ESR-2795 - Hilti, Inc.

advertisement
Most Widely Accepted and Trusted 0 ICC‐ES Report ESR‐2795
ICC‐ES | (800) 423‐6587 | (562) 699‐0543 | www.icc‐es.org
000 Reissued 06/2016
This report is subject to renewal 06/2017.
DIVISION: 03 00 00—CONCRETE SECTION: 03 16 00—CONCRETE ANCHORS DIVISION: 05 00 00—METALS SECTION: 05 05 23—METAL FASTENINGS REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 EVALUATION SUBJECT: HILTI LOW‐VELOCITY POWDER‐ACTUATED X‐HS THREADED ROD HANGER ASSEMBLIES Look for the trusted marks of Conformity! “2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence” ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
A Subsidiary of ICC-ES Evaluation Report
ESR-2795
Reissued June 2016
This report is subject to renewal June 2017.
www.icc-es.org | (800) 423-6587 | (562) 699-0543
A Subsidiary of the International Code Council ®
3.0 DESCRIPTION
DIVISION: 03 00 00—CONCRETE
Section: 03 16 00—Concrete Anchors
3.1 X-HS Threaded Rod Hanger Assembly:
The Hilti X-HS threaded rod hanger assembly consists of
a Hilti X-U low velocity, powder-actuated fastener
(recognized in ESR-2269) with two premounted washers
(one of zinc-plated steel, one of plastic), and a premounted
cold-formed steel bracket (threaded rod hanger) having a
1
3
/4- or /8-inch-diameter (6.4 or 9.5 mm) internally threaded
1
3
hole to accommodate connection of /4- or /8-inchdiameter (6.4 or 9.5 mm) UNC threaded steel rods,
respectively. The X-HS U19 and X-HS U32 hanger
assemblies described in this report, include Hilti X-U19 and
X-U32 fasteners, respectively, recognized in ESR-2269.
The X-U19 and X-U32 fasteners have shank lengths of
0.75 inch (19 mm) and 1.26 inches (32 mm), respectively.
The threaded rod hangers are manufactured from mild
carbon steel with a zinc coating in accordance with Hilti’s
specifications. See Figure 1 for an illustration of the X-HS
threaded rod hanger assembly.
DIVISION: 05 00 00—METAL
Section: 05 05 23—Metal Fastenings
REPORT HOLDER:
HILTI, INC.
7250 DALLAS PARKWAY, SUITE 1000
PLANO, TEXAS 75024
(800) 879-8000
www.us.hilti.com
HNATechnicalServices@hilti.com
EVALUATION SUBJECT:
HILTI LOW-VELOCITY POWDER-ACTUATED X-HS
THREADED ROD HANGER ASSEMBLIES
1.0 EVALUATION SCOPE
3.2 Substrate Materials:
Compliance with the following codes:
3.2.1 Steel: Structural steel used in supports must
comply with the minimum strength requirements of ASTM
A36, A572 Grade 50 or A992, and must have a minimum
3
thickness of /16-inch (4.76 mm).
®
 2012 International Building Code (IBC)
®
 2012 International Residential Code (IRC)
 2009, 2006 and 2003 International Building Code
(IBC)*
®
 2009, 2006 and 2003 International Residential Code
(IRC)*
®
3.2.2 Normal-weight Concrete: Normal-weight concrete
must be stone-aggregate and comply with IBC Chapter 19
or IRC Section R402.2, as applicable. The minimum
concrete compressive strength at the time of fastener
installation is noted in Table 2.
The ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced
in this report are the same sections in the ADIBC.
3.2.3 Lightweight Concrete: Lightweight concrete must
be sand-lightweight complying with IBC Chapter 19. The
minimum concrete compressive strength at the time of
fastener installation is noted in Table 3.
†
 2013 Abu Dhabi International Building Code (ADIBC)
†
*Codes indicated with an asterisk are addressed in Section
8.0.
Property evaluated:
Structural
2.0 USES
Hilti X-HS low-velocity, powder-actuated, threaded rod
hanger assemblies are used as alternatives to the cast-inplace anchors described in IBC Section1908 for placement
in concrete, and the welds and bolts used to attach
materials to steel, described in IBC Sections 2204.1 and
2204.2, respectively. The assemblies are used to connect
threaded steel rods to the supporting material. The hanger
assemblies may be used where an engineered design is
submitted in accordance with IRC Section R301.1.3.
3.2.4 Steel Deck Panels: Steel deck panels must
conform to a code-referenced material standard, with the
minimum thickness and minimum yield strength noted in
Table 3. See Figures 4 through 6 for panel configuration
requirements.
