LOW-PEAK® LPJ

advertisement
Bussmann®
LOW-PEAK
LPJ
®
Dual-Element Time-Delay Fuses
Class J – 600 Volt
Dimensional Data
2.25"
(± 0.03)
.81"
.5" (± 0.03)
1A to 30A
2.38"
(± 0.03)
.63"
35A to 60A
1.06"
(± 0.03)
Catalog Symbol: LPJ-_SP
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: 1 to 60A
Voltage Rating: 600Vac (or less)
300Vdc (or less)
Interrupting Rating: 300,000A RMS Sym. (UL)
100,000A dc
Agency Information:
UL Listed — Special Purpose*, Guide JFHR, File E56412
CSA Certified, 200,000 AIR, Class J per CSA 22.2 No. 248.8
Class 1422-02, File 53787
1-60 Amps
General Information:
• True dual-element fuses with a minimum 10 second timedelay at 500% overload.
• Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges.
• Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail.
• High interrupting rating to safely interrupt overcurrents up to
300,000A.
• High degree of current limitation due to the fast speed-ofresponse to short-circuits.
• Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices.
• Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components.
• Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1.
• Dual-element fuses have lower resistance than ordinary fuses
so they run cooler.
• Lower watts loss reduces power consumption.
• Unique dimensions assure that another class of fuse with
a lesser voltage rating, interrupting rating or current-Iimiting
ability cannot be substituted.
• Space-saving package for equipment down sizing.
*Meets all performance requirements of UL Standard 248-8 for Class J fuses.
Catalog Symbol and Ampere Ratings
LPJ-1SP
LPJ-3SP
LPJ-7SP
LPJ-25SP
LPJ-1⁄Ω¢SP
LPJ-3-¤Ω¡ºSP
LPJ-8SP
LPJ-30SP
LPJ-1-flꭧSP
LPJ-3⁄Ω™SP
LPJ-9SP
LPJ-35SP
LPJ-1-°Ω¡ºSP
LPJ-4SP
LPJ-10SP
LPJ-40SP
LPJ-2SP
LPJ-4⁄Ω™SP
LPJ-12SP
LPJ-45SP
LPJ-2⁄Ω¢SP
LPJ-5SP
LPJ-15SP
LPJ-50SP
LPJ-2⁄Ω™SP
LPJ-5flꭧSP
LPJ-17⁄Ω™SP
LPJ-60SP
LPJ-2°Ω¡ºSP
LPJ-6SP
LPJ-20SP
Recommended fuseblocks/fuseholders for
Class J 600V fuses
See Data Sheets listed below
• Finger-safe fuseholders - 1152
• Open fuseblocks - 1114
• Open pyramid fuseblocks - 1108
Carton Quantity and Weight
Ampere
Ratings
Weight**
Carton
Qty.
Lbs.
Kg.
1–30
10
1.09
0.494
35–60
10
1.78
0.808
**Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
10-2-02
SB02295
Form No. LPJ 1-60
Page 1 of 3
Data Sheet: 1006
Bussmann®
LOW-PEAK®
LPJ
Dual-Element Time-Delay Fuses
Class J – 600 Volt
1-60 Amps
60A
30A
15A
10A
6A
3A
1A
Time-Current Characteristic Curves–Average Melt
AMPERE
RATING
300
200
100
TIME IN SECONDS
10
1
1,000
100
1
.01
10
.1
CURRENT IN AMPERES
10-2-02
SB02295
Form No. LPJ 1-60
Page 2 of 3
Data Sheet: 1006
Bussmann®
LOW-PEAK®
Dual-Element Time-Delay Fuses
Class J – 600 Volt
LPJ
1-60 Amps
Current Limitation Curves
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
10-2-02
SB02295
Form No. LPJ 1-60
Page 3 of 3
Data Sheet: 1006
Bussmann®
LOW-PEAK®
LPJ
Dual-Element, Time-Delay Fuses
Class J – 600 Volt
70 to 600A
Dimensional Data
4.63"
(– 0.03)
3.63"
2.63"
.75"
1.13" (– 0.03)
1" .28"
.43"
70A to 100A
.13"
5.75"
(– 0.03)
4.38"
3.0"
110A to
200A
.43"
1.13"
.28"
1.63" (– 0.03)
1.38"
.19"
225A to 400A
Catalog Symbol: LPJ-_SP
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Ampere Rating: 70 to 600A
Voltage Rating: 600Vac (or less)*
Interrupting Rating: 300,000A RMS Sym.
