame assembly – copper-free aluminum • External hardware – stainless steel • Lens – heat- and impact-resistant refractor style glass • Gaskets – silicon rubber • Reflector – aluminum light sheet • Wire guard – stainless steel Features and Benefits: Certifications and Compliances: • NEC/CEC: Class I, Division 2, Groups A, B, C, D Class II, Class III & Simultaneous Presence (Class I, Division 2 and Class II) Class I, Zone 2 • IEC: Zone 2 Ex nR IIC • UL Standards: 844, 2279 Hazardous (Classified) Locations 1598 Luminaires 1598A Marine Locations • CSA Standards: C22.2 No. 137 • IEC Standards: 60079-15 Standard Finishes: • Aluminum – Corro-free™ epoxy powder coat • Stainless steel – natural Options: Description Suffix Restricted breathing construction................................................................................. S826 Class I, Division 2 & Zone 2 suitability Cooler operating temperatures (T-numbers) Certified for IEC Zone 2 (Suffix S826TB)....................................................................... S826TB Furnished with: Terminal Block Crimp Terminals Dedicated voltage ballasts (no MT, DT or TT) Factory assembled with lamp installed......................................................................... FA Fused - projects ballast and capacitors against abnormal line conditions.................. S658 (Not for use in Canada) (Not for Marine use) Electrical Rating Ranges: • • • • 52 watts 120–277V, 50–60 Hz 120V, 60 Hz 347V, 60 Hz About the Battery: • • • • • • • • • 10L • Unique compact shallow profile design mounts virtually anywhere • Side hinged cover with two screw closing for easy installation and maintenance • Gray Corro-free™ epoxy powder coat two-piece housing provides superior corrosion resistance • Unique stainless steel wire guard accessory attaches without any additional hardware for easy installation and maintenance • Glass refractor provides uniform light distribution to eliminate glare • Silicon gaskets make luminaire suitable for NEMA 4X, marine enviroments • High power factor ballasts (+90%) are standard, which allow more luminaires per circuit 10L Bodine fluorescent battery pack ballasts are UL component recognized Sealed, maintenance-free, high temperature nickel cadmium Solid state chargers are sealed inside the ballast case 90 minute illumination time 10-year life expectancy 2-year full warranty During auxiliary use 1 lamp has continuous operation A red indicator light indicates the battery is charging Wiring instructions for a "Push-to-Test" button is supplied with the fixture Accessories: Description Stainless steel wire guard............................................................................................. Cat. # P55 *Consult Cooper Crouse-Hinds. www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1155 1156-1157.qxp 5/30/2011 11:16 AM Page 1156 CPMVFB Emergency Compact Fluorescent 10L Ordering Information Dimensions & Weights Continuous Operation Champ-Pak™ Luminaires Ordering Information: Hub Size Lamp Watts Cat. # for use with ANSI Lamps /4 NPT 26 CPMVFB2W026 3 Standard Voltage Ballasts Voltage Suffix NEC/UL 120–277V 50–60 Hz /UNV CEC/CSA (cUL) 120V/60 Hz 347V 60 Hz /120CAN /347 Dimensions 10L In Inches: Net Weights: Luminaire Less Guard P55 Guard 1156 www.crouse-hinds.com 18.6 lbs. 0.5 lbs. US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1148-1149.qxp 5/30/2011 11:14 AM Page 1149 Cl. I, Div. 2; Groups A, B, C, D Restricted Breathing Cl. I, Div. 2 & Zone 2 (Suffix S826) Certified for IEC Zone 2 (Suffix S826TB) DMVF(B) – Exit Sign Fluorescent Luminaire Applications: DMVF(B) Exit Signs are used: • In any building or enclosed area where people work • Where illuminated exit signs are required • To provide distinct, highly visible exit markings • To indicate the direction of travel to exits • In locations deemed hazardous due to the presence of flammable vapors or gases, or combustible dusts Features: • Six inch letters on white glass sign panel make the word "exit" stand out boldly and clearly • Housings made of die-cast copper-free aluminum (less than 0.4 of 1% copper) for strength and resistance to corrosion • Mounting module equipped with integral hub set-screws for vibration resistance (ceiling and pendant mounts) • Hubs are provided with an integral conduit stop and bushing to help prevent damage to field wiring during installation • Epoxy powder finish and stainless steel external hardware for resistance to corrosion • Long life gaskets which provide seals between mounting module, housing, and globe assembly • Grounding wire for safety • Cool operating design • Optional emergency battery back-up operation during power outage About the Battery: Energy Savings: • Less wattage used with compact fluorescent lamps compared to equivalent incandescent lamps providing the same light output 10L Certifications and Compliances: • NEC and CEC: Class I, Division 2, Groups A, B, C, D Class II, Class III & Simultaneous Presence (Class I, Division 2 and Class II) Class I, Zone 2 • IEC: Zone 2 Ex nR IIC • UL Standards: 844, 2279 Hazardous (Classified) Locations 1598 Luminaires 1598A Marine Luminaires • CSA Standards: C22.2 No. 137 • IEC Standards: 60079-15 Standard Materials: • Ballast housings and mountings – copperfree aluminum (less than 0.4 of 1%) • Exterior hardware – stainless steel • Globe – heat- and