Most Widely Accepted and Trusted 0 ICC‐ES Report ESR‐2795 ICC‐ES | (800) 423‐6587 | (562) 699‐0543 | www.icc‐es.org 000 Reissued 06/2016 This report is subject to renewal 06/2017. DIVISION: 03 00 00—CONCRETE SECTION: 03 16 00—CONCRETE ANCHORS DIVISION: 05 00 00—METALS SECTION: 05 05 23—METAL FASTENINGS REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 EVALUATION SUBJECT: HILTI LOW‐VELOCITY POWDER‐ACTUATED X‐HS THREADED ROD HANGER ASSEMBLIES Look for the trusted marks of Conformity! “2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence” ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. A Subsidiary of ICC-ES Evaluation Report ESR-2795 Reissued June 2016 This report is subject to renewal June 2017. www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ® 3.0 DESCRIPTION DIVISION: 03 00 00—CONCRETE Section: 03 16 00—Concrete Anchors 3.1 X-HS Threaded Rod Hanger Assembly: The Hilti X-HS threaded rod hanger assembly consists of a Hilti X-U low velocity, powder-actuated fastener (recognized in ESR-2269) with two premounted washers (one of zinc-plated steel, one of plastic), and a premounted cold-formed steel bracket (threaded rod hanger) having a 1 3 /4- or /8-inch-diameter (6.4 or 9.5 mm) internally threaded 1 3 hole to accommodate connection of /4- or /8-inchdiameter (6.4 or 9.5 mm) UNC threaded steel rods, respectively. The X-HS U19 and X-HS U32 hanger assemblies described in this report, include Hilti X-U19 and X-U32 fasteners, respectively, recognized in ESR-2269. The X-U19 and X-U32 fasteners have shank lengths of 0.75 inch (19 mm) and 1.26 inches (32 mm), respectively. The threaded rod hangers are manufactured from mild carbon steel with a zinc coating in accordance with Hilti’s specifications. See Figure 1 for an illustration of the X-HS threaded rod hanger assembly. DIVISION: 05 00 00—METAL Section: 05 05 23—Metal Fastenings REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 (800) 879-8000 www.us.hilti.com HNATechnicalServices@hilti.com EVALUATION SUBJECT: HILTI LOW-VELOCITY POWDER-ACTUATED X-HS THREADED ROD HANGER ASSEMBLIES 1.0 EVALUATION SCOPE 3.2 Substrate Materials: Compliance with the following codes: 3.2.1 Steel: Structural steel used in supports must comply with the minimum strength requirements of ASTM A36, A572 Grade 50 or A992, and must have a minimum 3 thickness of /16-inch (4.76 mm). ® 2012 International Building Code (IBC) ® 2012 International Residential Code (IRC) 2009, 2006 and 2003 International Building Code (IBC)* ® 2009, 2006 and 2003 International Residential Code (IRC)* ® 3.2.2 Normal-weight Concrete: Normal-weight concrete must be stone-aggregate and comply with IBC Chapter 19 or IRC Section R402.2, as applicable. The minimum concrete compressive strength at the time of fastener installation is noted in Table 2. The ADIBC is based on the 2009 IBC. 2009 IBC code sections referenced in this report are the same sections in the ADIBC. 3.2.3 Lightweight Concrete: Lightweight concrete must be sand-lightweight complying with IBC Chapter 19. The minimum concrete compressive strength at the time of fastener installation is noted in Table 3. † 2013 Abu Dhabi International Building Code (ADIBC) † *Codes indicated with an asterisk are addressed in Section 8.0. Property evaluated: Structural 2.0 USES Hilti X-HS low-velocity, powder-actuated, threaded rod hanger assemblies are used as alternatives to the cast-inplace anchors described in IBC Section1908 for placement in concrete, and the welds and bolts used to attach materials to steel, described in IBC Sections 2204.1 and 2204.2, respectively. The assemblies are used to connect threaded steel rods to the supporting material. The hanger assemblies may be used where an engineered design is submitted in accordance with IRC Section R301.1.3. 3.2.4 Steel Deck Panels: Steel deck panels must conform to a code-referenced material standard, with the minimum thickness and minimum yield strength noted in Table 3. See Figures 4 through 6 for panel configuration requirements. 4.0 DESIGN AND INSTALLATION 4.1 Design: 4.1.1 Allowable Loads: The allowable tension, shear and 45-degree-angle loads for X-HS threaded rod hanger assemblies installed into steel are provided in Table 1. The allowable tension, shear and 45-degree-angle loads for X-HS threaded rod hanger assemblies installed into normal-weight concrete are provided in Table 2. The allowable tension, shear and 45-degree-angle loads for ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. 