Agency Information:
UL Listed – Special Purpose†, Guide JFHR, File E56412
CSA Certified, Class J per CSA C22.2 No. 248.8,
Class 1422-02, File 53787
*0-600A rated 300Vdc and 20 KAIC.
†Meets all performance requirements of UL Standard 248-8 for Class J fuses.
Catalog Symbol and Ampere Ratings
LPJ-70SP
LPJ-125SP
LPJ-250SP
LPJ-500SP
LPJ-80SP
LPJ-150SP
LPJ-300SP
LPJ-600SP
LPJ-90SP
LPJ-175SP
LPJ-350SP
—
LPJ-100SP
LPJ-200SP
LPJ-400SP
—
LPJ-110SP
LPJ-225SP
LPJ-450SP
—
Carton Quantity and Weight
Weight*
Ampere
Ratings
Carton
Qty.
Lbs.
Kg.
70–100
5
1.69
0.767
110–200
5
4.21
1.910
225–400
1
1.67
0.758
450–600
1
2.80
1.270
*Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
10-8-03
A03094
450A to 600A
General Information:
• True dual-element fuses with a minimum 10 second timedelay at 500% overload.
• Long time-delay minimizes needless fuse openings due to
temporary overloads and transient surges.
• Can often be sized for back-up protection against motor
burnout from overload or single-phasing if other overload
protective devices fail.
• High interrupting rating to safely interrupt overcurrents up
to 300,000A.
• High degree of current-limitation due to the fast speed-ofresponse to short-circuits.
• Faster response to damaging short-circuit currents than
mechanical overcurrent protective devices.
• Reduces let-through thermal and magnetic forces in order
to protect low withstand rated components.
• Proper sizing provides “no damage” Type “2” coordinated
protection for NEMA and IEC motor control in accordance
with IEC Standard 947-4-1.
• Dual-element fuses have lower resistance than ordinary
fuses, hence they run cooler.
• Lower watts loss reduces power consumption.
• Unique dimensions assure that another class of fuse with a
lesser voltage rating, interrupting rating or current-Iimiting
ability cannot be substituted.
• Space-saving package for equipment down sizing.
Form No. LPJ 70-600
Page 1 of 3
Data Sheet: 1007
Bussmann®
LOW-PEAK®
LPJ
Dual-Element, Time-Delay Fuses
Class J – 600 Volt
70-600A
Recommended fuseblocks for
Class J 600V fuses
See Data Sheet: 1114
600A
400A
200A
250A
125A
80A
100A
Time-Current Characteristic Curves–Average Melt
AMPERE
RATING
300
200
100
TIME IN SECONDS
10
1
.1
10,000
100
1,000
.01
CURRENT IN AMPERES
10-8-03
A03094
Form No. LPJ 70-600
Page 2 of 3
Data Sheet: 1007
Bussmann®
LOW-PEAK®
Dual-Element, Time-Delay Fuses
Class J – 600 Volt
LPJ
70-600A
Current-Limitation Curves
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
10-8-03
A03094
Form No. LPJ 70-600
Page 3 of 3
Data Sheet: 1007
Bussmann®
LOW-PEAK®
LP-CC
Time-Delay Fuses
Class CC – 600 Volt, ⁄Ω™ to 30 Amps
Dimensional Data
1.5" (±0.031)
(38.1mm)
.41" (±0.005)
(10.3mm)
Catalog Symbol: LP-CC
Time-Delay, Current-Limiting
Ampere Rating: ⁄Ω™ to 30A
AC Voltage Rating: 600V (or less)
Interrupting Rating: 200,000A RMS Sym.
