IEEE C57.ll5-1991 (Redesignation of IEEE Std 754, issued for trial UIW in May 1984) IEEE Guide for Loading Mineral-Oil-Immersed Power Transformers Rated in Excess of 100 MVA (65 "C Winding Rise) Sponsor Transformers Committee of the IEEE Power E n g i " g Society Approved March 21,1991 IEm3:dardSM Abstract: This guide covers modern power transformers rated above 100 MVA, three-phase equivalent, and 65 "C rise. The general approach is tutorial. Four different types of loading, that is, normal life expectancy loading, planned loading beyond nameplate rating, long-time emergency loading, and short-time emergency loading, are considered. The various effects of loading a transformer in excess of its nameplate rating are discussed. Temperature and maximum loading limitations are suggested. Keywords: emergency loading, loading, mineral-oil-immersed power transformers, nameplate rating, power transformers, temperature, transformers The Institute of Electrical and Electronics Engineers, Inc. 345 East 47th Street, New York, NY 10017-2394, USA Copyright 0 1991 by the Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 1991 Printed in the United States of America ISBN 1-55937-131-5 No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher. IEEE Standards documents are developed within the Technical Committees of the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Board. Members of the committees serve voluntarily and without compensation. They are not necessarily members of the Institute. The standards developed within IEEE represent a consensus of the broad expertise on the subject within the Institute as well a s those activities outside of IEEE that have expressed an interest in participating in the development of the standard. Use of an IEEE Standard is wholly voluntary. The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE Standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change brought about through developments in the state of the art and comments received from users of the standard. Every IEEE Standard is subjected to review at least every five years for revision or reaffirmation. When a document is more than five years old and has not been reaffirmed, it is reasonable to conclude that its contents, although still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the latest edition of any IEEE Standard. Comments for revision of IEEE Standards are welcome from any interested party, regardless of membership affiliation with IEEE. Suggestions for changes in documents should be in the form of a proposed change of text, together with appropriate supporting comments. Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as they relate t o specific applications. When the need for interpretations is brought to the attention of IEEE, the Institute will initiate action to prepare appropriate responses. Since IEEE Standards represent a consensus of all concerned interests, it is important to ensure that any interpretation has also received the concurrence of a balance of interests. For this reason IEEE and the members of its technical committees are not able to provide an instant response t o interpretation requests except in those cases where the matter has previously received formal consideration. Comments on standards and requests for interpretations should be addressed to: Secretary, IEEE Standards Board 445 Hoes Lane P.O. Box 1331 Piscataway, N J 08855-1331 P. n USA IEEE Standards documents are adopted by the Institute of Electricaland Electronics Engineers without regard to whether their adoption may involve patents on articles, materials, or processes. Such adoption does not assume any liability to any patent owner, nor does it assume any obligation whatever to parties adopting the standards documents. A Foreword (This Foreword is not a part of IEEE C57.115-1991, IEEE Guide for Loading Mineral-Oil-ImmersedPower Transformers Rated in Excess of 100 MVA (65 "C Winding Rise.) This guide for loading mineral-oil-immersed power transformers rated in excess of 100 MVA has been developed to cover modern power transformers rated above 100 MVA, three-phase equivalent, and 65 "C rise. I t was prepared t o make available the best engineering knowledge on subjects of concern to the industry. The general approach in this guide is tutorial. Four different types of loading (1 Normal Life Expectancy Loading (2) Planned Loading Beyond Nameplate Rating (3) Long-Time Emergency Loading (4) Short-Time Emergency Loading are considered. The various effects of loading a transformer in excess of its nameplate rating are discussed. Temperature and maximum loading limitations are suggested. The equations given in Section 3 are from IEEE C57.92-1981and have been in general industry use for many years. However, questions have now been raised on the accuracy of these equations, and a task force has been set up within the IEEE Transformers Committee t o review the state of the art in this area. One of the major concerns in this guide is based on the evidence that a reduction in dielectric strength may occur due to the formation of free gas bubbles a t temperatures above 140 "C in the insulated conductors. A potential risk could occur in the operation of the transformer above 140 "C.This risk is a function of the amount of free gas generated because it can cause dielectric failure during an overvoltage condition and possibly a t rated power frequency voltage. In the event of generation of free gas within the insulation, dielectric strength will be degraded while the gas is present. However, this fact does not necessarily indicate that any permanent dielectric degradation would occur. Tutorial appendixes covering gas evolution, ancillary parts, methods of calculating acceptable loading levels, and philosophy applicable t o older transformers are included. Comments on this guide are welcomed and should be addressed t o the Secretary IEEE Standards Board 445 Hoes Lane P.O. Box 1331 Piscataway, NJ 08855-1331, USA At the time that this guide was approved, the members of the Task Force to Develop a Loading Guide for Transformers Above 100 MVA of the Working Group on Guides for Loading within the Insulation Life Subcommittee were as follows: C . E. Mitchell, Secretary D. H. Douglas, Chair J. Aubin L. Burnett 0.0. Chew 0. R. Compton C. Crichton J. C. Dutton D. J. Fallon J. A. Forster C. M. Gardam R. L. Grubb C. C. Honey R. C. Kiercn J. J. Kunes W. Lampe C. Lindsay J. W. Matthews L. S. McCormick W. J. McNutt R. E. Minkwitz P. Q. Nelson R. A. Olsson J. H. Ottevangers B. K. Pate1 D. D. Perco D. H. Ryder T. Singh F. W. Thomason T. P. Traub R. A. Veitch R. J. Whearty E.J. Yasuda The following persons were members of the balloting group that approved this document for submission to the IEEE Standards Board as a trial-use standard: L. C. Aicher J. Alacchi D. J. Allen B. F. Allen R. Allustiarti R. I. Alton S. J. Antalis E. H. Aieski J. C. Arnold R. Bancroft G. M. Bell P. L. Bellaschi S. Bennon J. J. Bergeron J. V. Bonucchi J. D. Borst G. H. Bowers F. J. Brutt D. F. Buchanon D. J. Cash E. E. Chartier 0. R. Compton F. W. Cook J. Cockran M. G. Daniels R. C. Degeneff J. E. Dind D.H. Douglas P. P. Falkowski W. R. Farber H. G. Fisher J. A. Forster S.L. Foster M. Frydman H. E. Gabel, Jr. J. D. Douglass D. A. Duckett J. C. Dutton J. K. Easley E. C. Edwards R. L. Ensign C. G. Evans C. M. Gardarn D. A. Gillies A. W. Goldman J. C. Gorub W. F. Grifford R. L. Grubb G. Gunnels G. Hall J. L. Harbell J. H. Harlaw T. K. Hawkins F. W. Heinrichs J. J. Herrera K. R. Highton P. J. Hoefler C. C. Honey E. L. Hook E. J. Huber C. Hurty G. W. Iliff R. G. Jacobsen E. T. Jauch D. C. Johnson C. P. Kappeler 0. Keller J. J. Kelly A. D.Kline T. S. Lauber R. E. Liebich H. F. Light C. Lindsay T. G. Lipscomb L. W. Long R. I. Lowe M. L. Manning H. B. Margolis J. W.Matthews L. S.McCormick G. G. McCrae C. J. McMillen W.J. McNutt S.P. Mehta N. J. Melton C. K. Miller C. Millian R. E. Minkwitz, Sr. C. E. Mitchell H. P. Moser R. J. Musil W. H. Mutschler E. T. Norton R. A. Olsson J. H. Ottevangers H. A. Pearce D. A. Roach L. J. Savio R. L. Schmid B. E. Smith L. R. Smith I. W. W. Stein L. R. Stensland R. B. Stetson F. R. Stockum D. Takach A. L. Tanton R. C. Thomas F. W. Thomaeon T. P. Traub E. F. Troy D. E. Trusx R. E. Uptegraff, Jr. S. G. Vargo R. A. Veitch J. P. Vora J. W. Walton S. A. Weinck R. J. Whearty A. Wilks J. R. Woodall W. E. Wrenn A. C. Wurdack D. A. Yannucci At the time this recommended practice was published, it was under consideration for approval as an American National Standard. The Accredited Standards Committee on Transformers, Regulators, and Reactors, C57, had the following members at the time this document was sent to letter ballot : Leo J. Savio, Chair Organization Represented Electric Light and Power Group John G Gauthier,Secretary Name of Representative ................................................................................... P. E. Orehek S.M. A. Rizvi F. Stevens J. Sullivan J. C. Thompson M. C. Mingoia (Alt.) Institute of Electrical and Electronics Engineers .................................................................. J. D.Borst J. Davis J. H. Harlow L. Savio H. D. Smith R. A. Veitch f l National Electrical Manufacturers Association.. .............................................................. G. D. Coulter P. Dewever J. D. Douglas A. A. Ghafourian K. R. Linsley R. L. Plaster H. Robin R. E. Uptegraff, Jr. P. J. Hopkinson (Alt.) J. Nay (Alt.) ......................................................................................... F. A. Lewis Underwriters Laboratories, Inc. ............................................................................... W. T. O'Grady US Department of Agriculture, REA ................................................................................... J. Bohlk US Department of Energy, Western Area Power Administration ........................................ D. R. Torgerson US Department of the Interior, Bureau of Reclamation.. .................................................... F. W. Cook, Sr. US Department of the Navy, Civil Engineering Corps.. ...................................................... .H. P. Stickley Tennessee Valley Authority When the IEEE Standards Board approved this standard on March 21,1991, it had the following membership: Marco W.Migliaro, Chairman Donald C. Loughry, Vice Chairman Andrew G. Salem, Secretary Dennis Bodson Paul L. Borrill Clyde Camp James M. Daly Donald C. Fleckenstein Jay Forster" David F. Franklin Ingrid Fromm *Member Emeritus Thomas L. Hannan Donald N. Heirman Kenneth D. Hendrix John W. Horch Ben C. Johnson Ivor N. Knight Joseph L. Koepfinger* Irving Kolodny Michael A. Lawler John E. May, Jr. Lawrence V. McCall Donald T. Michael* Stig L. Nilsson John L. Rankine Ronald H. Reimer Gary S. Robinson Terrance R. Whittemore Contents r SECTION PAGE 1. Scope ...................................................................... 7 2. General..................................................................... 2.1 References .............................................................. 2.2 Effect of Loading Beyond Nameplate Rating .................................... 2.3 Types of Loading and Their Interrelationship .................................... 2.3.1 Normal Life Expectancy Loading ....................................... 2.3.2 Planned Loading Beyond Nameplate Rating ................................ 2.3.3 Long-Time Emergency Loading.......................................... 2.3.4 Short-Time Emergency Loading ......................................... 2.3.5 Interrelationship of Loading Types ...................................... 2.3.6 Risk Considerations.................................................. 2.4 Temperature Limitations................................................... 2.5 Maximum Loading Limitations .............................................. 2.6 Information for User Calculations............................................ 2.7 Voltage and Frequency Considerations........................................ 7 7 7 8 -8 8 9 9 11 11 12 12 12 13 3. Calculation of Temperature .................................................... 13 3.1 List of Symbols.......................................................... 13 3.2 Temperature Determination Equations ........................................ 14 3.3 Equation Corrections ..................................................... 14 3.4 OilTimeConstant ......................................................... 14 3.5 LoadLoss .............................................................. 15 3.6 ViscosityofOil .......................................................... 15 3.7 Aging of Insulation ....................................................... 15 3.8 Approximating Ambient Temperature for Air-cooled Transformers.................. 18 3.8.1 Average Temperature ................................................ 18 3.8.2 Average of Maximum Daily Temperatures................................. 