1000 Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 5 ESR-2795 | Most Widely Accepted and Trusted X-HS threaded rod hanger assemblies installed into sandlightweight concrete and into sand-lightweight concrete filled steel deck panels are provided in Table 3. For other angles of installation, allowable loads for assemblies subjected to combined shear and tension forces must be determined using the following equation: (p/Pa) + (v/Va) ≤ 1 where: p = Actual tension load, lbf (N). Pa = Allowable tension load, lbf (N). v = Actual shear load, lbf (N). Va = Allowable shear load, lbf (N). The stress increases and load reductions described in IBC Section 1605.3 are not allowed for wind loads acting alone or when combined with gravity loads. No increase is allowed for vertical loads acting alone. Allowable loads apply to the connection of the X-HS Hanger Assembly to the base material only with threaded rod installed. Design of the connection of the X-HS Hanger Assembly to the suspended material must comply with the applicable requirements of the IBC 4.1.2 Seismic Considerations: 4.1.2.1 Use with Structural Components: Resistance to seismic loads is outside the scope of this report. Therefore, the suitability of the Hilti X-HS Hanger Assemblies for use with structural components that are subjected to seismic loads is outside the scope of this report. 4.1.2.2 Use with Nonstructural Components: Seismic load resistance is outside the scope of this report, except when used with architectural, mechanical and electrical components described in Section 13.1.4 of ASCE 7 and as follows: Concrete Base Materials: The X-HS Hanger Assemblies fastened to concrete may be used to support acoustical tile or lay-in panel suspended ceiling systems, distributed systems and distribution systems where the service load on any individual X-HS Hanger Assembly does not exceed the lesser of 90 lbf (400 N) or the published allowable load shown in Table 2 or 3, as applicable. Steel Base Materials: The X-HS Hanger Assemblies fastened to steel may be used where the service load on any individual X-HS Hanger Assembly does not exceed the lesser of 250 lbf (1112 N) or the published allowable load shown in Table 1. 4.2 Installation: 4.2.3 General: The X-HS threaded rod hanger assemblies must be installed in accordance with this report and the Hilti, Inc., published installation instructions, including those shown in Figure 2. A copy of these instructions must be available on the jobsite at all times during installation. Installation is limited to dry, interior locations. Fastener placement requires the use of a low-velocity powder-actuated tool in accordance with Hilti, Inc. recommendations. Nailhead standoff distance must be as noted in the footnotes to the tables and as shown in Figure 2. Installers must be certified by Hilti and have a current, Hilti-issued, operator’s license. 4.2.4 Fastening to Steel: When installation is in steel, minimum spacing between fasteners must be 1 inch 1 (25.4 mm) and minimum edge distance must be /2 inch (12.7 mm). Page 2 of 5 4.2.5 Fastening to Concrete: Fasteners must be driven into the normal-weight or sand-lightweight concrete after the concrete attains the specified concrete compressive strength. Unless otherwise noted, minimum spacing between fasteners must be 4 inches (102 mm) and minimum edge distance must be 3 inches (76 mm). Unless otherwise noted in this report, concrete thickness must be a minimum of 3 inches (76 mm). 4.2.6 Fastening to Sand-lightweight Concrete Filled Steel Deck Panels: Installation in sand-lightweight concrete filled steel deck panels must comply with Figures 4 through 6. Minimum distances from fastener centerline to rolled deck panel flute edges must be as depicted in Figures 4 through 6. 5.0 CONDITIONS OF USE The Hilti X-HS threaded rod hanger assemblies described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The hanger assemblies are manufactured and identified in accordance with this report. 5.2 Hanger assembly installation complies with this report and the Hilti, Inc., published instructions. In the event of conflict between this report and Hilti, Inc., published instructions, this report governs. 5.3 Calculations demonstrating that the actual loads are less than the allowable loads described in Section 4.1.1 must be submitted to the code official for approval. The calculations must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is constructed. 5.4 Refer to Section 4.1.2 for seismic considerations. 5.5 The use of the hanger assemblies is limited to installation in uncracked concrete. Cracking occurs when ft > fr due to service loads or deformations. 