Circuit Breakers

advertisement
• Revised •
06/13/14
Circuit Breakers
Arc-Fault and Ground-Fault Breakers
Selection/Wiring Diagrams
Arc-Fault Circuit Interrupters (AFCI)
AFCI’s detect arcing faults (an unintentional arcing condition in a circuit) that
standard circuit breakers are unable to detect. The device is intended to mitigate
the effects of arcing faults by functioning to de-energize the circuit when an arcfault is detected.
Combination Type AFCI
Detects all three possible types of arc fault: line-to-ground, line-to-neutral, and series.
Breaker
Type
Ampere
Rating
22,000 A IR
65,000 A IR
10,000 A IR
Catalog Number Catalog Number Catalog Number
QAF2/QAFH2/HQAF2
15
20
QA115AFCa
QA120AFCa
QA115AFCHna
QA120AFCHna
QA115AFCHH
QA120AFCHH
QAF2/QAF2H
15
20
Q215AFCa
Q220AFCa
Q215AFCHna
Q220AFCHna
—
—
QA115AFHna
QA120AFHna
QA115AFHH
QA120AFHH
1-Pole 120V AC
2-Pole 120/240V AC
1-Pole Combination
Type AFCI
2-Pole Combination
Type AFCI
1-Pole Branch
Feeder AFCI
1-Pole Dual
Function AFCI/GFC
1-Pole GFCI
2-Pole GFCI
1-Pole Equipment
Protection
2-Pole Equipment
Protection
Branch-Feeder AFCI
Detects line-to-ground and line-to neutral arcs.
QAF2/QAFH2/HQAF2
1-Pole 120V AC
NEW
15
20
QA115AFa
QA120AFa
Dual Function AFCI/GFCI
The Dual Function Circuit Breaker combines Combination Type AFCI and GFCI, protecting against both Arc Faults and Ground Faults. The device includes the Self Test and
Lockout feature, making it the fist in class in electrical safety for homeowners.
QFGA2/QFGAH2/
HQFGA2
1-Pole 120V AC
15
20
QA115DF
QA120DF
Q115DFH
Q120DFH
Q115DFHH
Q120DFHH
Provides Class A (5mA) ground fault
protection. Intended for personnel
protection. De-energizes the circuit for all
ungrounded conductors of the circuit.
Provides protection of equipment from
damaging line-to-ground faults currents.
De-energizes the circuit for all ungrounded
conductors of the circuit.
Breaker
Type
QPF/
QPHF
1-Pole
120V AC
Plug-in
Amp
10,000 A IR 22,000 A IR
Rating Catalog No. Catalog No.
15
20
25
30
15
20
30
2-Pole 120/ 40
240V AC
50
Plug-in
60
QPF/
QPHF
QF115a
QF120a
QF125n
QF130
QF115Ha
QF120Hna
—
QF130H
QF215
QF220
QF230
QF240
QF250
QF260
QF215H
QF220H
QF230H
QF240H
QF250H
QF260H
QAF2/QPF/QE Accessories
Description
Catalog Number
Padlocking Device 1-Pole
ECPLD1
Padlocking Device 2-Pole
ECPLD2
Handle Block
ECBX231M
Breaker
Type
QE/
QEH
Amp
10,000 A IR 22,000 A IR
Rating Catalog No. Catalog No.
15
20
30
QE115a
QE120a
QE130
QE115Ha
QE120Ha
QE130H
15
20
30
2-Pole 120/ 40
240V AC
50
Plug-in
60
QE215
QE220
QE230
QE240
QE250
QE260n
QE215H
QE220H
QE230H
QE240H
QE250H
QE260Hn
1-Pole
120V AC
Plug-in
QE/
QEH
MOLDED CASE
CIRCUIT BREAKERS
Ground Fault Equipment
Protection (30mA)
Wiring Diagrams
n Built to order. Allow 2–3 weeks for delivery.
a
7
Ground-Fault Circuit
Interrupters (GFCI)
L Listed as SWD (Switching Duty) Rated, suitable for
U
120V AC Fluorescent Lighting.