18 3.9 Basic Logic Diagram of Computer Program ..................................... 18 4. Operation with Part or All of the Cooling Out of Service .............................. 18 4.1 For OA/FA and OA/FA/FA Transformers ..................................... 18 4.2 For OA/FA/FOA and OA/FOA/FOA Transformers .............................. 18 4.3 For FOA and FOW Transformers ............................................ 19 A FIGURES Fig 1 (a) Normal Life Expectancy Loading (b) Planned Loading Beyond Nameplate Rating (c) Long-Time Emergency Rating (d) Short-Time Emergency Rating ....................................................... Fig 2 Reciprocal of Absolute Temperature Scale..................................... Fig 3 Logic Diagram for a Computer Program that Meets the Requirements OutlinedintheGuide .................................................... 10 16 17 TABLES Table 1 Coordination of Suggested Loading Type, Duration, and Temperature Range .........9 Table 2 Suggested Maximum Temperature Limits for the Four Types of Loading ............9 Table 3 Suggested Design Limits for New Transformers when Loading Information isnotsupplied ........................................................ 12 APPENDIXES Appendix A Thermal Evolution of Gas from Transformer Insulation.(References) ...........21 Appendix B Effect of Loading Transformers Above Nameplate Rating on Bushings. Tap Changers. and Auxiliary Components ............................... 24 0 IEEE Guide for Loading Mineral-Oil-Immersed Power Transformers Rated in Excess of 100 MVA (65 "C Winding Rise) - 1.Scope This guide covers general recommendations for loading mineral-oil immersed power transformers manufactured in accordance with IEEE C57.12.00-1987Ill' and having a maximum nameplate rating in excess of 100 MVA (three phase) or 33 1/3 MVA (single phase). Such transformers have an average winding rise of 65 "C maximum and a hottestspot rise of 80 "C maximum a t rated load. [31 IEEE C57.92-1981,IEEE Guide for Loading Mineral-Oil-Immersed Power Transformers Up to and Including 100 MVA With 55 "C or 65 "C Average Winding Rise. 2.2 Effect of Loading Beyond Nameplate Rating. Application of loads in excess of nameplate rating involve some degree of risk. It is the purpose of this guide to identify these risks and to establish limitations and rules the application of which will minimize the risks to the fullest extent that present state-of-theart knowledge permits. While aging and longtime mechanical deterioration of winding insulation have been the basis for the loading of power transformers for many years, it is recognized that there are additional factors which may involve greater risk for transformers of higher megavoltampere and voltage ratings. The risk areas which should be considered when loading large transformers beyond nameplate rating are broadly defined as follows: (1)Evolution of free gas from insulation of winding and lead conductors (insulated conductors) heated by load and eddy currents (circulating currents between or within insulated conductor strands) may jeopardize dielectric integrity. Since the free gas is generated in the insulation near the conductor, where dielectric stresses are high, the risk of electrical failure is increased. This is principally a temporary risk which lasts for the period that the gas bubbles exist in the insulation. Following the period of overheating the gas bubbles will dissolve in the oil and full NOTE: When this guide is to be used for transformers purchased prior to publication of the guide, the applicability of 2.5 and 4.3 should be checked with the manufacturer. Also see Appendix D. 2. General 2.1 References [ll IEEE C57.12.00-1987,IEEE Standard General Requirements for Liquid-Immersed Distribution, Power, a n d Regulating Transformers.2 [21IEEE (257.91-1981, IEEE Guide for Loading Mineral-Oil-Immersed Overhead and PadMounted Distribution Transformers Rated 500 kVA and Less With 65 "C or 55 "C Average Winding Rise. The numbers in brackets correspond to the references listed in 2.1. zIEEE publications are available from the Institute of Electrical and Electronics Engineers, Service Center, 446 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08856-1331, USA. 7 IEEE CS7115-1991 IEEE GUIDE FOR LOADING MINERAL-OILIMMERSED POWER (6) Pressure build-up with bushings for currents above rating could result in leaking gaskets, loss of oil, and ultimate dielectric failure. See Appendix B for further discussion. (7) Increased resistance in the contacts of tap changers can result from a build-up of oil decomposition products in a very localized high temperature region at the contact point when the tap changer is loaded beyond its rating. In the extreme, this could result in a thermal runaway condition with contact arcing and violent gas evolution. See Appendix B for further discussion. (8) Auxiliary equipment internal to the transformer, such as reactors and current transformers, may also be subject to some of the risk identified above. See Appendix B for further discussion. (9)When the temperature of the top oil exceeds 105 "C (65 "C rise over 40 "C ambient according to IEEE C57.12.00-1987[ll),there is a possibility that oil expansion will result in an oil loss through the pressure relief device. The overflow may also create problems with the oil preservation system. dielectric integrity will retum unless partial insulation breakdown, which may produce carbonized tracking, occurs while the free gas is present. See Appendix A for further discussion. (2) Evolution of free gas from insulation adjacent to metallic structural parts linked by electromagnetic flux produced by winding or lead currents may also reduce dielectric strength. Since these parts are not located in the regions of high dielectric stress, evolved free gas has to migrate to areas of the insulation system where dielectric stresses are at more critical levels before they can have significant impact on dielectric integrity. In the course of migration, the free gas bubbles tend to be dissolved into the oil. As a consequence, slightly higher hottest-spot temperatures may be tolerated for other metallic parts than for insulated conductors. Any risk of reduced dielectric integrity lasts essentially for the period of free-gas evolution. (3) Aging or deterioration of conductor insulation as a function of time and temperature is the most widely recognized permanent effect of power transformer loading. Aging is fully described in IEEE C57.92-1981131. Over a relatively long period of time, there will be a cumulative degradation of the electrical and mechanical properties of the conductor insulation, which could result in failure. Loss of life calculations may be made as described in IEEE C57.92-1981 131. One should recognize that the calculated results may not be a s conservative for transformers rated above 100 MVA as they are for smaller units, since the calculation does not consider mechanical wear effects, which increase with megavoltampere rating. (4) Structural insulation materials also suffer cumulative permanent degradation of mechanical properties as a function of timetemperature history. In addition, there is some degree of temporary reduction of mechanical capability at elevated temperatures. These effects are expected to be of major concern during periods of transient over-current (shortcircuit faults) when mechanical forces reach their highest levels. (5)Thermal expansion of conductors, insulation materials, or structural parts at high temperatures may result in permanent defonnations which could contribute to mechanical or dielectric failures. /- 2.3 Types of Loading and Their Interrelationship. Loads in excess of nameplate rating may be applied to transformers on four different time-temperature bases. An increased risk is probable for each successive loading with its attendant increased temperature and duration. The applicable times and temperature ranges are shown in Table 1, maxi" temperatures in Table 2, and examples of loads which fall within these categories are illustrated in Fig 1 and described in 2.3.5. The four load types are described in 2.3.1 through 2.3.4. 2.3.1 Normal Life Expectancy Loading. Normal life expectancy loading is loading that may exceed nameplate rating provided the maximum conductor hottest-spot and maximum top-oil temperatures permitted in IEEE C57.12.00-1987C13 are not exceeded. Other metallic temperatures reached under this loading will not be of concern. This loading may be continued indefinitely and is considered risk-free with respect to the risks outlined in 2.2. 2.3;2 Planned Loading Beyond Nameplate Rating. Planned loading beyond nameplate rating results in either the conductor hottestspot or topoil temperature exceeding those suggested in Table 2 for normal life expectancy 8 A IEEE TRANSFORMERSRATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) C57.115-1991 Table 1 Coordination of Suggested Loading Type, Duration, and Temperature Range Type of Loading Daily Duration in the Specified Hottest-Spot Temperature Range (hour) Insulated** Conductor Hottest-Spot Temperature Range ("C) * 110-120 4 4 6 4 120-130 120-130 130-140 120-1 30 130-180 130-140 Normal life expectancy loading Planned loading beyond nameplate rating Long-time emergency loading Short-time emergency loading 1 G *Since loss-of-life is cumulative, transformers may be operated above 110 "C hottest-spot temperature (not to exceed 1 2 0 "C) for short periods provided they are operated for much longer periods at temperatures below 110 "C. **See 2.3.5 for explanations. Table 2 Suggested Maximum Temperature Limits for the Four Types of Loading Normal Life Expectancy Loading ("C) Planned Loading Beyond Nameplate Rating ("C) Long-Time Emergency Loading ("C) 120* 130 140 180** 140 105 150 160 110 200 110 Short-Time Emergency Loading ("C) ~ Insulated conductor hottest-spot temperature Other metallic hot-spot temperature (in contact and not in contact with insulation) Top-oil temperature 110 *110 "C on a continuous 24 h basis. **Operation at insulated conductor hottest-spot temperatures above 140 "C may cause gassing in the solid insulation and oil. Gassing may produce a potential risk to the dielectric strength of the transformer. This risk should be considered when the guide is applied. loading, and is accepted by the user as a normal, planned-for repetitive load. Suggested conductor hottest-spot temperatures coordinated with daily durations are presented in Table 1. This loading occurs with no system outages and some risk is associated with it as outlined in 2.2. 2.3.3 LongTime Emergency Loading. Longtime emergency loading results from the pro longed outage of some system element and causes either the conductor hottest-spot or the top-oil temperature to exceed those suggested for planned loading beyond nameplate rating. This is not a normal operating condition, but may persist for some time. It is expected that such occurrences will be rare. Suggested conductor hottest-spot temperatures coordinated with daily durations are presented in Table 1. Top-oil temperature should not exceed 110 "C at any time. This loading results from a system outage and is more severe than planned loading beyond nameplate rating. Both loss of insulation life and risk are greater than under planned loading beyond nameplate rating. It is expected that there will be only two or three such occurrences in the life of a transformer. 2.3.4 Short-Time Emergency Loading. Shorttime emergency loading is an unusually heavy loading brought about by the occurrence of one or more unlikely events which seriously disturb normal system loading and cause either the conductor hottest-spot or top-oil tempera- lEEE IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER CS7116-1991 r' ('C) 40 130 110- 0 ; I- z BO I , : 2 1 ! z 1 4 I b I bI I I I 1 i I I . 