5.6 Use of the hanger assemblies is limited to dry, interior locations. 5.7 Installers must be certified by Hilti, Inc., and have a current, Hilti-issued, operator’s license. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Fasteners Power-driven into Concrete, Steel and Masonry Elements (AC70), dated February 2013. 7.0 IDENTIFICATION The word “Hilti” and the designation “X-HS” are stamped on the hanger. The X-U fastener is imprinted with an “H” on the head. All hanger assemblies are identified on the packaging, with the Hilti, Inc. name, the hanger type, the fastener type and size, and the evaluation report number (ESR-2795). 8.0 OTHER CODES 8.1 Evaluation Scope: In addition to the 2012 IBC and 2012 IRC addressed in Sections 2.0 through 7.0, the products in this report were evaluated for compliance with the requirements of the following codes: 2009, 2006 and 2003 International Building Code (2009, 2006 and 2003 IBC) ® 2009, 2006 and 2003 International Residential Code (2009, 2006 and 2003 IRC) ® ESR-2795 | Most Widely Accepted and Trusted Page 3 of 5 8.2 Uses: 8.4 Design and Installation: The Hilti X-HS low-velocity threaded rod hanger assemblies are used to connect materials as described in Section 2.0. The hanger assemblies are used as alternatives to the cast-in-place anchors described in 2009 and 2006 IBC Sections 1911 and 1912, and 2003 IBC Sections 1912 and 1913 for placement in concrete, and the welds and bolts used to attach materials to steel, as described in 2009, 2006 and 2003 IBC Sections 2204.1 and 2204.2, respectively. The hanger assemblies may be used where an engineered design is submitted in accordance with 2009, 2006 and 2003 IRC Section R301.1.3, as applicable. 8.4.1 Design: 8.4.1.1 Allowable Loads: See Section 4.1.1. 8.4.1.2 Seismic Considerations: See Section 4.1.2. 8.4.2 Installation: See Section 4.2. 8.5 Conditions of Use: See Section 5.0. 8.6 Evidence Submitted: See Section 6.0. 8.7 Identification: 8.3 Description: See Section 7.0. See Section 3.0. TABLE 1—ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES DRIVEN INTO STEEL (lbf)1,2,3,4 LOADING CONDITION HANGER ASSEMBLY X-HS U19 Tension Shear 45-degree 270 220 2755 For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N. 1 Nailhead Standoff, hNVS, must be less than or equal to 3/8 in. See Figure 2. Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1/4- or 3/8-inch-diameter internally threaded hole. 3 See Figures 3a, 3b and 3c for load directions. 4 Allowable load capacities apply to base steel with minimum yield strength (Fy) of 36 ksi, a minimum tensile strength (Fu) of 58 ksi and a minimum thickness of 3/16-inch. 5 Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section 4.1.1. 2 TABLE 2—ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES INSTALLED IN NORMAL-WEIGHT CONCRETE (lbf)1,2,3,4,5 CONCRETE COMPRESSIVE STRENGTH HANGER ASSEMBLY 2000 psi Tension X-HS U32 Shear 75 4000 psi 45-degree Tension 606 100 Shear 85 45-degree 1206 150 For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa. 1 Fasteners must not be driven until the concrete has reached the specified compressive strength [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. 2 Concrete material thickness at the point of penetration must be a minimum of 3 inches. 3 Nailhead Standoff, hNVS, must be less than or equal to 3/8 in. for the X-HS U32 hanger assembly. See Figure 2. 4 Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1/4- or 3/8-inch-diameter internally threaded hole. 5 See Figures 3a, 3b and 3c for load directions. 6 Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section 4.1.1. TABLE 3—ALLOWABLE LOADS FOR HILTI X-HS THREADED ROD HANGER ASSEMBLIES INSTALLED INTO MINIMUM f′c = 3,000 psi SAND-LIGHTWEIGHT CONCRETE AND COMPOSITE STEEL DECK PANELS (lbf)1,2,3,4,5,6,7 FASTENER LOCATION HANGER ASSEMBLY Installed into Structural Sandlightweight Concrete Installed through 11/2 in. Deep Steel Deck Panel Into Sand-lightweight Concrete Upper Flute Installed through 3 in. Deep Steel Deck Panel Into Sand-lightweight Concrete Lower Flute Upper Flute Lower Flute 4545454545Tension Shear Tension Shear Tension Shear Tension Shear Tension Shear degree degree degree degree degree X-HS U32 95 115 1058 95 220 1358 95 220 1358 125 220 1758 95 220 1358 For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa. 1 Fasteners must not be driven until the concrete has reached the specified compressive strength [minimum of 24 MPa is required under ADIB Appendix L, Section 5.1.1]. 