INSTALLATION INSTRUCTIONS SUPPLEMENT DELEON SERIES LED EMERGENCY EXIT SIGNS WITH SELF DIAGNOSTICS OPTION DLTLX 120/277 EL N SD Caution: For safety and proper operation, read and follow instructions carefully before installation IMPORTANT SAFEGUARDS 1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS 2. Before wiring to power supply, turn off electricity at fuse or circuit breaker. 3. Disconnect A.C. power and Power Plug before servicing. 4. Refer to wiring diagram sheet for proper connections. 5. Be sure unit is wired to AC power before power plug is connected. 6. All servicing should be performed by qualified personnel. 7. Consult your local building code for approved wiring and installation. 8. Do not use outdoors. 9. Do not mount near gas or electric heater. 10. Fixture must be grounded to avoid potential electric shock. 11. Equipment should be mounted in location and at heights where it will not readily be subjected to tampering by unauthorized personnel. 12. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 13. Do not use this equipment for other than intended use. SAVE THESE INSTRUCTIONS U.S. PATENT NO. D383.501 IMPORTANT NOTE: This Instruction sheet supplement is to be used in conjunction with the Installation Instructions provided with the unit. 3825 Columbus Rd, Granville OH 43023 740-345-9631 www.holophane.com Page 1 PARTS DESCRIPTION 1. 2. 3. 4. 5. 6. 7. Charger PC Board Self-Diagnostics PC Board Pushnut Connectors Battery Battery Connector Lamp Connector Cable Self-Diagnostics Harness (to Test Switch/ Status Indicator connector) 8. Self-Diagnostics Harness (to Charger PCB) 9. Lampboard 10. Manual Test Switch 11. Test Switch/Status Indicator Connector 12. Magnetic Test Switch 13. Lamp Connector 14. Charger Board/Self-Diagnostics Connections FIGURE A SINGLE FACE EXIT SINGLE FACE LAMP EXIT INSTALLATION: 1. Refer to main Installation Instructions manual for all installation, mounting, cleaning instructions and additional figures detailing unit. IMPORTANT NOTE: Care should be taken to disconnect both the test switch status indicator connector (11), and the lampboard connector (13) before removing the lampboard (9) from the unit. SINGLE FACE LAMP 120 VOLT WIRING WIRING: NOTE: Select appropriate wiring diagram for input voltage to be used. IMPORTANT NOTES: 1. This equipment to be connected to an unswitched circuit only. 2. Cap all unused leads separately. 3. Canopy mount exits have polarized connectors on A.C. installation wire leads and option installation wire leads. 4. CAUTION: Damage to battery will occur if battery connector is connected to charger board for a prolonged period of time without continuous A.C. power provided. SINGLE FACE LAMP 277 VOLT WIRING Page 2 PARTS DESCRIPTION 1. 2. 3. 4. 5. 6. 7. Charger PC Board Self-Diagnostics PC Board Pushnut Connectors Battery Battery Connector Lamp Connector Cable Self-Diagnostics Harness (to Test Switch/ Status Indicator connector) 8. Self-Diagnostics Harness (to Charger PCB) 9. Lampboard 10. Manual Test Switch 11. Test Switch/Status Indicator Connector 12. Magnetic Test Switch 13. Lamp Connector 14. Charger Board/Self-Diagnostics Connections FIGURE B DOUBLE FACE EXIT DOUBLE FACE LAMP EXIT INSTALLATION: 1. Refer to main Installation Instructions manual for all installation, mounting, cleaning instructions and additional figures detailing unit. IMPORTANT NOTE: Care should be taken to disconnect both the test switch/status indicator connector (11), and the lampboard connector (13) before removing the lampboard (9) from the unit. DOUBLE FACE LAMP 120 VOLT WIRING WIRING: NOTE: Select appropriate wiring diagram for input voltage to be used. IMPORTANT NOTES: 1. This equipment to be connected to an unswitched circuit only. 2. Cap all unused leads separately. 3. Canopy mount exits have polarized connectors on A.C. installation wire leads and option installation wire leads. 4. CAUTION: Damage to battery will occur if battery connector is connected to charger board for a prolonged period of time without continuous A.C. power provided. DOUBLE FACE LAMP 277 VOLT WIRING Page 3 MANUALLY CLEARING A FAILURE: A failure indication may be cleared manually by: SELF DIAGNOSTICS TESTING: IMPORTANT NOTE: Emergency lighting systems should be tested as often as local codes require, or at least monthly, to ascertain that all components are operational. Allow battery to charge 24 hours before initial testing, and 168 hours to fully charge battery. 