Agency Information:
UL Listed, Std. 248-4, Class CC, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.4, Class 1422-02, File 53787
DC Voltage Rating: 300Vdc (or less)
⁄Ω™-2 °/⁄‚A and 20-30A, 20,000 AIR, UL 198L
150Vdc or less 3-15A, 20,000 AIR, UL 198L
Catalog Numbers
LP-CC-⁄Ω™
LP-CC-1⁄Ω™
LP-CC-3
LP-CC-6
LP-CC-12
LP-CC-flꭧ
LP-CC-1flꭧ
LP-CC-3¤Ω¡º
LP-CC-6⁄Ω¢
LP-CC-15
LP-CC-°Ω¡º
LP-CC-1°Ω¡º
LP-CC-3⁄Ω™
LP-CC-7
LP-CC-20
LP-CC-1
LP-CC-2
LP-CC-4
LP-CC-7⁄Ω™
LP-CC-25
LP-CC-1⁄Ω•
LP-CC-2⁄Ω¢
LP-CC-4⁄Ω™
LP-CC-8
LP-CC-30
LP-CC-1⁄Ω¢
LP-CC-2⁄Ω™
LP-CC-5
LP-CC-9
—
LP-CC-1›Ω¡º
LP-CC-2°Ω¡º
LP-CC-5flꭧ
LP-CC-10
—
Carton Quantity and Weight
Ampere
Ratings
Weight*
Carton
Qty.
Lbs.
Kg.
10
.193
.088
0-30
*Weight per carton.
Recommended fuseblocks/fuseholders for
Class CC 600V fuses
See Data Sheets listed below
• Open fuseblocks - 1105
• Finger-safe fuseholders - 1109, 1102, 1103, 1151
• Panel-mount fuseholders - 2114, 2113
• In-line fuseholders - 2126
General Information:
LP-CC LOW-PEAK Yellow™ Fuse
• A superior all-purpose, space-saving branch circuit fuse
that meets most protection requirements up to 30A.
• Very compact; physical size is only ⁄‹Ω£™∑ ≈ 1⁄Ω™∑ (10.3mm ≈
38.1mm) with rejection tip.
• The unique yellow color makes it easy to tell that the correct
fuse type is installed.
• Faster response to damaging short-circuit currents and
higher interrupting rating than mechanical overcurrent
protective devices.
200,000A Interrupting Rating
• Maximum interrupting rating for available fault current in
today's large capacity systems.
• Helps ensure that future growth will not obsolete the system.
Dual Characteristics
• Time-delay to avoid unwanted fuse openings from surge
currents.
• Fast speed of response under short-circuit conditions for a
high degree of current-limitation.
• ADVANTAGE: The LOW-PEAK ® fuse can be sized close
to full load ratings for maximum overload and short-circuit
protection.
• ADVANTAGE: Can be used where either a time-delay or
a fast-acting fuse is needed, making selection easier and
reducing spare fuse inventories for substantial cost reduction.
Superior Motor Protection
• For protection of small horsepower motor circuits.
• Proper sizing can provide Type “2” coordinated protection
for NEMA and IEC motor controllers.
• Motors receive maximum protection against burnout from
overloads and single phasing.