impact-resistant internally fluted glass Standard Finishes: • Aluminum – gray epoxy powder coat • Krydon material – high reflectance white • Stainless steel – natural Options: Description Suffix Lamps supplied with exit sign............................................... S714 Top hat with stainless steel threaded insert.......................... S806 Restricted breathing construction.......................................... S826 Class I, Division 2 & Zone 2 suitability Cooler operating temperatures (T-Numbers) Certified for IEC Zone 2......................................................... S826TB Furnished with: Terminal Block Crimp Terminals Dedicated voltage ballasts (no MT, DT or TT) 10L • Bodine fluorescent battery pack ballasts are UL component recognized • Sealed, maintenance-free, high temperature nickel cadmium • Solid state chargers are sealed inside the ballast case • 90 minute illumination time • 10-year life expectancy • 2-year full warranty • During emergency use 1 lamp has continuous operation • A red indicator light indicates the battery is charging • Wiring instructions for a "Push-to-Test" button is supplied with the fixture Cl. II, Groups E, F, G, Cl. III & Simultaneous Presence Marine & Wet Locations 3, 3R, 4X; IP66 Electrical Rating Ranges: • • • • 52 Watt 120–277V, 50–60 Hz 120V, 60 Hz 347V, 60 Hz Ordering Information: Mounting Type Supply Voltage Volts/Hertz Fluorescent Cat. # Pendant 120–277V / 50–60 Hz 120V / 60 Hz (Canada) 347V / 60 Hz DMVF2C052G/UNV EXD Ceiling 120–277V / 50–60 Hz 120V / 60 Hz (Canada) 347V / 60 Hz Wall 120–277V / 50–60 Hz 120V / 60 Hz (Canada) 347V / 60 Hz DMVF2TW052G/UNV EXD DMVFB2TW052G/UNV EXD DMVFB2TW052G/120CAN EXD DMVF2TW052G/347 EXD DMVFB2TW052G/347 EXD www.crouse-hinds.com US: 1-866-764-5454 DMVF2A052G/UNV EXD Fluorescent with Battery Back-up Cat. # DMVF2A052G/347 EXD DMVF2C052G/347 EXD CAN: 1-800-265-0502 DMVFB2A052G/UNV EXD DMVFB2A052G/120CAN EXD DMVFB2A052G/347 EXD DMVFB2C052G/UNV EXD DMVFB2C052G/120CAN EXD DMVFB2C052G/347 EXD Copyright© 2011 Cooper Crouse-Hinds 1149 1156-1157.qxp 5/30/2011 11:16 AM Page 1157 Cl. I, Div. 2, Groups A, B, C, D Restricted Breathing Cl. I, Div. 2 & Zone 2 (Suffix S826) Certified for IEC Zone 2 (Suffix S826TB) DMVFB Emergency Compact Fluorescent Continuous Operation Champ® Luminaires Applications: DMVF Series Champ Lighting Luminaires are used: • Where emergency lighting is required to permit workers in industrial areas to safely encounter their surroundings during power failures • Where emergency egress lighting is required, such as: catwalks, walkways, tunnels, doorways, stairs, stairwells, ramps, and aisles • In areas made hazardous by abnormal conditions resulting in the presence of flammable vapors or gases • In areas made hazardous by the presence of combustible dusts • Where combustible dusts and flammable vapors are present simultaneously • In marine applications where water spray and corrosive atmospheres are considerations • On installations where vibration and rough usage are problematic • Where a cool, efficient light source is required • In areas that require lamps to reach full illumination immediately • In refineries, chemical and petrochemical facilities, grain processing, handling or storage facilities, manufacturing plants, wastewater treatment plants, sewage treatment plants, oil terminals, food processing facilities, breweries, and any other manufacturing or processing facility where safe, reliable hazardous area fluorescent or auxiliary lighting is needed • Housings made of die-cast copper-free aluminum (less than 0.4 of 1% copper) for strength and resistance to corrosion • Mounting modules equipped with integral hub set-screws for vibration resistance (ceiling, pendant, and quad mounts) • Hubs are provided with an integral conduit stop and bushing to help prevent damage to field wiring during installation • Epoxy powder finish and stainless steel external hardware for resistance to corrosion • Long-life gaskets which provide seals between mounting module, housing, and optical assembly • Grounding wire for safety • Cool operating design • Optional stainless steel open bottom guard permits direct access to the globe for easy relamping • Battery pack ballast for emergency lighting 10L Certifications and Compliances: • NEC/CEC: Class I, Division 2, Groups A, B, C, D Class II, Class III & Simultaneous Presence (Class I, Division 2 and Class II) Class I, Zone 2 Emergency Lighting • IEC: Zone 2 Ex nR IIC • UL Standards: 844, 2279 Hazardous (Classified) Locations 1598 Luminaires 1598A Marine Locations 924 Emergency Lighting • CSA Standards: C22.2 No. 137 • IEC Standards: 60079-15 Standard Materials: • Ballast housings and mountings – copperfree aluminum (less than 0.4 of 1%) • External hardware guards – stainless steel • Reflectors – Krydon® fiberglassreinforced polyester material • Globe – heat- and impact-resistant internally fluted glass Standard Finishes: • Aluminum – gray epoxy powder coat • Krydon material – high reflectance white • Stainless steel – natural Options: Description Suffix • Restricted breathing construction................................ S826 -Class I, Division 2 & Zone 2 suitability -Cooler operating temperatures (T-numbers) • Certified for IEC Zone 2............. S826TB -Furnished with: Terminal Block Crimp Terminals • Emergency operation only – Consult Cooper-Hinds • Factory assembled with lamp installed....................................... FA • Fused – to protect ballast against abnormal line conditions (not for use in Canada) (not for marine use).................................. S658 • Lamps supplied with luminaire... S714 • Top hat with stainless steel threaded insert to attach ballast housing........................................ S806 • TEFLON® coating on globe for increased shatter protection....... S808 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Electrical Rating Ranges: • 52, 64, and 84 watts • 120–277V, 50–60 Hz • 347V, 60 Hz Accessories: (Order separately) Description Cat. # Dome 30° Angle RD739 RA739 10L Standard Features: Cl. II, Groups E, F, G; Cl. III & Simultaneous Presence Marine & Wet Locations 3, 3R, 4, 4X; IP66 Emergency Lighting Energy Savings • Less wattage used with compact fluorescent lamps compared to equivalent incandescent lamps providing the same light output About the Battery (DMVFB Units): • Bodine fluorescent battery pack ballasts are UL component recognized • Sealed, maintenance-free, high temperature nickel cadmium • Solid state chargers are sealed inside the ballast case • 90 minute illumination time • 10-year life expectancy • 2-year full warranty • During auxiliary use 1 lamp has continuous operation • A red indicator light indicates the battery is charging • Wiring instructions for a "Push-to-Test" button is supplied with the fixture Copyright© 2011 Cooper Crouse-Hinds 1157 1158-1159.qxp 10L 5/30/2011 11:17 AM Page 1158 DMVFB Emergency Compact Fluorescent Cl. I, Div. 2, Groups A, B, C, D Restricted Breathing Cl. I, Div. 2 & Zone 2 (Suffix S826) Certified for IEC Zone 2 (Suffix S826TB) Continuous Operation Champ® Luminaires Mounting Style Pendant Mount DMVFB Series Fluorescent with Battery Back-Up with G303 Globe and P33 Guard Cat. # DMVFB2A052GP DMVFB3A052GP DMVFB2A064GP DMVFB3A064GP DMVFB2A084GP DMVFB3A084GP /4 1 3 /4 1 3 /4 1 52 /4 /4 3 /4 52 64 84 DMVFB2HA052GP DMVFB2HA064GP DMVFB2HA084GP /4 1 3 /4 1 3 /4 1 52 DMVFB2C052GP DMVFB3C052GP DMVFB2C064GP DMVFB3C064GP DMVFB2C084GP DMVFB3C084GP /4 1 3 /4 1 3 /4 1 52 Quad-Mount Pendant, Adjustable Thru-Feed, 25° Angle, 121/ 2° Angle 3 /4 /4 3 /4 52 64 84 DMVFB25Q052GP DMVFB25Q064GP DMVFB25Q084GP Stanchion Mount 25° Angle 11/2 11/2 11/2 52 64 84 DMVFBJ052GP DMVFBJ064GP DMVFBJ084GP Stanchion Mount Straight 11/ 2 11/ 2 11/ 2 52 64 84 DMVFBP052GP DMVFBP064GP DMVFBP084GP 3 Flexible Pendant Mount 3 Ceiling Mount Thru-Feed 3 Wall Mount Thru-Feed 10L Hub Lamp Size (In.) Watts 64 84 3 64 84 3 64 84 3 DMVFB2TW052GP DMVFB3TW052GP DMVFB2TW064GP DMVFB3TW064GP DMVFB2TW084GP DMVFB3TW084GP Note: For technical information on family trees, temperature performance data, dimensions, weights, and photometrics, refer to Series in Section 6L. 1. Catalog numbers are basic numbers. Voltage must be specified. Standard Voltage Ballasts NEC/UL 1. Voltage Suffix 1158 CEC/CSA (cUL) 120–277V 50–60 Hz /UNV www.crouse-hinds.com US: 1-866-764-5454 Cl. II, Groups E, F, G; Cl. III & Simultaneous Presence Marine & Wet Locations 3, 3R, 4, 4X; IP66 Emergency Lighting 120V/60 Hz /120CAN CAN: 1-800-265-0502 347V 60 Hz /347 Copyright© 2011 Cooper Crouse-Hinds 1148-1149.qxp 10L 5/30/2011 11:14 AM Page 1148 EVLPF(B) – Exit Sign Fluorescent Luminaire Applications: EVLPF(B)-EXD Exit Signs are used: • In any building or enclosed area where people work – where illuminated exit signs are required • To provide distinct, highly visible exit marking • To indicate the direction of travel to exits • In locations deemed hazardous due to the presence of flammable vapors, gases, or combustible dusts Features and Benefits: • Six inch red letters on white glass sign panel make the word "EXIT" stand out boldly and clearly • Lightweight copper-free aluminum housing with powdered epoxy finish • All exterior hardware is corrosionresistant stainless steel • Three mounting arrangements: pendant, ceiling, and wall bracket • Integral ballast • High power factor (90%+) ballasts • Easier assembly, installation, and maintenance • Outdoor, hose down, marine and corrosive environments suitable • Ideal for adverse environments typical of industrial facilities • Ground wire for safety • Optional battery back-up for operation during power outage Cl. I, Div. 1, Groups B (suffix GB), C, D Cl. I, Zone 1, Groups IIB + H2 (GB suffix), IIB Cl. II, Div. 1, Groups E, F, G; Class III, Simultaneous Presence Marine & Wet Locations 3, 3R, 4, 4X; IP66 Certifications and Compliances: • NEC and CEC: Class I, Division 1, Groups B (GB suffix), C, D Class I, Zone 1, Groups IIB + H2 (GB Suffix), IIB, IIA Class II, Class III & Simultaneous Presence (Class I and Class II) • UL Standards: 844 Hazardous (Classified) Locations 1598 Luminaires 1598A Marine Locations • CSA Standards: C22.2 No. 137 Standard Materials: • Mounting modules, cover, ballast housing, globe holder – copper-free aluminum • Globe – heat- and impact-resistant glass • Exterior hardware – stainless steel Ratings (Electrical/Size): Sources/wattage: • 52W (2-26W lamps) • 120-277V, 50-60 Hz • 120V, 60 Hz • 347V, 60 Hz Conduit entries: • 3/4", 1" NPT – pendant, wall bracket, ceiling Standard Finishes: • Copper-free aluminum – Corro-free™ powdered epoxy Options: Description Group B suitability Factory assembled with lamps Suffix