1. Placing the unit in the manual test mode for more than 30 seconds. 2. Removing AC power for more than 30 seconds. NOTE: The self-diagnostics option performs tests to satisfy these test requirements, as well as local code testing requirements for most areas. 3. If a failure condition is detected during the next self-diagnostics test, the failure indicator will flash red, indicating a failure condition. STATUS INDICATOR 1. Normal Operation: When unit is functioning properly, with A.C. power supplied, the status indicator will be green and the exit lamp will be on. MANUAL TESTING: If desired, manual testing of the unit may be actuated as follows: 2. Testing: When the status indicator is flashing green with the exit lamp on, a test is in process. The exit performs two types of tests. Every 28 days (+/- 2 days) it performs a monthly test. The monthly test is a five minute diagnostics test of the battery, lamp(s), and charging circuit. Upon completion of the five minute test, the status indicator should return to green (steady) to indicate a properly functioning unit. A flashing red status indicator indicates a failure condition. Every 6 months (+/- 12 days) self-diagnostics performs a 6 month test. The 6 month test is a 30 minute diagnostics test of the battery, lamp(s), and charging circuit. After the 30 minute test, the status indicator should return to green (steady) to indicate a properly functioning unit. A flashing red status indicator indicates a failure condition. 3. Failure Indication: When the status indicator is flashing red, the exit needs service. The self-diagnostics system has detected a low battery, bad lamp(s), or a charger circuit failure. At this time the exit failure should be diagnosed and serviced by quailified personnel. NOTE: Turn off A.C. power and disconnect battery before servicing unit. Refer to the Maintenance section of these instructions when replacing parts. After the unit has been serviced, and continuous power applied to the unit, the diagnostic systems clock will reset. This will be indicated by the status indicator being green, and the exit lamp being on. FIGURE C Self-diagnostics status indicator and manual magnetic test switch Manual Magnetic Test Zone IMPORTANT NOTE: The self-diagnostics option performs test to satisfy local codes in most areas. Although self-diagnostics does not allow a manually initiated self-diagnostics test, there are two methods to simulate an AC power failure and initiate a test of the battery, lamp(s), and charger circuit: 1. Hold the magnet to the magnetic test zone. The status indicator will go out when the magnet is positoned correctly, indicating the manual test mode has been activated. Remove the magnet to end the test and return the unit to normal operation. The status indicator should return to green, indicating a properly functioning unit. 2. Press the manual test switch (located inside the unit on the lampboard). The status indicator will go out to indicate the manual test mode has been activated. Release the test switch to end the test and return the unit to normal operation. The status indicator should return to green, indicating a properly functioning unit. MAINTENANCE: NOTE: Turn off A.C. power and disconnect battery before servicing unit. LAMPBOARD REPLACEMENT: 1. Disconnect lamp connector (13), and test switch/status indicator connector (11) (if applicable). Remove four screws holding lampboard (9) in place and remove lampboard. Lampboard replacement is a reverse sequence of above. BATTERY REPLACEMENT 1. Cut cable tie holding battery (4) to bracket. Pry battery from battery bracket to release from tape. Replacement is a reverse sequence of above. CHARGER P.C. BOARD REPLACEMENT: 1. Cut tape and open enclosure box for Charger P.C. Board. Disconnect lamp connector, and test switch/status light connector. 2. Cut installation supply leads and charger board/self-diagnostics connections (14) at pushnut connector (3). Strip installation supply leads and self-diagnostics leads for pushnut connection. 3. Charger pc board replacement is a reverse sequence of above. Multi-color LED Status Indicator Green: Normal operation Green F lashing: Performing Self-Diagnostics Test Red Flashing: Failure Condition 3825 Columbus Rd, Granville OH 43023 740-345-9631 www.holophane.com Page 4 PART NUMBER EMCSA00872 REV B, 7.19.16