1 80 I 112 10 2 4 6 8 10 90 - , 1 2 ' ; 12 4 6 ' 8 10 I HOURS OF THE DAY l I2 l 2 ' I 6 8 " 4 I 10 l2 OF THE DAY HOURS ('C) ""1 W 3 4 W zl a ; 8 n I- 5 a 4 2 z_ 90- 80-*.,1 I I I I I I 1 1 1 I I 1 ' I I 90 i 12 1 I l ' h ' b ' 8 l ( I 1 0 1 2 HOURS " ' I 2 ' 4 ' I 6 J ' 8 I Fig 1 (a) Normal Life Expectancy Loading (b) Planned Loading Beyond Nameplate Rating (c) Long-Time Emergency Loading (d) Short-Time Emergency Loading 10 I i 1 0 1 2 OF THE D A Y IEEE TRANSFORMERS RATED IN EXCESS OF 100 MVA (65"C WINDING RISE) - ~ C57115-1991 again in the temperature range of 120 "C130 "C for approximately 2 h resulting in a total of 4 h in the temperature range of 12O"C-13O0C for the 24 h period. The hottest-spot temperature is allowed to exceed 120 "Cfor a maximum of 10 h. Short-time emergency loading defines a loading condition wherein a transformer is so loaded that its hottest-spot temperature is in the temperature range of 12O0C-130"C for a maximum of 4 h, in the temperature range of 13O0C-180"C and back to 140°C for 1 h, and in the temperature range of 13O"C-14O0C for a maximum of 6 h. The characteristics of this type of loading are a series of unlikely conditions on the transmission system (2nd or 3rd contingency), one or two occurrences over the normal lifetime of the transformer, each occurrence is 1 h duration or less, and the risk is greater than for long-time emergency loading. Figure l ( d ) illustrates a short-time emergency loading profile. This figure presents a temperature curve that has leveled off for the day until about 4 pm when a system condition occurs which loads the transformer so that its hottest-spot temperature rises rapidly to 163 "C in 1 h. Note that Fig l(d) presents a loading that is within the spirit of the guide. On the rising side of the curve the hottest-spot temperature is in the range of 120 "C-130 "C for approximately 15 min. The hottest-spQt temperature continues rising from 130°C toward 180°C and back to 140 "C in approximately 1 h while peaking at approximately 163°C. On the descending portions of the curve, the hottestspot temperature is in the 13O"C-14O0C range for approximately one-half hour and once again in the temperature range of 120 "C130 "C for 2 h, resulting in a total of 2 h 1 5 min in the temperature range of 120 "C-130 "C for the 24 h period. The total time above 120 "C is 3 h 30 min for this example as opposed to the 11 h maximum permitted. 2.3.6 Risk Considerations. Normal life expectancy loading is considered to be risk free; however, the remaining three types of loading have associated with them some indefinite level of risk. Specifically, the level of risk is based on the quantity of free gas and voltage. The presence of free gas as outlined in 2.2 can cause dielectric failure during an overvoltage condition and possibly at rated power frequency voltage. The Task Force has selected ture to exceed the temperature limits suggested for planned loading beyond nameplate rating. Acceptance of these conditions for a short time may be preferrable to other altematives. It is expected that this type of loading will be reduced to long-time emergency loading in not more than 1 h. Suggested conductor hottest-spot temperatures coordinated with daily durations are presented in Table 1. Top-oil temperature should not exceed 110 "C at any time. This type of loading, with its greater risk, is expected to occur rarely. 2.3.5 Interrelationship of Loading Types. Examples of hottest-spot temperature profiles for the four types of loading defined in 2.3.1 to 2.3.4 are illustrated in Fig l ( a ) through l(d). Note that for each higher temperature, a higher risk loading condition can be assumed to be additive to any lower risk condition accepted by the user except for the short-time emergency loading. For further clarification a brief description of the last three loading types are described below. Planned loading beyond nameplate rating defines a condition wherein a transformer is so loaded that its hottest-spot temperature is in the temperature range of 12OoC-130 "C for a maximum of 4 h daily. The characteristics of this type of loading are no system outages, regular and comparatively frequent occurrences, and there is some risk. Figure l ( b ) illustrates a planned loading beyond nameplate rating profile. Long-time emergency loading defines a condition wherein a transformer is so loaded that its hottest-spot temperature is in the temperature range of 120 "C-130 "C for a maximum of 4 h and in the temperature range of 130 "C140 "C for a maximum of 6 h daily. The characteristics of this type of loading are one long time outage of a transmission system element, two or three occurrences over the normal lifetime of the transformer, each occurrence may last several months, and the risk is greater than planned loading beyond nameplate rating. Figure l ( c ) illustrates a long-time emergency loading profile. Note that while the hottestspot temperature is increasing with time, it is in the temperature range of 12O0C-130"C for approximately 2 h. The hottest-spot temperature is in the temperature range of 130°C140 "C for 6 h. On the descending part of the curve the hottest-spot temperature is once 11 lEEE IEEE GUIDE FOR LOADING m R A L - O I L - m R S E D POWER C67116-1991 the temperature levels and time durations shown in Table 1for each of the defined types of loading which they subjectively believe will result in an acceptable degree of risk for the special circumstances which require loading beyond nameplate rating. A scientific basis for the users' evaluation of the degree of risk is not available at this time. Current research in the area of model testing has not established sufficient quantitative data on the relationship between conductor temperature, length of time at that temperature, and reduction in winding dielectric strength. Additionally, there are other important factors which may affect any reduction, such as moisture content of the winding insulation and rate of rise of conductor temperature. 2.4 Temperature Limitations. It is suggested that the temperature limitations in Table 2 should not be exceeded during any overload event. 2.5 Maximum Loading Limitations. M a x i " load capacity which a transformer user plans to utilize on a planned or emergency basis, or both, should be included in the specifications at the time of purchase. The following information should be given: (1)Prior steady-state load, percent of maximum rating (2) Ambient temperature, "C (3)Maximum load, percent of maximum rating (4) Duration of maximum load, hours ( 5 ) Type of loading, planned or emergency, long-time or short-time, or acceptable limiting temperatures ( 6 ) Acceptable loss-of-life, percent of normal life, per occurrence More than one set of loading conditions may be defined or a 24 h load cycle (with associated ambient temperatures) may be given. In the absence of specified loading capabilities, the maximum load and duration limits shown in Table 3 are suggested for transformers purchased after the publication of this guide. These suggestions apply to loading beyond nameplate rating on a long-time emergency basis for generator step-up transformers and a short-time emergency basis for system-tie or substation transformers. Other combinations of load, duration, prior load, and ambient temperature may be used, if the maximum loads shown in Table 3 and the insulated condutor hottest-spot temperature limits of 2.4 are not exceeded. Tap changers, bushings, leads, and other ancillary equipment will not normally restrict loading to levels below those given in Table 3, but the user may wish to specify that ancillary equipment not restrict loading to levels below those permitted by the insulated conductor and other metallic part hot-spots. P /--. 2.6 Information for User Calculations. If the user intends to perform calculations to help determine the loading capability of a transformer, the user should request information of the following type in his specification: (1)Top-oil temperature rise over ambient temperature (2) Bottom-oil temperature rise over ambient temperature (3) Average conductor temperature rise over ambient temperature Table 3 Suggested Design Limits for New Transformers when Loading Information Is Not Supplied Maximum Load (% of Maximum Rating) ADDlication (%I Generation step-up System tie Substation 110 150 Duration* (hours) 8 1 1 150 Insulated Conductor Maximum Hottest-Spot Temperature Not t o Exceed ("C) 140 180** 180** *Based on prior load of 100%of rated and 30 "C ambient. **This limit is based upon consideration of thermal aging and does not take into account the risk of insulation breakdown because of bubble formation above 140 ',C. (See 2.2(1).) 12 ,---. TRANSFORMERS RATED IN EXCESS OF 100 MVA (65"C WINDING RISE) - (4) Hottest-spot conductor temperature rise over ambient temperature (5) Load loss at rated load (6) No-load loss (7)Total loss in watts at rated load (8) Confirmation of oil flow design (that is, directed or nondirected) For all of the information in (1)through (8) state the conditions under which the measurements were made - load, ambient temperature, tap, etc. 2.7 Voltage and Frequency Considerations. Voltage and frequency influences should be recognized when determining limitations for loading a transformer beyond its nameplate. This is true even though in all probability there may be little control of these parameters during a loading beyond nameplate event. IEEE C57.12.00-1987113,4.1.6defines the capability of a transformer to operate above rated voltage and below rated frequency. The user of this guide should recognize that, during conditions of loading beyond nameplate, the voltage regulation through the transformer may increase significantly (depending on the transformer impedance) due t o the increased kilovoltampere loading and possibly dropping power factor. A conservative guideline, t o prevent excessive core heating due to saturation, is to reduce the transformer output volts per hertz limit by 1% for every 1%increase in voltage regulation during the loading beyond nameplate event. For example, if the voltage regulation at rated conditions is 6% and increases t o 9%at some load above nameplate, the output volts per hertz limit might be reduced from 105% to 102%. 3. Calculation of Temperature Top-oil temperature and winding conductor hottest-spot temperature may be calculated by the user employing methods defined in IEEE C57.92-1981131 if he or she wishes to assess the acceptability of any given load cycle. Before basing load capabilities on temperatures determined from temperature rise tests, it is wise to consider the following information: (1)Coolers for FOA and FOW transformers are designed to have a safety margin when tested in a new condition. This margin is called Em C57.115-1991 a fouling factor and allows for the fact that cooler efficiency will decrease as the coolers operate in normal service. For example, forced air coolers can become partially blocked with airborne dirt. If the coolers are not kept clean, their efficiency decreases and oil temperature rises. If load capability is based on test results with new coolers, the transformer temperatures may be exceeded if the coolers are not operating at their new condition efficiency. ( 2 ) The average winding rise is a temperature calculated from the resistance value of the total circuit. Within this circuit there will be bushings, insulated cables, and winding conductors connected in series. Hottest-spot temperatures of insulated cables may increase at a greater rate than hottest-spot temperatures of the windings. If load calculations are made to the maximum winding hottest-spot temperatures, heavily insulated cable temperatures may exceed winding temperatures by a considerable amount. (3) The load capability of ancillary equipment, such as tap changers, has little or no bearing on temperature rise test results for average winding rise. The proper operation of such equipment is much more dependent on current than temperature. Thus a lower than guaranteed average winding rise does not necessarily permit loading to greater than designed into the ancillary equipment. (4) Stray flux shielding, such as provided by magnetic shunts, it designed to prevent saturation under maximum load conditions required by the purchaser. Greater loads will cause the shunts to saturate allowing hot-spots to form in cores and structural members. Hot-spot temperatures for other metallic parts will not exceed the limiting values given in 2.4 provided that: (a) The maximum load values of 2.5 are not exceeded and (b) The top-oil temperature resulting from the maximum load and duration condition of 2.5 is not exceeded. 3.1 List of Symbols. Unless otherwise expressed, all temperatures are in "C and all times are in hours. 