GB FA 10L About the Battery: • Bodine fluorescent battery pack ballasts are UL component recognized • Sealed, maintenance-free, high temperature nickel cadmium • Solid state chargers are sealed inside the ballast case • 90 minute illumination time • 10-year life expectancy • 2-year full warranty • During emergency use 1 lamp has continuous operation • Red indicator light indicates the battery is charging • Wiring instructions for a "Push-to-Test" button is supplied with the luminaire Ordering Information: Supply Mounting Voltage Type Volts/Hertz Fluorescent Cat. # Pendant 120–277V / 50–60 Hz EVLPFA02520/UNV EXD EVLPFBA02520/UNV EXD 120V / 60 Hz (Canada) EVLPFBA02520/120CAN EXD 347V / 60 Hz EVLPFA02520/347 EXD EVLPFBA02520/347 EXD Ceiling 120–277V / 50–60 Hz EVLPFCX02520/UNV EXD EVLPFBCX02520/UNV EXD 120V / 60 Hz (Canada) EVLPFBCX02520/120CAN EXD 347V / 60 Hz EVLPFCX02520/347 EXD EVLPFBCX02520/347 EXD Wall 120–277V / 50–60 Hz EVLPFBX02520/UNV EXD EVLPFBBX02520/UNV EXD 120V / 60 Hz (Canada) EVLPFBBX02520/120CAN EXD 347V / 60 Hz EVLPFBX02520/347 EXD EVLPFBBX02520/347 EXD Energy Savings: • Less wattage used with compact fluorescent lamps compared to equivalent incandescent lamps providing the same light output 1148 www.crouse-hinds.com Fluorescent with Battery Back-up Cat. # US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1158-1159.qxp 5/30/2011 11:17 AM Page 1159 Cl. I, Div. 1, Groups B (GB Suffix), C, D Cl. I, Zone 1, Groups IIB + H2 (GB suffix), IIB, IIA Cl. II, Div. 1, Groups E, F, G; Class III, Simultaneous Presence EVLPFB Emergency Compact Fluorescent Continuous Operation Low Profile Luminaires Marine & Wet Locations 3, 3R, 4, 4X; IP66 Emergency Lighting 10L Applications: Cooper Crouse-Hinds Low Profile Hazard•Gard® Luminaires are used in: • Areas that require lamps to reach full lumination immediately • Where emergency lighting is required to permit workers in industrial areas to safely encounter their surroundings during power failures • Where emergency lighting is required such as: catwalks, walkways, tunnels, doorways, stairs, stairwells, ramps, and aisles • Areas where flammable or explosive vapors or gases are present • Hazardous areas, both indoors and outdoors, where long life and low maintenance costs are desired • Petroleum refineries, chemical, petrochemical and pharmaceutical plants, oil terminals, gas plants and other heavy process industry facilities • Waste treatment facilities • Drilling platforms and other coastal and offshore hazardous areas Features and Benefits: Certifications and Compliances: • NEC/CEC: Class I, Division 1, Groups B (with GB suffix), C, D Class I, Zone 1, Groups IIB + H2 (GB Suffix), IIB, IIA Class II, Class III & Simultaneous Presence (Class I and Class II) Emergency Lighting • UL Standards: 844 Hazardous (Classified) Locations 1598 Luminaires 1598A Marine Locations 924 Emergency Lighting • CSA Standards: C22.2 No. 137 Ratings (Electrical/Size): • Mounting modules, cover, ballast housing, globe holder – copper-free aluminum • Globe – heat- and impact-resistant glass • Exterior hardware – stainless steel • Reflectors (dome & angle) – Krydon® fiberglass-reinforced polyester Sources/Wattage: • Fluorescent continuous operation emergency lighting 52W (2-26W lamps) and 64W (2-32W lamps) compact fluorescent voltages • Fluorescent emergency lighting 120–277V, 50–60 Hz 120V, 60 Hz 347V 60Hz Conduit entries: • 3/4", 1" NPT – pendant, wall bracket, ceiling • 11/4" NPT – stanchion Standard Finishes: • Copper-free aluminum – Corro-free™ powdered epoxy • Krydon – white • Stainless steel guard Energy Savings • Less wattage used with compact fluorescent lamps compared to equivalent incandescent lamps providing the same light output Options: Description Group B suitability Fused (not for use in Canada) (not for marine use) Factory assembled with lamps Emergency operation only – Consult Cooper Crouse-Hinds Suffix GB S658* FA 10L • Small, compact size • Two start Acme threaded construction • Easier assembly, installation, and maintenance • Lightweight copper-free aluminum housing with powdered epoxy finish • All exterior hardware is corrosionresistant stainless steel • Four mounting arrangements: pendant, ceiling, wall bracket, and stanchion • Integral ballast • High power factor (90%+) ballasts • Uses same mounting modules as the standard Hazard•Gard® • Internally fluted glass globes • Krydon® construction dome and angle reflectors – won't rust, corrode, dent, chip, or peel • Now available in components – luminaire body, mounting module, guard, reflectors • Three wire construction • For energy conservation, luminaires can be switched off without affecting the emergency operation feature Standard Materials: *When ordering fuses for luminaires, option S658, you must specify the operating voltage. S658 cannot be ordered with /MT in the catalog number. Accessories: Description Cat. # Dome reflector Angle reflector RD739 RA739 About the Battery: • Bodine fluorescent battery pack ballasts are UL component recognized • Sealed, maintenance-free, high temperature nickel cadmium • Solid state chargers are sealed inside the ballast case; 90 minute illumination time; 10-year life expectancy • 2-year warranty • During emergency use, 1 lamp has continuous operation • A red indicator light indicates the battery is charging • Wiring instructions