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
7-19
• Revised •
03/06/13
Circuit Breakers
Type QP with INSTA-WIRE
Type
Continuous Current
Rating @ 40° C
1-Pole Plug-In (120V
Selection
QP
10,000A IR
Catalog Number
AC)e
Q110
Q115c
Q120c
Q125
Q130
Q135n
Q140
Q145n
Q150
Q160
Q170
10
15
20
25
30
35
40
45
50
60
70
Q210
Q215
Q220
Q225
Q230
Q235
Q240
Q245
Q250
Q260
Q270
Q280
Q290
Q2100
Q2110
Q2125
MOLDED CASE
CIRCUIT BREAKERS
7
2-Pole Plug-In (Common-Trip 240V
65,000A IR
Catalog Number
Catalog Number
—
Q115HHnc
Q120HHnc
Q125HHn
Q130HHn
Q135HHn
Q140HHn
Q145HHn
Q150HHn
Q160HHn
Q170HHn
—
Q215H
Q220H
Q225Hn
Q230H
Q235Hn
Q240H
Q245Hn
Q250H
Q260H
Q270H
Q280Hn
Q290H
Q2100H
Q2110H
Q2125H
AC)
—
Q215HH
Q220HH
Q225HHn
Q230HH
Q235HHn
Q240HHn
Q245HHn
Q250HH
Q260HH
Q270HH
Q280HHn
Q290HHn
Q2100HH
Q2110HHn
Q2125HH
Q215R
Q220R
Q230R
Q240R
Q250R
Q260R
Q270R
Q2100Rn
15
20
30
40
50
60
70
100
Type HQP
22,000A IR
—
Q115Hc
Q120Hc
Q125Hn
Q130H
Q135Hn
Q140H
Q145Hn
Q150H
Q160Hn
Q170Hn
AC)
2-Pole Plug-In (Common-Trip 120/240V
10
15
20
25
30
35
40
45
50
60
70
80
90
100
110
125
Type QPH
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Q315H
Q320H
Q325Hn
Q330H
Q335Hn
Q340H
Q345Hn
Q350H
Q360H
Q370H
Q380H
Q390H
Q3100H
Q315HHn
Q320HH
Q325HHn
Q330HH
Q335HHn
Q340HH
Q345HHn
Q350HH
Q360HH
Q370HHn
Q380HHn
Q390HHn
Q3100HH
3-Pole Plug-In (Common-Trip 240V AC)
Q315
Q320
Q325
Q330
Q335
Q340
Q345
Q350
Q360
Q370
Q380
Q390
Q3100
15
20
25
30
35
40
45
50
60
70
80
90
100
QP / QPH / HQP Internal Accessories
Control Voltage AC
120V Shunt Trip
24V Shunt Trip
120V Auxiliary Switch
Catalog Number
add suffix …00S01n
add suffix …00S07n
add suffix …01nb
n Built to order. Allow 2-3 weeks for delivery.
UL Listed for use with 60/75° wire through 40 amps,
UL listed for use with 75° wire only for 50 amps
and above, HACR rated.
b 1A and 1B contacts.
a
7-20
Field/Factory Installed
Factory
Factory
Factory
Modifications
Description
400 Hz Calibration
Marine 50˚C Ambient
Calibration
Fungus Proofing
Listed for frequent switching applications (SWD).
120V AC Fluorescent Lighting.
Listed for use on 3-phase grounded “B” systems ­­—
10,000 for this application.
e Shipped 12 per sleeve.
Catalog Number
add suffix …Yh
add suffix …M
add suffix …F
c UL
f Shipped
d UL
h UL
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
For external
accessories, please
refer to page 7-93
6 per sleeve.
4 per sleeve.
Listed 5 KA IR.
i Type
QP1, UL listed for 16 AWG conductors and
multiple wires.
g Shipped
Product Category RESI
• Revised •
04/30/13
Circuit Breakers
Duplex, Triplex and Quadplex Plug-In Breakers
Selection
Duplex Circuit Breakers
Breaker Type
QT
1-Pole
10K AIC
120V AC
Ampere
Rating
Catalog Number
15–15
Q1515
15–20
Q1520
20–20
Q2020
20–30
Q2030
30–15n
Q3015
30–20
Q3020
30–30
Q3030
SHIPPING: 12 per carton, (Wt. 4.8 lbs.)