8, = ambient temperature 8 = hottest-spot conductor rise over top- oil temperature 13 IEEE C67116-1991 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSEDPOWER Ultimate hottest-spot conductor rise over topoil for load L : = hottest-spot conductor rise over top- oil temperature at rated load 8 h E = hottest-spot winding temperature 0 = top-oil rise over ambient temperature 0 I = top-oil rise over ambient temperature at rated load ei = initial top-oil rise for t = 0 8 , = ultimate top-oil rise for load L A P = change in total loss in watts because of a change in kilovoltampere load K = ratio of load L to rated load L = load under consideration, in kilovoltampere R = ratio of load loss at rated load to noload loss e = 2.71828 (base of natural logarithm) t = duration of load in hours 7, = oil thermal time constant (in hours) of transformer for any load L and for any specific temperature differential between the ultimate topoil rise and the initial top-oil rise, or 0 average conductor rise over top oil 4 + 15 "C5 (Eq 5) For nondirected flow transformers: C = 0.06 - (weight of core and coil assembly in pounds) + 0.04 (weight of tank and fittings in pounds) + 1.33 (gallons of oil) - For directed flow transformers: n C = 0.06 (weight of core and coil assembly in pounds) + 0.06 (weight of tank and fittings in pounds) + 1.93 (gallons of Oil) 3.3 Equation Corrections. Theoretically, several corrections should be made when using the foregoing equations in calculating transient oil rises such as corrections for change in: (1)Time constant for loads above rating (2)Ultimate load loss at end of load period (3)Oil viscosity 3.2 Temperature Determination Equations (See Foreword, third paragraph.) Hottest-spot temperature : (Eq 3.4 Oil Time Constant. The oil time constant is the length of time which is required for the temperature of the oil to change from initial value to the ultimate value if the initial rate of change is continued until the ultimate temperature is reached. Transient heating equation for top-oil rise over ambient temperature: (Eq 2) ~ At rated kilovoltampere from manufacturer's test. In the absence of known values, the difference between the average conductor rise and the hottest-spot conductor temperature rise can be assumed to be approximately 15 "C. However, one should recognize that the actual temperature different may be higher than 15 "C for some designs and lower for others. Ultimate top-oil rise for load L: e,=ef,( I) = Time constant a t rated kilovoltampere: - Bi)/AP 7, = time constant (in hours) for rated load beginning with initial temperature rise of O "C P f I= total loss in watts at rated load C = thermal capacity of transformer (Wh/"C) n = exponential power of total loss versus top-oil temperature rise above ambient m = exponential power of winding loss versus winding temperature rise above oil KzR+l R+1 ( m = 0 . 8 for OA, OA/FA, OA/FA/FA and nondirected FOA, FOW, OA/FA/FOA, OA/FOA/FOA operation = 1.0 for directed flow FOA, FOW operation n = 0.8 for OA operation = 0.9 for OA/FA, OA/FA/FA operation = 1.0 for FOA, FOW, OA/FA/FOA,OA/ FOA/FOA operation T, = C(0, ehs=e,+eo +eg (Eq 4) 0 , = O s ( f l )K2" (Eq 3, 14 r' TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) If n (the exponent used in Eq 3) is equal to 1.0, 63% of the temperature change occurs in a length of time equal to the time constant regardless of the relationship of initial temperature rise and ultimate temperature rise. If n is not unity, the temperature change in a similar time interval will be different, depending on both initial temperature rise and ultimate temperature rise. For example, if n = 0.8, the change is 67% if the initial temperature rise B i = 0 "C and the applied load L = rated load. If the initial temperature rise > 0, the change < 67% and decreases as the initial temperature rise approaches a given ultimate temperature rise. If the initial temperature rise is approximately equal to the final temperature rise, whether just above or just below it, the change = 63%. If the initial temperature rise is greater than the ultimate temperature rise, the change < 63%. Since evaluation of the exact change for cases where n is not unity and where the initial temperature rise is not zero becomes very laborious, it is frequently advisable to use the value of 63% as an approximation. In the more frequently encountered cases where n x 0.8, the error resulting from this procedure is not large compared to the expected error in the input data. If n = 1.0, Eq 6 is correct for any load and any starting temperature. If n or m < 1.0, Eq 6 holds only for full-rating load L starting cold. The time constant for any load and for any starting temperature for either a heating cycle or cooling cycle is given in Eqs 7 and 8 as follows: (2)-($) 7, = 7, 1 1 - - (2) ($) - If starting cold, as B i = 0, Eq 7 reduces to: 3.5 Load Loss. Load loss in a transformer is greater for loads above rating than K 2 in (Eqs 3) IEEE C57.115-1991 and (4) indicate due to the increased temperature of the winding conductors and their consequent increase in resistance. Some of the increased loss in the conductors due to temperature increase is offset by a relative decrease in the conductor eddy current losses and losses in other metallic parts of the transformer due to stray magnetic flux. Therefore, if corrections to Eqs (3) and (4) are applied for increased conductor resistance, the exponents m and n will usually be different and lower than the recommended values. The manufacturer should be consulted when such a correction is considered since the correction is influenced by the proportion of the eddy and stray losses in the load loss. The correction factor for resistance change is a multiplier applied to the K 2 expressed in each equation. 3.6 Viscosity of Oil. The ultimate temperature rise of oil for a constant heat input decreases slightly as the temperature of the oil increases. This is due to a decrease in the viscosity of the oil. The viscosity change tends to offset the effect of increased ohmic resistance of conductors. 3.7 Aging of Insulation. Aging or deterioration of insulation is a function of temperature and the time it is at this temperature. Since, in most apparatus, the temperature distribution is not uniform, that part which is operating at the highest temperature will ordinarily undergo the greatest deterioration. Therefore, in aging studies, it is usual to consider the aging effects produced by the highest (hottestspot) temperature. 3.7.1 Much of the fundamental data on aging of insulation at different temperatures has been based on laboratory and model tests in which the decrease in mechanical and electrical strength has been measured. Under the auspices of the IEEE, a series of life expectancy tests were made under controlled conditions on production-type distribution transformers. Data from these tests were used as the basis for the distribution transformer life expectancy curves in IEEE C57.91-1981C21. While these are the best insulation life data available at this time, they are not directly applicable to power transformers. Because the end point strength of insulation (the final strength of aged insulation) must be greater in power transformers and because model tests of power 15 IEEE IEEE GUIDE FOR LOADING M I N E R A L - O I L - m m D POWER CS7116-1991 106 1 o3 ,- 1o'3 HOTTEST-SPOT TEMPERATURE IN *C RECIPROCAL OF ABSOLUTE TEMPERATURE SCALE Fig 2 Reciprocal of Absolute Temperature Scale transformers have not yet been reported, the power transformer insulation life expectancy curves were selected to be more conservative than those used for distribution transformers. The transformer life expectancy predictions contained herein are based on the insulation life expectancy curves shown in Fig 2 and do not take into account deterioration of gaskets, rusting of tanks, etc which result from factors other than winding temperatures. While the life expectancy curves are be- lieved to be conservative, any estimates of transformer life derived therefrom are intended only as a guide. 3.7.2 Because the cumulative effects of temperature and time in causing deterioration of transformer insulation are not thoroughly established, it is not possible to predict with any great degree of accuracy the life span of a transformer even under constant or closely controlled conditions, much less under widely varying service conditions. 16 P IEEE C57.115-1991 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) READ IN SYSTEM VOLTAGE, SPECIFIED MAXIMUM AGING. SPECIFIED TEMPERATURE LIMITS DAILY AMBIENT TEMPERATURE INFORMATION, TRANSFORMER CHARACTERISTICS CALCULATE STEP-BY-STEP FOR ALL INTERVALS: TOP OIL TEMPERATURE. WINDING HOTTEST-SPOT TEMPERATURE AND WINDING AGING FOR EACH OF THE WINDINGS ESTABLISH FOR EACH WINDING: TOTAL AGING HOTTEST-SPOT TEMPERATURE TIME ABOVE TEMPERATURE LIMITS TRANSFORMER OF THE ABOVE VALUES [F:Gkl& UCE LOAD MULTIPLIER 44 EDUCE LOAD MULTIPLIER *specify aging within tolerance criteria Fig 3 Logic Diagram for a Computer Program that Meets the Requirements Outlined in the Guide 17 IEEE IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER C67115-1991 recommended that these temperatures be increased by 5 "C since aging at higher than average temperature is not fully compensated by decreased aging at lower than average temperature. With this margin the approximated temperature will not be exceeded on more than few days per month and, where it is exceeded, the additional loss of life will not be serious. 3.7.3 This guide assumes the insulation deterioration relationship with respect to temperature and time follows an adaption of the Arrhenius reaction rate theory which states that the logarithm of insulation life is a function of the reciprocal of absolute temperature: Log, life (hours of life) = - 13.391 +& ,( 6972 15 3.9 Basic Logic Diagram of Computer Program. Calculating a load level for a transformer, which is at all times constrained by time/ temperature and maximum temperature limitations and that will yield a prescribed amount of aging is an iterative procedure. A basic logic diagram of such an iterative procedure for a computer program incorporating the fundamental ideas in this guide is shown in Fig 3. where T = absolute temperature in "K = ehs + 273 where O h s = temperature in "C at the hottest-spot at the end of time interval t 100 ( t ) 7% loss-of-life = 4. Operation with Part or All of the Cooling Out of Service 10 Where auxiliary equipment, such as pumps or fans, or both, is used to increase the cooling efficiency, the transformer may be required to operate for some time without this equipment functioning. The permissible loading under such conditions is given in the following paragraphs. for the time interval t hours. 3.8 Approximating Ambient Temperature for Air-cooled Transformers. It is often necessary to predict the load which a transformer can safely carry at some future time in an unknown ambient. The probable ambient temperature for any month may be approximated as follows from reports prepared by the National Weather Service of the US Department of Commerce for various sections of the country: 3.8.1 Average Temperature. Use average daily temperature for the month involved - averaged over a number of years. 3.8.2 Average of Maximum Daily Temperatures. Use average of the maximum daily temperatures for month involved - averaged over several years. These ambients should be used as follows: for loads with normal life expectancy, use 3.8.1 as the ambient for the month involved; for short-time loads with moderate sacrifice of life expectancy, use 3.8.2 for the month involved. During any one day the average of maximum temperatures may exceed the value derived from 3.8.1 or 3.8.2. To be conservative, it is 4.1 For OA/FA and OA/FA/FA Transformers. For dual rated forced-air-cooled transformers (OA/FA), if one or more fans are inoperative, use the self-cooled (OA) rating. For triple rated force-air-cooled transformers with part of the fans inoperative, use the nameplate rating based on the full stage of cooling remaining in operation, or if less than a full stage of fan cooling is operative, use the selfcooled (OA) rating. 4.2 For OA/FA/FOA and OA/FOA/FOA Transformers. For triple rated forced-air, forced-oil-cooled transformers with all or part of the cooling inoperative use the nameplate rating based on the full stage of cooling remaining in operation, or if less than a full stage of fan and pump cooling is operative, use the selfcooled (OA) rating. For loss of either fans or pumps on a stage of cooling, use the rating which pertains to total loss of that stage of cooling. 18 --.-. IEEE C57.115-1991 TRANSFORMERSRATED IN EXCESS OF 100 MVA (66"C WINDING RISE) - - eau = ultimate rise of average oil in "C 4.3 For FOA and FOW Transformers. In general, the heat exchangers used to cool FOA and FOW type transformers will dissipate only an insignificant amount of heat when either the forced-oil circulation or the forced cooling medium (air or water) is inoperative. If only part of the coolers are inoperative, then refer to 4.3.3 for load capability. If all of the coolers are inoperative, loading amounts and durations can be calculated as in 4.3.1. The amount of load carried, the duration of the load, the previous loading condition, the ambient temperature, and the physical parameters of the transformer determine its hottestspot temperature and the loss-of-life experienced during the period of loss of all cooling. The user should calculate in accordance with the method below and refer to other sections of this guide to determine the effects of the operating condition. During the period of loss of all cooling the only significant amount of heat dissipated by the transformer will depend on tank radiation and its convection characteristics which, in tum, are dependent on tank dimensions. Heat dissipation characteristics may be calculated from measurements obtained by measuring the actual unit or from estimations based on the transformer outline drawings. 4.3.1 An approximation of the effect of loading and time upon the oil and hottestspot temperature can be determined from 4.3.2. (More accurate data may be obtained from the manufacturer.) 