for a "Push-to-Test" button is supplied with the fixture www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1159 1160-1161.qxp 10L 5/30/2011 11:17 AM Page 1160 EVLPFB Emergency Compact Fluorescent Continuous Operation Low Profile Luminaires Cl. I, Div. 1, Groups B (GB Suffix), C, D Cl. I, Zone 1, Groups IIB + H2 (GB suffix), IIB, IIA Cl. II, Div. 1, Groups E, F, G; Class III, Simultaneous Presence Marine & Wet Locations 3, 3R, 4, 4X; IP66 Emergency Lighting Ordering Information: Pendant Mount Pendant Wall Bracket† Hub Size With Guard With Guard Watt (In.) Cat. # Cat. # Fluorescent with Emergency Ballast – High Power 3 /4 EVLPFBA02521 EVLPFBBX02521 EVLPFBA03521 EVLPFBBX03521 52W 1 11/4 3 /4 1 11/4 64W EVLPFBA02641 EVLPFBA03641 EVLPFBBX02641 EVLPFBBX03641 Ceiling† Stanchion With Guard With Guard Cat. # Cat. # Factor Ballast (Min. P.F. 90%) EVLPFBCX02521 EVLPFBCX03521 EVLPFBJ04521 EVLPFBCX02641 EVLPFBCX03641 Luminaire Body Less Mounting Module & Guard Cat. # EVLPFB0520 EVLPFB0640 EVLPFBJ04641 Complete Catalog Numbers as follows: Standard Voltage Ballasts NEC/UL 1. Voltage Suffix 2. Wall Bracket Mount† 120–277V 50–60 Hz /UNV CEC/CSA (cUL) 120V/60 Hz /120CAN 347V 60 Hz /347 Example: EVLPFB02521/UNV Other Voltages – Consult Cooper Crouse-Hinds Note: For technical information on family trees, temperature performance data, dimensions, weights, and photometrics, refer to DMVF Series in Section 6L. EVFPFB Fluorescent Emergency Lighting 10L • Three wire construction, for switching purposes, is standard on fluorescent emergency lighting. • For energy conservation, luminaires can be switched off without affecting the emergency operation feature. Ceiling Mount† *Test switch is remote mounted. Use Cooper Crouse-Hinds EDSC218 (Not furnished). Stanchion Mount †Ceiling and bracket mounts have 4 hubs: 3 are plugged. 1160 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1146-1147.qxp 5/30/2011 10L 11:14 AM Page 1146 EXL Explosionproof Exit Sign Cl. I, Div. 1 & 2, Groups C, D Cl. I, Zone 1 IIB Cl. II, Div. 1, Groups E, F, G Factory-sealed Applications: Ordering Information: EXL Exit Signs are used: • In locations deemed hazardous due to the presence of flammable vapors or gases, or combustible dusts • In any building or enclosed area where people work – where illuminated exit signs are required • To provide distinct, highly visible exit marking • To indicate the direction of travel to exits When ordering an EXL Series Exit Sign, you will need to specify: (A) Voltage (120VAC or 120VDC) (B) Mounting (Wall, End Bracket, or Pendant) (C) Exit Sign Designation All units come standard with 3/4" hubs and exit signs with red lettering and white background. Complete catalog numbering is as follows: Lamp Wattage: EXL (A) 2 (B) (C) (A) Voltage: 120VAC ............ leave blank 120VDC .......................... D (B) Mounting: Wall................................. 1 End Bracket.................... 2 Pendant .......................... 3 (C) Exit Sign Designation: A Single Face (Wall Mount) AA Double Face (End Bracket & Pendant) AB Double Face, one side arrowhead right, the other no arrowhead (End Bracket & Pendant) AC Double Face, one side arrowhead left, the other no arrowheads (End Bracket & Pendant) AD Double Face, one side arrowhead both ends, the other no arrowheads (End Bracket & Pendant) B Single Face, arrowhead right (Wall Mount) BC Double Face, one side arrowhead right, the other arrowhead left (End Bracket & Pendant) BD Double Face, one side arrowhead both ends, the other arrowhead right (End Bracket & Pendant) C Single Face, arrowhead left (Wall Mount) CD Double Face, one side arrowhead both ends, the other arrowhead left (End Bracket & Pendant) D Single Face, arrowhead both ends (Wall Mount) DD Double Face, both sides arrowhead both ends (End Bracket & Pendant) • Two 60 watt, 60T10 clear lamps for AC units • Two 25 watt, 25T10 clear lamps for DC units • Lamps not included with luminaire Mounting Type Sign Panel Description Hub Size (In.) AC Cat. # DC Cat. # Wall End Bracket Pendant Single face Double face Double face 3 Electrical Ratings: /4 /4 3 /4 EXL21A EXL22AA EXL23AA EXLD21A EXLD22AA EXLD23AA Features: • Two incandescent lamps (not included) wired in parallel – to provide extra margin of light source reliability • Solid state circuit for extended lamp life in AC units • Six inch red letters on white acrylic sign panel make word "exit" stand out boldly and clearly • Edge lighting characteristic of sign panel makes visibility excellent at all lighting levels • Factory-sealed explosionproof housing • Pendant, wall, and end bracket mounts provide universal installation options • Impact-resistant acrylic sign panel needs no guard – makes cleaning easy • Internal rectifier extends lamp life beyond 1,000-hour rated life – reduces relamping cost • Relamping tool provided 10L Certifications and Compliances: • NEC: Class I, Groups C, D Class II, Groups E, F, G • UL Standard: 844 • NFPA Life Safety Code No. 101-1991 Standard Materials: • Body – copper-free aluminum • Sign panel – acrylic Conduit Entrance: • 3/4" hubs • 120VDC or 120VAC operation Temperature Performance Data: (for both AC & DC operation): Ambient Temp. (°C) 25 40 1146 Class I (C, D) Class II (E, F, G) Supply Wire °C T3C T3C 150°C www.crouse-hinds.com Pendant Style End Bracket Style Wall Style 3 Options: Description Suffix Exit signs with green lettering on white background........................................................ GN Unit provided with epoxy powder coat............................................................................. S752 277VAC – (Order ECT413 Transformer Separately) US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1146-1147.qxp 5/30/2011 11:14 AM Page 1147 EXL Explosionproof Exit Sign 10L Factory-sealed Dimensions Dimensions In Inches: Wall Style Pendant Style 10L End Bracket Style www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1147 Ex-Lite LED Exit Signs Cl. I, Div. 2, Groups A, B, C, D Cl. I, Zone 1, AEx em ib IIC (NEC) Cl. I, Zone 1, Ex em ib IIC (CEC) Cl. II, Div. 2, Groups F, G (NEC) Cl. II, Div. 2, Groups E, F, G (CEC) 10L UL Listed IP66 The Ex-Lite Series of LED exit signs are designed for hazardous locations and are ideally suited for marking escape routes and exits in potentially explosive atmospheres. The Ex-Lite Z is available as an AC only version, while the Ex-Lite ZE is available with self-contained battery. As an emergency lighting luminaire with selfcontained battery system, the Ex-Lite ZE features a nickel cadmium battery with automatic test and monitoring feature. Applications: • In harsh and hazardous environments where illuminated exit signs are required Features and Benefits: Ordering Information: Catalog Number Material Number Description Ex Lite Z 12191001005 AC/DC Exit Sign Ex Lite ZE 12191130005 with Battery Light Source Life of LED Rated Voltage, VAC Frequency, Hz Rated Voltage, DC Power Consumption Battery LED 50K hours 120V-277V 50/60 110V-250V 6VA N/A -4ºF to 122ºF (-20ºC to 50ºC) Wall Ex-e 3 /4" IP66 LED 50K hours 120V-277V 50/60 110V-250V 6VA NiCad 41ºF to 95ºF (5ºC to 35ºC)* Wall Ex-e 3 /4" IP66 Allowable Temperature Range Mounting Cable Entry Conduit Entry Protection 10L LED Technology: • Long life (>50K hours) for years of maintenance-free operation • Energy-efficient for lower cost of operation • Low temperature operation with no loss of illumination • Rugged and durable light source for the harshest of environments Exit Sign System: • Can be used in a hazardous location • Conduit or cable entry • Can be installed in moist, humid, rain, and wet environments • Universal input voltage 110VAC-277VAC and 110VDC-250VDC reduces inventory • Ex-Lite ZE with self-monitoring, selfdiagnostic, and test capability • Premium heavy-duty nickel cadmium battery • 24-hour charge and recharge time increases safety by recovering quickly from outage • "EXIT" legend with alternative wings left, right, or left and right; simple field modification • Emergency lighting cycle three hours • The housing of the luminaire is constructed with a corrosion resistant, robust, lightweight aluminum alloy material and illumination of the sign is provided with red, high-efficient LEDs *Due to battery chemistry, the charging capacity will be limited at temperatures below 5ºC and above 35ºC. Dimensions In (mm): Certifications and Compliances: • • • • • • • • • • Class I, Division 2, Groups A, B, C, D Class I, Zone 1, AEx em ib IIC (NEC) Class I, Zone 1, Ex em ib IIC (CEC) Class II, Division 2, Groups F, G (NEC) Class II, Division 2, Groups E, F, G (CEC) IP66 UL844 UL924/CSA22.2 No. 141-02 UL60079/CSA22.2 E60079 UL1203/CSA22.2 E6124-1-1-02 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2012 Cooper Crouse-Hinds 1161 1150-1151.qxp 5/30/2011 10L 11:15 AM Page 1150 ELPS Light-Pak™ Emergency Lighting System Applications: ELPS Series Emergency Lighting Systems are used: • To provide safe, reliable illumination indoors or outdoors to designated areas during failure or interruption of power to the normal lighting system • In areas made hazardous by the presence of flammable gases and vapors, combustible dusts, or easily ignitible fibers and flyings • In areas where corrosion, vibration, moisture, dirt, and rough usage may be encountered • Where required by the National Electrical Code®, the Life Safety Code, or other codes • In refineries, chemical and petrochemical facilities, grain processing, handling or storage facilities, manufacturing plants, wastewater treatment facilities, and other areas where safe, reliable, hazardous area emergency lighting is needed 10L Features: • Compact factory-sealed luminaire assemblies are each furnished with a 12 watt tungsten-halogen lamp and inner reflector for appropriate photometrics in hazardous areas • Luminaire assemblies are fully adjustable and lockable on two axes to provide flexible and consistent light aiming capabilities • Luminaire lens ring is threaded for easy relamping and locks in place with hex head set-screw; will not loosen due to vibration • Ground joint cover with external flange design permits large opening and easy access to internal components; stud bolts in diagonally opposite corners of body ease cover removal and installation • Neoprene cover gasket seals out moisture for superior protection of internal components against wetness and corrosion • Lightweight, compact size, and mounting feet ease installation and allow placement in confined areas • Two 1" NPT drilled and tapped conduit openings, with plugs, are standard, for choice of top or bottom feed • Factory-installed PUSH-TO-TEST pushbutton enables easy testing of system • MAIN POWER ON pilot light indicates AC power