Specifier Product Information 74000 Series 75000 Series Panel-Mounted 7-Mode Surge Protective Devices (SPD’s) with Advanced Monitoring Capabilities APPLICATION Cat. Nos. 74000 and 75000 with removable modules are designed for installation at the service entrance and at branch panels, or as dedicated TVSS for critical equipment. These devices provide dedicated surge protection for each phase-toneutral, phase-to-ground and neutral-to-ground in three-phase WYE systems. The diagnostic features allow users to monitor surge events on the incoming AC power line, including the magnitude, date and time of the event. 74000 and 75000 Series TYPICAL SPECIFICATION All 74000/75000 units are designed for use where a multi-phase, transient voltage surge suppressor (TVSS) is specified. They provide full 7-mode protection in 120/208V and 277/480V WYEconfigured, 3-phase systems. 74000 series panels feature individually fused 40mm-diameter, metaloxide varistor arrays and EMI/RFI filter circuitry equipped with high-voltage-rise capacitors for harmonic tolerance. 75000 series panels employ arrester-grade 53mm-diameter MOV arrays for the most severe surge exposure environments. Features include advanced diagnostic monitoring of protection status for each phase, a surge event counter that records amplitude, date and time of event, an audible alarm for protection status, and replaceable plug-in modules. All units have been tested to ANSI/IEEE C62.45 standards for Category A, B and C environments and are UL 1449 (2nd Edition) Listed. They are also backed by Leviton’s Limited Ten-Year Warranty. Leviton Mfg. Co., Inc.—Power Quality Division • 860 Harold Place, Chula Vista, CA 91914 Tech line: 1-800-648-3332 • Fax: 619-205-8739 Inside view of the 74000 and 75000 Series 74000/75000 Series ................................. Performance Data Performance Specifications Cat. No. Replacement Rating Module Cat. No. Operating Frequency @ 50/ 60Hz Maximum Continuous Operating Voltage (MCOV) (L-N) Max. SinglePulse Transient Energy (10x1000µs) Joules Max. SinglePulse Surge Current (8x20µs) per mode Max. SinglePulse Surge Current (8x20µs) per phase (L-N) + (L-G) 74120-7M3 HC120-M40 120/208V AC 3-Phase, 5-wire (4-wire + ground) 150V AC 1440 per mode 10,080 per panel 200kA 400kA 74277-7M3 HC277-M40 277/480V AC 3-Phase, 5-wire (4-wire + ground) 320V AC 2560 per mode 17,920 per panel 200kA 400kA 75120-7M3 HC120-M53 120/208V AC 3-Phase, 5-wire (4-wire + ground) 150V AC 2280 per mode 15,960 per panel 320kA 640kA 75277-7M3 HC277-M53 277/480V AC 3-Phase, 5-wire (4-wire + ground) 320V AC 4400 per mode 30,800 per panel 320kA 640kA Clamping Performance Cat. No. UL 1449 Suppressed Voltage Ratings (SVR)† 75120-7M3 74120-7M3 L-L 800V L-N 400V L-G 400V N-G 400V 75277-7M3 74277-7M3 L-L 1600V L-N 800V L-G 800V N-G 800V †Suppressed Voltage Ratings (SVR) assigned at 6-inch lead length with 6kV/500A impulse in accordance with UL 1449 (2nd Edition) Category C3 Testing: All 74000 and 75000 7-Mode devices have been subjected to 1000 sequential Category C3 surges Interior detail of the 74000 and 75000 Series EMI/RFI Noise Rejection All Cat. No. 74000/75000 7-Mode SPD’s Normal Mode Common Mode Evaluation Bandwidth 5KHz – 5MHz 5KHz – 5MHz Noise Rejection @ 50 Ohms 20 – 40dB 20 – 40dB 74000/75000 Series ................................. Functionality Detail of Diagnostic Display Panel on the 74000 and 75000 Series DIAGNOSTIC CAPABILITIES • Monitors the status of each phase • Display will indicate “Fault”, “Alert”, and “Protection” status • Functions include a surge event counter, amplitude measurement, the date and the time of the event • Events are stored and can be recalled and downloaded by the user NORMAL OPERATIONS: • Green indicators (up to 3) will no longer be illuminated during a fault condition • Yellow indicator light will illuminate and audible alarm will sound when one of the fuses in the surge module opens due to surge activity. The module screen will flash the percentage of protection that is active (e.g., 75% protection when 1 fuse is open) • Red indicator light will illuminate and audible alarm will sound when protection level is at 50% or less • Information is easily downloadable via RS-232/422 port using the program “Hyperterminal” that comes standard on any Windows operating software • Arrow buttons allow user to view surge event history on each line by scrolling through data • Remove supervision—Cat. No. 52000-RS may also be used with 74000/75000 panels for remote monitoring 74000/75000 Series ................................. General Data DIMENSIONAL DRAWINGS 8.33 (211.6 mm) 7.48 (190.0 mm) 15.75 (400.0 mm) 19.69 (500.0 mm) PHYSICAL SPECIFICATIONS Housing NEMA Type 12 enclosure with a hinged front door secured with two key locks. Inside enclosure is a second hinged door that protects the diagnostic and surge-protective circuitry when the front door is open. Module system board constructed of UL-approved, fire-retardant plastic Physical Dimensions (approx.) H x W x D (approx.): 16.0" (406.4mm) x 20.0" (508.0mm) x 8.5" (215.9mm) Mounting Surface mount adjacent to protected equipment using (4) mounting holes on back panel and (4) 1/4" to 5/16" bolts Wiring Board cable terminals can accept up to 6AWG conductors Operating Temperature Range -10º to 60ºC Storage Temperature Range -20º to 85ºC AGENCY APPROVALS • Listed UL 1449 Standard (2nd Edition) • CSA Certified PRODUCT MAINTENANCE Information on the status panel of the LCD and an audible alarm will indicate when a module needs to be replaced. Plug-in module design facilitates module replacement for installation and maintenance by the user with the AC power disconnected. An alarm will sound when the module is at 50% of full protection capability. FEATURES • 7-mode protection (each phase-to-neutral, each phase-to-ground, and neutral-to-ground) for WYE-configured 3-phase AC systems • Advanced circuit board design • User-replaceable modules • Real-time diagnostics monitor power and suppression status for each mode • Provides surge magnitude, time and date for each surge event • Surge event history can be downloaded for storage • Clamping envelope tracks contour of the AC sine wave • Equipped with optically-isolated dry contacts rated 5A 120/240V AC for remote monitoring Leviton Mfg. Co., Inc.—Power Quality Division • 860 Harold Place, Chula Vista, CA 91914 Tech line: 1-800-648-3332 • Fax: 619-205-8739 Visit Leviton’s web site: www.leviton.com © 2002 Leviton Manufacturing Co., Inc. All rights reserved. C-627/D2-10M rs