2 Concrete material thickness at the point of penetration must be a minimum of 3 inches, except as shown in Figures 4, 5 and 6. 3 Deck panel must have a minimum No. 20 gage (0.0359 inch) base-metal thickness and a minimum yield strength of 33,000 psi. 4 Nailhead Standoff, hNVS, must be less than or equal to 3/8 in. for the X-HS U32 hanger assembly. See Figure 2. 5 Allowable loads apply to X-HS threaded rod hanger assemblies with either the 1/4- or 3/8-inch-diameter internally threaded hole. 6 See Figures 3a, 3b and 3c for load directions. 7 See Figures 4, 5 and 6 for nominal flute dimensions, fastener locations, and load orientations. 8 Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section 4.1.1. ESR-2795 | Most Widely Accepted and Trusted FIGURE 1—X-HS THREADED ROD HANGER ASSEMBLY FIGURE 2—X-HS INSTALLATION INSTRUCTIONS FIGURE 3—X-HS LOAD DIRECTIONS Page 4 of 5 ESR-2795 | Most Widely Accepted and Trusted FIGURE 4—HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION IN 3-INCH-DEEP COMPOSITE FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION FIGURE 5—HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION IN 11/2-INCH-DEEP FLOOR DECK PANEL, NORMAL DECK PANEL PROFILE ORIENTATION For SI: 1 inch = 25.4 mm, 1 psi = 6895 Pa. FIGURE 6—HILTI X-HS THREADED ROD HANGER ASSEMBLY LOCATION IN 11/2-INCH-DEEP FLOOR DECK PANEL, INVERTED DECK PANEL PROFILE ORIENTATION Page 5 of 5 ICC-ES Evaluation Report ESR-2795 FBC Supplement Reissued June 2016 This report is subject to renewal June 2017. www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ® DIVISION: 03 00 00—CONCRETE Section: 03 16 00—Concrete Anchors DIVISION: 05 00 00—METALS Section: 05 05 23—Metal Fastenings REPORT HOLDER: HILTI, INC. 7250 DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 (800) 879-8000 www.us.hilti.com HNATechnicalServices@hilti.com EVALUATION SUBJECT: HILTI LOW-VELOCITY POWDER-ACTUATED X-HS THREADED ROD HANGER ASSEMBLIES 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that the Hilti Low-Velocity Powder-Actuated X-HS Threaded Rod Hanger Assemblies, recognized in ICC-ES master report ESR-2795, have also been evaluated for compliance with the codes noted below Applicable Code Editions: 2010 Florida Building Code—Building 2010 Florida Building Code—Residential Property evaluated: Structural 2.0 CONCLUSIONS The Hilti Low-Velocity Powder-Actuated X-HS Threaded Rod Hanger Assemblies, described in Sections 2.0 through 7.0 and in Tables 1 through 3 of the master report ESR-2795, comply with the 2010 Florida Building Code—Building and the 2010 Florida Building Code—Residential, provided the design and installation are in accordance with the International Building Code® provisions noted in the master report, and the following additional conditions apply: Design wind loads must be based on Section 1609 of the 2010 Florida Building Code—Building or Section 301.2.1.1 of the 2010 Florida Building Code—Residential, as applicable. Load combinations must be in accordance with Section 1605.2 or 1605.3 of the 2010 Florida Building Code—Building, as applicable. Use of the Hilti threaded rod hanger assemblies has also been found to be in compliance with the High-Velocity Hurricane Zone provisions of the 2010 Florida Building Code—Building and the 2010 Florida Building Code—Residential under the following conditions: Design wind loads must be based on Section 1620 of the Florida Building Code—Building. The use of Hilti X-HS Threaded Rod Hanger Assemblies as a means of attachment for wood blocking, as defined in Section 2330.1.1 of the 2010 Florida Building Code—Building, in a roof assembly in the High-Velocity Hurricane Zone, is prohibited. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. 1000 Copyright © 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 2 ESR-2795 | Most Widely Accepted and Trusted Page 2 of 2 The fasteners have not been evaluated for use as cast-in-place anchors for compliance with the High-velocity Hurricane Zone provisions and this use is outside the scope of this evaluation report. The use of threaded rods for lateral bracing of habitable structures in the High-Velocity Hurricane Zone is prohibited, in accordance with Section 2222.3.3 of the 2010 Florida Building Code—Building and Section R4408.9.3.3 of the 2010 Florida Building Code—Residential. For products falling under Florida Rule 9N-3, verification that the report holder’s quality assurance program is audited by a quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the master evaluation report, reissued June 2016.