4.3.2 List of Symbols A = sum of surface areas of tank walls and cover neglecting braces, appurtenances, etc, square inches C = thermal capacity as defined in 3.1 and 3.2 for nondirected flow mode K = ratio of load to be carried to 100% FOA nameplate rating P = total losses at load to be maintained minus losses that will be dissipated by tank at f3a ,,watts F = 2 for directed oil flow and 1 for nondirected oil flow T L = total losses in watts, at load to be maintained LD = losses dissipated by the tank at reference temperature of e a eafl = average oil rise at maximum nameplate rating obtained from factory test data e,, average oil rise of unit at instant of loss of all cooling in "C 0 a t = average oil rise at time t O g = hottest-spot rise above top-oil rise at load to be maintained m = exponential as defined in 3.2 0 g ( f l ) = hottest-spot conductor rise over topoil temperature at rated load 8 a = ambient temperature e o = top-oil temperature rise "C 0 = hottest-spot temperature ,"C = (1)Estimate the losses in watts that will be dissipated by the tank at the 100% FOA oil rise after loss of all cooling. LD = (0.00365) (A) ( B a f 1 ) 1 . 2 1 Watts (Eq 11) (2) Estimate the ultimate rise of average oil for the load that is to be maintained. (3)The time constant corresponding to this loading condition should be calculated as follows: (4) The average oil rise at any time t for the transformer in this operating mode can be estimated from the following formula: _ -t eat = (eau - eatl) (I- e 7 L )+ o a f 1 (Eq 14) (5) During the time period of t h L = 0 to 0.1 5, the difference between top-oil temperature and average oil temperature can be estimated as follows: Ao, = 7t + 6 (t is in hours) (Eq 15) The estimated top-oil rise can then be determined as follows: It is recommended that 0 , 110 "C. + 8, not exceed NOTE: Estimates of top-oil rises at t/rL greater than 0.15 will have to be obtained from the manufacturer. 4.3.2.1 The hottest-spot rise above top-oil temperature, for directed oil flow units, will increase substantially when the forced-oil flow is stopped. An estimate of this rise can be obtained from the manufacturer. On the premise that some reasonable oil circulation will con19 IEEE IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER (267115-1991 tinue by natural convection, a rough estimate can be made as follows: O g ( f l ) = (avg wdg rise eg = eg(fl)~ 2 "c m - Bail) F+5 (Eq 17) (Eq 18) NOTE: The average winding rise and average oil rise should be obtained from the certified test reports for the maximum nameplate rating. 4.3.2.2 The hottest-spot temperature at the load to be maintained can be estimated as follows: eas = ea + e, + eg (Eq19) It is recommended that O h s not exceed 140 "C. CAUTION: In using the above guidelines, the following factors should be considered during a loss o f cooling situation. ( 1 ) Much of the normal overload protection (overcurrent relay, etc) installed on a transformer will be inadequate for this operating condition. (2) The hottest-spot relay (for alarm and in many cases trip), using the two input parameters of phase current and top-oil temperature, is calibrated to a hottest-spot rise over oil with forced oil circulation in the windings. It will indicate a temperature many degrees lower than actual hottestspot temperature if there is no forced-oil flow in the windings. (3)If the transformer is o f directed-flow design and pumps have been lost, it may be necessary to hold top-oil temperature well below normal to keep the hottest-spot temperature within its limitation, since, with drastically reduced oil flow, the hottest-spot gradient is greatly increased. Hence the top-oil temperatures must be kept lower to stay within design hottestspot limitation. , 4.3.3 For forced-oil cooled (FOA or FOW) transformer ratings with part of the coolers in operation, use the following reductions in permissible loading: % of Total Coolers in Operation 100 80 60 50 40 33 Permissible Load in 5% of Nameplate Rating 100 90 78 70 60 50 A These permissible loads will give approximately the same temperature rise as full load with all cooling in operation. n IEEE C57115-1991 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) Appendixes [Thee Appendixes are not a part of IEEE C67.116-1991, IEEE Guide for Loading Mineral-Oil-Immersed Power Transformem Rated in Excess of 100 MVA (66 "C Winding Rise), but are included for information only.] Appendix C provides assistance in calculating loading capabilities for both existing transformers and for new transformers being specified; the methods described include hand calculations and computer programs. Appendix D provides a philosophy in regard to loading older transformers. The Appendixes are intended for general and tutorial information and should not necessarily be applied for specific loading purposes. Appendixes A and B provide additional reference material for a broader understanding by the user in employing this guide. Appendix A Thermal Evolution of Gas from Transformer Insulation - (References) This paper extended the laboratory studies on hot-spot conductor gassing reported in the companion paper F-79-170-2 to full sized coreform pancake coils representative of 550 kV, BIL power transformer construction. The results of this study were conclusive indicating that the cellulose gassing mechanism disclosed in F-79-170-2 would produce a similar reduction in the impulse dielectric strengths of a transformer as predicted from th_e low frequency effects. Following are the results of the impulse tests applied to separate pancake coils at conductor temperatures representing a transformer before (90 "C) and during (145 "C) overload. Al. HEINRICHS, F. W. Bubble Formation in Power Transformer Windings at Overload Temperatures. Paper F-79-170-2 presented at the IEEE Winter Meeting, Feb 4-9, 1979; IEEE Transactions, vol PAS-98, no 5, Sept/ Oct 1979, pp 1576-1582. The paper considers known gas evolving mechanisms in oil, paper, and combinations of both and their relation to the physics of bubble formation. Thermal decomposition is postulated as the most likely gas bubble generating event during transformer overload. Laboratory experiments were conducted with transformer conductor insulation utilizing various models designed to isolate the separate effects of heat, power frequency electric stress, and finally conductor heating combined with electric stress typical of transformer designs. The thermal model produced quantities of visible gas bubbles which issued spontaneously from the paper pores at 130 "C-150 "C conductor temperatures. Simulated conductor models with both thermal and electrical stress demonstrated the simultaneous appearance of gas bubbles and partial discharge at 130 "C - 150 "C while at an average stress of 27.7 kV/cm. This work appears to provide the first tangible evidence for limiting the maximum allowable hottest-spot temperature in power transformer loading guides. Conductor temperature Oil temperature Mean breakdown Sigma 90 "C 90 "C 118kV 15.2 kV 145 "C 90 "c 50kV 4.4 kV ~~ Minute pearl-like bubbles were observed issuing from the conductor insulation at 145 "C. A3. McNUTT, W. J., KAUFMANN, G. H., VITOLS, A. P. MacDONALD, J. D.Short-Time Failure Mode Considerations Associated with Power Transformer Overloading. Paper F79 695-8, IEEE Transactions, vol PAS 99, no 3 May-June 1980, pp 1186-1197. Model assemblies representative of the constructions used in power transformer disk windings and heavily insulated leads were tested over a temperature range from 25 "C to 250 "C. Tests at 100 "C and higher involved immersion oil temperature of 80 "C, with additional conductor temperature rise achieved by A2. HEINRICHS, F. W., TRUAX, D. E, and PHILLIPS, J. D. The Effects of Gassing During Overloads of the Impulse Strength o f Transformer Insulation. Paper A79 434-2, presented at the IEEE Summer Power Meeting, July 1979. 21 IEEE C67116-1991 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSEDPOWER n 0 100 200 300 HOT SPOT TEMPERATURE,'C Fig A1 Sixty Hertz Breakdown Voltage in Percent of 25 "C Strength of Dry Paper (< 0.5% H,O) circulation of current through the conductors. Dielectric tests of 60 Hz and of 1 min duration were performed step-wise to breakdown after the heating current had been flowing for 30 min. The results are summarized in Fig Al. Results were also reported for a special test apparatus designed to make visual observations and quantitative measurements of gas evolved from heated metal in oil, with or without cellulose in contact with the metal. Visible gas bubbles were observed at metal temperature of 150 "C when pressboard was present, whereas bubbles were not visible to almost 350 "C with only oil in contact with the hot metal. An opinion was offered that "three factors make the temperature of metallic hot-spot less critical than conductor hottest-spots: reduced area of heated insulation, tendency for no gas entrapment, and generally lower level of dielectric stress. As a consequence, it appears that low level gassing associated with temperatures of 175 "C-200"C for metallic parts may constitute no greater risk than a temperature of 150 "C for insulated conductors." It was observed that "three types of cellulosic insulation at levels of dryness which may be anticipated in operating power transformers (0.2%-0.5% HzO by weight) evolved visible gas bubbles at temperatures as low as 140 "C." A4. KAUFMA", G. H.Gas Bubbles in Distribution Transformers, IEEE Trensaction, vol PAS-96,no 5 Sept/Oct 1977, pp 1596-1601. Distribution transformers were aged in a tank with a viewing port over various time/temperature cycles. Simulated rain was then applied to the tank of the loaded transformer. Visual observations were made of the intemal transformer assembly before and after the application of simulated rain, and impulse tests were conducted during the rain condition. It was reported that prior to the application of simulated rain, bubbles were not visible at rated load, but there were occasionaZ bubbles at 185% steady-state. This corresponds to 188 "C hobspot temperature. Bubbles were also seen approximately 10-15 min after the current was increased from 175%-300%. More detailed descriptions of the tests and observations are contained in KAUFMANN, G. H. ERDA Report CONS-2157-1, Sept 1976,Impulse Strength o f Distribution Transformers Under Load. This document reports A A IEEE C57.115-1991 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 “CWINDING RISE) PERCENT OF NO-LOAD IMPULSE BREAKDOWN VOLTAGE 120 % 100 80 60 40 20 0 0 20 40 60 .a0 100 120 140 160 HOT SPOT TEMPERATURE, ‘C 180 200 220 Fig A2 Impulse Breakdown Voltage of Unaged Shell Type Transformers As a Function of Hot-Spot Temperature “The paper describes a new functional test procedure for evaluating the impulse strength of distribution transformers under servicerelated conditions, including rated voltage, different current levels, and the effect of pre? cipitation. The test procedure was applied t o a representative sample of 54 commercial distribution transformers having a 1 5 kV class insulation system. Specimen transformers used in this project were taken from utility stockpiles. The results reported here showed a significant decrease of impulse strength with increasing load current and with aging under laboratory conditions.” Figure A2 presents a graph of impulse breakdown voltage of unaged shell-type dis- that “bubbles were observed during steadystate aging at 175% of rated current. Activity was observed only occasionally, usually in the form of single small bubbles at intervals of five minutes or more.” 175% of rated current correspond approximately to 160 “C hottest-spot temperature. A5. KAUFMANN, G. H. Impulse Testing of Distribution Transformers Under Load, IEEE Transactions, vol PAS-96, no 5, Sept/Oct 1977, pp 1583-1595. This reference reports a different phase of work under the same ERDA contract as 4 ERDA E (49-181-2157. See also ERDA Report CONS-2157-1,Sept 1976. 