Current-Limiting Effects
Prospective Short- *Let-Through Current (Apparent RMS Symmetrical)
Circuit Current
1⁄Ω¢A
2°Ω¡ºA
15A
20A
25A
30A
1,000
100
135
240
305
380
435
3,000
140
210
350
440
575
580
5,000
165
255
420
570
690
710
10,000
210
340
540
700
870
1,000
20,000
260
435
680
870
1,090
1,305
30,000
290
525
800
1,030
1,300
1,520
40,000
315
610
870
1,150
1,390
1,700
50,000
340
650
915
1,215
1,520
1,820
60,000
350
735
1,050
1,300
1,650
1,980
80,000
390
785
1,130
1,500
1,780
2,180
100,000
420
830
1,210
1,600
2,000
2,400
200,000
525
1,100
1,600
2,000
2,520
3,050
*RMS Symmetrical Amperes Short-Circuit
NOTE: To calculate Ip (Ipeak) multiply IRMS value ≈ 2.3.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 314-527-1270 for more information.
10-2-02
SB02295
Form No. LP-CC
Page 1 of 2
Data Sheet: 1023
Bussmann®
LOW-PEAK®
LP-CC
AMPERE
RATING
2-8/10
300
1-1/4
200
100
80
60
50
40
30
2,000
800
1,000
400
500
600
300
200
80
100
20
1,000
CURRENT IN AMPERES
100
10
1
PROSPECTIVE SHORT-CIRCUIT CURRENT–SYMMETRICAL RMS AMPS
.4
.01
AMPERE
RATING
600
500
400
10
.1
30
25
20
15
1,000
800
40
50
60
1
2,000
30
10
3,000
20
100
TIME IN SECONDS
4,000
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
200
10
3
3⁄Ω™
4
4⁄Ω™
6
8
10
12
15
20
25
30
⁄Ω™
flꭧ
°Ω¡º
1
1⁄Ω¢
Time-Delay Fuses
Class CC – 600 Volt, ⁄Ω™ to 30 Amps
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
10-2-02
SB02295
Form No. LP-CC
Page 2 of 2
Data Sheet: 1023
Bussmann®
Class J Fuseblocks
J600 Series
600 Volt, ⁄Ω™-600 Amps
Catalog Symbol: J600 Series
Ampere Rating: ⁄Ω™-600A
Voltage Rating: 600V
Withstand Rating: 200,000 RMS Sym. Amps
For use with Class J Fuses (Bussmann LPJ, JKS)
Agency Information:
UL Listed, UL 512, Guide IZLT, File E14853
CSA Certified, C22.2 No. 39, Class 6225-01, File 47235
UL Flammability: 94VO
Materials: Thermoplastic
Standard J Fuseblocks (600V) Catalog Data
Amps
⁄Ω™-30
31-60
61-100
101-200
201-400
401-600
Poles
Screw†
Pressure
Plate†
1
2
3
1
2
3
1
3
1
3
1
3
1
3
J60030-1S(2)
J60030-2S(2)
J60030-3S(2)
—
—
—
—
—
—
—
—
—
—
—
J60030-1P
J60030-2P
J60030-3P
—
—
—
—
—
—
—
—
—
—
—
Catalog Numbers
Box
Box Lug w/
Lug
Retaining Clip
J60030-1C
J60030-2C
J60030-3C
J60060-1C
J60060-2C
J60060-3C
—
—
—
—
—
—
—
—
Fig.
No.
J60030-1CR††
1
J60030-2CR††
2
J60030-3CR††
3
J60060-1CR††
1
J60060-2CR††
2
J60060-3CR††
3
J60100-1CR
4
J60100-3CR††
5
J60200-1CR
6
J60200-3CR
7
J60400-1CR(3)
8
J60400-3CR(3)
9
J60600-1CR
10
J60600-3CR(2) 11
Wire
Range
C, CR #2-14 CU, #2-8 AL
COR #2-14 CU ONLY
P, PR, S, SR #10-14 CU ONLY
C, CR, #2-14 CU/AL
COR #4-14 CU ONLY
COR 1/0-8 CU ONLY
CR, CRQ 1/0-8 CU/AL
CR 250kcmil-6 CU/AL
CR 500kcmil -4 CU/AL
CR (2) 500kcmil-4/0 CU/AL
†Clip reinforcing springs are standard on fuseblocks rated 100A and above. Available on 30A and 60A blocks by adding the letter “R” to the end of
the part number.
