1.OPEN CIRCUIT AND SHORT CIRCUIT TEST OF TRANSFORMER AIM:To conduct open circuit and short circuit test in given transformer. Predetermine the following 1. Efficiencies at various loads and power factors 2. Regulation at various power factor and loads MACHINE DETAILS:- METERIALS REQUIRED:1. 2. 3. 4. 5. 6. Ammeter (0-2.5A) MI 1NO Ammeter (0-15A)MI 1NO Volt meter (0-250v) 1no Voltmeter (0-50v) MI 1NO Wattmeter (150V,5A,LPF) 1NO Wattmeter (150V,15A,UPF) 1NO THEORY:The purpose of the OC test to determine the no load loss (core loss) at rated voltage and frequency. Shunt branch parameters of equalent circuit r0&x0 and the no load current of the transformer on winding of the transformer. In the open circuit test the primary load current is very small(2.6% of rated current )copper loss is negligibly small in the primary and is nil in the secondary is opened. The equalent circuit parameters r0&xo referred to LV side can be calculated from the test result. The no load power loss, Pi=V0*I0*COS φ0 COSφ0=Pi/V0*I0 Magnetising component of I0 =Im=I0SIN φ0 Energy component of I0=Ie=I0COS φ0 The noload resistance R0=V0/Ie and the no load reactance X0= V0/Im These values can be transferred to hv side as R0’=R0(V2/V1)2 and X0’=X0(V2/V1)2 SC Test is to conduct for determining the full load copper loss and the equalent resistance and resistance of the transformer as refferd to the metering side. In this test one winding usually LV side is solidly short circuited and a low voltage (2-12% of primary voltage ) is applied to the HV side such that rated current flows through the winding since applied voltage is very low ,iron losses are very small and may be neglected. Hence the wattmeter shows the full load copper loss Pcu for the bwhole transformer. If VSC is the voltage required to circulate the rated current I2(KVA X 1000/V1) Then the equavalent circuit parameters can be found as Z02=VSC/I2 and R02=PCu Then X02= ππππ + πΉππ These parameters can be transferred to the LV side as R2’=R2(V2/V1)2 and X2’=X2(V2/V1)2 secondary side R02 and X02 the regulation at any PF and loading factor(x) can be predetermind as regulation= XI2(R02 COS φ0+- X02 SIN φ0)/V2 Where (+) for lagging and(-) for leading power factors) from the full load copper loss and iron loss the efficiency at any loading factor and pf can be pre determind as πΏπππππ²π½π¨πΏ.π·π Efficiency= πΏπππππ²π½π¨πΏπ·π+πΏππ·ππ+π·π PROCEDURE:OC TEST 1. Collect the materials for the given work. 2. Connection are done as shown in connection diagram. 3. Keep auto transformer at zero position. 4. Adjust the auto transformer up to rated voltage. 5. Take voltmeter, ammeter and wattmeter reading. PROCEDURE:SC TEST 1. Collect the materials for the given work. 2. Connection are done as shown in connection diagram. 3. Keep auto transformer at zero position. 4. Adjust the auto transformer up to rated current 5.Take voltmeter, ammeter and wattmeter reading. π½πΆπͺ π°πΆπͺ πΎπΆπͺ π½πΊπͺ π°πΊπͺ πΎπΊπͺ MODEL CALCULATION OC TEST π½πΆπͺ = π°πΆπͺ = πΎπΆπͺ = πΎπΆπͺ==π½πΆπͺ π°πΆπͺ πͺπΆπΊ∅π ∅π =πππ−π (π½ πΎπΆπͺ πΆπͺ π°πΆπͺ ) Wattles component ππ = ππ πππ∅π Magnetizing component πµ = ππ πππ∅π π½ πΉπ = π°πΆπͺ πΎ π½ πΏπ = π°πΆπͺ µ These values can be transferred to hv side R0’=R0 x K2 SC TEST X0’=X0 x K2 π½πΊπͺ = π°πΊπͺ = πΎπΊπͺ = Zsc=Vsc/Isc πΉππ = π½ππ/π°πππ Xsc= (πππ² − πΉππ²) Z02=Vsc/ISC R02=PCU/ISC2 X02= ππππ + πΉππ These values can be transferred in to LV R01=R02/K2 X01=X02/K2 TO DRAW EFFICIENCY CURVE FOR A GIVEN P.F Out put at X times F.L=X(rated KVA x 1000) cos∅ Core loss Wi= W0 Copper loss Wcs= X²Wsc Efficiency=(Output /output+losses) x100. KVA Curresponding to maximum efficiency=KVArated X πͺπππ ππππ πͺπππππ ππππ then find efficiency as usual. Sl no Load Output(Watt) Wi(watt) Wcx(watt) Input %efficiency TO DRAW REGULATION V/S PF CURVE % regulation at F.L for a given P.F= Sl No cos∅ π°πππππ (πΉπππππ∅±πΏπππππ∅ π½π sin∅ % Regulation Procedure:OC Test 1. 2. 3. 4. 5. Make connection as per the circuit diagram Keep the autotransformer in minimum position Adjust the auto transformer upto rated voltage of the transformer Take the meter readings and tabulate the readings Finish the work SC Test 1. 2. 3. 4. 5. Make connection as per the circuit diagram Keep the autotransformer in minimum position Adjust the auto transformer upto rated current of the transformer Take the meter readings and tabulate the readings Finish the work RESULT:-Conducted the OC and SC test on the given single phase transformer and predetrermine the following 1. 2. 3. 4. 5. Efficiencies at various loads and power factors Regulation at various loads and power factors Equavalent circuit reffered to hv and lv side Maximum efficiencies at unity PF= Maximum efficiencies at 0.8PF= 2.LOAD TEST ON SINGLE PHASE TRANSFORMER AIM:To conduct a no load test on given SINGLE PHASE TRANSFORMER and determine the regulation for defferent load. MACHINE DETAILS:- METERIALS REQUIRED:1. 2. 3. 4. 5. 6. Ammeter (0-15A) MI Voltmeter (0-150v) MI Wattmeter (300v,15A,upf) Ammeter (0-5A) MI Voltmeter (0-250v) MI Wattmeter (300v,30A,upf) 1NO 1NO 1NO 1NO 1NO 1NO THEORY:In this test the efficiencies and regulation are detrermind by direct loading of the given single phase transformer . this test is very often carried out in practice excepting for small sizes ,owing to the difficulty of obtaining a suitable load and the loss of power involved. When ever a transformer is loaded its secondary terminal voltage changes with increased load ,if the supplied primary voltage is held constent.the change in secondary voltage from no load to full load expressed ias percentage of no load voltage is known a voltage is known as voltage regulatin of a transformer (ie, secondary voltage at noload –secondary voltage at full load) π¬π−π½π (the π¬π secondary rated voltage of a transformer is equal to the secondary voltage at no load,ie,E2 The efficienciy of a transformer is defaind as the ratio of output power to input power,thus efficeiency=output power/input power In this experiment input power is measured directly from the wattmeter connected in the primary side and output power is obtained by multiplying the volt meter reading and ammeter reading in the secondary side. PROCEDURE:1. 2. 3. 4. Connect the circuit diagram as per the circuit diagram Adjust the autotransformer till the voltmeter reads rated voltage. Note the no load readings and enter them as first set of readings in tabular column. Load the transformer gradually and take all meter readings each time till the secondary current reaches rated value. 