Catalog Number
Q1515NCa
Q1520NCa
Q2020NCa
—
—
—
Q3030NCa
Triplex Circuit Breakers
Ampere Rating
Breaker
Type
QT
2-Pole
10K AIC
120/240V AC
Inner Poles
Common Trip
Common-Trip
Single Pole
2-Pole
15
15
15
20
15
25
15
30
15
35
15
40
15
45
15
50
20
20
20
25
20
30
20
35
20
40
20
45
20
50
30
30
SHIPPING: 6 per carton, (Wt. 4.9 lbs.)
QT Duplex
These space saver duplex breakers combine two
independent 1/2" breaker poles in a common unit.
This unit plugs into one load center stab and
requires one panel space. HACR rated.
Catalog
Number
Q21515CT
Q21520CT
Q21525CTn
Q21530CT
Q21535CTn
Q21540CT
Q21545CTn
Q21550CT
Q22020CT
Q22025CTn
Q22030CT
Q22035CTn
Q22040CT
Q22045CTn
Q22050CT
Q23030CT
QT Triplex
These space saver triplex breakers provide
a 2-pole common trip breaker for 120/240V AC
circuits and two single poles for 120V AC circuits.
Triplex require two panel spaces. HACR rated.
Quadplex Circuit Breakers
Ampere Rating
QT
Catalog
Number
Q21515CT2
Q22020CT2
Q23020CT2
Q24020CT2
Q23030CT2
Q24030CT2
Q24040CT2
Q23050CT2
QT Quadplex
These space saver quadplex breakers provide
two sets of common trip, two-pole breakers for
120/240V AC circuits, and require two panel
spaces. HACR rated.
For external accessories,
please refer to page 7-93
For inches / millimeters conversion, see Application Data
section.
Product Category RESI
n Built to order. Allow 2–3 weeks for delivery.
a
on-CTL. For replacement use only in panels manufacN
tured before 1968
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
7-21
MOLDED CASE
CIRCUIT BREAKERS
2-Pole
10K AIC
120/240V AC
Inner and
Outter 2 Poles
Common Trip
Common-Trip
Common-Trip
2-Pole Inside
2-Pole Outside
15
15
20
20
20
30
20
40
30
30
30
40
40
40
50
30
SHIPPING: 6 per carton, (Wt. 4.8 lbs.)
7
Breaker
Type
Circuit Breakers
Special Application Breakers
Selection
HID Lighting
For high-intensity discharge lamp loads having in-rush currents
above the instantaneous trip setting of a standard breaker.
Breaker
Type
QP
1-Pole
120V AC
QP
2-Pole
120/240V AC
Wiring
Diagram
Figure 1
Figure 2
Complete Breaker UL Unenclosed
Ampere Rating Catalog Number
15
20
30
15
20
30
Q115HID a n
Q120HID a
Q130HID
Q215HID
Q220HID n
Q230HID n
Molded Case Switch
Switching Neutral
For applications that do not require overcurrent protection.
QP
1-Pole
120V AC
QP
2-Pole
120/240V AC
Figure 1
100
Q1100S
Figure 2
30
60
125
Q230S
Q260S
Q2125S
No-Noise
For applications that require a reduction in the 60-cycle hum of
a standard breaker.
QP
2-Pole
120/240V AC
Figure 2
50
60
70
90
Q250NNn
Q260NN
Q270NN
Q290NNn
Water Heater
Switching Neutrals
MOLDED CASE
CIRCUIT BREAKERS
7
Used where all conductors are required to be disconnected.
Neutral pole of the circuit breaker does not connect to load
center bus. One side is wired to neutral and the other side to
the device.
QG
2-Wire
Common Trip
120V AC
Figure 3
15
20
30
QG215
QG220
QG230n
Figure 4
15
20
30
QG315n
QG320
QG330n
QG
3-Wire
Common Trip
120/240V AC
Figure 1
Figure 2
Figure 3
Figure 4
Tungsten Lighting
For high wattage, tungsten-lamp loads having in-rush currents
above the instantaneous trip setting of a standard breaker.
