These are the mandatory lighting provisions we will cover today. 18

advertisement
These are the mandatory lighting provisions we will cover today.
18
First we see here the full array of lighting controls mandated by the IECC.
We’ll discuss each of these along with the specified exceptions.
19
Each area enclosed by walls or floor‐to‐ceiling partitions shall have at least one manual control for the lighting serving that area. The required controls shall be located within the area served by the controls or be a remote switch that identifies the lights served and indicates their status.
Exceptions to this requirement include
1. Areas designated as security or emergency areas that must be continuously lighted. AND
2. Lighting in stairways or corridors that are elements of the means of egress.
20
Each area that is required to have a manual control shall also allow the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern by at least 50 percent.
Lighting reduction shall be achieved by one of the following methods or as approved by the code official:
1. All lamps and luminaires can be controlled as a single entity; OR
2. Use dual switching of alternate rows of luminaires, alternate luminaires or alternate lamps; OR
3. By switching the middle lamps of luminaires independently of the outer lamps when using three or four lamp luminaires; or by
4. Switching each luminaire or each lamp independently.
===================================================================================
==
Exceptions to this requirement include:
1. Areas that have only one luminaire.
2. Areas that are controlled by an occupant‐sensing device.
3. Corridors, storerooms, restrooms or public lobbies.
4. Sleeping unit (more details about this will be provided later in section Section 505.2.3). AND
5. Spaces that use less than 0.6 watts per square foot.
21
Now let’s talk about the requirement for auto shutoff of the lighting
Buildings larger than 5,000 square feet shall be equipped with an automatic control device to shut off lighting in those areas. This automatic control device shall function on one of three options:
1. For the first option, the designer may designate a scheduled basis control, using time‐of‐day, with an independent program schedule that controls the interior lighting. For this option the areas shall not exceed 25,000 square feet and shall not include more than one floor; or
2. For option 2, an occupancy sensor may be used such that the lighting is automatically turned off once the space has been empty for a period no longer than 30 minutes; OR
3. The last option is to shut the lighting off based on a remote signal from another control or alarm system that indicates that the area is unoccupied.
=====================================================================
==
However, the following spaces shall not require an automatic control device:
1. Sleeping units (once again, we’ll discuss these more in section 505.2.3)
2. Lighting in spaces where patient care is directly provided. AND
3. Spaces where an automatic shutoff would endanger occupant safety or security.
22
Where an automatic time switch control device is installed to comply with this section it shall incorporate an override switching device that:
1. Is readily accessible.
2. Is located so that a person using the device can see the lights or the area controlled by that switch, or so that the area being lit is annunciated.
3. Is manually operated.
4. Allows the lighting to remain on for no more than 2 hours after the override is initiated. AND
5. Controls an area not exceeding 5,000 square feet.
=====================================================================
===
However, there are exceptions In malls and arcades, auditoriums, single‐tenant retail spaces, industrial facilities and arenas:
1. First when a captive‐key override system is utilized, override time shall be permitted to exceed 2 hours. AND
2. Second, the area covered by the override may go up to 20,000 square feet.
23
When an automatic time switch control device is installed in accordance with this section, it shall incorporate an automatic holiday scheduling feature that turns off all loads during holidays for at least 24 hours, then resumes the normally scheduled operation.
The following building types are exempted from this requirement:
Retail stores and associated malls, restaurants, grocery stores, places of religious worship and theaters.
24
Now let’s discuss daylight controls.
We first need to define what the IECC means by a ‘daylight zone’. Or, more exactly, the area of a daylight zone:
First, let’s look at the official definition of a daylight zone under skylights. The area under skylights whose horizontal dimension, in each direction, is equal to the skylight dimension in that direction plus either the floor‐to‐ceiling height or the dimension to a ceiling height opaque partition, or one‐half the distance to adjacent skylights or vertical fenestration, whichever is least.
=====================================================================
===
Now let’s look at a daylight zone adjacent to vertical fenestration. The design needs to document the area adjacent to vertical fenestration which receives daylight through the fenestration. For purposes of this definition and unless more detailed analysis is provided, the daylight zone depth is assumed to extend into the space a distance of 15 feet or to the nearest ceiling height opaque partition, whichever is less. The daylight zone width (that is the dimension parallel to the fenestration) is assumed to be the width of the window plus 2 feet on each side, or the window width plus the distance to an opaque partition, or the window width plus one‐half the distance to adjacent skylight or vertical fenestration, whichever is least.
25
Let’s see if an example will make this more clear … 25
Here we see a simple, rectagular room with:
A small skylight in the center,
3 windows on the west wall and
An L‐shaped ceiling‐height partition on the left.
Let’s now look at the resultant daylight zones:
26
On the left, in green, we see the daylight zones from the windows:
•In depth, they extend out from the windows 15’ (G1)
•Or to the ceiling height partition (G2)
•In width, they go out 2’ (G3) or they until hit the partition (G4), whichever is the least
On the right, in red, we see the daylight zone under the skylight; it extends:
•(R1) out a distance equal to the ceiling height or:
•(R2) To the ceiling height partition or
•(R3) Half way to the windows (whichever is the least)
27
Daylight zones, as defined by this code, shall be provided with individual controls that control the lights independent of the general area lighting. This allows the system to make the best use of the daylight to replace electric lighting.
Contiguous daylight zones adjacent to vertical fenestration are allowed to be controlled by a single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations (i.e., north, east, south, and west).
Daylight zones under skylights more than 15 feet from the perimeter shall be controlled separately from daylight zones adjacent to vertical fenestration.
However, daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a separate switch for the general area lighting.
28
Let’s now talk about sleeping units by first defining what a sleeping unit is. – you can see when you read the definition a couple of key points
(1) If the space has both bathroom fixtures and kitchen facilities, it is no longer just a sleeping unit, and
(2) if a space otherwise fits this definition but is part of a ‘dwelling’ unit, then it is not a sleeping unit. A ‘dwelling unit’ is a single unit providing complete independent living facilities for one or more persons including permanent provisions for living, sleeping, eating, cooking and sanitation.
=====================================================================
==
Now let’s discuss what lighting controls are required in such spaces.
Sleeping units in hotels, motels, boarding houses or similar buildings shall have at least one master switch at the main entry door that controls all permanently wired luminaires and switched receptacles, except those in the bathroom(s). Suites shall have a control meeting these requirements at the entry for each room or at the primary entry for the entire suite.
Now let’s discuss a couple of mandatory requirements not related to controls.
29
The following luminaires, when located within the same area, shall be tandem wired:
1. Fluorescent luminaires equipped with an odd number of lamps, that are recess mounted within 10 feet, center‐to‐center, of each other. OR
2. That are pendant‐ or surface‐mounted within 1 foot, edge‐ to‐edge, of each other.
Exceptions for this requirement are:
1. Where electronic high‐frequency ballasts are used.
2. When the luminaires are on emergency circuits. AND
3. Luminaires have no available pair in the same area.
30
Our last mandatory requirement for lighting equipment involves exit signs.
Internally illuminated exit signs shall not exceed 5 watts per side.
31
This last mandatory requirement is not lighting specific but is in the same section of the IECC.
In buildings having individual dwelling units, provisions shall be made to determine the electrical energy consumed by each tenant by separately metering individual dwelling units.
32
33
Download