23 IEEE C57.115-1991 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSEDPOWER a small number of sample coils demonstrated, paper and enamel conductor insulation retained functionality after aging for time periods in excess of five times the life defined in IEEE C57.92-1981, IEEE Guide for Loading Mineral-Oil-Immersed Power Transformers Up to and Including 100 MVA with 55 "C or 65 "C Winding Rise. Following this degree of simulated loading, the insulation had suffered approximately a 10% reduction of dielectric strength. In addition, the following facts related t o evolution of gas within the winding insulation were demonstrated: tribution transformers as a function of hot-spot temperature. A6. IEC 354-1972, Loading Guide for Oil-Immersed Transformem6 One of the limitations adopted in this guide is a conductor hottest-spot temperature of 40 "C. This limitation is amplified by the following note: NOTE: It has been mentioned by various authors that above 140 "C the Arrhenius law is not completely applicable, owing to accelerated deterioration effects, either because the formation of deterioration products is too fast for them to be taken away by the oil, or because a gaseous phase is started, sufficiently rapid to lead to oversaturation and the formation of bubbles that may endanger the electric strength. Temperature and pressure cycling with a gas blanket oil preservation system can lead to entrapment of free bubbles of the blanket gas within winding and lead conductor insulation. The result is significantly reduced dielectric strength of the insulation, which persists for long periods of time (weeks). With a loading cycle maximum temperature of lSO"C, thermally evolved free gas within the conductor insulation degraded the dielectric strength. However, this strength reduction disappeared within one day after temperature reduction. A7. McNUTT, W. J., KAUFMANN, G. H. Evaluation of a Functional Life Test Model for Power Transformers, Paper 82 SM 343-2, presented at the IEEE Summer Power Meeting, July 19,1982. A physical model of a power transformer winding was evaluated as a tool for establishing functional life characteristics. Test procedures similar to those described in IEEE (257.100-1986, IEEE Standard Test Procedure for Thermal Evaluation of Oil-Immersed Distribution Transformers, were utilized. In AppendkB Effect of Loading Transformers Above Nameplate Rating on Bushings, Tap Changers, and Auxiliary Components B1. Bushings. Bushings are normally designed to limit the bushing hottest-spot t o a 105 "C total temperature a t rated current of the transformer, assuming a top-oil temperature of 95 "C. Operating the transformer beyond nameplate current can result in bushing temperatures above 105 "C, and the bushing lossof-life will be a function of the actual temperature and time operating a t that temperature. "The severity of loss-of-life in a bushing can be lessened or minimized by installing bushings which have nameplate ratings greater than the transformer current ratings." A number of factors that reduce the severity of overloading bushings compared to transformer winding insulation include: (1) Top-oil temperature may be well below 95 "C at rated transformer output (2) Bushings are sealed units, preserving their insulation and thermal integrity (3) Bushing insulation is generally drier (4) Bushing insulation is not significantly stressed by fault-current forces. 61EC publications are available from IEC Sales Department, Case Postale 131,3 rue de Varemb6, CH 1211, Genbve 20, SwitzerlandSuisse. IEC publications are also available in the United States from the Sales Department, American National Standards Institute, 11 West 42nd Street, 13th Floor, New York, NY 10036, USA. 24 - IEEE TRANSFORMERS RATED IN EXCESS OF 100 MVA (66% WININ" RISE) Overload concerns include (1) Intemal pressure build-ups (2) Aging of gasket materials (3) Unusual increases in power factor indicating t h e r m a l deterioration of insulation (4) Gassing due to hottest-spots in excess of 140% (5) Thermal runaway due to increased dielectric losses at higher temperatures To coordinate bushings and their transformers, the following limits are established: - Ambient air, 40 "C max Transformer top-oil temp, 110 "C max Max current, 2 rated current of bushing Bushing insulation hottest-spot, 150 "C Bottom lead hottest-spot rise over ambient air a t rated current, 80 "C The importance of sizing the air end and oil end terminals is noted. B2.Tap Changers B2.1 Tap Changers for DeEnergized Operation (TCDO) General. The current rating of the TCDO is generally limited by the heating of the contacts or the cable connections to the switch. The ANSI or CSA standards do not specify details on which a given rating is based. However, a temperature rise limit of 20 "C for the contacts at rated throughput is used by some manufacturers. I t is recommended that for overload conditions the temperature of the contacts not be allowed to exceed the hottestspot temperature of the winding. Tap changers for de-energized operation are also sensitive t o overloading. Although tapchanger contacts may have certain overload capabilities when new, these capabilities may decrease due t o a thin film build-up on the contacts that occurs during normal service. Once a contact reaches a critical temperature, a thermal runaway condition can occur. The contacts overheat and a deposit builds up around the contacts, increasing contact resistance until it finally reaches a temperature that will generate gas. As a minimum, this will produce a gas alarm. As a maximum, the gas may trigger a dielectric failure of the transformer. (37116-1991 B2.2 Load Tap Changers (LTC). The ANSI standards presently do not cover details on which a given rating of LTC is based. Some of the North American manufacturers have been using IEC standards as a guide or have complied with the requirements of this standard. The Canadian standard CAN/CSA C88-M90 now refers t o IEC Pub 214, On-Load Tap Changers. According t o IEC standards, the (current) rating of the LTC is based on: (1) Temperature rise limit of 20 "C for any current carrying contact (in oil). (2) Temperature rise limit of 200 "C for transition resistors during half cycle operations (uninterrupted operation through the entire regulating range). (3) Breaking capability test (interrupting capability) a t twice the rated current and kilovoltampere. The overload capability of the LTC is derived from the breaking capacity of the switch. Most LTC manufacturers would allow solitary operation of LTC at twice rated current (and kVA). The frequency of such operations, however, has not been defined, but is considered to be in the order of a few operations per year, which would normally be adequate for emergency loading conditions. For more frequent and specific overload cycles, a switch with a higher rating is recommended. The wear of contacts and contamination of oil increases rapidly with current. Higher overloads on LTC will generally necessitate more frequent maintenance of the switch. IEC Pub 76-1 (1976), Part 1 , Power Transformers. IEC Pub 214 (1989), On-Load Tap Changers. IEC Pub 354 (1972), Loading Guide for OilImmersed Transformers. IEC Pub 542 (19761, Application Guide for On-Load Tap Changers. B3.Bushing Type-CurrentTransformers. In their normal location, bushing type current transformers have the transformer top-oil as their ambient, which is limited to 105 "C total temperature a t rated output for 65 "C rise transformers. Loading the power transformer beyond nameplate results in an increase in top-oil IEEE C57115-1991 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSEDPOWER It may also be possible t o select higher current transformer ratios to reduce secondary currents and thus increase the capability of the current t r a n ~ f o r m e r . ~ temperature and an increase in secondary current in the current transformer with an associated temperature rise. A factor in reducing the severity of the current transformer overload is that the top-oil temperature at rated transformer output maybe well below 105 "C. In cases where consideration of the loading and top-oil temperature rise of the power transformer and the current in the current transformer indicate the possibility of excessive operating temperatures in the current transformer, the manufacturer should be consulted on the current transformer capability before loading beyond nameplates. The capability of bushing current transformers under operating conditions cannot necessarily be derived from the rating factor. - B4. Insulated Lead Conductors. Within the transformer, connections to tap changer and line terminals and other internal connections are made with insulated leads and cables. The method of calculating the hottest-spot temperature for these leads is different from that employed for the windings. However, the same hottest-spot limits apply equally for both windings and leads since similar insulating materials are normally used. Table 1 of this guide thus refers to insulated conductors, which are intended to include the windings and leads. Appendixc Calculationsto show Methods ofDeterminingRatingsand SelectingTransformerSize A transformer application problem usually needs to answer the question: Is an available transformer suitable for a given load cycle? Calculations required to answer this question can be made by hand, or a computer program can be written to automate the calculation. This appendix will illustrate the determination of loading limits by a hand calculation and the selection of a transformer, using a computer program. It should be noted that the purpose of the illustration is to show one way that might be used to approach the problem. As in most engineering problems, different approaches are possible, and judgement must be used in interpreting the results. an Existing Transformer. For this example, a 65 "C rise triple rated, OA/FOA/FOA cooled transformer, rated 112 OOOLL49 333/186 666 kVA will be used. A load profile is given (see Table C1, normal load in per unit) for a day starting a t 6:OO A.M.; the hottest-spot winding temperature profile is required. Some simplifying assumptions will be made t o make the calculation easier. The first assumption is that maximum cooling will be used throughout the day, even though a t the lowest part of the load cycle, the loading will be less than the intermediate rating. The assumption may be optimistic; on the o t h e r h a n d , when loading beyond 'IEEE C57.13-1982, IEEE Standard Requirements for Instrument Transformers. C1. Hand Calculation Determining Rating of 26 - TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) I," v) 8 @d 8 0 m m 9 m c M z a - 4 0 m 27 EEE C67115-1991 IEEE IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER CS7116-1991 ( -L) + nameplate rating is applied on purpose, it is not unreasonable to assume that every measure is taken to assist the transformer, including the use of maximum cooling throughout the day. The second assumption is that the oil timeconstant correction will be ignored; refinements of this nature are more appropriate for a computer program. The third assumption is that the load is kept constant during the following hour. For the rising part of the load curve this assumption will give loads that are too low, but on the falling part of the load curve loading values that will be too high. It is possible to refine the load representation when there is need. Lastly, the ambient temperature is considered constant during the day. The transformer characteristics at 187 MVA are : Top-oil rise over ambient at rated load, epI= 36.0 "c Hottest-spot conductor rise over top-oil temperature, e,,,,, = 28.6 "C Ratio of load loss at rated load to no-load loss, R = 4.87 Oil thermal time constant for rated load, 7, = 3.5 h Exponential power of loss versus top-oil rise, n = 1.0 Exponential power of winding loss versus winding gradient, m = 1.0 The ultimate top-oil rise over ambient for load K will be, according to 3.2, Eq 3, B o = (29.87K2 + 6.13) 1 - e eo and for t eo K = (e, - e i ) (1 - e e (Eq (33) 2 =m 28.6 ~2 (Eq C4) = .\/[(0.81)2 i(0.68)2 + + (0.55)' (0.61)2 + (0.58)2 + (0.53)2]/6 = 0.634 Using C4 a load of this magnitude yields an ultimate top-oil rise of e, = 29.87 ~2 + 6.13 = 29.87(0.34)2 + 6.13 = 18.14 "C Using B i = 18.14 at 6:OO am, and K = 0.52 we can determine 0 ,at 7 :00 am as follows: eo eo (EqC1) After 1 h the top-oil temperature rise will be, Eq 2. e, = 3.98 ~2 + 0.82 + 0.87 One quantity, the initial top-oil rise, is still missing and we will have to estimate it. If we assume the load cycle for Normal Load found in Table C1, we may establish the rms value of the load curve, as an example, for the 6 h load preceding 6:OO am. (4.87) 1 4.87+1 = 29.87K2+ 6.13 (Eq C2) 0.5 h eg = egtn, ~ 1.0 =36.0 = 1.53 + 0.75 ei tl.e-= I The winding gradient will be according to 3.2, Eq 4, eu=6fl(Rtl)l [K 2 + ] K2R'1 = 7.42 K Z + 3.5 - t G)+ ei or rewritten - -t = 7.42 ~2 + 1.53 + o.75ei = 17.14 "c To determine the top-oil temperature rise at 8:OO am set Bi = B o , calculated at 7:OO am. Repeated application of Eq C2 will produce a top-oil temperature rise profile; however, a slight discrepancy occurs 24 h later at 6:OO am. When one continues to apply Eq C2, convergency to true values is soon obtained, as shown in Table C1, normal load, 8 , columns. The first column represents the first iteration and the second column represents the results after an additional iteration. The winding gradient 8 , is considered to be instantaneous. Only where current discontinuities occur will some consideration be given t o the winding time-constant. At 6:OO am e g = (28.6) (0.52)2 When we substitute 7 , = 7,. = 3.5 and the flu value of Eq C1, we obtain for t = 1 h = 28 7.73 "C for example. IEEE C57115-1991 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) 0 ehs P L B N C x 130 - 120 - 110 -up:; - - x- - ehs -K- NORMAL LOADING LOAD PROFILE -o---o-- t 100 - 1.0 90 - 0.9 80 - 0.8 70 - 0.7 60 - 0.6 I I 6 I 8 I I 10 J , 12 , lb I 16 I I 18 I I 20 I I 22 I I 24 I I 2 > *- I I 4 I I 6 HOURS Fig C1 Planned Loading Beyond Nameplate In 3.2, Eq 1, ohs = e o + eg + ea, will be used to establish the hottest-spot winding temperature 8 h s, using for ambient temperature 8, = 30.0 "C. A complete daily normal load cycle is presented in Table C1 and shown in Fig C1. C2. Planned Loading Beyond Nameplate (PLBN). The constraint on PLBN loading is hottest-spot winding temperatures in the 120130 "C range for a maximum of 4 h; therefore, 0, + Og = 120 "C - 6, = 90 "C.The three highest temperatures for the normal loading cycle are just over 90.3 "C; therefore, eo+ 6, = 60.3"C. To estimate what load multiplier K should be to produce B o + O s = 90 "C, we proceed as follows: K 2 R + l --90 R + 1 60.3 K = 1.26 The top-oil rise is not quite proportional to the square of the load current (no-load losses are constant) but the winding gradient is proportional to the square of the load current. The multiplier may have to be corrected if it is unsatisfactory. Again we have to estimate an initial top-oil temperature. Following the same procedures as for the normal load, we obtain a temperature profile, based on the load cycle given in Table C1 under PLBN and shown in Fig C1. The hottest-spot temperature is in the 120 "(3-130 "C for close to 4 h. C3. Long-time Emergency Loading (LTE). A user has to consider carefully the emergency IEEE IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER CS7115-1991 ? l 8 O1l 7 0 160 - 150- 140- 130- 'ER JNIT t 120- 1.6 1 1 0 - 1.4 100- 1.2 90- 1 .o 8 0 . 