4.0 DESIGN AND INSTALLATION
4.1 Design:
4.1.1 Allowable Loads: The allowable tension, shear
and 45-degree-angle loads for X-HS threaded rod hanger
assemblies installed into steel are provided in Table 1. The
allowable tension, shear and 45-degree-angle loads for
X-HS threaded rod hanger assemblies installed into
normal-weight concrete are provided in Table 2. The
allowable tension, shear and 45-degree-angle loads for
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
Page 1 of 5
ESR-2795 | Most Widely Accepted and Trusted
X-HS threaded rod hanger assemblies installed into sandlightweight concrete and into sand-lightweight concrete
filled steel deck panels are provided in Table 3. For other
angles of installation, allowable loads for assemblies
subjected to combined shear and tension forces must be
determined using the following equation:
(p/Pa) + (v/Va) ≤ 1
where:
p
= Actual tension load, lbf (N).
Pa = Allowable tension load, lbf (N).
v
= Actual shear load, lbf (N).
Va = Allowable shear load, lbf (N).
The stress increases and load reductions described in
IBC Section 1605.3 are not allowed for wind loads acting
alone or when combined with gravity loads. No increase is
allowed for vertical loads acting alone. Allowable loads
apply to the connection of the X-HS Hanger Assembly to
the base material only with threaded rod installed. Design
of the connection of the X-HS Hanger Assembly to the
suspended material must comply with the applicable
requirements of the IBC
4.1.2 Seismic Considerations:
4.1.2.1 Use with Structural Components: Resistance to
seismic loads is outside the scope of this report. Therefore,
the suitability of the Hilti X-HS Hanger Assemblies for use
with structural components that are subjected to seismic
loads is outside the scope of this report.
4.1.2.2 Use with Nonstructural Components: Seismic
load resistance is outside the scope of this report, except
when used with architectural, mechanical and electrical
components described in Section 13.1.4 of ASCE 7 and as
follows:
 Concrete Base Materials: The X-HS Hanger
Assemblies fastened to concrete may be used to
support acoustical tile or lay-in panel suspended ceiling
systems, distributed systems and distribution systems
where the service load on any individual X-HS Hanger
Assembly does not exceed the lesser of 90 lbf (400 N)
or the published allowable load shown in Table 2 or 3,
as applicable.
 Steel Base Materials: The X-HS Hanger Assemblies
fastened to steel may be used where the service load
on any individual X-HS Hanger Assembly does not
exceed the lesser of 250 lbf (1112 N) or the published
allowable load shown in Table 1.
4.2 Installation:
4.2.3 General: The X-HS threaded rod hanger
assemblies must be installed in accordance with this report
and the Hilti, Inc., published installation instructions,
including those shown in Figure 2. A copy of these
instructions must be available on the jobsite at all times
during installation. Installation is limited to dry, interior
locations.
Fastener placement requires the use of a low-velocity
powder-actuated tool in accordance with Hilti, Inc.
recommendations. Nailhead standoff distance must be
as noted in the footnotes to the tables and as shown in
Figure 2. Installers must be certified by Hilti and have a
current, Hilti-issued, operator’s license.
4.2.4 Fastening to Steel: When installation is in steel,
minimum spacing between fasteners must be 1 inch
1
(25.4 mm) and minimum edge distance must be /2 inch
(12.7 mm).
Page 2 of 5
4.2.5 Fastening to Concrete: Fasteners must be driven
into the normal-weight or sand-lightweight concrete after
the concrete attains the specified concrete compressive
strength. Unless otherwise noted, minimum spacing
between fasteners must be 4 inches (102 mm) and
minimum edge distance must be 3 inches (76 mm). Unless
otherwise noted in this report, concrete thickness must be
a minimum of 3 inches (76 mm).
4.2.6 Fastening to Sand-lightweight Concrete Filled
Steel Deck Panels: Installation in sand-lightweight
concrete filled steel deck panels must comply with Figures
4 through 6. Minimum distances from fastener centerline to
rolled deck panel flute edges must be as depicted in
Figures 4 through 6.
5.0 CONDITIONS OF USE
The Hilti X-HS threaded rod hanger assemblies described
in this report comply with, or are suitable alternatives to
what is specified in, those codes listed in Section 1.0 of
this report, subject to the following conditions:
5.1 The hanger assemblies are manufactured and
identified in accordance with this report.
5.2 Hanger assembly installation complies with this report
and the Hilti, Inc., published instructions. In the event
of conflict between this report and Hilti, Inc., published
instructions, this report governs.
5.3 Calculations demonstrating that the actual loads are
less than the allowable loads described in Section
4.1.1 must be submitted to the code official for
approval. The calculations must be prepared by a
registered design professional where required by the
statutes of the jurisdiction in which the project is
constructed.
5.4 Refer to Section 4.1.2 for seismic considerations.
5.5 The use of the hanger assemblies is limited to
installation in uncracked concrete. Cracking occurs
when ft > fr due to service loads or deformations.