is being supplied to the battery charger; pilot light jewel is threaded for easy lamp replacement • Stainless steel drain minimizes moisture collection; stainless steel breather with aluminum cap provides ventilation, minimizes moisture collection Cl. I, Div. 1 & 2, Groups C, D Cl. I, Div. 1 & 2, Groups B, C, D (with suffix GB) Cl. II, Div. 1, Groups E, F, G Cl. III • CID 101 corrosion inhibitor device is provided with each ELPS system to help protect electrical components and connections • Rugged, long-life, maintenance-free, nickel cadmium battery provides 30 watts of power for the required 11/2 hours • Solid state battery charger for long life and reliable service prevents deep discharge by automatically disconnecting luminaires from battery • Terminal block facilitates field wiring connections • Instruction sheet and maintenance record card provided with unit in a protective plastic envelope • A time delay is standard; time delay is preset at factory for 5 minute delay but can be field set for 5 seconds or 15 minutes, thus allowing HID type lamps time to restrike and reach desired illumination levels • Solid state battery charger will accept 120, 220/240 or 277 VAC, 50/60 Hz Certifications and Compliances: • NEC: Class I, Groups B, C, D Class II, Groups E, F, G Class III Simultaneous Presence • NEMA: 3R, 12 (ELPS power supply) • Suitable for wet locations (EVLA fixtures) • Marine (EVLA fixtures) • UL Standard: 844 – Electric Luminaire – Hazardous Locations 924 – Emergency Lighting and Power Equipment 1203 – Explosionproof and DustIgnitionproof Electrical Equipment • Life Safety Code: Section 5-9 (Emergency Lighting) • Suitable for Wet Locations • NEMA 3, 3R, 12 • Marine Standard Materials: • Power supply enclosure and luminaire assembly – copper-free aluminum (less than 0.4 of 1% copper) Standard Finishes: • Power supply enclosure and fixture assemblies – powder coat epoxy paint finish Electrical Ratings: • Power Supply: Input: 120, 220/240, 277 VAC, 50 or 60 Hz 0.5 Amps Maximum Output: 12 VDC UL listed for 28 watts for 11/2 hours at 0° – 40°C • Luminaires: Voltage: 12 VDC Lamp Type: #789, miniature Tungsten halogen, G4, 2-pin, 14 watt Options: Description Suffix • Remote mounted lamp head and arm .... EVLA12 • Key operated disconnect switch as part of the ELPS502 emergency light system .......................... S794 • Keyless operated designated disconnect switch as part of the ELPS502 emergency light system .......... S854 Ordering Information: Description www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Cat. # • Standard unit with ELPS502† adjustable heads............ • Replacement power interior, includes circuit ELPS K50 board and battery pack • Power supply ................. ELPS50† • Lamphead and arm ....... EVLA12† • Exit sign, double sided ELPS502 EXD with EVI, red letters........ • Exit sign, double sided ELPS502 EXD GN with EVI, green letters.... • Exit sign, single or double sided with Group B EVA, ELPS502 EXD GB red letters....................... • Exit sign, single or double sided with Group B EVA, green letters ............................. ELPS502 EXD GB GN • Exit sign, single sided with EVI, red letters........ ELPS502 EXS • Exit sign, single sided with EVI, green letters ................... ELPS502 EXS GN †Base unit comes standard with Class I, Division 1, Group B. 1150 Cl. I, Zone 1 Simultaneous Presence Wet Locations NEMA 3, 3R, 12 Copyright© 2011 Cooper Crouse-Hinds 1150-1151.qxp 5/30/2011 11:15 AM Page 1151 ELPS Light-Pak™ Emergency Lighting System Temperature Performance Data Photometric Data Dimensions and Weights Temperature Performance Data: Cat. # Class Maximum Ambient Temperature 55°C I II* EVLA12 III* 10L Photometric Data: T-number T4A T3B T3B Maximum Ambient Temperature 40°C ELPS EVI ELPS EVA T3C T4 T3C T4 *For Class II and Class III applications, fixtures must not be aimed more than 30° above horizontal (see diagram below). Dimensions In Inches: 10L Unit Net Weights: • ELPS502 complete emergency lighting system – 50 lbs. • ELPS50 power supply – 40 lbs. • EVLA12 luminaire assembly – 5 lbs. Status Indication: LED Status Condition No light Meaning of the Indication AC power is removed from the circuit • Steady light (no blinking) Fully charged • Light blinks once Charging •• Light blinks twice Battery failure Light blinks three times Light blinks four times Circuit failure Lamp failure ••• •••• www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1151 10L LED N2LPS LIGHT-PAK™ Emergency Lighting System Applications: LED N2LPS Light-Pak™ emergency lighting systems are used: • To provide reliable illumination for egress areas during failure or interruption of power to the normal lighting system • In areas where flammable gases or vapors may become present due to abnormal, unusual, or accidental conditions • In manufacturing plants, refineries, petrochemical and chemical plants, waste and sewage treatment facilities, oil terminals, food processing facilities, breweries, and other industrial manufacturing or process industry facilities subject to wet or corrosive conditions • To illuminate machinery or panels during a loss of AC power • Where moisture, dirt, dust, or corrosion will limit the life and reliability of ordinary emergency lighting systems • Where required by the National Electrical Code®, the Life Safety Code® or