5. Tabulate the readings. And finish the work TABULATION Sl No I1 in Amps V1 in volts W in watts I2 in Amps V2 in volts Input in watts Output=V2xI2 %efficiency % Regulation CALCULATION Output=V2xI2. Input= W πΆ/π %efficiency= π/π x100. Regulation= ππ½π−π½π x100. ππ½π RESULT:Load test on single phase transformer is conducted and efficiency and regulation curve were plotted. 3.SWIMBERN’S TEST AIM:Conduct no load test on dc shunt motor and [predetermine the efficiency of the machine under the following working conditions. a)machine working as a generator b) Machine working as a motor c) plot efficiency vs output MACHINE DETAILS:- METERIALS REQUIRED:1) 2) 3) 4) 5) 6) 7) Ammeter Ammeter voltmeter voltmeter Rheostat Rheostat Tachometer 0-5A MC 0-3A MC 0-300v MC 0-30v MC 100β¦,5A 370β¦,1.1A 2NO 1NO 1NO 1NO 1NO 1NO 1NO THEORY:This is a no load test to determine the losses of the machine. the losses in the motors are Iron loss or core losses, frictional losses, windage losses, arm copper losses Work as generator Efficiency= ππππππ ππππππ−ππππππ Work as motor Efficiency = πππππ−πππππ πππππ PROCEDURE:1. 2. 3. 4. 5. 6. Connection are as shown in connection diagram. Armature rheostat at maximum position. Field rheostat at minimum position. Switch on the supply and run the motor at no load. Adjust the field rheostat bring motor speed to rated speed. Note the readings and tabulate the readings TABULATION Si Voltage V no (in volts) π°πΊπ― AMPS π°π¨π AMPS π°π= π°π¨π + π°πΊπ― AS MOTOR: Sl No Fraction of load(X) Voltage(v) Current Ia in Amps Total loss= Input X²Ia²Ra+Wc power o/p power efficiency Voltage(v) Current Ia in Amps Total loss= Input X²Ia²Ra+Wc power o/p power efficiency AS GENERATOR Sl No Fraction of load(X) CALCULATIUON: Constant losses Wc= V ( Iao+ Ish)-Iao²Ra. AS MOTOR: I/p power=F.L o/p Power+Ia²Ra+Wc.,O/p power= Vπ°π³ , π°π³ =Ia+ Ish. Total loss= Ia²Ra+Wc. O/p=I/p-Losses. πΆ/π Efficiency= π/π x100. AS GENERATOR: Full load o/p power=Vxπ°π³ . I/p=o/p+ losses. πΆ/π %efficiency= π/π x100. RESULT Efficiency of the DC shunt machine when work as 1)Motor 2) Generator are pre-determined also efficiency curves are plotted. 4.LOAD TEST ON A DC SERIES MOTOR AIM; To conduct a load test on DC series motor and plot the following graph. 1) 2) 3) 4) Torque v/s armature current Speed v/s armature current Speed v/s torque Efficiency v/s o/p MACHINE DETAILS: APPARATUS REQUIRED: 1) Voltmeter 2) Ammeter 3) Tachometer 0-250V(MC) 0-15A(MC) 1No 1 No THEORY: In series motor the torque is directly proportional to armature current. Speed N is proportional to Ed/∅. In a series motor the field carries same current as the armature ie, ∅ ∝Ia. The series motor cannot be started without load. Toque= (S1-S2)xgr Output= πΠπ΅π» . ππ Input=VI. πΆ/π %efficiency= π/π x100. TABULATION: Sl N o Voltage(V ) Speed(RPM ) Spring balance S 1 S 2 S1~s 2 CALCULATION: V= ……………….. Speed,N=…………………………. Spring balance, S1=……………………………. S2=…………………………………………….. Torque,T= (s1~s2)rg, r=Radius of break drum g= 9.8 Output= πΠπ΅π» . ππ πΆ/π %efficiency= π/π x100. Torque = (S1s2)rg Output(W ) Input(W ) Efficiency(% ) PROCEDURE: 1) 2) 3) 4) 5) 6) Connections are made as per diagram. Apply a small load to the motor and start the motor. Note the meter readings Vary the spring balance at different load. Note the corresponding readings. Tabulate the reading and plot the graph. RESULT: The load test on series motor is conducted and plotted the graphs. 