5.6 Use of the hanger assemblies is limited to dry, interior
locations.
5.7 Installers must be certified by Hilti, Inc., and have a
current, Hilti-issued, operator’s license.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Fasteners Power-driven into Concrete, Steel and
Masonry Elements (AC70), dated February 2013.
7.0 IDENTIFICATION
The word “Hilti” and the designation “X-HS” are stamped
on the hanger. The X-U fastener is imprinted with an “H”
on the head. All hanger assemblies are identified on the
packaging, with the Hilti, Inc. name, the hanger type, the
fastener type and size, and the evaluation report number
(ESR-2795).
8.0 OTHER CODES
8.1 Evaluation Scope:
In addition to the 2012 IBC and 2012 IRC addressed in
Sections 2.0 through 7.0, the products in this report were
evaluated for compliance with the requirements of the
following codes:
 2009, 2006 and 2003 International Building Code
(2009, 2006 and 2003 IBC)
®
 2009, 2006 and 2003 International Residential Code
(2009, 2006 and 2003 IRC)
®
ESR-2795 | Most Widely Accepted and Trusted
Page 3 of 5
8.2 Uses:
8.4 Design and Installation:
The Hilti X-HS low-velocity threaded rod hanger
assemblies are used to connect materials as described in
Section 2.0. The hanger assemblies are used as
alternatives to the cast-in-place anchors described in 2009
and 2006 IBC Sections 1911 and 1912, and 2003 IBC
Sections 1912 and 1913 for placement in concrete, and the
welds and bolts used to attach materials to steel, as
described in 2009, 2006 and 2003 IBC Sections 2204.1
and 2204.2, respectively. The hanger assemblies may be
used where an engineered design is submitted in
accordance with 2009, 2006 and 2003 IRC Section
R301.1.3, as applicable.
8.4.1 Design:
8.4.1.1 Allowable Loads: See Section 4.1.1.
8.4.1.2 Seismic Considerations: See Section 4.1.2.
8.4.2 Installation: See Section 4.2.
8.5 Conditions of Use:
See Section 5.0.
8.6 Evidence Submitted:
See Section 6.0.
8.7 Identification:
8.3 Description:
See Section 7.0.
See Section 3.0.
TABLE 1—ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES DRIVEN INTO STEEL (lbf)1,2,3,4
LOADING CONDITION
HANGER ASSEMBLY
X-HS U19
Tension
Shear
45-degree
270
220
2755
For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N.
1
Nailhead Standoff, hNVS, must be less than or equal to 3/8 in. See Figure 2.
Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1/4- or 3/8-inch-diameter internally threaded hole.
3
See Figures 3a, 3b and 3c for load directions.
4
Allowable load capacities apply to base steel with minimum yield strength (Fy) of 36 ksi, a minimum tensile strength (Fu) of 58 ksi and a
minimum thickness of 3/16-inch.
5
Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section 4.1.1.
2
TABLE 2—ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES
INSTALLED IN NORMAL-WEIGHT CONCRETE (lbf)1,2,3,4,5
CONCRETE COMPRESSIVE STRENGTH
HANGER ASSEMBLY
2000 psi
Tension
X-HS U32
Shear
75
4000 psi
45-degree
Tension
606
100
Shear
85
45-degree
1206
150
For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa.
1
Fasteners must not be driven until the concrete has reached the specified compressive strength [minimum of 24 MPa is required under
ADIBC Appendix L, Section 5.1.1].
2
Concrete material thickness at the point of penetration must be a minimum of 3 inches.
3
Nailhead Standoff, hNVS, must be less than or equal to 3/8 in. for the X-HS U32 hanger assembly. See Figure 2.
4
Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1/4- or 3/8-inch-diameter internally threaded hole.
5
See Figures 3a, 3b and 3c for load directions.
6
Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section 4.1.1.
TABLE 3—ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES INSTALLED INTO MINIMUM f′c = 3,000 psi
SAND-LIGHTWEIGHT CONCRETE AND COMPOSITE STEEL DECK PANELS (lbf)1,2,3,4,5,6,7
FASTENER LOCATION
HANGER
ASSEMBLY
Installed into
Structural Sandlightweight Concrete
Installed through 11/2 in. Deep Steel Deck Panel
Into Sand-lightweight Concrete
Upper Flute
Installed through 3 in. Deep Steel Deck Panel Into
Sand-lightweight Concrete
Lower Flute
Upper Flute
Lower Flute
4545454545Tension Shear
Tension Shear
Tension Shear
Tension Shear
Tension Shear
degree
degree
degree
degree
degree
X-HS U32
95
115
1058
95
220
1358
95
220
1358
125
220
1758
95
220
1358
For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa.