††Copper only connections available by changing “CR” suffix to “COR”.
(2)No UL, No CSA Certification
(3)UL Recognized, CSA Certification
Dimensional Data
All dimensions (±0.015)
61-100A
⁄Ω™-60A
1.702"
3.202"
.750"
2.250"
4.702"
2.415"
2.250"
750"
5"
2.28"
.30"
C
L
4.005"
.94"
1.583"
.22"
Dia.
.5"
C'Bore
6.28"
CL
3.14"
1.500"
1.75"
FIGURE 1.
FIGURE 2.
FIGURE 3.
FIGURE 4.
1.5"
FIGURE 5.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
11-12-03
SB03116
Form No. J600 Series
Page 1 of 2
Data Sheet: 1114
Bussmann®
Class J Fuseblocks
J600 Series
600 Volt, ⁄Ω™-600 Amps
101-200A
3.1"
3.06"
.75"
c'bore
6.125"
7.00"
.31"
.5"
3.15"
8.31"
.75"
3"
2"
.344" dia. hole through
.750 dia. c'bore
6.125"
1.69"
.34"
dia.
.750"
FIGURE 7.
FIGURE 6.
201-400A
10.51"
4"
3"
1.75"
.56"
.625"
3.5"
7.50"
.75"
c'bore
.34"
dia.
7.5"
4.00"
9.00"
6.00"
1"
.344" dia. hole through
.750 dia. c'bore
2.00"
.50"
.5"
1.00"
FIGURE 8.
FIGURE 9.
401-600A
4.99"
4"
1.75"
1.125"
4.99"
14.144"
1"
11.00"
.56"
3.25"
8.875"
.75"
c'bore
.34" dia.
2.375"
FIGURE 10.
.344" dia.
hole through
.750 dia.
c'bore
8.875"
2.88"
FIGURE 11.
.50"
1.00"
All dimensions (±0.015)
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected,
it should be tested by the user in all possible applications.
11-12-03
SB03116
Form No. J600 Series
Page 2 of 2
Data Sheet: 1114
Cooper Bussmann
CH Series Modular Fuse Holders
Class J
Class J – 600 Volt 1-60A
Features:
• Choice of Indication:
–Easy ID window to view indicator on Cooper Bussmann
LPJ-(amp)SPI fuses for permanent fuse indication, even
when power is disconnected.
–Neon indicator is field installable or can be purchased
installed from the factory.
• Comes in standard 1, 2 & 3 Pole ganged assemblies where
all fuses are extracted simultaneously.
• Kits are available for ganging units in the field.
• Meets requirements of IEC 60529 for IP-20 finger safe rating.
• 35mm DIN rail and chassis (6-32 UNC Pan Head
Recommended) mounting features.
• Fuseholder wire ports dual wire rated from 18 to 3AWG.
Specifications:
Fuse Sizes
Voltage Rating
Amperage Rating
35 to 60A Class J
600V
600V
30A
60A
Torque
IP Rating
18-1AWG Single
18-3AWG Dual
75°C
35in-lbs
IP-20 (Finger Safe)
18-1AWG Single
18-3AWG Dual
75°C
35in-lbs
IP-20 (Finger Safe)
Clip Material
Tin Plated Copper
Tin Plated Copper
UL 94 VO
Thermoplastic
90V
UL 94 VO
Thermoplastic
90V
34mA (460Vac)
34mA (460Vac)
Wire Range
Housing Material
Catalog Symbol: CH30J_(I) CH60J_ (I)
Ampere Rating: 1 to 60A
Voltage Rating: 600Vac (or less)
Interrupting Rating: 200,000A RMS Sym.