QP
1-Pole
120V AC
Figure 1
15
20
Figure 5
Q115T a n
Q120T a
Water Heater
When installed in a loadcenter, the water heater circuit breaker
does not make electrical connection with the loadcenter bussing. Separate metered circuit is connected to line terminals of
the breaker. Used in special rate water heating areas.
QW
2-Pole
120/40V AC
Plug-In
Figure 5
15
20
30
Wiring Diagrams
QW215
QW220
QW230
n Built to order. Allow 2–3 weeks for delivery.
a UL
Listed as SWD (Switching Duty) Rated, suitable for 120V AC Fluorescent Lighting.
Note: All circuit breakers on this page are 10K AIC
7-22
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
Product Category RESI
Circuit Breakers
3/4 Inch Plug-In Breakers
Selection
Features
b 3/4" format
b HACR Rated
b UL Classified for use in certain Square D
load centers
Type QD Circuit Breakers
The Type QD circuit breaker line is
available in 1-pole and 2-pole common
trip versions listed on this page.
The circuit breakers are UL Classified
and UL Listed.
All QD breakers are supplied with load
side connectors suitable for 60/75°C
wire and are calibrated for 40°C
maximum ambient applications.
Product Category RESI
2-Pole
120V
120/240V Common Trip
Catalog Number
Catalog Number
D115 a
D120 a
D130
D140
D150
D160
D215
D220
D230
D240
D250
D260
Shipping Weights
Number of
Number Per
Poles
Carton
Shipping
Weight (lbs.)
1
2
3.8
4.2
16
8
Panelboard Compatibility List
Listed Panelboards—Square D—Catalog Numbers
QO2L30F/S
QO2-4L70F/S
QO2-4L70TS
QO2-4L70RB
QO6-12L100F/S
QO6-12L100DF/S
QO6-12L100TF/S
QO6-12L100DTF/S
QO6-12L100RB
QO8-16L100F/S
QO8-16L100DF/S
QO8-16L100TF/S
QO-16L100DTF/S
QO8-16L100RB
QO112M100/RB
QO116M100/RB
QO120M100/RB
QO124M100
QO12L100DF/S
QO12L100RB
QO12-20M100/RB
QO12-20M100TF/S
a
QO12M100/RB
QO16-20M100/RB
QO16M100/RB
QO20M100/RB
QO112L125G/RB
QO112-24L125/RB
QO112-24L125GWGC
QO116L125G
QO116-24L125G/RB
QO12-24L125/RB
QO120-24L125G
QO120-24L125GWGC
QO120L125G
QO124L125G/RB
QO124M125/RB
QO16L125/RB
QO16-12M125FTRB
QO16-24L125/RB
QO20L125/RB
QO20-24L125/RB
QO24L125/RB
QO120-30L150G
QO120-30M150/RB
QO124L150G
QO124M150
QO130L150G/RB
QO130M150/RB
QO16L150/RB
QO16M150/RB
QO16-30L150/RB
QO18-16M150FTRB
QO20-30M150/RB
QO20-30M150TF/S
QO20-30L150
QO24L150/RB
QO24M150/RB
QO30L150/RB
QO30M150/RB
QO8-16M200FT/RB
QO112L200G/RB
QO120-40M200/RB
QO120-40M200TC
QO124M200
QO130L200G/RB
QO130-40M200
QO130200/RB
QO130-40L200G/RB
QO140M200/RB
QO16L200/RB
QO16M200/RB
QO18-16M200FTRB
QO20-40L200/RB
QO20-40M200TF/S
QO20-40M200/RB
QO24L200/RB
QO24M200/RB
QO30L200/RB
QO30M200/RB
QO30-40L200/RB
QO30-40M200/RB
QO40M200/RB
QO140M225
QO142L225G/RB
L Listed for frequent switching applications (SWD).
U
120V AC Fluorescent Lighting. One or two load
conductors.
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
7-23
MOLDED CASE
CIRCUIT BREAKERS
For inches / millimeters conversion, see Application Data
section.
15
20
30
40
50
60
1-Pole
7
UL Classified
Siemens Type QD circuit breakers are
UL Classified for use in specific Square
D load centers in place of Square D Type
QO® circuit breakers. A Panelboard
Compatibility List packaged with each
QD breaker shows which type QD
circuit breakers are acceptable for
use in Square D load centers.