5.LOAD TEST ON A DC SHUNT MOTOR AIM; To conduct a load test on DCshunt motor and plot the following graph. 5) 6) 7) 8) Torque v/s armature current Speed v/s armature current Speed v/s torque Efficiency v/s o/p MACHINE DETAILS: APPARATUS REQUIRED: 1) 2) 3) 4) 5) Voltmeter 0-250V(MC) Ammeter 0-15A(MC) Ammeter 0-3A (MC) Rheostat 500β¦,3A Tachometer 1No 1 No 1No 1No THEORY: A load test is direct method,and this method is used only for small motors, because in the case of large motors it is difficult to dissipate large amount of heat generation Toque= (S1-S2)xgr Output= πΠπ΅π» . ππ Input=VI. πΆ/π %efficiency= π/π x100. TABULATION: Sl N o Voltage(V) Speed (RPM) Ish Ia IL=I a+ Ish CALCULATION: V= ……………….. Speed,N=…………………………. Spring balance, S1=……………………………. S2=…………………………………………….. Torque,T= (s1~s2)rg, r=Radius of break drum g= 9.8 Output= πΠπ΅π» . ππ πΆ/π %efficiency= π/π x100. Spring balance S1 S2 S1~s2 Torque = (S1s2)rg Outp ut(W ) Input(W ) Efficien cy(%) PROCEDURE: 1) Connections are made as per diagram. 2) Rheostat kept in min. position 4) Start the motor using 4 point starter 5)Note the meter readings 6) Vary the spring balance at different load. 7) Note the corresponding readings. 8) Tabulate the reading and plot the graph. RESULT: The load test on shunt motor is conducted and plotted the graphs. 6.POLARITY TEST AND TURN`S RATIO TEST ON SINGLE PHASE T RANSFORMER Aim : To conduct polarity test, and determine turn`s ratio, transformation ratio, and magnetizing component of No Load current of single phase transformer. (115/ 220 V, 5 KVA) Apparatus required : Theory:- Turns ratio of a transformer = No of turns of primary/No of turns of secondary. Transformation ratio K = Secondary induced EMF/ Primary induced EMF= E2/E1 E1 = 4.444 φm.f.N1Volts., and E2 = 4.444 φm.f.N2Volts ... K= E /E 2 1 K =4.444 φm.f.N2/4.444 φm.f.N1 , =N2/N1 ...Turns ratio, N1/N2=E1/E2 No load input power, W0= V0 I0 Cosφ0, Cosφ0= W0/ V0 I0, Magnetizing component of no load current Iµ = I0 Sinφ0 ... φ0 =Cos-1(W0/ V0 I0) Procedure:- 1) Polarity test. 1 Connections are made as shown in figure (1) 2. Checked the connections and given a specified voltage to primary. 3. Noted the volt meter reading and verified the polarity of the transformer.ie If the voltmeter reading in the inter connected voltmeter is greater than the input voltage, then the polarity is additive , So Opposite polarity on the other adjacent terminal on secondary. 4. Interchanged the connections to confirm first determined polarity. Turn`s ration and transformation ratio; 1. Connections are made as in figure (2) 2. Checked the connections and given the supply gradually from minimum voltage to rated voltage of primary using autotransformer. 3. Noted the V/m readings on primary and secondary and the A/m and W/m reading when applying the rated primary voltage. 4. Completed the experiment neatly and correctly. Result:- Checked the polarity and determined the turns ratio transformation ratio, and magnetizing component of no load current of 115/220/V 5 KVA transformer. Turns ratio= Transformation ratio= Magnetizing component of no load current Iµ = Determined the polarity of the transformer also. Sl No Prim V/m reading E1 Sec V/m reading E2 Watt meter A/m reading W0 reading I0 Turns ratio Transf. ratio =K