Agency Approvals:
Listed UL 512, Guide IZLT, File E14853
CSA Certified per C22.2 Nos. 39 Class 6225-01,
File LR47235
Other Electrical Certifications:
CE compliance for the European Union Low Voltage Directive
Recommended Cooper Bussmann Fuses:
Class J Time Delay LPJ (Data Sheet 1006)
Class J Fast Acting JKS (Data Sheet 1026)
0 to 30A Class J
Minimum Indicating Voltage
(Neon Lamp)
Nominal Operating Current
(Neon Lamp)
Max Operating Temperature
Storage Temperature
85°C
85°C
-20°C to +65°C
-20°C to +65°C
CE logo denotes compliance with European Union Low Voltage Directive (50-1000Vac,
75-1500Vdc). Refer to Data Sheet: 8002 or contact Cooper Bussmann Application
Engineering at 314-527-1270 for more information.
7-5-05
SB05189
Form No. Class J 1-60
Page 1 of 2
Data Sheet: 2144
Cooper Bussmann
CH Series Modular Fuse Holders
Class J
Class J – 600 Volt 1-60A
E
H
D
G
Dimensional Data
F
3 POLE CLASS
J Modular Fuse Holder
Dimension
CH30J in [mm]
CH60J in [mm]
A
1.28 [32.5]
1.58 [40.0]
B
2.56 [65.0]
3.16 [80.0]
C
3.84 [97.5]
4.72 [120.0]
D
4.59 [116.6]
4.88 [124.0]
E
2.83 [71.8]
3.31 [84.1]
F
3.56 [90.4]
3.85 [97.9]
G
1.28 [32.5]
1.58 [40.0]
H
0.18 [4.44]
0.18 [4.44]
A
B
C
Catalog Numbers
Easy ID Window
30A Class J
30A AND 60A
Ganging Assembly
60A Class J
Neon Indicating
1Pole
CH30J1
CH30J1I
2Pole
CH30J2
CH30J2I
3Pole
CH30J3
CH30J3I
1Pole
CH60J1
CH60J1I
2Pole
CH60J2
CH60J2I
3Pole
CH60J3
CH60J3I
Accessories
Part Number
Description
Carton Qty.
2A1073
Ganging Kit
(3 Pole)
2 Spring Pins
6 Plastic Connectors
2A1164
Neon Indication
3
2A1777
Circuit Markers
100
INDICATOR ASSEMBLING
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to
change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
7-5-05
SB05189
Form No. Class J 1-60
Page 2 of 2
Data Sheet: 2144
Bussmann®
Class CC Fuseblocks
BCA
Series
600 Volt, 30 Amps
Dimensional Data All dimensions ±.015’’
(.38mm)
Catalog Symbol: BCA Series
Class CC Fuseblocks
For use with Class CC Fuses (Bussmann LP-CC, KTK-R,
and FRQ-R)
Ampere Rating: ⁄Ω¡º to 30
Voltage Rating: 600V
Withstand Rating: 200,000A, RMS Sym.
Agency Information:
UL Listed, UL 512, Guide IZLT, File E14853
CSA Certified, C22.2 No. 39, Class 6225-01, File 47235
UL Flammability: 94 VO
Materials: Base - Thermoplastic
Clips - Bright tin-plated bronze
Catalog Data
Terminal Type
Amps
⁄Ω¡º
to
30
Poles
Adder
1
2
3
Screw with
Quick
Connect*
BCA603ASQ
BCA6031SQ
BCA6032SQ
BCA6033SQ
Pressure
Plate with
Quick
Connect*
BCA603APQ
BCA6031PQ
BCA6032PQ
BCA6033PQ
Fuse blocks feature a unique adder block which can be
snapped onto 1-, 2-, or 3-pole blocks to form multi-pole
segmented blocks of as many poles as desired.
Wire
Range
CU Only
#10-#18
*QUICK CONNECT RATED FOR 20A MAXIMUM.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
4-12-05
SB05085
Form No. BCA Series
Page 1 of 1
Data Sheet: 1154
Download