• Revised • 06/13/14 Circuit Breakers Arc-Fault and Ground-Fault Breakers Selection/Wiring Diagrams Arc-Fault Circuit Interrupters (AFCI) AFCI’s detect arcing faults (an unintentional arcing condition in a circuit) that standard circuit breakers are unable to detect. The device is intended to mitigate the effects of arcing faults by functioning to de-energize the circuit when an arcfault is detected. Combination Type AFCI Detects all three possible types of arc fault: line-to-ground, line-to-neutral, and series. Breaker Type Ampere Rating 22,000 A IR 65,000 A IR 10,000 A IR Catalog Number Catalog Number Catalog Number QAF2/QAFH2/HQAF2 15 20 QA115AFCa QA120AFCa QA115AFCHna QA120AFCHna QA115AFCHH QA120AFCHH QAF2/QAF2H 15 20 Q215AFCa Q220AFCa Q215AFCHna Q220AFCHna — — QA115AFHna QA120AFHna QA115AFHH QA120AFHH 1-Pole 120V AC 2-Pole 120/240V AC 1-Pole Combination Type AFCI 2-Pole Combination Type AFCI 1-Pole Branch Feeder AFCI 1-Pole Dual Function AFCI/GFC 1-Pole GFCI 2-Pole GFCI 1-Pole Equipment Protection 2-Pole Equipment Protection Branch-Feeder AFCI Detects line-to-ground and line-to neutral arcs. QAF2/QAFH2/HQAF2 1-Pole 120V AC NEW 15 20 QA115AFa QA120AFa Dual Function AFCI/GFCI The Dual Function Circuit Breaker combines Combination Type AFCI and GFCI, protecting against both Arc Faults and Ground Faults. The device includes the Self Test and Lockout feature, making it the fist in class in electrical safety for homeowners. QFGA2/QFGAH2/ HQFGA2 1-Pole 120V AC 15 20 QA115DF QA120DF Q115DFH Q120DFH Q115DFHH Q120DFHH Provides Class A (5mA) ground fault protection. Intended for personnel protection. De-energizes the circuit for all ungrounded conductors of the circuit. Provides protection of equipment from damaging line-to-ground faults currents. De-energizes the circuit for all ungrounded conductors of the circuit. Breaker Type QPF/ QPHF 1-Pole 120V AC Plug-in Amp 10,000 A IR 22,000 A IR Rating Catalog No. Catalog No. 15 20 25 30 15 20 30 2-Pole 120/ 40 240V AC 50 Plug-in 60 QPF/ QPHF QF115a QF120a QF125n QF130 QF115Ha QF120Hna — QF130H QF215 QF220 QF230 QF240 QF250 QF260 QF215H QF220H QF230H QF240H QF250H QF260H QAF2/QPF/QE Accessories Description Catalog Number Padlocking Device 1-Pole ECPLD1 Padlocking Device 2-Pole ECPLD2 Handle Block ECBX231M Breaker Type QE/ QEH Amp 10,000 A IR 22,000 A IR Rating Catalog No. Catalog No. 15 20 30 QE115a QE120a QE130 QE115Ha QE120Ha QE130H 15 20 30 2-Pole 120/ 40 240V AC 50 Plug-in 60 QE215 QE220 QE230 QE240 QE250 QE260n QE215H QE220H QE230H QE240H QE250H QE260Hn 1-Pole 120V AC Plug-in QE/ QEH MOLDED CASE CIRCUIT BREAKERS Ground Fault Equipment Protection (30mA) Wiring Diagrams n Built to order. Allow 2–3 weeks for delivery. a 7 Ground-Fault Circuit Interrupters (GFCI) L Listed as SWD (Switching Duty) Rated, suitable for U 120V AC Fluorescent Lighting. Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 7-19 • Revised • 03/06/13 Circuit Breakers Type QP with INSTA-WIRE Type Continuous Current Rating @ 40° C 1-Pole Plug-In (120V Selection QP 10,000A IR Catalog Number AC)e Q110 Q115c Q120c Q125 Q130 Q135n Q140 Q145n Q150 Q160 Q170 10 15 20 25 30 35 40 45 50 60 70 Q210 Q215 Q220 Q225 Q230 Q235 Q240 Q245 Q250 Q260 Q270 Q280 Q290 Q2100 Q2110 Q2125 MOLDED CASE CIRCUIT BREAKERS 7 2-Pole Plug-In (Common-Trip 240V 65,000A IR Catalog Number Catalog Number — Q115HHnc Q120HHnc Q125HHn Q130HHn Q135HHn Q140HHn Q145HHn Q150HHn Q160HHn Q170HHn — Q215H Q220H Q225Hn Q230H Q235Hn Q240H Q245Hn Q250H Q260H Q270H Q280Hn Q290H Q2100H Q2110H Q2125H AC) — Q215HH Q220HH Q225HHn Q230HH Q235HHn Q240HHn Q245HHn Q250HH Q260HH Q270HH Q280HHn Q290HHn Q2100HH Q2110HHn Q2125HH Q215R Q220R Q230R Q240R Q250R Q260R Q270R Q2100Rn 15 20 30 40 50 60 70 100 Type HQP 22,000A IR — Q115Hc Q120Hc Q125Hn Q130H Q135Hn Q140H Q145Hn Q150H Q160Hn Q170Hn AC) 2-Pole Plug-In (Common-Trip 120/240V 10 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 Type QPH — — — — — — — — — — — — — — — — Q315H Q320H Q325Hn Q330H Q335Hn Q340H Q345Hn Q350H Q360H Q370H Q380H Q390H Q3100H Q315HHn Q320HH Q325HHn Q330HH Q335HHn Q340HH Q345HHn Q350HH Q360HH Q370HHn Q380HHn Q390HHn Q3100HH 3-Pole Plug-In (Common-Trip 240V AC) Q315 Q320 Q325 Q330 Q335 Q340 Q345 Q350 Q360 Q370 Q380 Q390 Q3100 15 20 25 30 35 40 45 50 60 70 80 90 100 QP / QPH / HQP Internal Accessories Control Voltage AC 120V Shunt Trip 24V Shunt Trip 120V Auxiliary Switch Catalog Number add suffix …00S01n add suffix …00S07n add suffix …01nb n Built to order. Allow 2-3 weeks for delivery. UL Listed for use with 60/75° wire through 40 amps, UL listed for use with 75° wire only for 50 amps and above, HACR rated. b 1A and 1B contacts. a 7-20 Field/Factory Installed Factory Factory Factory Modifications Description 400 Hz Calibration Marine 50˚C Ambient Calibration Fungus Proofing Listed for frequent switching applications (SWD). 120V AC Fluorescent Lighting. Listed for use on 3-phase grounded “B” systems ­­— 10,000 for this application. e Shipped 12 per sleeve. Catalog Number add suffix …Yh add suffix …M add suffix …F c UL f Shipped d UL h UL Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog For external accessories, please refer to page 7-93 6 per sleeve. 4 per sleeve. Listed 5 KA IR. i Type QP1, UL listed for 16 AWG conductors and multiple wires. g Shipped Product Category RESI • Revised • 04/30/13 Circuit Breakers Duplex, Triplex and Quadplex Plug-In Breakers Selection Duplex Circuit Breakers Breaker Type QT 1-Pole 10K AIC 120V AC Ampere Rating Catalog Number 15–15 Q1515 15–20 Q1520 20–20 Q2020 20–30 Q2030 30–15n Q3015 30–20 Q3020 30–30 Q3030 SHIPPING: 12 per carton, (Wt. 4.8 lbs.) Catalog Number Q1515NCa Q1520NCa Q2020NCa — — — Q3030NCa Triplex Circuit Breakers Ampere Rating Breaker Type QT 2-Pole 10K AIC 120/240V AC Inner Poles Common Trip Common-Trip Single Pole 2-Pole 15 15 15 20 15 25 15 30 15 35 15 40 15 45 15 50 20 20 20 25 20 30 20 35 20 40 20 45 20 50 30 30 SHIPPING: 6 per carton, (Wt. 4.9 lbs.) QT Duplex These space saver duplex breakers combine two independent 1/2" breaker poles in a common unit. This unit plugs into one load center stab and requires one panel space. HACR rated. Catalog Number Q21515CT Q21520CT Q21525CTn Q21530CT Q21535CTn Q21540CT Q21545CTn Q21550CT Q22020CT Q22025CTn Q22030CT Q22035CTn Q22040CT Q22045CTn Q22050CT Q23030CT QT Triplex These space saver triplex breakers provide a 2-pole common trip breaker for 120/240V AC circuits and two single poles for 120V AC circuits. Triplex require two panel spaces. HACR rated. Quadplex Circuit Breakers Ampere Rating QT Catalog Number Q21515CT2 Q22020CT2 Q23020CT2 Q24020CT2 Q23030CT2 Q24030CT2 Q24040CT2 Q23050CT2 QT Quadplex These space saver quadplex breakers provide two sets of common trip, two-pole breakers for 120/240V AC circuits, and require two panel spaces. HACR rated. For external accessories, please refer to page 7-93 For inches / millimeters conversion, see Application Data section. Product Category