The interrupting rating on these circuit
breakers is 10,000A IR maximum and
they are not series rated with Square D
circuit breakers or equipment. This UL
Classification allows a Siemens Type QD
circuit breaker to be used in place of a
Square D Type QO circuit breaker in
those load centers that are specifically
shown on the Panelboard Compatibility
list. For additional information, contact
your local Siemens sales engineer.
Continuous
Current Rating
@ 40°C
• Revised •
11/05/13
Circuit Breakers
Main and Branch Circuit Breakersa
Breaker
Type
QN
2-Pole
120/240V AC
Ampere
Rating
150
175
200
Selection
Catalog
Number
Catalog
Number
QN2150
QN2175n
QN2200
QN2150R b
QN2175R b n
QN2200R b
QNH
150
QN2150H
QN2150RH b
175
QN2175RH bn
QN2175H n
200
QN2200H
QN2200RH b
150
HQN2150
HQN2150R b
HQN
—
175
HQN2175 n
2-Pole
120/240V AC
200
HQN2200
HQN2200R b
Requires 4 panel spaces, 2 adjacent and 2 opposite. SHIPPING: 1 per carton
2-Pole
120/240V AC
UL Interrupting
Ratings (kA)
10
10
10
22
22
22
65
65
65
(Wt. 3 lbs.)
QNRe
QNe
Main Breaker Kits
For use in Ultimate Load Centersd
For use in EQIII Load Centers
UL
Type
EQ8681
EQ8682
EQ8693
—
EQ8695
EQ8696
UL
Type
EQ9675
EQ9677
EQ9683
EQ9684
EQ9685
EQ9686
Ampere
Rating
100
125
150
—
200
225
Catalog
Number
MBK100A
MBK125A
MBK150A
—
MBK200A
MBK225A
Ampere
Rating
100
125
150
175
200
225
Catalog
Number
MBK100
MBK125
MBK150
MBK175n
MBK200
MBK225
Breaker
Type
Ampere
Rating
Catalog
Number
UL Interrupting
Ratings (kA)
QPJ
125
150
200
QPJ3125
QPJ3150
QPJ3200
10
10
10
c
3-Pole
240V AC
UL Interrupting
Ratings (kA)
22
22
22
22
22
22
EQ96XX
Requires 6 spaces due to cross over design. Fits only EQIII 125-400A 3-phase
load centers
MBK
(100,125)A
SHIPPING: 5 per carton (Wt. 17 lbs.)
MOLDED CASE
CIRCUIT BREAKERS
7
Breaker
Type
QPP
2-Pole
120/240V AC
QPPH
2-Pole
120/240V AC
HQPP
2-Pole
120/240V AC
HQPPH
2-Pole
120/240V AC
Ampere
Rating
125
150
175
200
225
125
150
175
200
225
125
150
175
200
225
100
125
150
175
200
225
Catalog
Number
Q2125B
Q2150B
Q2175Bn
Q2200B
Q2225B
Q2125BH
Q2150BH
Q2175BHn
Q2200BH
Q2225BHn
Q2125BHHn
Q2150BHH
Q2175BHHn
Q2200BHH
Q2225BHHn
HQ2100BHn
HQ2125BHn
HQ2150BHn
HQ2175BHn
HQ2200BHn
HQ2225BHn
For inches / millimeters conversion, see Application Data section.
n Built to order. Allow 2–3 weeks for delivery.
UL Interrupting
Breaker Ratings (kA)
Volts AC 120/240
10
10
10
10
10
22
22
22
22
22
65
65
65
65
65
100
100
100
100
100
100
a All circuit breakers on this page are common trip.
b Reverse handle.
c CSA Listed.
d MBK100A
for use in 100 and 125A load centers.
MBK125A for use in 125A load centers.
MBK150A for use in 150, 200 and 225A load centers.
MBK200A for use in 200 and 225A load centers.
MBK225A for use in 225A load centers.
MBK175A for use in 200 and 225A load centers.
