Guideline 1 (2) unofficial translation Transmission Service 15.2.2007 STANDARD RATED VALUES OF THE GRID RATED VOLTAGE, kV 110 400 MAXIMUM PERMITTED OPERATING VOLTAGE, kV INSULATION LEVELS OF SUBSTATIONS Minimum impulse test voltage (both polarities), kV - phase-to-earth - clearance between open contacts Minimum switching test voltage (dry and wet, both polarities), kV - phase-to-earth - clearance between open contacts Minimum test voltage at 50 Hz frequency (dry), kV - phase-to-earth - clearance between open contacts REQUIRED MINIMUM OPERATING TEMPERATURE OF APPARATUS In Southern and Western Finland, ºC In Northern and Eastern Finland, ºC INSULATION LEVELS OF OVERHEAD LINES Minimum impulse test voltage, kV Minimun switching test voltage, kV Minimum 50 Hz test voltage in one minute rain test, kV Minimum creepage distance, mm FLASHOVER DISTANCE ON INSULATOR STRING (clearance of arcing horns) suspension string, mm tension string, mm PHASE-TO-PHASE SPACING OF AN OVERHEAD LINE Minimum phase-to-phase spacing, m 123 420 550 630 1425 1425(+240) - 1050 900 (+345) 230 265 520 610 -40 -50 -40 -50 450 230 1960 1300 1050 6720 RADIO INTERFERFENCE TEST VOLTAGE, kV ) 870...890 2700...2750 1000..1020 2900...2950 4,0 1,1 8,5 123 3 1,1 420 3 RADIO INTERFERFENCE, CORONA AND ELECTROMAGNETIC FIELDS Equipment and installations shall be designed and implemented so that corona and other electrical discharge and radio interferences are minimized and do not exceed levels measured according to publicaation IEC - CISPR 18. For radio interferences requirements are as follows at 0,5 MHz frequency and at 20 m distance from outermost equipment or phase conductor: At substations (fair weather/rainy weather) < 60/75 dBm (µV/m) On power lines (fair weather/rainy weather) < 50/65 dBm (µV/m) Sound level shall not exceed by the side of the fence of substation and for power lines at distance of 20 m from the outermost phase conductor on fair weather the value of 45 dB (A) and on rainy and hoar-frost generating weather the value of 65 dB (A). The substation switchgears and busbar systems shall be designed so that maximum permissible exposure values of electromagnetic field are not exceeded at substation area at height 1 m of the ground. Electric field strength shall not exceed 10 kV/m nor shall magnetic field strength exceed value 500 T, unless stay on such areas is obstructed. CURRENT-CARRYUNG CAPACITIES Load rating and fault current rating requirements will always be defined on a case by case basis. The value put in brackets is the peak value of alternating voltage on opposite pole while testing the clearance between open contacts. Voltage distance and creepage distance of a tranposition string shall be at leat 1,7 -fold compared to standard suspension string. If phase conductors lie vertically over one another will phase-to-phase distance be determined according to "vahvavirtailmajohtomääräykset" (= "Overhead power line regulations" in Finnish). Guideline unofficial translation Transmission Service 15.2.2007 Required minimum operating temperature of apparatus 2 (2)