RESI n Built to order. Allow 2–3 weeks for delivery. a on-CTL. For replacement use only in panels manufacN tured before 1968 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 7-21 MOLDED CASE CIRCUIT BREAKERS 2-Pole 10K AIC 120/240V AC Inner and Outter 2 Poles Common Trip Common-Trip Common-Trip 2-Pole Inside 2-Pole Outside 15 15 20 20 20 30 20 40 30 30 30 40 40 40 50 30 SHIPPING: 6 per carton, (Wt. 4.8 lbs.) 7 Breaker Type Circuit Breakers Special Application Breakers Selection HID Lighting For high-intensity discharge lamp loads having in-rush currents above the instantaneous trip setting of a standard breaker. Breaker Type QP 1-Pole 120V AC QP 2-Pole 120/240V AC Wiring Diagram Figure 1 Figure 2 Complete Breaker UL Unenclosed Ampere Rating Catalog Number 15 20 30 15 20 30 Q115HID a n Q120HID a Q130HID Q215HID Q220HID n Q230HID n Molded Case Switch Switching Neutral For applications that do not require overcurrent protection. QP 1-Pole 120V AC QP 2-Pole 120/240V AC Figure 1 100 Q1100S Figure 2 30 60 125 Q230S Q260S Q2125S No-Noise For applications that require a reduction in the 60-cycle hum of a standard breaker. QP 2-Pole 120/240V AC Figure 2 50 60 70 90 Q250NNn Q260NN Q270NN Q290NNn Water Heater Switching Neutrals MOLDED CASE CIRCUIT BREAKERS 7 Used where all conductors are required to be disconnected. Neutral pole of the circuit breaker does not connect to load center bus. One side is wired to neutral and the other side to the device. QG 2-Wire Common Trip 120V AC Figure 3 15 20 30 QG215 QG220 QG230n Figure 4 15 20 30 QG315n QG320 QG330n QG 3-Wire Common Trip 120/240V AC Figure 1 Figure 2 Figure 3 Figure 4 Tungsten Lighting For high wattage, tungsten-lamp loads having in-rush currents above the instantaneous trip setting of a standard breaker. QP 1-Pole 120V AC Figure 1 15 20 Figure 5 Q115T a n Q120T a Water Heater When installed in a loadcenter, the water heater circuit breaker does not make electrical connection with the loadcenter bussing. Separate metered circuit is connected to line terminals of the breaker. Used in special rate water heating areas. QW 2-Pole 120/40V AC Plug-In Figure 5 15 20 30 Wiring Diagrams QW215 QW220 QW230 n Built to order. Allow 2–3 weeks for delivery. a UL Listed as SWD (Switching Duty) Rated, suitable for 120V AC Fluorescent Lighting. Note: All circuit breakers on this page are 10K AIC 7-22 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog Product Category RESI Circuit Breakers 3/4 Inch Plug-In Breakers Selection Features b 3/4" format b HACR Rated b UL Classified for use in certain Square D load centers Type QD Circuit Breakers The Type QD circuit breaker line is available in 1-pole and 2-pole common trip versions listed on this page. The circuit breakers are UL Classified and UL Listed. All QD breakers are supplied with load side connectors suitable for 60/75°C wire and are calibrated for 40°C maximum ambient applications. Product Category RESI 2-Pole 120V 120/240V Common Trip Catalog Number Catalog Number D115 a D120 a D130 D140 D150 D160 D215 D220 D230 D240 D250 D260 Shipping Weights Number of Number Per Poles Carton Shipping Weight (lbs.) 1 2 3.8 4.2 16 8 Panelboard Compatibility List Listed Panelboards—Square D—Catalog Numbers QO2L30F/S QO2-4L70F/S QO2-4L70TS QO2-4L70RB QO6-12L100F/S QO6-12L100DF/S QO6-12L100TF/S QO6-12L100DTF/S QO6-12L100RB QO8-16L100F/S QO8-16L100DF/S QO8-16L100TF/S QO-16L100DTF/S QO8-16L100RB QO112M100/RB QO116M100/RB QO120M100/RB