ED1800 Single Pole Single Throw On/Off (Part of the Emergency

advertisement
ED1800 Single Pole Single Throw On/Off
(Part of the Emergency/Combined Disconnect Series)
1800A
The ED1800 range of switches have been designed to provide a rapid means of disconnecting
batteries or other power supplies in the event of serious electrical faults. Designed for use with
uninterrupted high current battery powered systems such as those found in Telecommunication
Power Distribution Units, all types are capable of safely rupturing full load battery currents in the event
of an emergency.
•
Uninterrupted current - no or infrequent load switching requirements (maintains a lower contact resistance).
The ED1800 is a manually operated device with a snap action for both opening and closing of the main
contacts. They have paralleled double breaking contacts with silver alloy tips which are weld resistant,
hard wearing and have excellent conductivity. The ED1800 is easy to install (see drilling details) and can be
mounted using the main terminal busbars or secured with supplied M5 posidrive mounting screws on the frame
of the device.
Precautions:
The switch is to be used to rupture current in an emergency or as a no-load isolator.
Do not use as a regular On-Load Switching Device.
ED1800
Drilling Details for Mounting
Application
Uninterrupted
Thermal Current Rating (Ith)
1800A
Intermittent Current Rating:
30% Duty
3285A
40% Duty
2845A
50% Duty
2545A
60% Duty
2325A
70% Duty
2150A
Rated Fault Current Breaking Capacity (Icn) Resistive Load:
(in accordance with UL508*)
2700A at 60v D.C.
ED1800 Contactor Performance
Maximum Recommended Contact Voltages (Ue):
60V D.C.
Typical Voltage Drop per pole
across New Contacts at 100A
<50mV
Mechanical M.T.B.F
>10,000
- 40˚C to + 60˚C
Guideline Contactor Weight:
Copper busbar
Key:
Magnetic Blowouts
400
300
965mm2 [1.49inch2]
Contact Performance Key:
Connection Diagram
Uninterrupted
Current
30
00
50
27
00
Current (Amperes)
= Uninterrupted
Note: Where applicable values shown are at 20˚C
25
0
50
100
•
•
•
v2-02-14
X
†
X
Mounting Brackets
X
Closed Contact Housing
X
Environmentally Protected IP55
X
EE Type (Steel Shroud)
X
Lockable
X
Contacts
* Please check our web site for product UL status
•
A
X
†
Magnetic Blowouts - High Powered
22
Advised Connection Sizes for Maximum Continuous Current0
○
Auxiliary Contacts - V3
500
200
2750 gms
Suffix
Auxiliary Contacts
Figures are for guideline
purposes only
600
00
ED1800
700
20
Operating Ambient Temperature
General
800
Time (Seconds)
ED1800
ED1800 Available Options
900
17
50
ED1800
Dimensions in mm [inches]
Performance data provided should be used as a guide only. Some de-rating or
variation from figures may be necessary according to application
Thermal current ratings stated are dependant upon the size of conductor
being used
For further technical advice email: technical@albrightinternational.com
Albright reserve the right to change data without prior notice
Large Tips
X
Textured Tips
X
Silver Plating (fitted as standard)
○
Key: Optional ○
†
Not Available X
Connections become polarity sensitive
Albright International Ltd, Evingar Trading Estate, Ardglen Road, Whitchurch, Hampshire, RG28 7BB, UK
Tel: +44 (0)1256 893060, Fax: +44 (0)1256 893562, Dedicated Sales Tel: +44 (0)1256 890030, Fax: +44 (0)1256 890043
E-mail: sales@albrightinternational.com or technical@albrightinternational.com Web Site: www.albrightinternational.com
Copyright © 2014 Albright International LTD