Attachment to FAQ Motion Control drives / software (DriveES, Tools) PROFIBUS, redundant bus operation with MASTERDRIVES drives ( basic implementation ) Configuring a MASTERDRIVE for operation on a redundant PROFIBUS. The configuration assumes that each of the two CBP boards on each PROFIBUS line is supplied with the same information. This means that the output data must always be simultaneously output at 2 peripheral address ranges. The values sensed in MASTERDRIVEs, values are also always feed back in parallel to the two PROFIBUS lines. Drive inverter parameterization assumes the following configuration: System 1 System 2 First CBP K3000 Second CBP K8000 Masterdrives M The redundancy changeover in the drive inverter/converter can be implemented using the following parameterization based on the configuration illustrated. Technische Aenderungen vorbehalten. Siemens AG 2001 redundancy.doc page 1 / 6 version 02/21/2001 Attachment to FAQ Motion Control drives / software (DriveES, Tools) PROFIBUS, redundant bus operation with MASTERDRIVES drives ( basic implementation ) Version 1: Most basic implementation The most basic method uses the changeover of the BICO data set, i.e. the first CBP serves data set 1 and the second, data set 2 in the drive. Changeover between the data sets can be initiated using the telegram failure binectors B035 ( first bus ) and B45 ( second bus ). Set the parameters to select the BICO_data sets ( P590 ) to value 35 ( binector 35 ). Make the following assignment between commands and setpoints: Main setpoint: P443 Index 1 = 3002 P443 Index 2 = 8002 Setpoint from the first CBP Setpoint from the second CBP, if the first detects a bus failure. Control commands: P554 Index 1 = 3100 P554 Index 2 = 8100 ON/OFF command from the first CBP ON/OFF command from the second CBP P565 Index 1 = 3107 P565 Index 2 = 8107 Fault acknowledgement from the first CBP Fault acknowledgement from the second CBP The telegram failure monitoring in the drive must remain active ( P722 = 10 ), otherwise binectors B35 and B45 will not be correctly processed. In order that a bus system failure does not cause a drive inverter fault trip, the initiation of fault trip with F082 must be disabled using parameter P781. In this case, Index 13 and Index 14 of P781 should be set to 101. The drive inverter is not fault tripped, even if both of the buses have failed. The drive continues to operate with the data which was last received. Free blocks used in the drive: NONE Technische Aenderungen vorbehalten. Siemens AG 2001 redundancy.doc page 2 / 6 version 02/21/2001 Attachment to FAQ Motion Control drives / software (DriveES, Tools) PROFIBUS, redundant bus operation with MASTERDRIVES drives ( basic implementation ) Version 2: Basic implementation with fault trip if both buses are faulted With this version, if both of the bus systems are faulted, the drive is fault tripped with F148. Free blocks which are used in the drive: AND1 (FB78), inverter 1 (FB108), AND2 (FB79) and fault initiation F148 (FB259) The following parameters still have to be set, supplementing version 1: U061 = 602 U950.78 =4 U221.1 = 35 U950.79 =4 U221.2 = 641 U951.08 =4 U221.3 = 1 U952.59 =4 U222.1 = 35 U222.2 = 45 U222.3 = 1 U251 = 45 Version 3: Implementing a priority circuit configuration of a bus using the PLC and fault trip if both buses are faulted In this version, in addition, the PLC can switch a bus as priority bus, i.e. the evaluation of the bus information ( bus 1 or bus 2 ) can be controlled from the PLC. In this case, the changeover is controlled via bit 15 in control word 1 ( first telegram word ). Alternatively, a binary input (i.e. a hardware signal from the PLC) can be used. Free blocks which are used in the drive: AND1 (FB78), inverter 1 (FB108), AND3 (FB89), OR1 (FB90), binary switch 1 (FB94), AND2 (FB79) and fault initiation F148 (FB259) The following parameters still have to be set, supplementary to version 1: U061 = 602 U950.78 =4 U223.1 U221.1 = 35 U950.79 =4 U223.2 U221.2 = 641 U950.89 =4 U223.3 U221.3 = 1 U950.90 =4 U239.1 U222.1 = 35 U950.94 =4 U239.2 U222.2 = 45 U951.08 =4 U239.3 U222.3 = 1 U952.59 =4 U271.1 U251 = 45 U271.2 = 601 U271.3 = 603 Technische Aenderungen vorbehalten. Siemens AG 2001 redundancy.doc page 3 / 6 = 641 = 619 =1 = 3115 = 8115 =0 = 619 version 02/21/2001 Attachment to FAQ Motion Control drives / software (DriveES, Tools) PROFIBUS, redundant bus operation with MASTERDRIVES drives ( basic implementation ) Circuit to implement basic redundancy changeover with fault initiation due to faults on both buses: We reserve the right to make changes. Siemens AG 2001 redundancy.doc Page 4 / 6 Edition 21.02.2001 Attachment to FAQ Motion Control drives / software (DriveES, Tools) PROFIBUS, redundant bus operation with MASTERDRIVES drives ( basic implementation ) Circuit to implement redundancy with priority changeover from the PLC side ( Page 1 ) B3115 B8115 To P590 on Page 2 B35 B45 We reserve the right to make changes. Siemens AG 2001 redundancy.doc Page 5 / 6 Edition 21.02.2001 Attachment to FAQ Motion Control drives / software (DriveES, Tools) PROFIBUS, redundant bus operation with MASTERDRIVES drives ( basic implementation ) Circuit to implement redundancy with priority changeover from the PLC side ( Page 2 ) B641 from Page 1 We reserve the right to make changes. Siemens AG 2001 redundancy.doc Page 6 / 6 Edition 21.02.2001