QO124M100 QO12L100DF/S QO12L100RB QO12-20M100/RB QO12-20M100TF/S a QO12M100/RB QO16-20M100/RB QO16M100/RB QO20M100/RB QO112L125G/RB QO112-24L125/RB QO112-24L125GWGC QO116L125G QO116-24L125G/RB QO12-24L125/RB QO120-24L125G QO120-24L125GWGC QO120L125G QO124L125G/RB QO124M125/RB QO16L125/RB QO16-12M125FTRB QO16-24L125/RB QO20L125/RB QO20-24L125/RB QO24L125/RB QO120-30L150G QO120-30M150/RB QO124L150G QO124M150 QO130L150G/RB QO130M150/RB QO16L150/RB QO16M150/RB QO16-30L150/RB QO18-16M150FTRB QO20-30M150/RB QO20-30M150TF/S QO20-30L150 QO24L150/RB QO24M150/RB QO30L150/RB QO30M150/RB QO8-16M200FT/RB QO112L200G/RB QO120-40M200/RB QO120-40M200TC QO124M200 QO130L200G/RB QO130-40M200 QO130200/RB QO130-40L200G/RB QO140M200/RB QO16L200/RB QO16M200/RB QO18-16M200FTRB QO20-40L200/RB QO20-40M200TF/S QO20-40M200/RB QO24L200/RB QO24M200/RB QO30L200/RB QO30M200/RB QO30-40L200/RB QO30-40M200/RB QO40M200/RB QO140M225 QO142L225G/RB L Listed for frequent switching applications (SWD). U 120V AC Fluorescent Lighting. One or two load conductors. Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 7-23 MOLDED CASE CIRCUIT BREAKERS For inches / millimeters conversion, see Application Data section. 15 20 30 40 50 60 1-Pole 7 UL Classified Siemens Type QD circuit breakers are UL Classified for use in specific Square D load centers in place of Square D Type QO® circuit breakers. A Panelboard Compatibility List packaged with each QD breaker shows which type QD circuit breakers are acceptable for use in Square D load centers. The interrupting rating on these circuit breakers is 10,000A IR maximum and they are not series rated with Square D circuit breakers or equipment. This UL Classification allows a Siemens Type QD circuit breaker to be used in place of a Square D Type QO circuit breaker in those load centers that are specifically shown on the Panelboard Compatibility list. For additional information, contact your local Siemens sales engineer. Continuous Current Rating @ 40°C • Revised • 11/05/13 Circuit Breakers Main and Branch Circuit Breakersa Breaker Type QN 2-Pole 120/240V AC Ampere Rating 150 175 200 Selection Catalog Number Catalog Number QN2150 QN2175n QN2200 QN2150R b QN2175R b n QN2200R b QNH 150 QN2150H QN2150RH b 175 QN2175RH bn QN2175H n 200 QN2200H QN2200RH b 150 HQN2150 HQN2150R b HQN — 175 HQN2175 n 2-Pole 120/240V AC 200 HQN2200 HQN2200R b Requires 4 panel spaces, 2 adjacent and 2 opposite. SHIPPING: 1 per carton 2-Pole 120/240V AC UL Interrupting Ratings (kA) 10 10 10 22 22 22 65 65 65 (Wt. 3 lbs.) QNRe QNe Main Breaker Kits For use in Ultimate Load Centersd For use in EQIII Load Centers UL Type EQ8681 EQ8682 EQ8693 — EQ8695 EQ8696 UL Type EQ9675 EQ9677 EQ9683 EQ9684 EQ9685 EQ9686 Ampere Rating 100 125 150 — 200 225 Catalog Number MBK100A MBK125A MBK150A — MBK200A MBK225A Ampere Rating 100 125 150 175 200 225 Catalog Number MBK100 MBK125 MBK150 MBK175n MBK200 MBK225 Breaker Type Ampere Rating Catalog Number UL Interrupting Ratings (kA) QPJ 125 150 200 QPJ3125 QPJ3150 QPJ3200 10 10 10 c 3-Pole 240V AC UL Interrupting Ratings (kA) 22 22 22 22 22 22 EQ96XX Requires 6 spaces due to cross over design. Fits only EQIII 125-400A 3-phase load centers MBK (100,125)A SHIPPING: 5 per carton (Wt. 17 lbs.) MOLDED CASE CIRCUIT BREAKERS 7 Breaker Type QPP 2-Pole 120/240V AC QPPH 2-Pole 120/240V AC HQPP 2-Pole 120/240V AC HQPPH 2-Pole 120/240V AC Ampere Rating 125 150 175 200 225 125 150 175 200 225 125 150 175 200 225 100 125 150 175 