1
Fasteners must not be driven until the concrete has reached the specified compressive strength [minimum of 24 MPa is required under ADIB
Appendix L, Section 5.1.1].
2
Concrete material thickness at the point of penetration must be a minimum of 3 inches, except as shown in Figures 4, 5 and 6.
3
Deck panel must have a minimum No. 20 gage (0.0359 inch) base-metal thickness and a minimum yield strength of 33,000 psi.
4
Nailhead Standoff, hNVS, must be less than or equal to 3/8 in. for the X-HS U32 hanger assembly. See Figure 2.
5
Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1/4- or 3/8-inch-diameter internally threaded hole.
6
See Figures 3a, 3b and 3c for load directions.
7
See Figures 4, 5 and 6 for nominal flute dimensions, fastener locations, and load orientations.
8
Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section 4.1.1.
ESR-2795 | Most Widely Accepted and Trusted
FIGURE 1—X-HS THREADED ROD HANGER ASSEMBLY
FIGURE 2—X-HS INSTALLATION INSTRUCTIONS
FIGURE 3—X-HS LOAD DIRECTIONS
Page 4 of 5
ESR-2795 | Most Widely Accepted and Trusted
FIGURE 4—HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION
IN 3-INCH-DEEP COMPOSITE FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION
FIGURE 5—HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION
IN 11/2-INCH-DEEP FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION
For SI: 1 inch = 25.4 mm, 1 psi = 6895 Pa.
FIGURE 6—HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION
IN 11/2-INCH-DEEP FLOOR DECK PANEL, INVERTED DECK PANEL PROFILE ORIENTATION
Page 5 of 5
ICC-ES Evaluation Report
ESR-2795 FBC Supplement
Reissued June 2016
This report is subject to renewal June 2017.
www.icc-es.org | (800) 423-6587 | (562) 699-0543
A Subsidiary of the International Code Council ®
DIVISION: 03 00 00—CONCRETE
Section: 03 16 00—Concrete Anchors
DIVISION: 05 00 00—METALS
Section: 05 05 23—Metal Fastenings
REPORT HOLDER:
HILTI, INC.
7250 DALLAS PARKWAY, SUITE 1000
PLANO, TEXAS 75024
(800) 879-8000
www.us.hilti.com
HNATechnicalServices@hilti.com
EVALUATION SUBJECT:
HILTI LOW-VELOCITY POWDER-ACTUATED X-HS THREADED ROD HANGER ASSEMBLIES
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that the Hilti Low-Velocity Powder-Actuated X-HS Threaded
Rod Hanger Assemblies, recognized in ICC-ES master report ESR-2795, have also been evaluated for compliance with the
codes noted below
Applicable Code Editions:
 2010 Florida Building Code—Building
 2010 Florida Building Code—Residential
Property evaluated:
Structural
2.0 CONCLUSIONS
The Hilti Low-Velocity Powder-Actuated X-HS Threaded Rod Hanger Assemblies, described in Sections 2.0 through 7.0 and
in Tables 1 through 3 of the master report ESR-2795, comply with the 2010 Florida Building Code—Building and the 2010
Florida Building Code—Residential, provided the design and installation are in accordance with the International Building
Code® provisions noted in the master report, and the following additional conditions apply:
 Design wind loads must be based on Section 1609 of the 2010 Florida Building Code—Building or Section 301.2.1.1 of
the 2010 Florida Building Code—Residential, as applicable.
 Load combinations must be in accordance with Section 1605.2 or 1605.3 of the 2010 Florida Building Code—Building, as
applicable.
Use of the Hilti threaded rod hanger assemblies has also been found to be in compliance with the High-Velocity Hurricane
Zone provisions of the 2010 Florida Building Code—Building and the 2010 Florida Building Code—Residential under the
following conditions:
 Design wind loads must be based on Section 1620 of the Florida Building Code—Building.
 The use of Hilti X-HS Threaded Rod Hanger Assemblies as a means of attachment for wood blocking, as defined in
Section 2330.1.1 of the 2010 Florida Building Code—Building, in a roof assembly in the High-Velocity Hurricane Zone, is
prohibited.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000
Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved.
Page 1 of 2
ESR-2795 | Most Widely Accepted and Trusted
Page 2 of 2
 The fasteners have not been evaluated for use as cast-in-place anchors for compliance with the High-velocity Hurricane
Zone provisions and this use is outside the scope of this evaluation report.
 The use of threaded rods for lateral bracing of habitable structures in the High-Velocity Hurricane Zone is prohibited, in
accordance with Section 2222.3.3 of the 2010 Florida Building Code—Building and Section R4408.9.3.3 of the 2010
Florida Building Code—Residential.
For products falling under Florida Rule 9N-3, verification that the report holder’s quality assurance program is audited by a
quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master evaluation report, reissued June 2016.
Download