7-24
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
MBK
(150,200,225)A
2-Pole QPP
QPJ
e
NR required for horizontal applications or vertical
Q
applications where the lugs are facing up. The QN
breaker is required for vertical applications where the
lugs are facing down as shown.
Product Category RESI
Circuit Breakers
Main and Branch Circuit Breakers
QS Breaker
PowerMod's core offering of residential Meter Stacks, type WMM, offers the
widest product offering & flexibility in the industry. Each meter stack houses the
QuickSystem features to maximize productivity and minimize labor costs. To
further simplify installation, our 225 Amp meter stacks feature the QS breaker.
The QS breaker adds to the Siemens exclusive feature set in our Power Mod
product line. Benefits and part numbers include:
Front View
▪ An exclusive side wired design saves wiring space and eliminates
difficult "S bends"
▪ No need for costly filler plates — QS 225 Amp breaker takes the
same space as standard 100 Amp QPs
▪ Single right hand bend wiring - saves time and wire
▪ Provides 100K AIC flexibility from 100 up to 225 Amps
▪ 10K to 100K AIC Series Rating
QS Breaker
Breaker Type
QS
QSH
QSHH
HQS
HQSH
Amperage
10K AIC
22K AIC
42K AIC
65K AIC
100K AIC
100
QS2100
QS2100H
QSH2100
QS2100HH
HQS2100H
125
QS2125
QS2125H
QSH2125
QS2125HH
HQS2125H
150
QS2150
QS2150H
QSH2150
QS2150HH
HQS2150H
175
QS2175
QS2175H
QSH2175
QS2175HH
HQS2175H
200
QS2200
QS2200H
QSH2200
QS2200HH
HQS2200H
225
QS2225
QS2225H
QSH2225
QS2225HH
HQS2225H
QS Breaker Dimension Drawing
.19
1.00
.58
.96
7
PRECAUCION
MOLDED CASE
CIRCUIT BREAKERS
CAUTION
1.38
7.89
4.31
000A
000000
ON
2.22
20
NEUTRAL
OFF
.99
20
.19
.28
1.39
2.01
2.38
2.56
2.66

.16
1.34
.37
1.06
1.16
2.12
For PowerMod information, please refer to
Section 2, page 2-49
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
7-25
• Revised •
06/13/14
Circuit Breakers
Line Diagrams
1-Pole
Dimension Drawings
2-Pole
3-Pole
3"
23/8"
31/8"
Type QT
Type QPF, QPHF, QE, QAF2, QAF2H
Type EQ8681, EQ8682
Type EQ8693, EQ8695, EQ8696
Type QPJ
Type QN, QNH, HQN
Type QNR, QNRH, HQNR
Type QPP, QPPH, HQPP, HQPPH
MOLDED CASE
CIRCUIT BREAKERS
7
QP, QPH, HQP
a
ll standard circuit breakers are calibrated to 40°C maxiA
mum ambient application.
7-26
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
• Revised •
06/13/14
Circuit Breakers
Lug Data
Circuit Breaker Type
Reference
Circuit Breaker
Ampere Rating
Cables
Per Connector
Connector
Wire Range
2
#14-#16 AWG Cu
1
1
1
1
1
1
1
1
#14–#6 AWG Cu
#14–#6 AWG Al
#8–#6 AWG Cu
#8–#4 AWG Al
#8-#2/0 AWG Cu
#8-#2/0 AWG Al
#14–#6 AWG Cu
#14–#6 AWG Al
1
#8 AWG CU-Al
1
1
1
1
1
1
#8–#6 AWG Cu
#8–#4 AWG Al
#14–#10 AWG Cu
#12–#8 AWG Al
#8–#6 AWG Cu
#8–#4 AWG Al
15–20
1
1
#14–#12 AWG Cu
#12–#10 AWG Al
15–20
2
#14–#8 AWG Cu Only
1
1
1
1
1
1
#14–#12 AWG Cu
#12–#10 AWG Al
#10–#8 AWG Cu
#10–#6 AWG Al
#8–#6 AWG Cu
#8–#4 AWG Al
150–200
1
#1–300kcmil Cu-Al
100–225
1
#3–300kcmil Cu-Al
100
1
#4–3/0 AWG Cu-Al
125
1
#4–3/0 AWG Cu-Al
150
1
#1–300kcmil Cu-Al
200
1
#1–300kcmil Cu-Al
225
1
#1–300kcmil Cu-Al