200 225 Catalog Number Q2125B Q2150B Q2175Bn Q2200B Q2225B Q2125BH Q2150BH Q2175BHn Q2200BH Q2225BHn Q2125BHHn Q2150BHH Q2175BHHn Q2200BHH Q2225BHHn HQ2100BHn HQ2125BHn HQ2150BHn HQ2175BHn HQ2200BHn HQ2225BHn For inches / millimeters conversion, see Application Data section. n Built to order. Allow 2–3 weeks for delivery. UL Interrupting Breaker Ratings (kA) Volts AC 120/240 10 10 10 10 10 22 22 22 22 22 65 65 65 65 65 100 100 100 100 100 100 a All circuit breakers on this page are common trip. b Reverse handle. c CSA Listed. d MBK100A for use in 100 and 125A load centers. MBK125A for use in 125A load centers. MBK150A for use in 150, 200 and 225A load centers. MBK200A for use in 200 and 225A load centers. MBK225A for use in 225A load centers. MBK175A for use in 200 and 225A load centers. 7-24 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog MBK (150,200,225)A 2-Pole QPP QPJ e NR required for horizontal applications or vertical Q applications where the lugs are facing up. The QN breaker is required for vertical applications where the lugs are facing down as shown. Product Category RESI Circuit Breakers Main and Branch Circuit Breakers QS Breaker PowerMod's core offering of residential Meter Stacks, type WMM, offers the widest product offering & flexibility in the industry. Each meter stack houses the QuickSystem features to maximize productivity and minimize labor costs. To further simplify installation, our 225 Amp meter stacks feature the QS breaker. The QS breaker adds to the Siemens exclusive feature set in our Power Mod product line. Benefits and part numbers include: Front View ▪ An exclusive side wired design saves wiring space and eliminates difficult "S bends" ▪ No need for costly filler plates — QS 225 Amp breaker takes the same space as standard 100 Amp QPs ▪ Single right hand bend wiring - saves time and wire ▪ Provides 100K AIC flexibility from 100 up to 225 Amps ▪ 10K to 100K AIC Series Rating QS Breaker Breaker Type QS QSH QSHH HQS HQSH Amperage 10K AIC 22K AIC 42K AIC 65K AIC 100K AIC 100 QS2100 QS2100H QSH2100 QS2100HH HQS2100H 125 QS2125 QS2125H QSH2125 QS2125HH HQS2125H 150 QS2150 QS2150H QSH2150 QS2150HH HQS2150H 175 QS2175 QS2175H QSH2175 QS2175HH HQS2175H 200 QS2200 QS2200H QSH2200 QS2200HH HQS2200H 225 QS2225 QS2225H QSH2225 QS2225HH HQS2225H QS Breaker Dimension Drawing .19 1.00 .58 .96 7 PRECAUCION MOLDED CASE CIRCUIT BREAKERS CAUTION 1.38 7.89 4.31 000A 000000 ON 2.22 20 NEUTRAL OFF .99 20 .19 .28 1.39 2.01 2.38 2.56 2.66 .16 1.34 .37 1.06 1.16 2.12 For PowerMod information, please refer to Section 2, page 2-49 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 7-25 • Revised • 06/13/14 Circuit Breakers Line Diagrams 1-Pole Dimension Drawings 2-Pole 3-Pole 3" 23/8" 31/8" Type QT Type QPF, QPHF, QE, QAF2, QAF2H Type EQ8681, EQ8682 Type EQ8693, EQ8695, EQ8696 Type QPJ Type QN, QNH, HQN Type QNR, QNRH, HQNR Type QPP, QPPH, HQPP, HQPPH MOLDED CASE CIRCUIT BREAKERS 7 QP, QPH, HQP a ll standard circuit breakers are calibrated to 40°C maxiA mum ambient application. 