other applicable codes • Outdoor applications 10L Features: • Compact, factory-assembled luminaire featuring LED lamps for improved lumen performance, on-time, and lamp life • Nonmetallic, enclosed, and gasketed housing provides corrosion protection in the most extreme environments • Durable and marine rated LED lamp head assemblies provide protection against water ingress, corrosion, and impact • High temperature rated nickel cadmium battery for reliable operation up to 55ºC ambient • Solid state battery charger for long life and reliable battery operation prevents deep discharge by automatically disconnecting the battery from the luminaire • Factory-installed "push-to-test" button • Self-test, monitoring, and diagnostics reduce costly maintenance checks • Remote luminaire head assemblies (one or two) are available for mounting of luminaire heads away from main power system • Stainless steel drain minimizes moisture collection • Standard battery disconnect switch (Krydon® unit) 1152 www.crouse-hinds.com Cl. I, Div. 2, Groups B, C, D Cl. I, Zone 2 Wet Locations, Marine NEMA 3, 3R, 4X Ambient 0ºC to 55ºC Certifications and Compliances: NEC/CEC: • Class I, Division 2, Groups B, C, D, Zone 2 UL Standards: • 1598A (Supplemental Requirements for Luminaires for Installation on Marine Vessels) • 924 (Emergency Lighting and Power Equipment) • 844 (Electric Luminaires Hazardous Locations) CSA Standards: • C22.2 No. 141-M1985 unit equipment for emergency lighting • C22.2 No. 137-M1981 non-incendive electrical equipment for use in Class I, Division 2 hazardous locations • Life Safety Code NFPA101® – Section 5-9 (Emergency Lighting) • Marine wet locations suitability, Type 4X Standard Materials: • Power supply and remote luminaire enclosures – Krydon® fiberglassreinforced polyester • LED lamp head assembly – epoxy powder coated stainless steel • Exterior hardware – nylon, plastic coated, and stainless steel • Cover gasket – Hypalon® synthetic rubber Electrical Ratings: • Power supply – Input: 120, 220, 230, 240, or 277 VAC, 50 or 60 Hz; 28 watts max. Output: 12 VDC • Luminaire heads – Voltage: 12 VDC; Lamp: 3 watt LED Total lumen output: 80 Unit Net Weights: • • • • Temperature Performance Data: Based on 55°C ambient Cat. # Class I, Division 2 N2LPS (all) N2RF (all) Note: Note: 40ºC - T5; 55ºC - T4A T5 Ambient temperature at which the Light-Pak system is rated is 0°C to 55°C. Operation at temperatures outside this range will affect the battery life and/or charging performance. Battery time in emergency mode is 90 minutes. National Electrical Code and Life Safety Code are registered trademarks of the National Fire Protection Association, Inc. Noryl is a registered trademark of General Electric Company. US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2012 Cooper Crouse-Hinds N2LPS12222 – 16 lbs. N2LPS12220 – 12 lbs. N2RF1221 – 8 lbs. N2RF1222 – 9 lbs. 1152-1153.qxp 5/30/2011 11:15 AM Page 1153 LED N2LPS LIGHT-PAK™ Emergency Lighting System 10L Cl. I, Div. 2, Groups B, C, D Cl. I, Zone 2 Wet Locations, Marine NEMA 3, 3R, 4X Ambient 0ºC to 55ºC Ordering Information: Description Cat. # 28 watt, 12 volt power supply assembly with two 3 watt LED lamp heads 28 watt, 12 volt stainless steel power supply assembly with two 3 watt LED lamp heads 28 watt, 12 volt power supply assembly less luminaire heads Remote luminaire assembly with one 3 watt LED lamp head Remote luminaire assembly with two 3 watt LED lamp heads 28 watt, 120V LED Light-Pak with single sided exit sign** 28 watt, 277V LED Light-Pak with single sided exit sign** 28 watt, 120V LED Light-Pak with double sided exit sign** 28 watt, 277V LED Light-Pak with double sided exit sign** N2LPS12222 N2LPS12222 SS N2LPS12220* N2RF1221* N2RF1222* N2LPS12222/120 N2LPS12222/277 N2LPS12222/120 N2LPS12222/277 EXS DR0391734 EXS DR0391734 EXD DR0391734 EXD DR0391734 *Not cUL approved. UL Listed only. **Exit sign operates in both normal and emergency mode. Note: Up to four (4) remote LED lamp assemblies can be connected to the N2LPS12222. Up to six (6) remote LED lamp assemblies can be connected to the N2LPS12220. Wire Sizing for Remote Installation: For Copper Wire – Running Distance† (ft.) Between Power Supply and Remote Luminaire Load In Watts Load In Watts Wire Size 8 16 24 32 Wire Size 8 16 24 32 16 AWG 14 AWG 12 AWG 26 42 66 13 21 33 6 10 16 3 5 8 10 AWG 8 AWG 6 AWG 106 168 270 53 84 135 26 42 67 13 21 33 †Maximum distance to limit line voltage drop to 5%. Dimensions (N2LPS): 1.1 13.5 10L 16.0 7.5 5.0 13.8 14.5 7.4 18.0 Standard – N2LPS LED Light-Pak™ www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds 1153 1154-1155.qxp 5/30/2011 11:16 AM Page 1154 LED N2LPS LIGHT-PAK™ Emergency Lighting System 10L Cl. I, Div. 2, Groups B, C, D Cl. I, Zone 2 Wet Locations, Marine NEMA 3, 3R, 4X Ambient 0ºC to 55ºC Dimensions (N2LPS): EXS, EXD Option – N2LPS LED Light-Pak™ with Optional Emergency Exit Luminaire Dimensions (N2RF): 9.50 10L 9.50 3.83 3.83 7.27 4.38 11.77 Detail Indication Logic: Status Indication Status Description Status Definition * *-* **-** ***-*** No Light Steady Light (No Blinks) Light Blinks Once Light Blinks Twice Light Blinks Three Times AC Power Removed from Circuit Fully Charged Battery Charging Battery Failure Circuit Failure 1154 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2011 Cooper Crouse-Hinds