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
#1 AWG Cu
#2/0 AWG Al
#1/0 AWG Cu
#3/0 AWG Al
#2/0 AWG Cu
#4/0 AWG Al
#3/0 AWG Cu
250kcmil AWG Al
#4/0 AWG Cu
300kcmil AWG Al
#8-#2/0 AWG Cu
#8-#2/0 AWG Al
#8-#2/0 AWG Cu
#8-#2/0 AWG Al
#1/0 AWG Cu
#3/0 AWG Al
#3/0 AWG Cu
250kcmil AWG AL
#3/0 AWG Cu
250kcmil AWG Al
#4/0 AWG Cu
300kcmil AWG Al
1
#2–300kcmil Cu-Al
LOAD SIDE
QP, QPH, HQP, Plug-in
10
15–35
40–50
55-125
QT
15–35
40
40–50
QPF, QPHF
15–30
40–60
QAF2, QAFH2, QFGA2,
QFGAH2
QD
15–20
25–35
40–60
150
175
200
225
EQ9675-EQIII
EQ9677-EQIII
EQ9683-EQIII
EQ9684
EQ9685-EQIII
EQ9686-EQIII
QPJ
100
125
150
175
200
225
125–200
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
MOLDED CASE
CIRCUIT BREAKERS
125
7
QN, QNH, HQN
QS, QSH, QSHH, HQS, HQSH
EQ8681-Ultimate
EQ8682-Ultimate
EQ8693-Ultimate
EQ8695-Ultimate
EQ8696-Ultimate
QPP, QPPH, HQPP, HQPPH
7-27
Surge Protection
Circuit Breaker and Surge Protective Device (SPD)
Features
Circuit Breaker and
Surge Protective Device (SPD)
▪ 2 inch wide plug-on design
— Includes (2) 1 Pole circuits breakers
­— No loss of load center spaces
▪ Easy to install and perfect for retrofit
▪ LEDs provide protection status
Benefits
By installing a Siemens Circuit Breaker and Surge Protective Device (SPD) in the
load center of the residence, surge protection is provided for all branch circuits.
Two green LED indicator lights are provided to show that surge protection is provided for all circuits connected to the load center. These breakers should be used
for circuit protection of frequently used household or facility circuits because the
lights and devices connected to these circuits provide an effective indication that
surge protection is being provided.
The circuit breaker and SPD utilize Siemens-built 150V AC, 40mm, metal oxide
varistors (MOVs). The maximum impulse rating for the SPD module is 40kA. The
standard interrupting rating for the circuit breakers is 10k AIC. All Type QP circuit
breakers and SPD are plug-on style, with load terminals provided. The devices
are rated for 120/240V AC and are calibrated for 40 degrees C maximum ambient
applications.
Breaker Type
QP
1- Pole
120/240V AC
10K AIC
Ampere Rating
Catalog Number
Surge Type
(2) 15
QSA1515SPD
SPD
(2) 20
QSA2020SPD
SPD
MOLDED CASE
CIRCUIT BREAKERS
7
Catalog Number
Amperage
Number of Poles
Initial Clamping Level
Transient Energy Rating
Transient Suppression
Voltage Rating
Peak Current Rating (impulse)
Discharge Voltage Characteristic
Discharge Current Withstand Rating
Circuit Breaker Interrupting Rating
Listings/Certifications

QSA1515SPD
QSA2020SPD
15 or 20 Amp
(2) 1-Pole Circuit Breakers
240 Volts
360 Joules line-to-neutral
720 Joules line-to-line
500 volts peak, line-to-neutral
1000 volts peak, line-to-line
40,000 amperes
@ 1,500A, 600 volts
@ 5,000A, 800 volts
(both line-to-neutral)
10,000 amperes
line-to-neutral
10,000A, 120/240V AC
UL, CSA
Meets UL 1449 3rd Edition
For warranty information please refer to the surge
website www.usa.siemens.com/surge
7-28
Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog
Product Category RESI
Download