0.8 LOAD 70 0.6 60 - 1 6 1 1 8 1 1 10 1 1 12 1 1 '14 1 1 1 16 1 18 1 1 1 20 1 1 22 1 24 1 1 2 1 1 4 1 1 6 + HOURS Fig C2 Hottest-Spot Temperature Profile Repeated application of Eq C2 finally gives at 19:OO h an equation for 8, and O g in terms of K2 : loading conditions that may occur on his system. A maximum period of 6 h is used in our example. Assume that the long time emergency begins at 13:OO h, and was preceded by a PLBN loading. Suppose a load multiplier of value K2 is applied. At 13:OO h 8, = 33.90 "C which is equal to 8, in the PLBN loading; apply Eq C2 to find A t 1 4 : 0 0 h 8 , = (7.42 0.93 K g ) + 1.53 + (0.75 34.14) = 6.42 KE + 27.14 e, = (28.6 0.96 K;) = 26.36 K ; At. 15:OO h e , = (7.42 0.96 K g ) + 1.53 + (0.75) (6.42 Kg + 27.14) e, = 11.66 K; + 21.89 e, = 2 7 . 4 7 ~ ; e, + eg = 51.25 K; + 11.11 The LTE restraint is 140 O C , thus 51.25 K; + 11.11 + 30.0 = 140.0 and K2 = 1.39. Table C1 shows the top-oil rise and the winding gradient. At 13:OO h and at 19:OO h there is a discontinuity in current. The winding timeconstant usually is in the order of 3-5 min. After 20 min 8, will be according to the new load. Figure C2 shows the hottest-spot temperature profile. The 140 "C temperature limitation has been met. The hottest-spot temperature is less than the permissible 6 h in the 130 "C140 "C range but longer than 4 h in the 30 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65"CWINDING RISE) - - IEEE C57115-1991 sults of the four load cycles, Tables C3, C4, C5,and C6 show the following results. (1)A normal load cycle - meets the load requirement, is below daily loss-of-life of 0.0369%, and temperature at hottest-spot is not in excess of the 120 "C limit. (2)Planned loading beyond nameplate - for the required loading condition, the 250 MVA transformer's calculated hottest-spot 165.3 "C, significantly exceeds the limiting hottest-spot of 130 "C. (3)Short Time Emergency Loading - for the required loading condition, calculated hottest-spot - 188.5 "C exceeds the guide limit of 180 "C. (4)Long Time Emergency Loading - for the required loading condition, calculated hottest-spot - 169.4 "C exceeds the guide limit of 140 "C. 120 "C-130"C range, so a value of 1.39 applied to the per unit load from 13:OO-19:OOh seems t o be in order. C4. Short Time Emergency Loading (STE). In our example an STE is assumed to occur at 13:OO h, following a PLBN loading. After one half hour, the load is reduced to the LTE loading which will persist for 5.5 h. We will use an interval load value K , . The STE constraint is a maximum hottest-spot temperature of 180 "C. At 13:OO h B i = 34.14 "C Apply Eq C3 (for t = 0.5h)to obtain at 13:30h e o = 3.98K; + 0.82 + (0.87)(34.14) eg = 28.6K ; ehs = e o + eg + ea = 32.58Kg + 30.52 + 30.0 = 180.0 K , = 1.92 At 13:30 h B o = 45.19,8 , = 105.43,O h s = 180.6,load = 1.29 per unit At 14:OO h B o = (3.98) (1.29)2 + 0.82 + (0.87)(45.19)= 46.76 Figure C2 shows the temperature excursion to be within the limits for the STE loading. The hottest-spot temperature will be somewhat longer in the 130 "C-140"C range but will be well within the 6 h limit. Conclusion: 250 MVA unsatisfactory for the required loading conditions. C5.2 Second Test - 275 MVA. Tables C7, C8, C9,and C10 show the following results of the four-load cycles with a 275 MVA transformer: (1)Normal load cycle - meets load requirement, is below daily loss-of-life requirement, and maximum hotteat-spot temperature 107.3 "C is below the guide limit of 120 "C. (2)Planned loading beyond nameplate - the 275 MVA transformer maximum hottestspot of 145.2"C exceeds the limit of 130°C. (3)Short time emergency loading - the maximum hottest-spot of 164.8"C is within the guide limit of 180 "C. (4)Long time emergency load - the maximum hottest-spot of 148.7 "C exceeds the limit of 140 "C. Since the guide limits are exceeded for planned loading beyond nameplate, the 275 MVA size is inadequate. Tests as shown in Tables C11, C12, C13, and C14 were run for a 300 MVA transformer which produced results for conditions C5.2(1), (2), (3) and (4) which meet the requirements. This, then, is the transformer required to satisfy load needs and be within guide limits. C5. Computer Calculation Method. (Determining required transformer rating to meet a set of stipulated loads.) Input Data (1)Ambient temperatures. See output format for hourly ambients used - Tables C3 through C14. (2)MVA load values for various load conditions. See Table C3 through C14. (3)Voltages of system in this example are 138 kV and 69 kV (high voltage and low voltage), and typical estimated values of transformer constants required in the calculation are given in Table C2. (4)Data is prepared and computer programs run to determine whether the transformer selected meets the loading requirements and limiting conditions of loading within the guide. C5.1 First Test - 250 MVA. The first test considers a 250 MVA rated transformer. Re- 31 IEEE IEZE GUIDE FOR LOADING MINERAL-OIL-IMMERSEDPOWER C67116-1991 Table C2 Typical Estimated Values of Transformer Constants Required in Calculations MVA 250 Weight of transformer core and coil - lb Weight of tank - lb Volume of oil - gallon Total transformer loss at full load - watt Loss ratio at rated load/no load loss - factor Rise of winding by resistance - "C Top fluid rise - "C m value n value 275 344 000 150 000 22 575 1 160 000 9.0 60.9" 42.7" 0.8 1.0 378 165 24 1280 300 000 000 900 000 9.0 60.9" 42.7" 410 000 180 000 27 000 1 4 0 0 000 9.0 60.9" 42.7" 0.8 1.0 0.8 1.0 Table C3 Transformer 250 MVA 138 - 69 kV Normal Life Expectancy Loading Hour Load MVA Top Oil Rise Ambient Temperature 26.00 24.76 26.00 19.89 26.00 16.87 24.00 15.01 23.00 13.86 23.00 14.41 25.00 16.32 27.00 19.24 29.00 23.10 30.00 30.11 31.00 37.10 33.00 41.42 35.00 44.09 35.00 45.75 35.00 46.77 35.00 47.41 35.00 47.80 35.00 48.04 34.00 45.54 33.00 42.75 31.00 41.03 30.00 38.77 31.00 36.25 29.00 31.57 Total loss of life for 24 hours is 0.0288 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 134.00 112.00 112.00 112.00 112.00 134.00 157.00 179.00 202.00 246.00 268.00 268.00 268.00 268.00 268.00 268.00 268.00 268.00 246.00 235.00 235.00 224.00 213.00 179.00 32 Hottest-Spot cu 63.00 55.08 52.06 48.20 4 6.04 49.65 57.09 65.69 75.70 92.46 105.20 111.52 116.20 117.85 118.88 119.51 119.90 120.15 111.89 105.82 102.10 96.62 92.95 80.02 Loss of Life % 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0002 0.0008 0.0018 0.0027 0.0033 0.0037 0.0042 0.0042 0.0042 0.0018 0.0009 0.0006 0.0003 0.0002 0.0 Em C57115-1991 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) Table C4 Transformer 250 MVA 138 - 69 kV Planned Loading Beyond Nameplate Rating Hour Load MVA Top Oil Rise Ambient Temperature 134.00 25.95 26.00 2 112.00 20.62 26.00 3 112.00 26.00 17.33 4 112.00 15.29 24.00 5 112.00 14.03 23.00 6 134.00 14.52 23.00 7 157.00 16.39 25.00 8 179.00 19.28 27.00 9 202.00 23.12 29.00 10 246.00 30.12 30.00 11 268.00 37.10 31.00 12 268.00 41.42 33.00 13 268.00 44.10 35.00 14 268.00 45.75 35.00 15 348.00 58.33 35.00 16 348.00 66.11 35.00 17 348.00 70.92 35.00 18 348.00 73.90 35.00 19 246.00 61.54 34.00 20 235.00 52.65 33.00 21 235.00 47.15 31.00 22 224.00 42.56 30.00 23 213.00 38.60 31.00 24 179.00 33.02 29.00 Total loss of life for 24 hours is 0.7632 1 Hottest-Spot CU Loss of Life 64.19 55.81 52.52 48.48 46.22 49.76 57.16 65.73 75.73 92.48 105.21 111.53 116.20 117.86 149.69 157.47 162.28 165.26 127.89 115.72 108.22 100.41 95.29 81.47 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0002 0.0008 0.0018 0.0027 0.0033 0.0769 0.1429 0.2353 0.2857 0.0091 0.0027 0.0011 0.0004 0.0002 0.0 % Table C5 Transformer 250 MVA 138 - 69 kV ShortrTime Emergency Loading Hour Load MVA Top Oil Rise Ambient Temperature 134.00 26.26 26.00 2 112.00 20.82 26.00 3 112.00 17.45 26.00 4 112.00 15.36 24.00 5 112.00 14.07 23.00 6 134.00 14.55 23.00 7 157.00 16.41 25.00 8 179.00 19.29 27.00 9 202.00 23.13 29.00 10 246.00 30.13 30.00 11 268.00 37.11 31.00 12 268.00 41.43 33.00 13 268.00 44.10 35.00 14 268.00 45.75 35.00 15 348.00 58.33 35.00 16 348.00 66.11 35.00 17 348.00 70.92 35.00 18 400.00 83.02 35.00 19 246.00 67.18 34.00 20 235.00 56.14 33.00 21 235.00 49.31 31.00 22 224.00 43.90 30.00 23 213.00 39.43 31.00 24 179.00 33.53 29.00 Total loss of life for 24 hours is 2.3053 1 *Denotes temperature has exceeded limit. 33 Hottest-Spot cu 64.50 56.00 52.64 48.55 46.26 49.79 57.18 65.74 75.74 92.48 105.21 111.53 116.20 117.86 149.69 157.47 162.28 188.45 133.54 119.21 110.38 101.75 96.12 81.99 Loss of Life % 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0002 0.0008 0.0018 0.0027 0.0033 0.0769 0.1429 0.2353 1.8182* 0.0172 0.0037 0.0014 0.0006 0.0003 0.0 IEEE IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER C57115-1991 Table C6 Transformer 250 MVA 138 - 69 kV Long-Time Emergency Loading Hour Load MVA ~ Top Oil Rise ~~ ~ Ambient Temperature 26.00 39.34 30.97 26.00 26.00 25.79 22.58 24.00 20.60 23.00 21.47 23.00 24.67 25.00 29.51 27.00 29.00 35.98 30.00 47.90 59.66 31.00 66.93 33.00 71.43 35.00 74.22 35.00 35.00 75.94 77.00 35.00 77.66 35.00 78.07 35.00 73.94 34.00 69.18 33.00 66.24 31.00 62.33 30.00 58.05 31.00 50.27 29.00 Total loss of life for 24 hours is 2.5776 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Hottest-Spot cu Loss of Life 83.93 71.01 65.83 60.62 57.64 63.06 73.65 85.97 100.77 127.18 147.01 156.29 162.79 165.57 167.30 168.36 169.02 169.43 157.22 147.82 142.88 134.43 127.95 108.93 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0005 0.0083 0.0588 0.1333 0.2500 0.3077 0.3448* 0.3636* 0.4167* 0.4167* 0.1429 0.0667 0.0400 0.0172 0.0091 0.0012 % ~~ 174.00 146.00 146.00 146.00 146.00 174.00 204.00 232.00 262.00 320.00 348.00 348.00 348.00 348.00 348.00 348.00 348.00 348.00 320.00 305.00 305.00 290.00 276.00 233.00 *Denotes temperature has exceeded limit. Table C7 Transformer 275 MVA 138 - 69 kV Normal Life Expectancy Loading Hour Load MVA Top Oil Rise Ambient Temperature 26.00 21.18 17.16 26.00 26.00 14.67 24.00 13.13 23.00 12.18 23.00 12.64 14.22 25.00 27.00 16.63 19.82 29.00 25.62 30.00 31.40 31.00 33.00 34.97 37.18 35.00 35.00 38.55 35.00 39.40 35.00 39.92 35.00 40.24 35.00 40.44 34.QO 38.37 33.00 36.07 31.00 34.64 30.00 32.78 31.00 30.70 29.00 26.82 Total loss of life for 24 hours is 0.0070 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 134.00 112.00 112.00 112.00 112.00 134.00 157.00 179.00 202.00 246.00 268.00 268.00 268.00 268.00 268.00 268.00 268.00 268.00 246.00 235.00 235.00 224.00 213.00 179.00 34 Hottest-Spot cu Loss of Life 57.69 51.04 48.56 45.02 43.06 46.15 52.76 60.34 69.09 83.40 94.26 99.83 104.04 105.41 106.25 106.78 107.10 107.30 100.15 94.89 91.46 86.69 83.76 72.53 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0002 0.0004 0.0007 0.0008 0.0009 0.0010 0.0010 0.0010 0.0004 0.0002 0.0001 0.0 0.0 0.0 % IEEE C67115-1991 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) Table C8 Transformer 275 MVA 138 - 69 kV Planned Loading Beyond Nameplate Rating Hour Load MVA Top Oil Rise 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 134.00 112.00 112.00 112.00 112.00 134.00 157.00 179.00 202.00 246.00 268.00 268.00 268.00 268.00 348.00 348.00 348.00 348.00 246.00 235.00 235.00 224.00 213.00 179.00 Ambient Temperature 21.90 26.00 17.60 26.00 14.94 26.00 13.30 24.00 23.00 12.28 12.70 23.00 14.26 25.00 16.66 27.00 19.84 29.00 25.63 30.00 31.41 31.00 34.98 33.00 37.19 35.00 38.55 35.00 48.95 35.00 55.39 35.00 