7-26 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog • Revised • 06/13/14 Circuit Breakers Lug Data Circuit Breaker Type Reference Circuit Breaker Ampere Rating Cables Per Connector Connector Wire Range 2 #14-#16 AWG Cu 1 1 1 1 1 1 1 1 #14–#6 AWG Cu #14–#6 AWG Al #8–#6 AWG Cu #8–#4 AWG Al #8-#2/0 AWG Cu #8-#2/0 AWG Al #14–#6 AWG Cu #14–#6 AWG Al 1 #8 AWG CU-Al 1 1 1 1 1 1 #8–#6 AWG Cu #8–#4 AWG Al #14–#10 AWG Cu #12–#8 AWG Al #8–#6 AWG Cu #8–#4 AWG Al 15–20 1 1 #14–#12 AWG Cu #12–#10 AWG Al 15–20 2 #14–#8 AWG Cu Only 1 1 1 1 1 1 #14–#12 AWG Cu #12–#10 AWG Al #10–#8 AWG Cu #10–#6 AWG Al #8–#6 AWG Cu #8–#4 AWG Al 150–200 1 #1–300kcmil Cu-Al 100–225 1 #3–300kcmil Cu-Al 100 1 #4–3/0 AWG Cu-Al 125 1 #4–3/0 AWG Cu-Al 150 1 #1–300kcmil Cu-Al 200 1 #1–300kcmil Cu-Al 225 1 #1–300kcmil Cu-Al 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 #1 AWG Cu #2/0 AWG Al #1/0 AWG Cu #3/0 AWG Al #2/0 AWG Cu #4/0 AWG Al #3/0 AWG Cu 250kcmil AWG Al #4/0 AWG Cu 300kcmil AWG Al #8-#2/0 AWG Cu #8-#2/0 AWG Al #8-#2/0 AWG Cu #8-#2/0 AWG Al #1/0 AWG Cu #3/0 AWG Al #3/0 AWG Cu 250kcmil AWG AL #3/0 AWG Cu 250kcmil AWG Al #4/0 AWG Cu 300kcmil AWG Al 1 #2–300kcmil Cu-Al LOAD SIDE QP, QPH, HQP, Plug-in 10 15–35 40–50 55-125 QT 15–35 40 40–50 QPF, QPHF 15–30 40–60 QAF2, QAFH2, QFGA2, QFGAH2 QD 15–20 25–35 40–60 150 175 200 225 EQ9675-EQIII EQ9677-EQIII EQ9683-EQIII EQ9684 EQ9685-EQIII EQ9686-EQIII QPJ 100 125 150 175 200 225 125–200 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog MOLDED CASE CIRCUIT BREAKERS 125 7 QN, QNH, HQN QS, QSH, QSHH, HQS, HQSH EQ8681-Ultimate EQ8682-Ultimate EQ8693-Ultimate EQ8695-Ultimate EQ8696-Ultimate QPP, QPPH, HQPP, HQPPH 7-27 Surge Protection Circuit Breaker and Surge Protective Device (SPD) Features Circuit Breaker and Surge Protective Device (SPD) ▪ 2 inch wide plug-on design — Includes (2) 1 Pole circuits breakers ­— No loss of load center spaces ▪ Easy to install and perfect for retrofit ▪ LEDs provide protection status Benefits By installing a Siemens Circuit Breaker and Surge Protective Device (SPD) in the load center of the residence, surge protection is provided for all branch circuits. Two green LED indicator lights are provided to show that surge protection is provided for all circuits connected to the load center. These breakers should be used for circuit protection of frequently used household or facility circuits because the lights and devices connected to these circuits provide an effective indication that surge protection is being provided. The circuit breaker and SPD utilize Siemens-built 150V AC, 40mm, metal oxide varistors (MOVs). The maximum impulse rating for the SPD module is 40kA. The standard interrupting rating for the circuit breakers is 10k AIC. All Type QP circuit breakers and SPD are plug-on style, with load terminals provided. The devices are rated for 120/240V AC and are calibrated for 40 degrees C maximum ambient applications. Breaker Type QP 1- Pole 120/240V AC 10K AIC Ampere Rating Catalog Number Surge Type (2) 15 QSA1515SPD SPD (2) 20 QSA2020SPD SPD MOLDED CASE CIRCUIT BREAKERS 7 Catalog Number Amperage Number of Poles Initial Clamping Level Transient Energy Rating Transient Suppression Voltage Rating Peak Current Rating (impulse) Discharge Voltage Characteristic Discharge Current Withstand Rating Circuit Breaker Interrupting Rating Listings/Certifications QSA1515SPD QSA2020SPD 15 or 20 Amp (2) 1-Pole Circuit Breakers 240 Volts 360 Joules line-to-neutral 720 Joules line-to-line 500 volts peak, line-to-neutral 1000 volts peak, line-to-line 40,000 amperes @ 1,500A, 600 volts @ 5,000A, 800 volts (both line-to-neutral) 10,000 amperes line-to-neutral 10,000A, 120/240V AC UL, CSA Meets UL 1449 3rd Edition For warranty information please refer to the surge website www.usa.siemens.com/surge 7-28 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog Product Category RESI