59.37 35.00 61.83 35.00 51.60 34.00 44.25 33.00 39.70 31.00 35.91 30.00 32.63 31.00 28.02 29.00 Total loss of life for 24 hours is 0.1364 Hottest-Spot cu Loss of Life 58.41 51.49 48.83 45.19 43.17 46.21 52.80 60.36 69.11 83.41 94.26 99.83 104.04 105.41 132.34 138.77 142.75 145.22 113.38 103.07 96.52 89.82 85.69 73.72 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0002 0.0004 0.0007 0.0008 0.0133 0.0278 0.0400 0.0500 0.0020 0.0006 0.0003 0.0001 0.0 0.0 % Table C9 Transformer 275 MVA 138 - 69 kV Short-Time Emergency Loading Hour Load MVA Top Oil Rise Ambient Temperature 26.00 22.15 26.00 17.76 26.00 15.04 24.00 13.36 23.00 12.32 23.00 12.73 25.00 14.28 27.00 16.67 29.00 19.85 30.00 25.63 31.00 31.41 33.00 34.98 35.00 37.19 35.00 38.55 35.00 48.95 35.00 55.39 35.00 59.37 35.00 18 69.37 34.00 19 56.27 33.00 20 47.14 31.00 41.49 21 22 30.00 37.01 23 31.00 33.32 24 29.00 28.44 Total loss of life for 24 hours is 0.3738 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 134.00 112.00 112.00 112.00 112.00 134.00 157.00 179.00 202.00 246.00 268.00 268.00 268.00 268.00 348.00 348.00 348.00 400.00 246.00 235.00 235.00 224.00 213.00 179.00 35 Hottest-Spot cu 58.66 51.64 48.93 45.25 43.21 46.24 52.82 60.37 69.11 83.41 94.27 99.84 104.04 105.41 132.34 138.77 142.75 164.83 118.04 105.95 98.30 90.93 86.38 74.15 Loss of Life % 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0002 0.0004 0.0007 0.0008 0.0133 0.0278 0.0400 0.2857 0.0033 0.0009 0.0003 0.0001 0.0 0.0 ZEEE C67J.15-1991 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER Table C10 Transformer 275 MVA 138 - 69 kV Long-Time Emergency Loading ~ Load MVA Hour ~~ Top Oil Rise Ambient Temperature Hottest-Spot cu Loss of Life % ~ 1 174.00 33.24 26.00 2 146.00 26.32 26.00 3 146.00 22.04 26.00 4 146.00 19.39 24.00 17.75 23.00 5 146.00 6 174.00 18.47 23.00 7 204.00 21.12 25.00 8 232.00 25.12 27.00 30.48 29.00 9 262.00 10 320.00 40.33 30.00 11 348.00 50.05 31.00 12 348.00 56.07 33.00 13 348.00 59.79 35.00 14 348.00 62.09 35.00 15 348.00 63.51 35.00 16 348.00 64.39 35.00 17 348.00 64.94 35.00 18 348.00 65.27 35.00 19 320.00 61.85 34.00 20 305.00 57.92 33.00 21 305.00 55.49 31.00 22 290.00 52.25 30.00 23 276.00 48.72 31.00 24 233.00 42.28 29.00 Total loss of life for 24 hours is 0.4385 75.20 64.37 60.09 55.44 52.80 57.44 66.71 77.42 90.20 112.64 129.44 137.45 143.17 145.48 146.90 147.78 148.32 148.66 138.16 130.10 125.67 118.40 113.11 96.75 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0001 0.0020 0.0105 0.0222 0.0400 0.0500 0.0588 0.0667 0.0667 0.0714 0.0250 0.0118 0.0077 0.0033 0.0020 0.0003 Table C11 Transformer 300 M V A 138 - 69 kV Normal Life Expectancy Loading ~~~ Hour Load MVA TopOil Rise Ambient Temperature 1 134.00 18.42 26.00 2 112.00 15.04 26.00 3 112.00 12.96 26.00 4 112.00 11.67 24.00 5 112.00 10.88 23.00 6 134.00 11.28 23.00 7 157.00 12.63 25.00 8 179.00 14.67 27.00 9 202.00 17.36 29.00 10 246.00 22.25 3 0.00 11 268.00 27.12 31.00 12 268.00 30.12 33.00 13 268.00 31.97 35.00 14 268.00 33.11 35.00 15 268.00 33.81 35.00 16 268.00 34.24 35.00 17 268.00 34.51 35.00 18 268.00 34.67 35.00 19 246.00 32.92 34.00 20 235.00 30.97 33.00 21 235.00 29.77 31.00 22 224.00 28.21 30.00 23 213.00 26.45 31.00 24 179.00 23.19 29.00 Total loss of life for 24 hours is 0.0019 36 Hottest-Spot Loss of Life cu % 53.56 47.90 45.82 42.54 40.75 43.43 49.41 56.20 63.99 76.42 85.84 90.84 94.69 95.83 96.53 96.96 97.23 97.39 91.09 86.43 83.23 79.01 76.64 66.72 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0001 0.0002 0.0003 0.0003 0.0003 0.0003 0.0003 0.0001 0.0 0.0 0.0 0.0 0.0 IEEE C57.115-1991 TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 OC WINDING RISE) Table C12 Transformer 300 MVA 138 - 69 kV Planned Loading Beyond Nameplate Rating Hour Load MVA Top Oil Rise Ambient Temperature 19.01 26.00 15.40 26.00 13.18 26.00 11.81 24.00 10.97 23.00 11.34 23.00 12.66 25.00 27.00 14.69 17.37 29.00 10 22.26 30.00 11 27.13 31.00 12 30.12 33.00 13 31.97 35.00 14 33.11 35.00 15 41.89 35.00 16 47.30 35.00 17 50.63 35.00 18 52.69 35.00 19 44.02 34.00 20 37.81 33.00 21 33.99 31.00 22 30.80 30.00 23 28.05 31.00 24 24.17 29.00 Total loss of life for 24 hours is 0.0322 1 2 3 4 5 6 7 8 9 134.00 112.00 112.00 112.00 112.00 134.00 157.00 179.00 202.00 246.00 268.00 268.00 268.00 268.00 348.00 348.00 348.00 348.00 246.00 235.00 235.00 224.00 213.00 179.00 Hottest-Spot cu 54.15 48.26 46.04 42.67 40.83 43.48 49.44 56.22 64.01 76.43 85.84 90.84 94.69 95.83 118.99 124.40 127.73 129.79 102.19 93.27 87.45 81.61 78.25 67.70 Loss of Life ?& 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0001 0.0002 0.0003 0.0037 0.0062 0.0091 0.0118 0.0006 0.0002 0.0 0.0 0.0 0.0 Table C13 Transformer 300 MVA 138 - 69 kV Short-Time Emergency Loading Hour Load MVA 134.00 112.00 112.00 112.00 112.00 134.00 157.00 179.00 202.00 246.00 268.00 268.00 268.00 268.00 348.00 348.00 348.00 400.00 246.00 235.00 235.00 224.00 213.00 179.00 Top Oil Rise Ambient Temperature 26.00 19.21 26.00 15.53 26.00 13.26 24.00 11.86 23.00 11.00 11.36 23.00 25.00 12.67 14.70 27.00 29.00 17.38 22.26 30.00 31.00 27.13 33.00 30.12 35.00 31.97 35.00 33.11 35.00 41.89 47.30 35.00 35.00 50.63 35.00 59.07 34.00 47.95 33.00 40.23 31.00 35.48 30.00 31.72 31.00 28.62 29.00 24.52 Total loss of life for 24 hours is 0.0798 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Hottest-Spot cu 54.36 48.39 46.12 42.72 40.86 43.50 49.45 56.23 64.01 76.43 85.85 90.84 94.69 95.83 118.99 124.40 127.73 146.67 106.12 95.70 88.94 82.53 78.81 68.05 Loss of Life % 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0001 0.0002 0.0003 0.0037 0.0062 0.0091 0.0588 0.0009 0.0003 0.0001 0.0 0.0 0.0 IEEE B E E GUIDE FOR LOADING MINERAL-OIL-IMMERSEDPOWER C57116-1991 Table C14 Transformer 300 MVA 138 kV - 69 kV Long-Time Emergency Loading Hour Load MVA Top Oil Rise Ambient Temperature 26.00 174.00 28.53 26.00 146.00 22.71 26.00 146.00 19.12 24.00 146.00 16.91 146.00 23.00 15.55 23.00 16.18 174.00 25.00 204.00 18.43 27.00 232.00 21.81 262.00 29.00 26.33 320.00 30.00 34.64 11 348.00 31.00 42.84 33.00 47.88 12 348.00 35.00 50.99 13 348.00 35.00 52.91 14 348.00 54.09 15 348.00 35.00 54.82 16 348.00 35.00 55.27 17 348.00 35.00 55.54 18 348.00 35.00 34.00 52.65 19 320.00 49.32 20 305.00 33.00 47.28 21 305.00 31.00 44.55 22 290.00 30.00 41.58 23 276.00 31.00 24 233.00 36.15 29.00 Total loss of life for 24 hours is 0.0946 1 2 3 4 5 6 7 8 9 10 38 Hottest-Spot cu 68.41 59.19 55.61 51.40 49.04 53.07 61.34 70.82 82.06 101.46 115.93 122.98 128.09 130.01 131.19 131.92 132.36 132.64 123.46 116.41 112.37 106.00 101.63 87.31 Loss of Life % 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0005 0.0027 0.0056 0.0091 0.0118 0.0125 0.0133 0.0133 0.0143 0.0056 0.0027 0.0018 0.0009 0.0006 0.0 IEEE TRANSFORMERS RATED IN EXCESS OF 100 MVA (65 "C WINDING RISE) Cb7115-1991 Appendix D Philosophy of Guide Applicable to Older Transformers I 100 MVA rating rarely causes interruption of customers. However, loss of one transformer due to its failure or due to the failure of some other part in the electrical circuit can result in increased loading of the back-up transformers. Most utilities do not design for second contingencies without loss of load. The adverse consequences are therefore rather great if the increased loading of the backup transformers results in a failure. Common sense and good planning is required to keep the economic gains in balance with the risks of failure. Because excessive transformer temperatures weaken the insulation structures physically and because many of these older transformers have low impedances, shortcircuit failures should also be considered. The types of transformer construction are a factor in making this assessment. Most utilities load these transformers conservatively. Gas evolution in power transformers is not a new insulation contaminant. There are at least eight causes of gas within the transformer that have been documented in the literature. The risk of having a failure due to free gas in the insulation structure should take into consideration the insulation margins used and the construction of the insulation structures. The risk of failure increases when the insulation levels are reduced three full steps such as use of 650 kV BIL on 230 kV transformers. The risk decreases when no insulation collars are used in highly stressed parts of these transformers with reduced BIL. Knowledgeable transformer engineers have paid close attention to gas evolution when specifying and designing these transformers. The loading of transformers having 55 "C ratings is considered outside of the scope of this guide and will therefore not be discussed in this section. Discussions Concerning the greater than nameplate load capability of transformers built before publication of this guide can be very controversial. There is some hope of agreement on the loading limits if they have been clearly specified prior to the design of the transformer. However, since there has been new knowledge gained in recent years concerning stray flux fields and their effects on metallic temperatures, it is desirable to confirm greater than nameplate load capabilities with the manufacturers of transformers on critical systems. Some users have considerable experience in loading power transformers above nameplate using computer programs in conjunction with the IEEE C57.92-1981 Appendix and NEMA TR98-1978, Guide for Loading Oil Immersed Power Transformers with 65 "C Average Winding Rise. Since this approach deals with loss of life due to the effects of thermal aging of the windings, it should always be accompanied with due consideration given to the load capabilities of all other components in the transformer. These components include the bushings, various tap changers and terminal boards, and leads. Relay settings should also be checked so that load is not dumped. Consideration should also be given to oil expansion and its effect on possible mechanical relief device operation, subsequent possible operation of the fault-pressure relay, and oil clogging of breathing devices. Forced-oil cooler fouling should also be a consideration when determining load capability. This fouling is particularly found in areas having salt spray environments or dust and chemical contaminants present. These computer programs should be modified to reflect this new loading guide where its use may lead to more conservative loading. The loss of a single transformer of over 39 IEEE C57115-1991 Appendix E Unusual Temperature and Altitude Conditions El. Unusual Temperatures and Altitude without exceeding temperature limits, provided the average temperature of the cooling air does not exceed the values of Table E l for the respective altitudes. Service Conditions Transformers may be applied at higher ambient temperatures or at higher altitudes than specified in IEEE C57.12.00-1987111, but performance may be affected and special consideration should be given t o these applications. NOTES:(1)See Section 4.3.2of IEEE C57.12.00-1987[l]for transformer insulation capability at altitudes above 3300 R (1000m). (2) Operation in low ambient temperature with the top liquid a t a temperature lower than -20"C may reduce dielectric strength between internal energized components below design levels. E2. Effect of Altitude on Temperature Rise The effect of the decreased air density due to high altitude is to increase the temperature rise of transformers since they are dependent upon air for the dissipation of heat losses. E4. Operation at Less than Rated kVA Transformers may be operated at altitudes greater than 3300 f t (1000 m) without exceeding temperature limits, provided the load to be carried is reduced below rating by the percentages given in Table E2 for each 330 f t (100 m) that the altitude is above 3300 f t (1000 m). E3. Operation at Rated kVA Transformers may be operated at rated kVA at altitudes greater than 3300 f t (1000 m) Table E l Maximum Allowable Average Temperature* of Cooling Air for Carrying Rated kVA Method of Cooling Apparatus Liquid-Immersed Self-Cooled Liquid-Immersed Forced-Air-cooled Liquid-Immersed Forced-Oil-Cooled with Oil-to-Air Cooler 1000 Meters (3300 Feet) 2000 Meters (6600 Feet) 30 30 28 26 30 26 3000 Meters (9900 Feet) Degrees C 4000 Meters ( 1 3 200 Feet) 25 23 23 20 23 20 *It is recommended that the average temperature of the cooling air be calculated by averaging 24 consecutive hourly readings. When the outdoor air is the cooling medium, the average of the maximum and minimum daily temperatures may be used. The value obtained in this manner is usually slightly higher, by not more than 0.3 'C, than the true daily average. Table E2 Rated kVA Correction Factors for Altitudes Greater than 3300 f t (1000 m) Derating Factor Types of Cooling Liquid-immersed air-cooled Liquid-immersed water-cooled Liquid-immersed forced-air-cooled Liquid-immersed forced-liquidcooled with liquid-to-air cooler Liquid-immersed forced-liquidcooled with liquid-to-water cooler 40 (%) 0.4 0.0 0.5 0.5 0.0